EXTERIOR RESEARCH & DESIGN, LLC.
Certificate of Authorization #9503
353 CHRISTIAN STREET, UNIT#13
OXFORD, CT 06478
(203) 262-9245
Boral Roofing D kTE 3((r510, Evaluation Report M35710.12.10-R9
7575 Irvine Center Drive, Suite 100 PLkN-'S kND PEPMIT MUST BE KEPT ON JOB FL14317-R8
Irvine, CA. 92618 0Z 1 N0 LNSPEdTION WELL BE MODE Date of Issuance: 12/21/2010
(602) 269-2288 Revision 9:10/14/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: Boral Roof Underlayments
LABELING: Labeling shall be in accordance with the i requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is vali 1
Quality Assurance documentation changes, or provisl
this Evaluation Report by the named client constit
changes or the referenced Quality Assurance docum
Evaluation Report relative to updated Code requirem
ADVERTISEMENT: The Evaluation Report number preci
advertising literature. If any portion of the Evaluatioi
INSPECTION: Upon request, a copy of this entire Evalu;
its distributors and shall be available for inspection al
This Evaluation Report consists of pages 1 through 7.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
CERTIFICATION OF INDEPENDENCE:
1. Trinity IERD does not have, nor does it intend to acquire
distributing products it evaluates.
2. Trinity l ERD is not owned, operated or controlled by any cc
3. Robert Nieminen, P.E. does not have nor will acquire, a fii
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a fi
product.
5. This is a building code evaluation. Neither Trinityl ERD n
project on which this Evaluation Report, or previous versi
specifically for that purpose.
THESE PLANS AND ALL PROPOSED WORK
ARE SUBJECT TO ANY CORRECTIONS
REQUIRED BY FIELD INSPECTORS THAT
MAY BE NECESSARY IN ORDER TO
COMPLY VY0 A14 �P41OAILA gQDEII
until such time as the named product(s) changes, the referenced
ins of the Code that relate to the product change. Acceptance of
tes agreement to notify Robert Nieminen, P.E. if the product
ntation changes. Trinity I ERD requires a complete review of this
!nts with each Code Cycle.
ded by the words "Trinity I ERD Evaluated" may be displayed in
Report is displayed, then it shall be done in its entirety.
Report shall be provided to the user by the manufacturer or
job site at the request of the Building Official.
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. on 10/14/2017. This does not serve as an
electronically signed document.
or will it acquire, a financial interest in any company manufacturing or
iany manufacturing or distributing products it evaluates.
cial interest in any company manufacturing or distributing products for
al interest in any other entity involved in the approval process of the
Robert Nieminen, P.E. are, in any way, the Designer of Record for any
thereof, is/was used for permitting or design guidance unless retained
EDFASTENERS ORATTACHMENTS
THE RFSFONSI91LnY OF THE C^ 1%Y
ff grim
*AiAACT9HOF�ECORA
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Underlayment
Compliance Statement: Boral Roof Underl;
with the following sections of the 6t11 Editio
following Standards. Compliance is subject
forth herein.
2. STANDARDS:
ments, as marketed by Boral Roofing, have demonstrated compliance
(2017) Florida Building Code through testing in accordance with the
the Installation Requirements and Limitations / Conditions of Use set
Section
Property
Standard
Year
1504.3.1
Wind Uplift
I
UL 1897
2012
1507.1.1, T1507.1.1, 1507.2.9.2
Physical Properties
ASTM D1970
2015
1507.3.3
Physical Properties
FRSA/TRI April 2012 (04-12)
2012
3. REFERENCES:
Entity
Examination
Reference
Date
ERD (TST 6049)
Physical Properties
M36790.07.11
09/30/2011
ERD (TST 6049)
Physical Properties
840380.08.12
08/28/2012
ERD (TST 6049)
Tensile Adhesion / LTA
C41420.09.12-2
09/11/2012
ERD (TST 6049)
Adhesion
641940.09.12
09/13/2012
ERD (TST 6049)
Tensile Adhesion / LTA
B47390.07.14-1
07/31/2014
ERD (TST 6049)
Tensile Adhesion / LTA
B47390.09.14
09/04/2014
PRI (TST 5878)
ASTM D1970
NEI-031-02-02:REV
10/27/2010
PRI (TST 5878)
ASTM D1970
NEI-029-02-01:REV
12/03/2010
PRI (TST 5878)
Tensile Adhesion / LTA
NEI-046-02-01REV
12/17/2010
PRI (TST 5878)
FRSA/TRI April 2012
NEI-076-02-01
02/14/2011
PRI (TST 5878)
ASTM D1970
NEI-034-02-02
01/29/2013
PRI (TST 5878)
Wind Uplift
BORR-001-02-01
03/17/2015
PRI (TST 5878)
Wind Uplift
BORR-005-02-01
06/24/2015
UL, LLC. (QUA 9625)
Quality Assurance
Service Confirmation
Exp. 08/21/2020
4. PRODUCT DESCRIPTION:
4.1 Self -Adhering Underlayments:
4.1.1 7nderlayment;
le I° 50"T is a nominal 50-I
ets ASTM D1970.
