Flexible Air Duct'
Product Specifications and Key Features
Quietflex® manufactures flexible duct for the commercial, residential and manufactured home industries.
We produce 3" through 22" duct in R4.2, R6 and R8 insulation thickness.
• Johns Manville Formaldehyde -free fiber glass insulation
• GREENGUARD® Certified insulated products
• Galvanized metal core reinforcing
• Oversized core to fit on collars and register boxes
• Weather -resistant packaging
• Easy -to -carry package: Up to 10" bags are strapped to
form a pair
• Available in boxes and bags
• 12.5; 25' and 50' and custom lengths available
• HUD/FHA standards 515.2.1, Paragraph B
• NFPA standards 90A and 90B
• BOCA, City of Chicago, meets most federal,
state and local codes and standards
• ETL Listed/Approved to UL 181
"Rip Stop" Silver Jacket
The Quietflex Rip -Stop Silver Jacket Flex Duct has a metallic, polyester -vapor
barrier with a special "rip -stop" scrim reinforcement.
BAG.
30 40 4.2
' 70 80 6.6
84 85 U
f(` OX BAG 4" 5" 6" 8 9" lo" 12" 1 14" 1 16" 18" AC
50 60 6.0 • • • • • •
V 10 20 1 4.2
.'.a ._
flr 54 65 8.0
Mobile Horne
The Quietflex Mobile Home Flex Duct has an extra heavy-duty, UV -Inhibited,
polyethylene -vapor barrier and complies with HUD standards for outdoor use
with mobile homes.
SERIES
R-VALUE.•,®®
DIAMETER
Uninsulated Air Connector
SERIES
DIAMETER
_ ®W®W®WW
. „`
®�®�®��
=000000000aoa0000.
Installation Notes:
• Not to be installed in lengths greater than 14'.
• Not to be used to vent appliances for cooling, heating, and clothes drying unless approved and
recommended by appliance manufactures
Performance Data (Applies to all products)
• Rated Positive Pressure 10" W.C. per UL 181
• Rated Negative Pressure 1/2" W.C. per UL 181
• Velocity 6,000 FPM
• Temperature Range —20°F to 200°F (Intermittent) / —20°F to 180°F (Continuous)
• Flame. Spread/Smoke Developed Less than 25/1-ess than 50
LIMITED WARRANTY I LIMITATION OF LIABILITY I DISCLAIMER OF UNSTATED WARRANTIES
The flexible air duct is warranted by Quietflex Manufacturing Company, L.P., for ten (10) years against defects in material and workmanship. This warranty is for exchange. of duct
only and does not include installation. - -
WARRANTY EXCLUSIONS
Warranty is excluded if flexible air duct is used in the follGwing installations / applications; -
1. Where duct is exposed to direct or indirect light -
2. Where duct is used on the high— pressure side of variableair— volume (VAV).systems.
LIMITATION OF LIABILITY
Quietllex's liability for damages, whether in contract, in tort, under warranty, in naglNence orotherwise, Shall not exceed the return of the amount of .
the purchase price paid for the Quietflex products: Quietflex shall not be tfable far specisl,andirect orconsorluentiai damages:; Specitii*fon and
performance data listed herein are sublect to change wi!hout jtot4cc(
DISCLAIMER OF UN�WARf2AN TATM ` F
lE5a s` `st #
'(ltrswartanfytsVhsop�tv�ri�dr�i ot;Q t�,p,)3 *�1"j�` •`r�".a .' ��'��"'� Il'�"dr�nh�ct�f�Yn' 1 '� t `'
..` dfQuteiltexMan3k"ict'ptr dig,. o . ��'�E,.,...'r �.. �.-.,;.. •-.e«�.'!: � . k:.,. ....�:" ..���::�"'t�i.a-a "?:�:�,`'_""i, �'f*:.-:'s-�:;7-.:-'t
www.quietflex.com
Quietflex Manufacturing Company, L.P.
4518 Brittmoore Road
Houston, Texas 77041
Phone 713.849.2163
Fax 713.849.0753
Toll Free 877.694.3669
Specification Sheet
Ultra*Duct'O Black Duct Mari
PRODUCT DESCRIPTION
Basic Use: Ultra*Duch Black Duct Board
is a rigid board designed for fabrication
into supply and return air HVAC duct
work. The product can be used in heating
and cooling systems which operate at
velocities up to 5,000 fpm (25.4 m/s),
temperatures up to 250`17 (121'C) and
maximum internal pressures of ± 2"
(51mm) water gauge.
Benefits: This product is strong, resistant to mold, bacteria and microbial growth, and easy to clean.
In addition, Ultra*Duct Black provides excellent thermal properties, absorbs unwanted crosstalk,
equipment and air rush noise, and exhibits low air flow resistance. It also meets all applicable fire
resistance standards and building code requirements. The product can be precision cut using both
manual and automatic cutting equipment.
Composition and Materials: Composed of resin -bonded glass fibers with a reinforced foil laminate
air barrier/vapor retarder facing applied to the outside surface and a fiber glass textile mat bonded to
the airstream surface. The airstream surface contains an EPA -registered antimicrobial agent in order
to reduce the potential of microbial growth that may affect this producti The antimicrobial properties
are intended to protect only this product.
Limitations: Ultra*Duct Black is not to be used under poured concrete slabs or to convey exhaust
fumes, solids or corrosive gases. Ducts exposed to the weather must be weather protected and
reinforced per industry standards. Ducts must not be used as vertical risers more than two stories in
height. They must not be used adjacent to high -temperature heating coils. Insulation should be kept
clean and dry during shipping, storage and system operation. i
Sizes: See table on back for available sizes. Contact CertainTeed for availability and minimum
order quantities. 11
INSTALLATION
Ultra*Duct Black must be fabricated and installed in accordance with the NAIMA or SMACNA Fibrous
Glass Duct Construction Standards and all closure systems must meet the requirements of UL 181A.
The installed duct system should be purged prior to occupancy to remote any loose material.
i
AVAILABILITY AND COST
Manufactured and sold throughout the United States and Canada. For availability and cost, contact
your local distributor or call CertainTeed Sales Support Group in Malvern, PA at 800-233-8990.
WARRANTY
Refer to CertainTeed's Limited Lifetime Warranty for Ultra*Duct Black Di ct Board (30-32-113).
MAINTENANCE
An inspection and maintenance program for the HVAC system is recommended to ensure optimum
performance. Use NAIMA guidelines for duct cleaning methods and procedures.
