HomeMy WebLinkAboutFLEXIBLE AIR DUCKSCANNED www.quietflex.com dAr FILE. COP SS 1 Flexible Air Duct' Product Specifications and Key Features Quietflex® manufactures flexible duct for the commercial, residential and manufactured home industries. We produce 3" through 22" duct in R4.2, R6 and R8 insulation thickness. • Johns Manville Formaldehyde -free fiber glass insulation • GREENGUARD® Certified insulated products • Galvanized metal core reinforcing • Oversized core to fit on collars and register boxes • Weather -resistant packaging • Easy -to -carry package: Up to 10" bags are strapped to form a pair • Available in boxes and bags • 12.5; 25' and 50' and custom lengths available • HUD/FHA standards 515.2.1, Paragraph B • NFPA standards 90A and 90B • BOCA, City of Chicago, meets most federal, state and local codes and standards • ETL Listed/Approved to UL 181 "Rip Stop" Silver Jacket The Quietflex Rip -Stop Silver Jacket Flex Duct has a metallic, polyester -vapor barrier with a special "rip -stop" scrim reinforcement. BAG. 30 40 4.2 ' 70 80 6.6 84 85 U f(` OX BAG 4" 5" 6" 8 9" lo" 12" 1 14" 1 16" 18" AC 50 60 6.0 • • • • • • V 10 20 1 4.2 .'.a ._ flr 54 65 8.0 Mobile Horne The Quietflex Mobile Home Flex Duct has an extra heavy-duty, UV -Inhibited, polyethylene -vapor barrier and complies with HUD standards for outdoor use with mobile homes. SERIES R-VALUE.•,®® DIAMETER Uninsulated Air Connector SERIES DIAMETER _ ®W®W®WW . „` ®�®�®�� =000000000aoa0000. Installation Notes: • Not to be installed in lengths greater than 14'. • Not to be used to vent appliances for cooling, heating, and clothes drying unless approved and recommended by appliance manufactures Performance Data (Applies to all products) • Rated Positive Pressure 10" W.C. per UL 181 • Rated Negative Pressure 1/2" W.C. per UL 181 • Velocity 6,000 FPM • Temperature Range —20°F to 200°F (Intermittent) / —20°F to 180°F (Continuous) • Flame. Spread/Smoke Developed Less than 25/1-ess than 50 LIMITED WARRANTY I LIMITATION OF LIABILITY I DISCLAIMER OF UNSTATED WARRANTIES The flexible air duct is warranted by Quietflex Manufacturing Company, L.P., for ten (10) years against defects in material and workmanship. This warranty is for exchange. of duct only and does not include installation. - - WARRANTY EXCLUSIONS Warranty is excluded if flexible air duct is used in the follGwing installations / applications; - 1. Where duct is exposed to direct or indirect light - 2. Where duct is used on the high— pressure side of variableair— volume (VAV).systems. LIMITATION OF LIABILITY Quietllex's liability for damages, whether in contract, in tort, under warranty, in naglNence orotherwise, Shall not exceed the return of the amount of . the purchase price paid for the Quietflex products: Quietflex shall not be tfable far specisl,andirect orconsorluentiai damages:; Specitii*fon and performance data listed herein are sublect to change wi!hout jtot4cc( DISCLAIMER OF UN�WARf2AN TATM ` F lE5a s` `st # '(ltrswartanfytsVhsop�tv�ri�dr�i ot;Q t�,p,)3 *�1"j�` •`r�".a .' ��'��"'� Il'�"dr�nh�ct�f�Yn' 1 '� t `' ..