4.1. leSeal° HT i a nominal 60-m
yment; ets ASTM D1970 ai
4.1.3 GatorSeal° is a nominal 55-mil thick
bitumen roof underlayment; meets A
I thick, polyester -surfaced, self -adhering SBS modified bitumen roof
thick, polyester -surfaced, self -adhering SBS modified bitumen roof
J FRSA/TRI 04-12.
granular -surfaced, fiberglass reinforced, self -adhering SBS modified
TM D1970.
4.1.4 Citadel° Plus is a nominal 48-mil thick, fabric -surfaced, fiberglass reinforced, self -adhering SBS modified
bitumen roofing underlayment for use as a base -layer in two-ply underlayment systems; meets ASTM
D1970.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity) ERD nor Robert Nieminen, P.E. are, in anyway, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
Exterior Research and Design, U.C. I Evaluation Report M35710.12.10-R9
Certificate ofAuthori:ation #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL14317-R8
Boral Roof Underpayments; (602) 269-2288 Revision 9: 10/14/2017
Page 2 of 7
5.3
5.4
5.5
Fire Classification is not part of Ithis Laboratory Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
Boral Roof Underlayments may be used with any prepared roof cover where the product is specifically
referenced within FBC approval documents. If not listed, a request may be made to the Authority Having
Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof
covering.
Allowable Roof Covers: Table 1 pertains to use of each listed underlayment by -itself beneath the stated
roof covers. Refer to the installation instructions and Table 2 for two-ply underlayment options.
Asphalt
Adhesive -set
wood Shakes
Underlayment
Nail -On Tile
Metal
Slate
Shingles
Tile
& Shingles
Boral TileSeal 50"�
No
Yes
Yes°:
Yes'
HT
Yes
Boral TileSeal
YeSN
Yes
E yes
Yes„,
Yes
(See 5 5 1) <<
GatorSealNo
,a
Na a
Yes'n
Yes .
5.5.1 "Adhesive -set Tile" is limited to use of following Approved tile adhesives / underlayment combinations.
5.6
5.6.1
5.6.2
TAS' ';IA ALtOV1►ABLE111EADtiESlttE;�UNpERLAYBJIENTGONIBINAT10NS1
Adhesive
I
Florida Product Approval
Underlayments
DAP Foam Touch'n Seal StormBond Roof
Tile Adhesive
FL14506
Boral TileSeal"T
Dow TILE BOND'' Roof Tile Adhesive
I
FL22525
Boral TileSeal"T
ICP Adhesives Polyset® AH-160
FL6332
Boral TileSeal"T
ICP Adhesives Polyset® RTA-1
FL6276
Boral TileSeal"T
Allowable Substrates:
Direct -Bond to Deck:
Citadel Plus, Boral TileSeal 50"T, Boral TileSeal"T or GatorSeal:
➢ Plywood (unprimed or primed with ASTM D41 primer).
BoraI TileSeal"T:
➢ OSB primed with ASTM D41 primer.
Note: Refer to Section 5.6.4 for upilift limitations associated with direct -deck underlayment installations
where the overlying roof cover is adhesive -set tile roofing
Bond to Base Laver Underlayment:
Citadel Plus, Boral TileSeal 50"T, Boral TileSeal"T or GatorSeal:
➢ ASTM D226, Type II felt; Citadel Plus.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirements. For installations under adhesive -set tile systems, base layer shall be
attached per minimum requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in
Section 5.6.4 herein, or as tested in accordance with FBC 1504.3.1.
1 Refer to Tile Manufacturer's or Adhesive
s Florida Product Approval for Overturning Moment Resistance Performance.