TECHNICAL SERVICES
Technical assistance can be obtained either from your local CertainTeed sales representative,
or by calling CertainTeed Sales Support Group in Malvern, PA at 800-2 3-8990
CertainTeed
R CertamTeed Ultra*Duci� '2
Product
Black Duct Board " �1
Manufacturer CertainTeed Corporation
—^ a
Address ` ' 20 Moores Road � � � 4j
Malvern, PA i9355"
Phone 610-341 7000 * 800-233-8990
5
Fax q ;; " 610' 341 7571 � �4 Y
Website www.certainteed.com/insulation
TECHNICAL DATA
AVAILABLE
Product Type
Thickness
Width
Length
No. Boards Per
Edge
in:.'"°.;
mm
in:
mm
•in. =
mm
.Carton _
Pallet
475 '
Shipp or
1 ('
25
" 120 ''.
3048
6
44
96 _ `-
2438
:- 6
.
Butt Edge
48
1219
Shiplap or
'
120
3048
4
800 _:
Butt Edge
1Yz
38
30
96
2438
4
3
-
ButtEdge
2
51
120
3048
3°.;
22
Product Type
ACOUSTICAL PERFORMANCE
Absorption Coefficients @ Octave Band Frequencies (Hz)
T
EI.
Thickness
125
,,250'_ .
500
;- -1000-
2000
4000-
NRC
In.
475'
1
=:25
0.07
; - 0.2li
0.63
='. 0 90 .`'
0.97
1.00
0.70
1 Yz
38
010
0 42 :
0.91
104
1.04
f.04 %
0.85
i
2
51
017
0 63' :'
110
105 i
1.04
,1 CIE 'o-.
0.95
Sound absorption tested in accordance with ASTM C423 using Type A mounting per ASTM
Product
K-Value
C-Value
R-Value
Ei.
Thickness
Btu•in
W
Btu
W
Btu
W ._
• „
h•ft'•°F
me'G.,_
heft. F
m?. C ,:
heft:..F
mz. G
in.
mm .'
475
1
25 ': =
0.23
0 033: v;
0.23
1' 3i
4.3
0 76 ` =.
38
0.15
D 87 -
6.5
115
800
2
51
0.12
0'65 ',
8.7
1.53',°.
`•
Thermal conductance (C) and resistance (R) values are derived from the material thermal conductivity (K) value.
Tested in accordance with ASTM C518 at 75°F (24°C) mean temperature.
MENBOP
Seal and
Insulate
':,'•., ,' with
NAIMA • , , ENERGY STAR
-Mir1(
SAINT-GOBAI,N
CertainTeed Corporation
ROOFING • SIDING • TRIM • DECKING • RAILING • FENCE • GYPSUM • CEILINGS a INSULATION
20 Moores Road Malvern, PA 193SS Professional: 800-233-8990 Consumer: 800-782-8777 certainteed.eom
011116 CertainTeed Corporation, Printed in the USA, Code No. 30-34-029
6;ietftex
FLEX DUCT PRODUCT:
RIP STOP
SILVER JACKET
SUBMITTAL DRAWING
Metalized
:Vapor; Barrier.
VAPOR BARRIER
- The Quietflex Rip Stop Silver Jacket Flex Duct has a metalized polyester -vapor barrier with a special
"rip stop" scrim reinforcement.
- Vapor Transmission: 0.05 perms
- R4.2, R6 and R8 certified by ETL and the Air Diffusion Council using ASTM C-518 at installed
thickness of insulation
- Made of formaldehyde free materials
- Two layers of polyester film encapsulate a
- Rated positive pressure is 10" W.C. and ni
- Rated maximum air velocity is 6000 FPM
SURFACE BURNING CHARACTERISTICS
- Flame spread: Less than 25
- Smoke developed: Less than 50
- Class 1 rated duct assembly
OPERATING TEMPERATURE RANGE .
- -20 deg F to 180 deg F - Continuous
- -20 deg F to 200 deg F - Intermittent
zed or bronze coated wire helix
pressure is 1/2" W.C. per the UL 181 standard
CONFIGURATIONS
- Diameters available: W-10", 1211, 14", 16", 18", 20", 22"
- Lengths available: 25 ft
'ALS
- ETL Listed/Approved to UL 181 Standard
- NFPA standards 90A and 90B
- HUD/FHA standards 515.2.1 Paragraph B
- Meets most federal, state and local codes and standards
- GREENGUARD certified entire duct construction
Made in the USA
Job Name Submitter:l Date:
Location Class 1 Insulated Flexible Air Duct
Contractor Metalized Polyester vapor barrier/
Engineer Silver jacket
Architect QFSD-002-01
Quietflex Manufacturing Company LP, 4518 Brittmoore IRd, Houston, TX 77041, Telephone: 713.849.2163 0110
Fax: 713.849.0753 Toll Free: 877.694.3669 www.auietflex.com
Load Short F
�°- 03;
``� Mlcarethcmh,rnaplati¢ Entire House
ProCalcs, LLC
P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882 5700 Email:
For:
3827 St. Mark Dr., Fort Pierce, FL 34982
Htg Clg
Outside db (OF)
42
90
Inside db (OF)
70
72
Design TD (OF)
28
18
Daily range
-
L
Inside humidity (%)
30
50
Moisture difference (gr/lb)
1
68
Method
Construction quality
Fireplaces
Job: Laffont Residence
Date: Mar 13, 2017
By: Tom Piatania
/�,a`.aam P�iu2
License: CAC1815254 RTIN #0105474
Infiltration
Simplified
Semi -loose
HEATING EQUIPMENT
COOLING EQUIPMENT
Make
Make Rheem
Trade
Trade RHEEM
Model
Cond RA1430AJ1NA
AHRI ref
Coil RH1T3621MTANJA
AHRI ref 7491227
Efficiency
100 EFF
Efficiency 13.0 EER, 16 SEER
Heating input
8.0
kW
Sensible cooling
24000
Btuh
Heating output
27297
Btuh
Latent cooling
6000
Btuh
Temperature rise
50
OF
Total cooling
30000
Btuh
Actual air flow
497
cfm
Actual air flow
1000
cfm
Air flow factor
0.019
cfm/Btuh
Air flow factor
0.047
cfm/Btuh
Static pressure
0.60
in H2O
Static pressure
0.60
in H2O
Space thermostat
Load sensible heat ratio
0.79
0
ROOM NAME
Area
(ft2)
Htg load
(Btuh)
Clg load
(Btuh)
Htg AVF
(cfm)
Clg AVF
(cfm)
Bedroom 2
209
4007
2875
76
134
WIC
142
2584
907
49
42
LN
4
0
0
0
0
Bath 2
90
141
106
3
5
Utility
138
3836
2478
73
116
Bath
50
77
550
1
26
Dining Room
125
2705
1705
51
80
Living Rm
317
3462
3957
65
185
FL RM
231
6690
4537
108
212
Bedroom 1
157
1340
899
.25
42
AH
5
0
0
0
0
Hall
65
.0
0
0
0
Kitchen
195
2424
3381
46
158
CL
23
0
0
0
0
Calculations approved byACCA
to meet all requirements of Manual
J 8th Ed.