` dfQuteiltexMan3k"ict'ptr dig,. o . ��'�E,.,...'r �.. �.-.,;.. •-.e«�.'!: � . k:.,. ....�:" ..���::�"'t�i.a-a "?:�:�,`'_""i, �'f*:.-:'s-�:;7-.:-'t www.quietflex.com Quietflex Manufacturing Company, L.P. 4518 Brittmoore Road Houston, Texas 77041 Phone 713.849.2163 Fax 713.849.0753 Toll Free 877.694.3669 Specification Sheet Ultra*Duct'O Black Duct Mari PRODUCT DESCRIPTION Basic Use: Ultra*Duch Black Duct Board is a rigid board designed for fabrication into supply and return air HVAC duct work. The product can be used in heating and cooling systems which operate at velocities up to 5,000 fpm (25.4 m/s), temperatures up to 250`17 (121'C) and maximum internal pressures of ± 2" (51mm) water gauge. Benefits: This product is strong, resistant to mold, bacteria and microbial growth, and easy to clean. In addition, Ultra*Duct Black provides excellent thermal properties, absorbs unwanted crosstalk, equipment and air rush noise, and exhibits low air flow resistance. It also meets all applicable fire resistance standards and building code requirements. The product can be precision cut using both manual and automatic cutting equipment. Composition and Materials: Composed of resin -bonded glass fibers with a reinforced foil laminate air barrier/vapor retarder facing applied to the outside surface and a fiber glass textile mat bonded to the airstream surface. The airstream surface contains an EPA -registered antimicrobial agent in order to reduce the potential of microbial growth that may affect this producti The antimicrobial properties are intended to protect only this product. Limitations: Ultra*Duct Black is not to be used under poured concrete slabs or to convey exhaust fumes, solids or corrosive gases. Ducts exposed to the weather must be weather protected and reinforced per industry standards. Ducts must not be used as vertical risers more than two stories in height. They must not be used adjacent to high -temperature heating coils. Insulation should be kept clean and dry during shipping, storage and system operation. i Sizes: See table on back for available sizes. Contact CertainTeed for availability and minimum order quantities. 11 INSTALLATION Ultra*Duct Black must be fabricated and installed in accordance with the NAIMA or SMACNA Fibrous Glass Duct Construction Standards and all closure systems must meet the requirements of UL 181A. The installed duct system should be purged prior to occupancy to remote any loose material. i AVAILABILITY AND COST Manufactured and sold throughout the United States and Canada. For availability and cost, contact your local distributor or call CertainTeed Sales Support Group in Malvern, PA at 800-233-8990. WARRANTY Refer to CertainTeed's Limited Lifetime Warranty for Ultra*Duct Black Di ct Board (30-32-113). MAINTENANCE An inspection and maintenance program for the HVAC system is recommended to ensure optimum performance. Use NAIMA guidelines for duct cleaning methods and procedures. TECHNICAL SERVICES Technical assistance can be obtained either from your local CertainTeed sales representative, or by calling CertainTeed Sales Support Group in Malvern, PA at 800-2 3-8990 CertainTeed R CertamTeed Ultra*Duci� '2 Product Black Duct Board " �1 Manufacturer CertainTeed Corporation —^ a Address ` ' 20 Moores Road � � � 4j Malvern, PA i9355" Phone 610-341 7000 * 800-233-8990 5 Fax q ;; " 610' 341 7571 � �4 Y Website www.certainteed.com/insulation TECHNICAL DATA AVAILABLE Product Type Thickness Width Length No. Boards Per Edge in:.'"