Exterior Research and Design, LLC. IEvaluation Report M35710.12.10-R9
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL14317-118
Boral Roof Undi rlayments; (602) 269-2288 Revision 9: 10/14/2017
Page 3 of 7
5.6.3 Bond to Other Substrate Types:
Citadel Plus, Boral TileSeal 50"T,
➢ ASTM D41 primed metal (e
Boral TileSeal"T:
➢ Huber Zip Deck (unprimed
Note: For installation under mec
per minimum requirements of th(
5.6.4 Wind Resistance for Underlaymen'
does not address wind uplift resi
where the underlayment forms
underlayment systems that are nc
tile applications. Maximum Desi
allowable wind loads, and reflects
per FBC 1504.9 has already been
FBC 1609 for determination of des
l
coral TileSeal"T or GatorSeal:
;., flashing metal, valley metal, etc).
r primed with ASTM D41 primer); Dens Deck Prime.
anically attached prepared roof coverings, insulation shall be attached
prepared roof covering manufacturer's Product Approval.
: Systems in Adhesive -set Tile Applications: FRSA/TRI April 2012 (04-12)
itance of all underlayment systems beneath adhesive -set tile systems,
)art of the load -path. The following wind uplift limitations apply to
t addressed in FRSA/TRI April 2012 (04-12) and are used in adhesive -set
;n Pressure is the result of testing for wind load resistance based on
the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety
ipplied). Refer to FRSA/TRI April 2012 (04-12), Appendix A, Table 1A or
ie?n wind loads
#1 Maximum Design Pressure = -105 bsf:
Deck:
Min. 15/32-inc, plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Base Ply:
(Optional) Citadel Plus, self -adhered
Underlayment:
Boral TileSeal"TJ self -adhered and back -nailed within the selvedge -edge side laps using
12 ga. x 1%" ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c.
1
#2 Maximum Design Pressure = -120.0 psf:
Deck:
Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Primer:
ASTM D41 to the, plywood deck
Base Ply:
Citadel Plus, self -adhered
Cap Sheet:
Boral TileSeal"T, self -adhered, and back -nailed within the selvedge -edge side laps using
12 ga. x 1%" ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c.
#3 Maximum Design Pressure = -202.5 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Primer: A5TM D41 to the plywood deck
Base Ply: None
Cap Sheet: Boral TileSeal"T, self -adhered, and back -nailed within the selvedge -edge side laps using
12 ga. x 1%" ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c.
#4 Maximum Design Pressure = -120.0 psf:
Deck: Min. 2,500 psi structural concrete to meet project requirements to satisfaction of
Authority Having Jurisdiction.
Primer: ASTM D41 to the concrete deck
Base Ply: (Optional) Citadel Plus, self -adhered
Cap Sheet: Boral TileSeaIHT, Iself-adhered
5.6.4.1 Note: For adhesive -set tile systems, if there is a base ply or mid -ply of Citadel Plus in the system, the
project design pressure requirements may not exceed -120 psf.
Exterior Research and Design, I.I.C. I Evaluation Report M35710.12.10-R9
Certificate ofAuthori:ation #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL14317-R8
Boral Roof U 1 derlayments; (602) 269-2288 Revision 9: 10/14/2017
Page 4 of 7
5.7 Exposure Limitations:
GatorSeal shall not be left
roof cover.
5.8
for longer than 30-days after installation, prior to placement of final
Boral TileSeal 50"r and Boral TileSealHT shall not be left exposed for longer than 180-days after
installation, prior to placement of final roof cover.
Citadel Plus, for use as a base -layer in a two-ply underlayment system, shall not be left exposed for longer
than 180-days after installation, prior to placement of subsequent underlayment layer.
When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall
be as follows. These slope limitations can only be exceeded by using battens during loading of the roof
tiles.
,TA13LE 2 .TILE SLIPPAGE'LIMITATIONS
FORT DIRECT -DECK TILE INSTALLATIONS`` `
Underlayment
Tile Profile
Stagging Method
Maximum Slope
Boral TileSeal"r
Flat
Max. 10-tile stack
6:12
Lugged
Max. 10-tile stack
6:12
6. INSTALLATION:
6.1 Boral Roof Underlayments shall Ibe installed in accordance with Boral Roofing published installation
instructions subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debris prior to application, and prime the substrate (if applicable).