wrightsoft°
Right -suites Universal 2017 17.0.19
RSU17939
2017-Mar-15 10:28:30Page
ACCk ...Laffont\Working Drawings%Laffont Load Calcs.rup Calc = MJ8
Front Door faces: SE
1
a
Entire House 1749 26266 21395 497 1000
Other equip loads 0 0
Equip. @ 1.00 RSM 21395
Latent cooling 5611
TOTALS
1749
Calculations approved by
wnghtsoft' Right-Suite®Unnrersal 201717.0.19
ACCA ...LaffontlWorking DrawingslLaffant Load Calcs.rup Calc = MJ8 I
26266 1 27006 1 497 ' 1000
to meet all requirements of Manual J 8th Ed.
Door faces: SE
2017-Mar-15 10:28:30
Page 2
Building Analysis
'Wcareat he mb:ln9 preae Entire House
ProCalcs, LLC
P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email-....
Job: Laffont Residence
Date: Mar 13, 2017
By: Tom Platania
Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474
For: Laffont Residence
3827 St. Mark Dr., FortPierce, FL 34982
Location:
Indoor:
Heating
Cooling
Fort Pierce, FL, US
Indoor temperature (°F)
70
72
Elevation: 25 ft
Design TD (°F)
28
18
Latitude: 27°N
Relative humidity (%
30
50
Outdoor: Heating
Cooling
Moisture difference ()gr/lb)
1.1
67.9
Dry bulb (°F) 42
90
Infiltration:
Daily range °F) -
15 (L )
Method
Simplified
Wet bulb (°F� -
78
Construction quality
Semi -loose
Wind speed (mph) 15.0
7.5
Fireplaces
0
Component
Btuh/ftz
Btuh
% of
load
Walls
4.0
5847
22.3
Glazing
12.6
3840
14.6
Doors
10.9
459
1.7
Ceilings
1.2
2061
7.8
Floors
3.8
6691
25.5
Infiltration
2.6
4764
18.1
Ducts
2605
9.9
Piping
0
0
Humidification
0
0
Ventilation
0
0
Adjustments
0
Total
1
1 26266
100.0
Component
Btuh/ftz
Btuh
% of
load
Walls
2.9
4336
20.3
Glazing
24.0
7323
34.2
Doors
12.5
524
2.4
Ceilings
1.0
1748
8.2
Floors
0
0
0
Infiltration
0.9
1609
7.5
Ducts
1564
7.3
Ventilation
0
0
Internal gains
4290
20.1
Blower
0
0
Adjustments
0
Total
21395
100.0
Latent Cooling Load = 5611 Btuh
Overall U-value = 0.247 Btuh/W-OF
Data entries checked.
Glazir
c
Gla
2017-Mer--15 10:28:30
"� vvrightSOft' Right -Suite® Universal 2017 17.0.19 RSU17939 Page 1
ACCK ...Laffont\Working DrawingMLaffont Load Calcs.rup Calc = MJ8 (Front Door faces: SE
i
.. Project Summ
RD" CS Entire House
'Wcart: themhdng piece_
ProCalcs, LLC
P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email:
For: Laffont Residence
3827 St. Mark Dr.,
Notes: Above All Air H
3233 Route 1
Fort Pierce, FL
Weather:
Winter Design Conditions
Outside db 42 OF
Inside db 70 OF
Design TD .28 OF
Heating Summary
Structure 23661 Btu
Ducts 2605 Btu
Central vent (0 cfm) 0 Btu
(none)
Humidification 0 Btu
Piping 0 Btu
Equipment load 26266 Btu
Infiltration
Method
Construction quality
Fireplaces
Heating
Area (ft2) 1749
Volume (ft3) 15743
Air changes/hour 0.59
Equiv. AVF (cfm) 155
U
D1749
15143
Heating Equipment Summary
Make
Trade
Model
AHRI ref
Efficiency
Heating input
Heating output
Temperature rise
Actual air flow
Air flow factor
Static pressure
Space thermostat
Job: Laffont Residence
Date: Mar 13, 2017 .
By: Tom Platania
Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474
Pierce, FL 34982
& Cooling, LLC
Pierce, FL, US
Summer Design Conditions
Outside db
90 OF
Inside db
72 OF
Design TD
18 OF
Daily range
L
Relative humidity
50 %
Moisture difference
68 gr/lb
Sensible Cooling Equipment Load Sizing
Structure
19831
Btuh
Ducts
1564
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Blower
0
Btuh
Use manufacturer's data
Rate/swing multiplier
Equipment sensible load
1.00
21395
Btuh
Latent Cooling Equipment Load Sizing
Structure
4352
Btuh
Ducts
1259
Btuh
Central vent (0 cfm)
0
Btuh
(none)
Equipment latent load
5611
Btuh
.31 Equipment total load 27006 Btuh
81 Req. total capacity at 0.80 SHR 2.2 ton
100 EFF
8.0
kW
27297
Btuh
50
OF
497
cfm
0.019
cfm/Btuh
0.60
in H2O
Cooling Equipment Summary
Make Rheem
Trade RHEEM
Cond RA1430AJl NA
Coil RH1 T3621 MTANJA
AHRI ref 7491227
Efficiency
13.0 EER, 16 SEER
Sensible cooling
24000
Btuh
Latent cooling
6000
Btuh
Total cooling
30000
Btuh
Actual air flow
i 1000
cfm
Air flow factor
0.047
cfm/Btuh
Static pressure
0.60
in H2O
Load sensible heat ratio 0.79
Calculations approved by AaCA to meet all requirements of Manual J 8th Ed.
�y, Wrl IhtSogt° 2017-Mar-1510:28:30
Y' g Right Suite® Universal 201717.0.19 RSU17939 Page 1
AOCK ...Laffont\Working Drawings\Laffont Load Calcs.rup Calc = M.18 Front Door faces: SE
1i
1VR@) I Right-JO Worksheet Job: Laffont Residence
`�` °F•�� °° ° Entire House Date: Mar 13, 2017
ProCalcs, LLC By: Tom Platania
P.O. Box 88203Z Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474
1
2
3
4
5
Room name
Exposed wall
Room height
Room dimensions
Room area
Entire House
202.5 ft
9.0 ft
1749.3 ft'
Bedroom 2
29.0 ft
9.0 ft heat/cool
15.5 x 13.5 ft
209.3 ft2
Ty
Construction
number
U-value
(Btuh/ft L"7)
Or
HTM
(Btuh/M
Area (W)
or perimeter (ft)
Load
(Btuh)
Area (ft2)
or perimeter (ft)
Load
(Btuh)
Heat
Cooll
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
W '.