°.; mm in: mm •in. = mm .Carton _ Pallet 475 ' Shipp or 1 (' 25 " 120 ''. 3048 6 44 96 _ `- 2438 :- 6 . Butt Edge 48 1219 Shiplap or ' 120 3048 4 800 _: Butt Edge 1Yz 38 30 96 2438 4 3 - ButtEdge 2 51 120 3048 3°.; 22 Product Type ACOUSTICAL PERFORMANCE Absorption Coefficients @ Octave Band Frequencies (Hz) T EI. Thickness 125 ,,250'_ . 500 ;- -1000- 2000 4000- NRC In. 475' 1 =:25 0.07 ; - 0.2li 0.63 ='. 0 90 .`' 0.97 1.00 0.70 1 Yz 38 010 0 42 : 0.91 104 1.04 f.04 % 0.85 i 2 51 017 0 63' :' 110 105 i 1.04 ,1 CIE 'o-. 0.95 Sound absorption tested in accordance with ASTM C423 using Type A mounting per ASTM Product K-Value C-Value R-Value Ei. Thickness Btu•in W Btu W Btu W ._ • „ h•ft'•°F me'G.,_ heft. F m?. C ,: heft:..F mz. G in. mm .' 475 1 25 ': = 0.23 0 033: v; 0.23 1' 3i 4.3 0 76 ` =. 38 0.15 D 87 - 6.5 115 800 2 51 0.12 0'65 ', 8.7 1.53',°. `• Thermal conductance (C) and resistance (R) values are derived from the material thermal conductivity (K) value. Tested in accordance with ASTM C518 at 75°F (24°C) mean temperature. MENBOP Seal and Insulate ':,'•., ,' with NAIMA • , , ENERGY STAR -Mir1( SAINT-GOBAI,N CertainTeed Corporation ROOFING • SIDING • TRIM • DECKING • RAILING • FENCE • GYPSUM • CEILINGS a INSULATION 20 Moores Road Malvern, PA 193SS Professional: 800-233-8990 Consumer: 800-782-8777 certainteed.eom 011116 CertainTeed Corporation, Printed in the USA, Code No. 30-34-029 6;ietftex FLEX DUCT PRODUCT: RIP STOP SILVER JACKET SUBMITTAL DRAWING Metalized :Vapor; Barrier. VAPOR BARRIER - The Quietflex Rip Stop Silver Jacket Flex Duct has a metalized polyester -vapor barrier with a special "rip stop" scrim reinforcement. - Vapor Transmission: 0.05 perms - R4.2, R6 and R8 certified by ETL and the Air Diffusion Council using ASTM C-518 at installed thickness of insulation - Made of formaldehyde free materials - Two layers of polyester film encapsulate a - Rated positive pressure is 10" W.C. and ni - Rated maximum air velocity is 6000 FPM SURFACE BURNING CHARACTERISTICS - Flame spread: Less than 25 - Smoke developed: Less than 50 - Class 1 rated duct assembly OPERATING TEMPERATURE RANGE . - -20 deg F to 180 deg F - Continuous - -20 deg F to 200 deg F - Intermittent zed or bronze coated wire helix pressure is 1/2" W.C. per the UL 181 standard CONFIGURATIONS - Diameters available: W-10", 1211, 14", 16", 18", 20", 22" - Lengths available: 25 ft 'ALS - ETL Listed/Approved to UL 181 Standard - NFPA standards 90A and 90B - HUD/FHA standards 515.2.1 Paragraph B - Meets most federal, state and local codes and standards - GREENGUARD certified entire duct construction Made in the USA Job Name Submitter:l Date: Location Class 1 Insulated Flexible Air Duct Contractor Metalized Polyester