6.3 Install self -adhering underlayment when ambient and surface temperatures are minimum 407 and rising.
6 4 Cita el Plus a
6.4.1 Citadel Plus is limited to use as a base or mid -layer in multi -ply underlayment systems beneath Boral
HT HT I
TileSeal 50 , Boral TileSeal or GatorSeal.
6.4.2 Slope limitations are those associated with the top -layer underlayment.
6.4.3 Direct to Deck:
Cut the membrane into manageable lengths, typically 10 to 12 ft. Align the membrane parallel to the roof
edge, extending over by Y.-inch. Fold the membrane away from the edge onto itself. Remove the release
sheet. Place the membrane with the exposed rubberized asphalt onto the deck, pressing firmly into place.
Roll into place with a weighted roller.
Boral recommends fastening of the top edge of the sheet to the deck with roofing nails, nails & tin -tags or
1-inch diameter plastic or steel cap nails spaced 24-inch o.c. for slopes below 7:12 and 12-inch o.c. for
slopes 7:12 and greater. Overlap successive courses minimum 2 inches (horizontal lap) and minimum 4"
end (vertical) laps.
Install final underlayment layer atop Citadel Plus per 'direct -to -deck' instructions for Boral TileSeal 50"r
Boral TileSeal"r or GatorSeal.
6.4.4 To Base Sheet:
Install base sheet of ASTM D226, type II felt in accordance with Code requirements or install base ply of
Citadel Plus in accordance with Boral Roofing published installation instructions and Section 6.4.3 and
when used as part of a multi -ply system.
Install optional Citadel Plus as a mid -ply in accordance with Boral Roofing published installation
instructions and Section 6.4.3.
Install final underlayment layer atop Citadel Plus per 'direct -to -deck' instructions for Boral TileSeal 50"r,
Boral TileSeal"r or GatorSeal.
Exterior Research and Design, I.I.C. Evaluation Report M35710.12.10-R9
Certificate ofAuthorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION F1.14317-118
Boral Roof Underlayments; (602) 269-2288 Revision 9: 10/14/2017
Page 5 of 7
Note: For adhesive -set tile
project design pressure requ
if there is a base ply or mid -ply of Citadel Plus in the system, the
may not exceed -120 psf.
6.5.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
6.5.2 Do not use Boral TileSeal 50"T on roof pitches less than 2:12.
6.5.3 Non -Tile Applications, Direct to Deck:
6.5.4
Cut the membrane into manageable lengths, typically 10 to 12 ft. Align the membrane parallel to the roof
edge, extending over by X-inch. Fold the membrane away from the edge onto itself. Remove the release
sheet. Place the membrane with he exposed rubberized asphalt onto the deck, pressing firmly into place.
Roll into place with a weighted roller.
Boral recommends fastening of the black selvedge edge to the deck with roofing nails, nails & tin -tags or f-
inch diameter plastic or steel cap nails spaced 24-inch o.c. for slopes below 7:12 and 12-inch o.c. for slopes
7:12 and greater. Overlap successive courses the width of the black -selvedge area, minimum 3-inch.
Seal under end (vertical) laps using approved mastic, or use Joined and Folded Seam or Inverted Sheet
Seam method detailed in Boral Roofing published installation instructions.
Install ASTM D226, Type II felt in accordance with Code requirements or install Citadel Plus in accordance
with Boral Roofing published installation instructions and Section 6.4.
Install Boral TileSeal 50"T in accordance over ASTM D226, Type II felt or Citadel Plus with Boral Roofing
published installation instructions and Section 6.5.3, except end (vertical) laps, described below.
Apply SBS Mastic under all end (vertical) laps or any other laps where the self -adhering bituminous
underside is in contact with the fabric top surface, rolling the interface into place with a weighted roller.
6.6.1 Shall be installed in compliances with the requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared) roof covering to be installed.
6.6.2 Do not use GatorSeal on roof pitces less than 2:12.
6.6.3 Non -Tile applications, Direct to Deck:
Cut the membrane into manageable lengths, typically 10 to 12 ft. Align the membrane parallel to the roof
edge, extending over by %-inch. Fold the membrane away from the edge onto itself. Remove the release
sheet. Place the membrane with the exposed rubberized asphalt onto .the deck, pressing firmly into place.
Roll into place with a weighted roller.
Boral recommends fastening of the black selvedge edge to the deck with roofing nails, nails & tin -tags or 1-
inch diameter plastic or steel cap nails spaced 24-inch o.c. for slopes below 7:12 and 12-inch o.c. for slopes
7:12 and greater. Overlap successive courses the width of the black -selvedge area, minimum 3-inch.