UAl
t-G
-
12B-0sw
Block Wall 4-1
4A5-2ovd
Block'Wall4 1 .'
2 glazing dr low e
2 glazing dr toinr
2 glazing drlow e
116
Block Wall 4-1
10D-v
2 glazing, dr lower
2 glazing, drlow-e
2 glazing cir low-e
126 Osw .
Block Wall 4-1
10D-v
2 glazing, cir low-e
4A5-2ovd
16X30-0td . '
22A tpm
0. 09Z
0.143
0.450
-0 143
0 450
0 450
0 450
0 390..
0.143
0.450
0.450
0.450
0.450
0.097
0.143
0.450
0.450
0.450
0 408
1.180
';, ne
ne
ne
sa'
' se
•.se
-`se
§e
sw
sw
sw
sw
sw
':nw
nw
nw
nw
nw
,':-
2 72
4.00
12.60
'4 00
-A 2.
17:60
72:60
10.92
4.00
12.60
12.60
12.60
12.60
2:72
4.00
12.60
12.60
12.60
1.18
33.04
1 t3Q
2.97
26.52
2:97
.24:18
24.18
25:20
. ' 12.48
2.97
19.46
24.18
24.18
24.18
1:86
2.97
19.16
26.30
26.52
,. 1:00
0.00
°. ' 24
368
40
{509
20
48
13
,42
414
40
12
24
26
24
485
20
24
37
:. " -1749
1749
24
327
0
' _ 385
4
10
2
.::. 42
312
0
3
5
5
". .24,-
404
0
0
0
, '..,1749
203
`: , 65
1311
507
. ` 1542
252
605
169.
... ;; 459
1248
507
151
302
328
65
1616
253
302
464
.,. r2061'
6691
-' . , 45
974
1066
' 1145
484
1161
'' 338
, • 524
927
782
290
580
629
>' .. 45
1200
385
631
977
."' •':.1748'
0
U`
0
0
;, 0
:- 0
;` 0
"- 0
_., 0
122
40
0
0
0
'_ : ` .. 0
140
0
24
0
' 209
209
0
0
0
_; 0..
0
0
0
0
81
0
0
0
0
0
116
0
0
0
• , ,;: 209
29
0°
0
0
0
0
0
0
p
326
507
0
0
0
0
462
0
302
0
,•'. 247'
- 958
: - , 0
0
0
- 0,
0
0.
0
0
242
782
0
0
0
0.
344
0
631
0
209
0
W.
C _
F
6
c)AED excursion I
-
0
173
Envelope loss/gain
18898
13931
2802
2381
12
a) Infiltration
b) Room ventilation
4764
0
1609
0
682
0
230
0
13
Internal gains: Occupants aQ 230
Appliances/other
3
690
3600
0
10
0
Subtotal (lines 6 to 13)
23661
19831
3484
2612
14
151
Less external load
Less transfer
Redistribution
Subtotal
Duct loads
11%
8%
0
0
0
23661
2605
0
0
0
19831
1564
11%
8%
0
0
125
3609
397
0
0
53
2665
210
Total room load
Air required (cfm)
262 66
497
21395
1000
4007
76
2875
134
-#- wrightsoft" Right -Suite® Universal 2017 17.0.19 RSU17939
ACGA LaffonttWorking Drawings\Laffont Load Calcs.rup Catc = MI8Front Door faces: SE
2017-Mar-15 10:28:30
Page 1
tiv�...a4.�..sroN�•
Right-M Woi
Entire House
ProCalcs, LLC
P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-8825700 Email:
Job: Laffont Residence
Date: Mar 13, 2017
By: Tom Platania
Web: ww&.ProCalcs.Net License: CAC1815254 RTIN #0105474
1
2
3
4
5
Room name
Exposed wall
Room height
Room dimensions
Room area
WIC
24.0 ft
9.0 ft heat/cool
10.6 x 13.5 ft
141.8 ft2
LN
0 ft
9.0 ft heat/cool
2.0 x 2.0 ft
4.0 ft"'
Ty
Construction
number
U-value
(Btuh/R'-'F)
Or
HTM
Area (ft")
or perimeter (ft)
Load
(Btuh)
Area (ftz)
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
W . '-':
VjJ
-C
129=0sw
Block Wall 4-1
4A5-2ovd
Block'Wa114 T''
2'glazing clrlow-e
2 glazing clr.lowe
2'glazing cirlowe;
,11D0,.> ::
Block Wall4-1
10D v
2 glazing, cir low-e
2 glazing, clr low-e
2 glazing triow-e.
12B- sw ... _ •
10D-v
2 glazing, clr low-e
4A5-2ovd
;16X3Mtd
22A-tpm. _.
0:097
0.143
0.450
0 143
0450
0 450
"0.450
, .0:390
0.143
0.450
0.450
0.450
0.450
' -6.697,
0.143
0.450
0.450
0.450
'.0:408
1.180
' rie=
ne
ne
'se
`,se
''se
° se-
, se
sw
sw
sw
sw
sw
. nw
nw
nw
nw
nw
: -
.. -
"2.72
4.00
12.60
' 4.00
12,60
12t50
: A2s80
"_. 1092
4.00
12.60
12.60
12.60
12.60
" 2.72
4.00
12.60
12.60
12.60
1.18
33.04
:= 1:Bfi
2.97
26.52
2.9y
24.18
'24:18
. 25 20
:,1248
2.97
19.46
24.18
24.18
24.16
'. 1_86
2.971
19.16
26.30;
26.52
].0.0
0.00
24
98
0
0
0
;; 0
0
0
0
0
0
0
::` 24
71
0
0
0
. = .. 142
142
24
98
0
' - 0
0
0
0
0
0
0
0
0
0
' 24
71
0
0
0
142
24
'," '- , .66
390
0_
0
0
0
0
0
0
0
0
0
0
65
282
0
0
0
. - ..= 167
. 793
- _ -; i45
290
0
0,
0
0
-. 0'
, ; _ O
0
0
0
0
0
:' :`. ' 45.