vapor barrier/ Engineer Silver jacket Architect QFSD-002-01 Quietflex Manufacturing Company LP, 4518 Brittmoore IRd, Houston, TX 77041, Telephone: 713.849.2163 0110 Fax: 713.849.0753 Toll Free: 877.694.3669 www.auietflex.com Load Short F �°- 03; ``� Mlcarethcmh,rnaplati¢ Entire House ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882 5700 Email: For: 3827 St. Mark Dr., Fort Pierce, FL 34982 Htg Clg Outside db (OF) 42 90 Inside db (OF) 70 72 Design TD (OF) 28 18 Daily range - L Inside humidity (%) 30 50 Moisture difference (gr/lb) 1 68 Method Construction quality Fireplaces Job: Laffont Residence Date: Mar 13, 2017 By: Tom Piatania /�,a`.aam P�iu2 License: CAC1815254 RTIN #0105474 Infiltration Simplified Semi -loose HEATING EQUIPMENT COOLING EQUIPMENT Make Make Rheem Trade Trade RHEEM Model Cond RA1430AJ1NA AHRI ref Coil RH1T3621MTANJA AHRI ref 7491227 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 8.0 kW Sensible cooling 24000 Btuh Heating output 27297 Btuh Latent cooling 6000 Btuh Temperature rise 50 OF Total cooling 30000 Btuh Actual air flow 497 cfm Actual air flow 1000 cfm Air flow factor 0.019 cfm/Btuh Air flow factor 0.047 cfm/Btuh Static pressure 0.60 in H2O Static pressure 0.60 in H2O Space thermostat Load sensible heat ratio 0.79 0 ROOM NAME Area (ft2) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) Clg AVF (cfm) Bedroom 2 209 4007 2875 76 134 WIC 142 2584 907 49 42 LN 4 0 0 0 0 Bath 2 90 141 106 3 5 Utility 138 3836 2478 73 116 Bath 50 77 550 1 26 Dining Room 125 2705 1705 51 80 Living Rm 317 3462 3957 65 185 FL RM 231 6690 4537 108 212 Bedroom 1 157 1340 899 .25 42 AH 5 0 0 0 0 Hall 65 .0 0 0 0 Kitchen 195 2424 3381 46 158 CL 23 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft° Right -suites Universal 2017 17.0.19 RSU17939 2017-Mar-15 10:28:30Page ACCk ...Laffont\Working Drawings%Laffont Load Calcs.rup Calc = MJ8 Front Door faces: SE 1 a Entire House 1749 26266 21395 497 1000 Other equip loads 0 0 Equip. @ 1.00 RSM 21395 Latent cooling 5611 TOTALS 1749 Calculations approved by wnghtsoft' Right-Suite®Unnrersal 201717.0.19 ACCA ...LaffontlWorking DrawingslLaffant Load Calcs.rup Calc = MJ8 I 26266 1 27006 1 497 ' 1000 to meet all requirements of Manual J 8th Ed. Door faces: SE 2017-Mar-15 10:28:30 Page 2 Building Analysis 'Wcareat he mb:ln9 preae Entire House ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email-.... Job: Laffont Residence Date: Mar 13, 2017 By: Tom Platania Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 For: Laffont Residence 3827 St. Mark Dr., FortPierce, FL 34982 Location: Indoor: Heating Cooling Fort Pierce, FL, US Indoor temperature (°F) 70 72 Elevation: 25 ft Design TD (°F) 28 18 Latitude: 27°N Relative humidity (% 30 50 Outdoor: Heating Cooling Moisture difference ()gr/lb) 1.1 67.9 Dry bulb (°F) 42 90 Infiltration: Daily range °F) - 15 (L ) Method Simplified Wet bulb (°F� - 78 Construction quality Semi -loose Wind speed (mph) 15.0 7.5 Fireplaces 0 Component Btuh/ftz Btuh % of load Walls 4.0 5847 22.3 Glazing 12.6 3840 14.6 Doors 10.9 459 1.7 Ceilings 1.2 2061 7.8 Floors 3.8 6691 25.5 