Seal end (vertical) laps using SBS Mastic under all side (vertical) laps or any other laps where the self -
adhering bituminous underside is in contact with the granular or mineral top surface, rolling the interface
into place with a weighted roller, or using the Inverted Sheet Seam detailed in Boral Roofing published
installation instructions.
6.6.4 Non -Tile Applications, to Base Sheet:
Install ASTM D226, Type II felt in accordance with Code requirements or install Citadel Plus in accordance
with Boral Roofing published installation instructions and Section 6.4.
Install GatorSeal over ASTM D226, Type II felt or Citadel Plus in accordance with Boral Roofing published
installation instructions and Section 6.6.3 except end (vertical) laps, described below.
Apply SBS Mastic under all side (vertical) laps or any other laps where the self -adhering bituminous
underside is in contact with the granular top surface, rolling the interface into place with a weighted roller.
Exterior Research and Design, I.I.C. Evaluation Report M35730.12.10-R9
Certificate ofAuthorizatian #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION F1.14317-118
Boral Roof Underlayments; (602) 269-2288 Revision 9:10/14/2017
Page 6 of 7
6.7.1 Shall be installed in complianc
1507.1.1 for the type of prepare
6.7.2 Do not use Boral TileSeal HT on n
6.7.3 Non -Tile Applications, Direct to I
6.7.4
For OSB substrate, prime with A!
into manageable lengths, typical
over by''/< -inch. Fold the membri
membrane with the exposed rub
with a weighted roller.
Boral recommends fastening of tl
inch diameter plastic or steel cap
7:12 and greater. Overlap succe!
Seal under end (vertical) laps w
Seam method detailed in Boral R
Install ASTM D226, Type II felt it
with Boral Roofing published ins'
Install Boral TileSeal HT over AS
published installation instructior
Apply SBS Mastic under all en
underside is in contact with the I
6.7.5 Tile Applications:
Reference is made to FRSA/TR
instructions noted above as a gu
For mechanically fastened tile r
sheet(s), Base Sheet fastening sh
For adhesive -set tile application!
Note: For adhesive -set tile syst
project design pressure requirer
Refer to Section 5.8 for tile stal
TileSeal HT with roof pitches of
battens are required.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or
this product.
8. MANUFACTURING PLANTS:
Brentwood, NH
9. QUALITY ASSURANCE ENTITY:
UL, LLC. — QUA9625; (631) 546-2458;
with the requirements for ASTM D1970 underlayment in FBC Table
roof covering to be installed.
pitches less than 2:12.
A D41 primer and allow to dry prior to installation. Cut the membrane
10 to 12 ft. Align the membrane parallel to the roof edge, extending
away from the edge onto itself. Remove the release sheet. Place the
rized asphalt onto the deck, pressing firmly into place. Roll into place
ie black selvedge edge to the deck with roofing nails, nails & tin -tags or 1-
nails spaced 24-inch o.c. for slopes below 7:12 and 12-inch o.c. for slopes
sive courses the width, of the black -selvedge area, minimum 3-inch.
ng approved mastic, or use Joined and Folded Seam or Inverted Sheet
lofing published installation instructions.
accordance with Code requirements or install Citadel Plus in accordance
Illation instructions and Section 6.4.
M D226, Type II felt or Citadel Plus in accordance with Boral Roofing
and Section 6.7.3, except end (vertical) laps, described below.
(vertical) laps or any other laps where the self -adhering bituminous
bric top surface, rolling the interface into place with a weighted roller.
April 2012 (04-12) Installation Manual and Table 1 herein, using the
leline.
ofing, over 2-ply system, consisting of Base Sheet and self -adhering top
II be not less than FRSA/TRI April 2012 (04-12), Table 1.
refer to Section 5.6.4 herein.
ms, if there is a base ply or mid -ply of Citadel Plus in the system, the
ents may not exceed -120 psf.
ng limitations. Battens must be used for all tile installations atop Boral
to less than 3:12. Boral Roofing's Elevated Batten System or counter
iority Having Jurisdiction in order to properly evaluate the installation of
OF EVALUATION REPORT -
Exterior Research and Design, LLC. Evaluation Report M3S710.12.10-R9
Certificate ofAuthorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL14317-RS
Boral Roof Underlayments; (602) 269-2288 Revision 9:10/14/2017
Page 7 of 7