210
0
0
0
: F 142
0
0
0
0
0
0
0
;.. 0
si 0
0
0
0
0
0
' . 0
0
0
0
0
4
_ 4
0
0
0
0
D
:: 0
p
0
0
0
0
0
0
. 0
0
0
0
0
' '4
0
"0
0
0
0
0:
0
r0
0
0
0
0
0
0
:_ 0
0
0
0
0
:5:
0
0
0
0
0
, p
0'-
. '0
0
0
0
0
0
0
0
0
0
0
4
0
W
TE�BlockWa84-1
C- .
F
6
c)AED excursion
-81
0
Envelope loss/gain
1763
650
5
4
12
a) Infiltration
b) Room ventilation
565
0
191
0
0
0
0
0
13
Internal gains: Occupants @ 230
Appliances/other
0
0
0
0
0
0
Subtotal (lines 6 to 13)
2328
841
5
4
14
15
Less external load
Less transfer
Redistribution
Subtotal
Duct loads
11 %
8%
0
0
0
2328
256
0
0
0
841
66
11 %
8%
0
0
-5
0
0
0
0
-4
0
0
Total room load
Air required (cfm)
2584
49
907
42
0
0
0
0
Cal
44+ wri9"" q t' Right-SufteO Universal 2017 17.0.19 RSU17939
�4CCA ...LaffontlWorking Drawings\Laffont Load Calcs.rup Calc = W8 Front Door faces: SE
8th
2017-Mar-15 10:28:30
Page 2
Ics
Right-M Wol
Entire House
ProCales, LLC
P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email:
Job: Laffont Residence
Date: Mar 13, 2017
By: Tom Platania
Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474
1
2
Room name
Exposed wall
Bath 2
0 ft
Utility
34.0 ft
3
Room height
9.0 ft heat/cool
9.0 ft heat/cool
4
5
Room dimensions
Room area
10.0 x 9.0 ft
90.0 ft'
11.0 x 12.5 ft
137.5 ftz
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area (ft2)
Load
number
(Btuhlft? "F)
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cooll
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
. W '
12B-0sw
-.0.097
'ne
.-2t72
. 1.86
; - ,co
0
---0
0
-0
- 0
0
11
MI
T-G
Block Wall 4-1
4A5-2ovd
Block Wall4 T
2 glazing, dr1oW-e
2 glazing dr low-e
0.143
0.450
0.143
-0.450
6," 456
ne
ne
': se
. se
•`- se
4.00
12.60
;4-M
12.80
12 60
2.97
26.52
, - .2:97
; 24.78,
24.18
0
0
0
0
0
0
0
0
0..
0
0
0
0
_; 0.:
0
0
0
- __ 0
•. 0
° 0
113
0
95
'' 0
0
113
0
-4
- 0
0
450
0_
294
0:
0
335
0
219
.0
0'
,
2glazing drlow-e
.6.450
,se
12:60
2520
0
•, . 0
0
•< 0
; 0
0
0
0,
11bv--
:: ,.:0.390
'se
.' ;T0 92
. ,12.48
.:: 0
, . ;:• Q
; <` -. :,0
. :0
; •'; 21
21
229,
'. •. '262
Block Wall 4-1
1013-v
0.143
0.450
sw
sw
4.00
12.60
2.97
19.46
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2 glazing, dr low -a
2 glazing, clrlow-e
2 glazing cir lower
129-0sw
Block Wail 4-1
0.450
0.450
0.450
0.097
0.143
sw
sw
sw
' nw
nw
12.60
12.60
12.60
2:72
4.00
24.18
24.18
24A8
. • 1:86
2.97
0
0
- 0
0
0
0
0
0
0
0
0
0
0
.' , , 0
0
0
0
0
.'- ' . 0
0
0
0
0
0
99
0
0
0
0
99
0
0
0
' , 0
396
0
0
0
: 0
294
W
yy!!
�--G
10D-v
0.450
nw
12.60
19.16
0
0
0
0
0
0
0
0
IL�C
2 glazing, drlow-e
4A5-2ovd
0.450
0.450
nw
nw
12.60
12.60
26.30
26.52
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
C '
F
.16X30-0td
22A-tpm -
10.408
1.180
. -
-
-_ - 1.1.8
33.04
;- 1:00
.. - 0..
,'90
0 90
_ 90
. 0
• .- 106
.._..- 0
?.
.: _ . ; ' . 90
-.. • 0
r:'1138
138
138
34
'
-. 1.123
137
0
6
c)AED excursion
-8
-221
Envelope loss/gain l
106
82
2656
1026
12
a) Infiltration
0
0
800
270
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
0
1000
Subtotal (lines 6 to 13)
106
82
3456
2296
Less external load
0
0
0
0
Less transfer
0
0
0
0
14
Redistribution
Subtotal
21
127
16
99
0
3456
0
2296
15
Duct loads
11%
8%
14
8
11%
8%
380
181
Total room load
Air required (cfm)
141
3
106
5
3836
73
2478
116
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
+b-'wrightsoft• Right -Suite® Universal 201717.0.1 9 RBU17939
A=', ...LaffonNWorking Drawings\Laffont Load Calcs.rup Calc = W8 Front Door faces: SE
2017-Mar-15 10:28:30
Page 3
4 - '�� Right4di Worksheet
Job: Laffont Residence
Entire House
Date: Mar 13, 2017
By: Tom Platania
ProCalcs, LLC
P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net
Web: www ProCalcs.Net License: CAC1815254 RTIN #0105474
1
Room name
Bath
Dining Room
2
Exposed wall
0 It
22.5 ft
3
Room height
9.0 It heaUcool
9.0 ft heat1cool
4
Room dimensions
1.0 x 50.0 ft
12.5 x 10.0 ft
5
Room area
50.0 ftz
125.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area (ftz)
Load
number
(Btuh/ft;"F)
(Btuh/ft-)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
W
126-0suv
0097
ne
2=72
1'86�
`.._0
0
0
0
0'
0
"'0
' 0
V�/
t-G
Block Wall 4 1
0.143
ne
4.00
2.97i
0
0
0
0
90
90
360
268
4A5 2ovd
0.450
ne
12 60
26.52
0
0
0
0
0
0
0
0
Block Wall 4 1
0 143
se •
4 00'
2.97
0
0
0
0
113
89
354
263'
11A-2
2 glazing.°cir►ow� ;
0450
se•i
12.60
24.18
0
0
0
0
0
.'. 0
0
0
2 gfaz�ng; dr low a
0.450
§e:
12.60
24;18
0
0.302
; 580`
glazing =cirlow-e-
M50
• se'
12 60
' 25 20
'0
]1D0 =;:
'0'.390
>se` .