Infiltration 2.6 4764 18.1 Ducts 2605 9.9 Piping 0 0 Humidification 0 0 Ventilation 0 0 Adjustments 0 Total 1 1 26266 100.0 Component Btuh/ftz Btuh % of load Walls 2.9 4336 20.3 Glazing 24.0 7323 34.2 Doors 12.5 524 2.4 Ceilings 1.0 1748 8.2 Floors 0 0 0 Infiltration 0.9 1609 7.5 Ducts 1564 7.3 Ventilation 0 0 Internal gains 4290 20.1 Blower 0 0 Adjustments 0 Total 21395 100.0 Latent Cooling Load = 5611 Btuh Overall U-value = 0.247 Btuh/W-OF Data entries checked. Glazir c Gla 2017-Mer--15 10:28:30 "� vvrightSOft' Right -Suite® Universal 2017 17.0.19 RSU17939 Page 1 ACCK ...Laffont\Working DrawingMLaffont Load Calcs.rup Calc = MJ8 (Front Door faces: SE i .. Project Summ RD" CS Entire House 'Wcart: themhdng piece_ ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: For: Laffont Residence 3827 St. Mark Dr., Notes: Above All Air H 3233 Route 1 Fort Pierce, FL Weather: Winter Design Conditions Outside db 42 OF Inside db 70 OF Design TD .28 OF Heating Summary Structure 23661 Btu Ducts 2605 Btu Central vent (0 cfm) 0 Btu (none) Humidification 0 Btu Piping 0 Btu Equipment load 26266 Btu Infiltration Method Construction quality Fireplaces Heating Area (ft2) 1749 Volume (ft3) 15743 Air changes/hour 0.59 Equiv. AVF (cfm) 155 U D1749 15143 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat Job: Laffont Residence Date: Mar 13, 2017 . By: Tom Platania Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 Pierce, FL 34982 & Cooling, LLC Pierce, FL, US Summer Design Conditions Outside db 90 OF Inside db 72 OF Design TD 18 OF Daily range L Relative humidity 50 % Moisture difference 68 gr/lb Sensible Cooling Equipment Load Sizing Structure 19831 Btuh Ducts 1564 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data Rate/swing multiplier Equipment sensible load 1.00 21395 Btuh Latent Cooling Equipment Load Sizing Structure 4352 Btuh Ducts 1259 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 5611 Btuh .31 Equipment total load 27006 Btuh 81 Req. total capacity at 0.80 SHR 2.2 ton 100 EFF 8.0 kW 27297 Btuh 50 OF 497 cfm 0.019 cfm/Btuh 0.60 in H2O Cooling Equipment Summary Make Rheem Trade RHEEM Cond RA1430AJl NA Coil RH1 T3621 MTANJA AHRI ref 7491227 Efficiency 13.0 EER, 16 SEER Sensible cooling 24000 Btuh Latent cooling 6000 Btuh Total cooling 30000 Btuh Actual air flow i 1000 cfm Air flow factor 0.047 cfm/Btuh Static pressure 0.60 in H2O Load sensible heat ratio 0.79 Calculations approved by AaCA to meet all requirements of Manual J 8th Ed. �y, Wrl IhtSogt° 2017-Mar-1510:28:30 Y' g Right Suite® Universal 201717.0.19 RSU17939 Page 1 AOCK ...Laffont\Working Drawings\Laffont Load Calcs.rup Calc = M.18 Front Door faces: SE 1i 1VR@) I Right-JO Worksheet Job: Laffont Residence `�` °F•�� °° ° Entire House Date: Mar 13, 2017 ProCalcs, LLC By: Tom Platania P.O. Box 88203Z Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Entire House 202.5 ft 9.0 ft 1749.3 ft' Bedroom 2 29.0 ft 9.0 ft heat/cool 15.5 x 13.5 ft 209.3 ft2 Ty Construction number U-value (Btuh/ft L"7) Or HTM (Btuh/M Area (W) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cooll Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W '. UAl t-G - 12B-0sw Block Wall 4-1 4A5-2ovd Block'Wall4 1 .' 