10g2;
1248
.. 0
0
0 .:.
0
;:
0
=
0
0
0
Block Wall 4-1
0.143
sw
4.00
2.97
0
0
0
0
0
0
0
0
10D-v
0.450
sw
12.60
19.46
0
0
0
0
0
0
0
0
2 glazing, cirlow-e
0.450
sw
12.60
24.18
0
0
0
0
0
0
0
0
2 glazing, drlow-e
0.450
sw
12.60
24.18
0
0
0
0
0
0
0
0
2 glazing, cir low-e
0.450
sw
12.60
24.18
0
0
0
0
0
0
0
0
W . _;
126-0sw
009 :7
nw=
2 72'
....;1:86
Block Walt 4-1
0.143
nw
4.00
2.97
0
0
0
0
0
0
0
0
10D-v
0.450
nw
12.60
19.16
0
0
0
0
0
0
0
0
2 glazing, cirlow-e
0.450
nw
12.60
26.30
0
0
0
0
0
0
0
0
4A5-2ovd
0.450
nw
12.60
26.52
0
0
0
0
0
0
0
0
C
16X30 0td `.
0.;408
= .
118'
.. :"1.00
. 50
;; 50
59
'. 50
`;;..
125
`' '
:1'47
:'",
125
F
22A-tpm
1.180
-_.
33.04
0.00
50
0
,:
0
0
125
,.125
23
_ 743
0
6
c)AED excursion
1-48
1
165
Envelope loss/gain
59
2
1908
1402
12
a) infiltration
0
0
529
179
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
500
0
Subtotal (lines 6 to 13)
59
502
2437
1580
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
11
8
0
0
14
Subtotal
69
510
2437
1580
15
Duct loads
11%
8%
8
40
11%
8%
268
125
Total room load
77
550
2705
1705
Air required (afm)
1
26
51
80
Calculations approved by ACCA
to meet all requirements of Manual J 8th Ed
-1'1-'.wtrightsoft- RightSuite® Universal 2017 17A.19 RSU17939
2017-Mar-15 10:28:30
'CC0. ...LaffantlWorking DrawmgslLaffont Load Calcs.rup Calc = W8 Front
Door faces: SE Page 4
x�_��� .�• , RI ht-J® Worksheet Job: Laffont Residence
�:.=LYUV�IC g Date: Mar 13, 2017
;•��^• Entire House
By: Tom Platania
ProCalcs, LLC
P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474
1
Room name
Living Rm
FL RM
2
Exposed wall
24.5 ft
42.5 it
3
Room height
9.0 it heat/cool
9.0 ft heat/cool
4
5
Room dimensions
Room area
1.0 x 316.8 ft
316.8 ft2
1.0 x 230.8 ft
230.8 W
Ty
Construction
U-value
Or
HTM
Area (W)
Load
Area (W)
Load
number
(Btuh/ft2-°F)
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool I
Gross
WP/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
W.:.,
126-0sw
:A 097
%na
2:72,
... 9e8.6
0
-` :0
0
:; "0
Q
.. 0•
t-G
Block Wall 4-1
0.143
ne
4.00
2.97
9
9
36
27
0
0
0
0
11
4A5 2ovd
2glazing dr low e
2;glazing cir low-e,
2 glazing cir lows
0.450
6143
0 450
0450
6 450
ne
:'se
se
sse
se
12.60
4.00
12.60
1260
42.60
26.52
2.97
24.18
24a1�
25.20
0
203
0
24
" ` 13
0
0
5
2
0
57
0
, 302
. 169
0
49
.. 0
'- 580:.
338
0
20
0
' : o
0
9
4
0
' 0
0
1Block:Wa04 6
252
0
0
0
2
35144
: 48.4
0
= 0
11.D0 ', . ..
0.390
`se
10.92
_r, 12.48
.. , 21
21.
229
'-262
` 0
0
' . 0
0
Block Wall 4-1
10D-v
0.143
0.450
sw
sw
4.00
12.60
2.97
19.416
9
0
9
0
36
0
27
0
189
0
139
0
557
0
413
0
W "`
VVV���lll
2 glazing, clr low-e
2 glazing, cir low-e
2 glazing. cir low-e
12B-0sw
Block Wall 4-1
10D-v
2 glazing, dr low-e
0.450
0.450
0.450
0.097,
0.143
0.450
0.450
sw
sw
sw
nw
nw
nw
nw
12.60
12.60
12.60
... 27.2
4.00
12.60
12.60
24.18
24.1�8
24.1,8
.:.. <1,86
2.97
19.16
26.30
0
0
0
,:. .. • 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
• ; 0
0
0
0
0
24
26
.'' ,"." .,0
95
0
0
0
5
5
0
58
0
0
0
302
328
,. 0
231
0
0
0
580
629
., 0.
171
0
0
C ; ,-
4A5-2ovd
`1.6X30-Otd: _ - _
0.450
0:408
nw.
, -:-,.
12.60
:,1:18
26.52
'1;d0
0
,' ,, 317
0
' : •::.317,
0
373
0
: -317
37
; -231
0
231
464
272
977
"': 231
F
22A-tpm ... ., .,_
1.180
-_-
33.04
0.00
317
25
, ._ 809
0
231
43
1404
. 0.
6
c)AED excursion
127
148
Envelope loss/gain
2532
2105
4126
3868
12
a) Infiltration
576
195
1000
338
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants @ 230
2
460
0
0
Appliances/other
900
0
Subtotal (lines 6 to 13) I
3109
3660
5126
4206
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
10
8
0
0
14
Subtotal
3118
3668
5126
4206
15
Duct loads
11%
8%
343
289
11%
8%
564
332
F1Total
room load
3462
3957
5690
4537
Air required (cfm)
65
185
108
212
to meet all
wrightP
.8CA' Right -Suite® Universal 2017 17.0 19 RSU17939 2017-Mar-15 1 age 5
Page 5
s1CGA ...LaffontlWorking Drawings\Laffont Load Calcs.rup Caic = MJB; Front Door faces: SE 9
Job: Laffont Residence
�R cc, caks Right-J@ Worksh et
Date: Mar 13,2017
Entire House By: Tom Platania
ProCales, LLC
P.O. 13ox882032, Port Saint Lucie, FL34988 Phone: 772-882-5700 Email: tom@pmcales.net Web: wwww.ProCaics.Net License: CAC1815254 RTIN #0105474
1
1
Room name
Bedroom 1
AH
2
3
4
5
Exposed wall
Room height
Room dimensions
Room area
8.0 ft
9.0 ft heat1cool
1.0 x 156.5 it
156.5 ft2
0 ft
9.0 ft heat/cool
2.0 x 2.5 ft
5.0 ft2
Ty
Construction
U-value
Or
HTM
Area (W)
Load
Area (W)
Load
number
(Btuh/ft3-*F)
(Btuh/ft)
I or perimeter (ft)
(Bt h)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool-
Gross
N/P/S
Heat
Cool
6
11
W
LBlock
G
W-.
Block Wall 4-1
4A52ovd
wocklwan4-i'
2:glazing;-drIow-e,
0.143
0.450
:6,A43
-'0'450,
ne,
ne
ne
-se
�se
1- 21Z
4.00
12.60
---4--60
1260
1.86
2.97
26.52
2.97
.-24.18
0
J.- 0-
-0.
0
0
0
0
0
0
0
----0
0
'0
0
0
.0
0
.0
.0
.0
0
0
0
0
0
0
0
0
.1- 0
0
,0
0
0
'0
Jo
w
G
glazing,�clr ow
2 -6
Zgjazing 16W-e;r.-'
11DO
0
0.460
Eno
se
I. sw
S6
12.60
-1260
--:24:16
-25 20
12,48
0
:0
0
0
'0
.0
0
0
0''
.0
�-o
'0
0
�O
0
0
�0
--G,
_Z
Block Wall 4-1
1013-v
2 glazing, dr low-e
2 glazing, dr low-e
2 glazing, dr low-e
0.143
0.450
0.450
0.450
0.450
sw
sw
sw
sw
sw
4.00
12.60
12.60
12.60
12.60
2.97
19.46
24.19
24.18
24.18
72
0
12
0
0
60
0
3
0
240
0
151
0
0
178
0
290
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
V
12M S-W
Block Wall 4-1
-6.691
0.143
nw,
nw
2.72
4.00
1.8
2.97
0
0
...0
;�' - 0
0
:. -b
0
r -
0
0
0
-
6
0
0
0
--.
0
0
10D-v
2 glazing, dr low-e
4A5-2ovd
16)d0-0td,:
22A-tpM
0.450
0.450
0.450
.-10;406,,'-
1.180
nw
mv
nw
12.60
12.60
12.60
1 18.1
33.04
19.16
26.30
26.5
.00
0.00
6
0
0
0
157
157
0
0
0
1 ',',157
8
0
0
0
-:,..'184
264
0
0
0
7156
0
0
0
0
.5
0
0
0
6
0
0
0
0
6
0
s
0
0
5
0
C
F
6
c) AED excursion
63
0
Envelope loss/gain
840
688
6
5
12
a) Infiltration
b) Room ventilation
188
0
64
0
0
0
0
a
13
Internal gains: Occupants @ 230
0
0
0
0
Appliances/other
0
0
Subtotal (lines 6 to 13)
1028
751
6
5
Less external load
0
0
0
0
14
Less transfer
Redistribution
Subtotal
0
179
1207
0
82
833
0
-6
0
0
-5
0
15
Duct loads
11%1
8%
133
66,
11%
8%
0
0
Total room load
Air required (cfm)
1340
25
899
42
0
0
0
01
S a
wrights'Oft' Right -Suite® Universal 2017 17.0.19 1 RSU17939 2017-Mar-15 10:28:30
Page 6
... LafforitlWorking DravAngski-aflont Lead Calos.rup Calc=MJ8 Front Door faces: SE
�. p.
. I
Right-M Worksheet
Job: Laffont Residence
°='•--��
Enure House
Date: Mar 13, 2017
By: Tom Platania
ProCalcs, LLC
P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-8825700 Email: tom(�procalcs.net
Web: www.PmCalcs.Net License:
CAC1815254 RTIN ft0105474
1
Room name
Hall
Kitchen
2
Exposed wall
0 ft
15.5 ft
3
Room height
9.0 ft
heaUcool
9.0 ft heat/coal
4
Room dimensions
4.5 x
14.5 ft
1.0 x 195.0 ft
5
Room area
65.3 ftz
195.0 ft'
Ty
Construction
U-value
Or
HTM
Area OF)
Load
Area (ftj
Load
number
(BtuhtWF)
(Btuh/ft-)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
I Gross
WP/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
W ;"
;126-0sw:-: "•.
0097
._net
2:72:
1a16
0
0
:.'; .0
,`' 0,
.,:': 0
', 0
s0
..... 0.
Block Wall 4-1
0.143
ne
4.00
2.97
0
0
0
0
59
18
73
54
4A5 2ovd
0.450
ne
12.60
26.52
0
0
0
0
40
01.
507
1066
""
?Block Wall4 1
0:143
.se•
4 00,
2:97
0
0
0
0
0
_
0
.0
11
2 alazma_;driow�•..
OA90
rse
1260:
24:18
, ;'n
n
-0
'11DO
0390
se`;
"10 c
Block Wall 4-1
0.143
sw
4.(
10D-v
0.450
sw
12.E
2 glazing, cir low-e
0.450
sw
12.(
2 glazing, dr lowe
0.450
sw
12.(
2 glazing, dr lowe
0.450
sw
12.E
12B=0sw. ".
0 097
nw,'
Z i
Block Wall 4-1
0.143
nw
4.(
IOD-vglazing,
0.450
nw
12.E
2
2 glazing, clr lowe
0.450
nw
12.E
4A5-2ovd
0.450
nw
12.E
C •
IOX30'-0td .. _
;0408
,.,, i=
1 1
F _
22A7tpm _ _
- 1"160
-
33.(
MI
24As
0
0
0
0
0
'0`261.20
0
0'
.12:48
:0
t 0.
0
0 ,'
0 :'
. : `0
' " "0
0
2.97
0
0
0
0
0
0
0
0
19.46
0
0
0
0
0
0
0
0
24.18
0
0
0
0
0
0
0
0
24.18
0
0
0
0
0
0
0
0
24.18
0
0
0
0
0
0
0
0
2.97
0
0
0
0
81
61
244
161
19.16
0
0
0
0
20
0
253
385
26.30
0
0
0
0
0
0
0
0
26.52
0
0
0
0
0
0
0
0
Y00
65
65
195
_' "-1:95
. " -230
195':
0.00.
65
0
_ 0
0 _.