2 glazing dr low e 2 glazing dr toinr 2 glazing drlow e 116 Block Wall 4-1 10D-v 2 glazing, dr lower 2 glazing, drlow-e 2 glazing cir low-e 126 Osw . Block Wall 4-1 10D-v 2 glazing, cir low-e 4A5-2ovd 16X30-0td . ' 22A tpm 0. 09Z 0.143 0.450 -0 143 0 450 0 450 0 450 0 390.. 0.143 0.450 0.450 0.450 0.450 0.097 0.143 0.450 0.450 0.450 0 408 1.180 ';, ne ne ne sa' ' se •.se -`se §e sw sw sw sw sw ':nw nw nw nw nw ,':- 2 72 4.00 12.60 '4 00 -A 2. 17:60 72:60 10.92 4.00 12.60 12.60 12.60 12.60 2:72 4.00 12.60 12.60 12.60 1.18 33.04 1 t3Q 2.97 26.52 2:97 .24:18 24.18 25:20 . ' 12.48 2.97 19.46 24.18 24.18 24.18 1:86 2.97 19.16 26.30 26.52 ,. 1:00 0.00 °. ' 24 368 40 {509 20 48 13 ,42 414 40 12 24 26 24 485 20 24 37 :. " -1749 1749 24 327 0 ' _ 385 4 10 2 .::. 42 312 0 3 5 5 ". .24,- 404 0 0 0 , '..,1749 203 `: , 65 1311 507 . ` 1542 252 605 169. ... ;; 459 1248 507 151 302 328 65 1616 253 302 464 .,. r2061' 6691 -' . , 45 974 1066 ' 1145 484 1161 '' 338 , • 524 927 782 290 580 629 >' .. 45 1200 385 631 977 ."' •':.1748' 0 U` 0 0 ;, 0 :- 0 ;` 0 "- 0 _., 0 122 40 0 0 0 '_ : ` .. 0 140 0 24 0 ' 209 209 0 0 0 _; 0.. 0 0 0 0 81 0 0 0 0 0 116 0 0 0 • , ,;: 209 29 0° 0 0 0 0 0 0 p 326 507 0 0 0 0 462 0 302 0 ,•'. 247' - 958 : - , 0 0 0 - 0, 0 0. 0 0 242 782 0 0 0 0. 344 0 631 0 209 0 W. C _ F 6 c)AED excursion I - 0 173 Envelope loss/gain 18898 13931 2802 2381 12 a) Infiltration b) Room ventilation 4764 0 1609 0 682 0 230 0 13 Internal gains: Occupants aQ 230 Appliances/other 3 690 3600 0 10 0 Subtotal (lines 6 to 13) 23661 19831 3484 2612 14 151 Less external load Less transfer Redistribution Subtotal Duct loads 11% 8% 0 0 0 23661 2605 0 0 0 19831 1564 11% 8% 0 0 125 3609 397 0 0 53 2665 210 Total room load Air required (cfm) 262 66 497 21395 1000 4007 76 2875 134 -#- wrightsoft" Right -Suite® Universal 2017 17.0.19 RSU17939 ACGA LaffonttWorking Drawings\Laffont Load Calcs.rup Catc = MI8Front Door faces: SE 2017-Mar-15 10:28:30 Page 1 tiv�...a4.�..sroN�• Right-M Woi Entire House ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-8825700 Email: Job: Laffont Residence Date: Mar 13, 2017 By: Tom Platania Web: ww&.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area WIC 24.0 ft 9.0 ft heat/cool 10.6 x 13.5 ft 141.8 ft2 LN 0 ft 9.0 ft heat/cool 2.0 x 2.0 ft 4.0 ft"' Ty Construction number U-value (Btuh/R'-'F) Or HTM Area (ft") or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W . '-': VjJ -C 129=0sw Block Wall 4-1 4A5-2ovd Block'Wa114 T'' 2'glazing clrlow-e 2 glazing clr.lowe 2'glazing cirlowe; ,11D0,.> :: Block Wall4-1 10D v 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing triow-e. 12B- sw ... _ • 10D-v 2 glazing, clr low-e 4A5-2ovd ;16X3Mtd 22A-tpm. _. 0:097 0.143 0.450 0 143 0450 0 450 "0.450 , .0:390 0.143 0.450 0.450 0.450 0.450 ' -6.697, 0.143 0.450 0.450 0.450 '.0:408 1.180 ' rie= ne ne 'se `,se ''se ° se- , se sw sw sw sw sw . nw nw nw nw nw : - .. - "2.72 4.00 12.60 ' 4.00 12,60 12t50 : A2s80 "_. 