195
_ 16
512
_. 0
61
c)AED excursion
-6
-301
Envelope, loss/gain
77
59
1819
1580
12
a) Infiltration
0
0
365
123
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants Q 230
0
0
1
230
Appliances/other
0
1200
Subtotal (lines 6 to 13)
77
59
2183
3133
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
-77
59
0
0
14
Subtotal
0
0
2183
3133
15
Duct loads
11%
8%
0
0
11%
8%
240
247
Total room load
0
0
2424
3381
Air required (cfm)
0
0
46
158
wrightsOft^ Right -Suite® Universal 2017 17.0.19 RSU17939
ACC'Q` ...LaffontlWorking Drawings\Laffont Load Calcs.rup Calc = MJ8 Front Door faces: SE
2017-Mar-15 10:28:30
Page 7
ri Job: Laffont Residence
jCS Right-M Worksheet
�` Entire House Date: Mar13,2017
ProCalcs, LLC By: Tom Platania
P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tomQa procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474
1
Room name
CL
2
3
4
5
Exposed wall
Room height
Room dimensions
Room area
2.5 ft
9.0 ft heatIcool
9.0 x 2.5 ft
22.5 ft2
Ty
Construction
number
U-value
(Btuh/ftz "F)
Or
HTM
(Btuh/fo
Area (ft2)
or perimeter (ft)
Load
(Btuh)
Area
or perimeter
Load
Heat
Cool
I Gross
N/P/S
Heat
Cool
Gross
WP/S
Heat
Cool
6
11
1N =
yJ
I--G
126 0sw, -...
Block Wall 4-1
4A5-2ovd
Block Wall 4 1 ' :'
2glazing clrloW-e
2 glazing, ciriow -e.
2 glazing clr.low�e
11 D0' ; :., :: =
:.. 0 097
0.143
0.450
0.143
'0450
0.450
.0.450
0 390
,.. ne
ne
ne
'se
;se
`"se
,-se
:.se
'2:72
4.00
12.60
4.00
12:60
I2.60
: 12.60
_ 10: 2
2.97,
26.52
2.97,
241$
24c18
25:20
a2f4.8
0
0
0
0
0
' : 0
> . 0
0
0
0
0
0
lJ
0.:
0
0
0
0
0
0
0
0
0
0
-;- 0
` ` -- 0
D
c 0
:... '0
, _ '•
.:
"
;-
.:
.: .
Block Wall 4-1
10D-v
2 glazing, clr low-e
2 glazing, cirlow-e
2 glazing clr low-e
0.143
0.450
0.450
0.450
0.450
sw
sw
sw
sw
sw
4.60
12.60
12.60
12.60
12.60
2.97'
19.46
24.19
24.18
24.18
23
0
0
0
0
23
0
0
0
0
90
0
0
0
0
67
0
0
0
0
VII •: _
yyJJ
�-G
128 0
Block Wall 4-1
0
0.143
nw
._`
4.00
,
2.97
0
0
.0-
0
0
0
10D-v
2 glazing, cir low-e
4A5-2ovd
0.450
0.450
0.450
nw
nw
nw
12.60
12.60
12.60
19.1(§
26.30
26.52
0
0
0
0
0
0
0
0
0
0
0
0
C
F . . .
16X30.0td _
22A-tpm .
0:408
1.180
:_ -
....-.
1:18
33.04
' ; 1.00
0.00
=;: 23
.-- - 23
- _ 23
3
.. 27
83
; . 22
_ 0
6
c)AED excursion
-10
Envelope loss/gain I
199
80
12
a) Infiltration
b) Room ventilation
59
0
20
0
13
Internal gains: Occupants @ 230
0
0
Appliances/other
0
Subtotal (lines 6 to 13) I
258
100
Less external load
0
0
14
15
Less transfer
Redistribution
Subtotal
Duct loads
11 %
8%
0
258
0
0
0
-100
0
0
FI--
Total room load
Air required (cfm)
0
0
0
0
I
Calculations approved by ACCA
to meet all requirements of Manual J 8th Ed
WI'1 htSOft` g 2017-Mar-1510:28:30
Ri ht-Suite® Universal 2017 17.0. 9 RSU17939
e` At...LaffontlWorking DrawingslLaffont Load Calcs.rup Calc = MJ8 � Front Door faces: SE Page 8
The following pages summarize ft
ACCA Manual J8 calculation pros
given to ProCalcs in the form of di
ProCalcs may make assumptions
accurate for the location of concer
contractor to verify the design con
Any load calculations provided in i
provided by the party submitting a
does not independently verify that
and any calculations made by Pro
third parties. ProCalcs makes no c
complete.
ProCalcs, LLC.
DISCLAIMER
heat gain and heat loss of the building using the
lure. The calculations are based on the information
Kings, sketches, and interviews. In certain cases,
3out design conditions that may or may not be
It is the responsibility of the installing HVAC
Lions before equipment purchase and installation.
following pages are based upon information
articular project to ProCalcs. ProCalcs has not and
ie data provided to ProCalcs is correct or complete,
3Ics are based upon the information provided by
iim that the information given to us is correct or
ProCalcs utilizes WrightSoft Residential 15.0 which is an ACCA Certified and ASHRAE
recommended computer program to determine the heating and cooling loads presented
in this report, and is therefore veryaccurate. If the information given to ProCalcs is
accurate, and the building is built as per the plans submitted, then the load calculations
presented in this report can be assumed to be accurate. A licensed mechanical
contractor may use these calculations as a starting point in system sizing and selection.
ProCalcs does not provide archite
or for use by contractors or constr
ProCalcs works with architectural
connection with their designs of hi
layout installed on -site DOES NO"
ProCalcs, then ProCalcs cannot a
duct design. All branch ducts Ml
delivery to each room. Final HV/
HVAC contractor. Many factors be
to final system selection and desic
availability and selections, system
distribution and cycling, Uniform 8
requirements, and many other sta
Society of Heating, Refrigeration,
ProCalcs therefore assumes nc
system design. Various modific
may have occurred after this Di
would require that this Design
accurate. After reviewing ProCc-
installation, please inform ProC
assumptions and
tural or engineering plans or diagrams for the public
ation companies as final "construction documents".
nd engineering firms and with contractors in.
rting and air conditioning systems. If the HVAC duct
match the Manual D duct design prepared by
d will not guarantee the performance of any altered
;T have adjustable dampers to ensure proper air
sizing and selection should be done by a licensed
and the scope of this report must be considered prior
i, such as: exact equipment
:ontrols and location of controls, system air
ilding Code requirements, Uniform Mechanical Code
lard design conventions as listed by the American
id Air Conditioning Engineers (ASHRAE).
liability for final equipment selection or final
ations to the information provided to ProCalcs
sign Support information was prepared, which
oupport information be modified in order to be
Ics report, and prior to any system purchase or
alcs in writing of any changes which may alter the
calculations contained in this report._