1092 4.00 12.60 12.60 12.60 12.60 " 2.72 4.00 12.60 12.60 12.60 1.18 33.04 := 1:Bfi 2.97 26.52 2.9y 24.18 '24:18 . 25 20 :,1248 2.97 19.46 24.18 24.18 24.16 '. 1_86 2.971 19.16 26.30; 26.52 ].0.0 0.00 24 98 0 0 0 ;; 0 0 0 0 0 0 0 ::` 24 71 0 0 0 . = .. 142 142 24 98 0 ' - 0 0 0 0 0 0 0 0 0 0 ' 24 71 0 0 0 142 24 '," '- , .66 390 0_ 0 0 0 0 0 0 0 0 0 0 65 282 0 0 0 . - ..= 167 . 793 - _ -; i45 290 0 0, 0 0 -. 0' , ; _ O 0 0 0 0 0 :' :`. ' 45. 210 0 0 0 : F 142 0 0 0 0 0 0 0 ;.. 0 si 0 0 0 0 0 0 ' . 0 0 0 0 0 4 _ 4 0 0 0 0 D :: 0 p 0 0 0 0 0 0 . 0 0 0 0 0 ' '4 0 "0 0 0 0 0: 0 r0 0 0 0 0 0 0 :_ 0 0 0 0 0 :5: 0 0 0 0 0 , p 0'- . '0 0 0 0 0 0 0 0 0 0 0 4 0 W TE�BlockWa84-1 C- . F 6 c)AED excursion -81 0 Envelope loss/gain 1763 650 5 4 12 a) Infiltration b) Room ventilation 565 0 191 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 2328 841 5 4 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 11 % 8% 0 0 0 2328 256 0 0 0 841 66 11 % 8% 0 0 -5 0 0 0 0 -4 0 0 Total room load Air required (cfm) 2584 49 907 42 0 0 0 0 Cal 44+ wri9"" q t' Right-SufteO Universal 2017 17.0.19 RSU17939 �4CCA ...LaffontlWorking Drawings\Laffont Load Calcs.rup Calc = W8 Front Door faces: SE 8th 2017-Mar-15 10:28:30 Page 2 Ics Right-M Wol Entire House ProCales, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: Job: Laffont Residence Date: Mar 13, 2017 By: Tom Platania Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 2 Room name Exposed wall Bath 2 0 ft Utility 34.0 ft 3 Room height 9.0 ft heat/cool 9.0 ft heat/cool 4 5 Room dimensions Room area 10.0 x 9.0 ft 90.0 ft' 11.0 x 12.5 ft 137.5 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ft2) Load number (Btuhlft? "F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cooll Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 . W ' 12B-0sw -.0.097 'ne .-2t72 . 1.86 ; - ,co 0 ---0 0 -0 - 0 0 11 MI T-G Block Wall 4-1 4A5-2ovd Block Wall4 T 2 glazing, dr1oW-e 2 glazing dr low-e 0.143 0.450 0.143 -0.450 6," 456 ne ne ': se . se •`- se 4.00 12.60 ;4-M 12.80 12 60 2.97 26.52 , - .2:97 ; 24.78, 24.18 0 0 0 0 0 0 0 0 0.. 0 0 0 0 _; 0.: 0 0 0 - __ 0 •. 0 ° 0 113 0 95 '' 0 0 113 0 -4 - 0 0 450 0_ 294 0: 0 335 0 219 .0 0' , 2glazing drlow-e .6.450 ,se 12:60 2520 0 •, . 0 0 •< 0 ; 0 0 0 0, 11bv-- :: ,.:0.390 'se .' ;T0 92 . ,12.48 .:: 0 , . ;:• Q ; <` -. :,0 . :0 ; •'; 21 21 229, '. •. '262 Block Wall 4-1 1013-v 0.143 0.450 sw sw 4.00 12.60 2.97 19.46 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, dr low -a 2 glazing, clrlow-e 2 glazing cir lower 129-0sw Block Wail 4-1 0.450 0.450 0.450 0.097 0.143 sw sw sw ' nw nw 12.60 12.60 12.60 2:72 4.00 24.18 24.18 24A8 . • 1:86 2.97 0 0 - 0 0 0 0 0 0 0 0 0 0 0 .' , , 0 0 0 0 0 .'- ' . 0 0 0 0 0 0 99 0 0 0 0 99 0 0 0 ' , 0 396 0 0 0 : 0 294 W yy!! �--G 10D-v 0.450 nw 12.60 19.16 0 0 0 0 0 0 0 0 IL�C 2 glazing, drlow-e 4A5-2ovd 0.450 0.450 nw nw 12.60 12.60 26.30 26.52 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C ' F .16X30-0td 22A-tpm - 10.408 1.180 . - - -_ - 1.1.8 33.04 ;- 1:00 .. - 0.. ,'90 0 90 _ 90 . 0 • .- 106 .._..- 0 ?. .: _ . ; ' . 90 -.. • 0 r:'1138 138 138 34 ' -. 1.123 137 0 6 c)AED excursion -8 -221 Envelope loss/gain l 106 82 2656 1026 12 a) Infiltration 0 0 800 270 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 1000 Subtotal (lines 6 to 13) 106 82 3456 2296 Less external load 0 0 0 0 Less transfer 0 0 0 0 14 Redistribution Subtotal 21 127 16 99 0 3456 0 2296 15 Duct loads 11% 8% 14 8 11% 8% 380 181 Total room load Air required (cfm) 141 3 106 5 3836 73 2478 116 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. +b-'wrightsoft• Right -Suite® Universal 201717.0.1 9 RBU17939 A=', ...LaffonNWorking Drawings\Laffont Load Calcs.rup Calc = W8 Front Door faces: SE 2017-Mar-15 10:28:30 Page 3 4 - '�� Right4di Worksheet Job: Laffont Residence Entire House Date: Mar 13, 2017 By: Tom Platania ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name Bath Dining Room 2 Exposed wall 0 It 22.5 ft 3 Room height 9.0 It heaUcool 9.0 ft heat1cool 4 Room dimensions 1.0 x 50.0 ft 12.5 x 10.0 ft 5 Room area 50.0 ftz 125.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/ft;"F) (Btuh/ft-) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 126-0suv 0097 ne 2=72 1'86� `.._0 0 0 0 0' 0 "'0 ' 0 V�/ t-G Block Wall 4 1 0.143 ne 4.00 2.97i 0 0 0 0 90 90 360 268 4A5 2ovd 0.450 ne 12 60 26.52 0 0 0 0 0 0 0 0 Block Wall 4 1 0 143 se • 4 00' 2.97 0 0 0 0 113 89 354 263' 11A-2 2 glazing.°cir►ow� ; 0450 se•i 12.60 24.18 0 0 0 0 0 .'. 0 0 0 2 gfaz�ng; dr low a 0.450 §e: 12.60 24;18 0 0.302 ; 580` glazing =cirlow-e- M50 • se' 12 60 ' 25 20 '0 ]1D0 =;: '0'.390 >se` . 10g2; 1248 .. 0 0 0 .:. 0 ;: 0 = 0 0 0 Block Wall 4-1 0.143 sw 4.00 2.97 0 0 0 0 0 0 0 0 10D-v 0.450 sw 12.60 19.46 0 0 0 0 0 0 0 0 2 glazing, cirlow-e 0.450 sw 12.60 24.18 0 0 0 0 0 0 0 0 2 glazing, drlow-e 0.450 sw 12.60 24.18 0 0 0 0 0 0 0 0 2 glazing, cir low-e 0.450 sw 12.60 24.18 0 0 0 0 0 0 0 0 W . _; 126-0sw 009 :7 nw= 2 72' ....;1:86 Block Walt 4-1 0.143 nw 4.00 2.97 0 0 0 0 0 0 0 0 10D-v 0.450 nw 12.60 19.16 0 0 0 0 0 0 0 0 2 glazing, cirlow-e 0.450 nw 12.60 26.30 0 0 0 0 0 0 0 0 4A5-2ovd 0.450 nw 12.60 26.52 0 0 0 0 0 0 0 0 C 16X30 0td `. 0.;408 = . 118' .. :"1.00 . 50 ;; 50 59 '. 50 `;;.. 125 `' ' :1'47 :'", 125 F 22A-tpm 1.180 -_. 33.04 0.00 50 0 ,: 0 0 125 ,.125 23 _ 743 0 6 c)AED excursion 1-48 1 165 Envelope loss/gain 59 2 1908 1402 12 a) infiltration 0 0 529 179 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13) 59 502 2437 1580 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 11 8 0 0 14 Subtotal 69 510 2437 1580 15 Duct loads 11% 8% 8 40 11% 8% 268 125 Total room load 77 550 2705 1705 Air required (afm) 1 26 51 80 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed -1'1-'.wtrightsoft- RightSuite® Universal 2017 17A.19 RSU17939 2017-Mar-15 10:28:30 'CC0. ...LaffantlWorking DrawmgslLaffont Load Calcs.rup Calc = W8 Front Door faces: SE Page 4 x�_��� .�• , RI ht-J® Worksheet Job: Laffont Residence �:.=LYUV�IC g Date: Mar 13, 2017 ;•��^• Entire House By: Tom Platania ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name Living Rm FL RM 2 Exposed wall 24.5 ft 42.5 it 3 Room height 9.0 it heat/cool 9.0 ft heat/cool 4 5 Room dimensions Room area 1.0 x 316.8 ft 316.8 ft2 1.0 x 230.8 ft 230.8 W Ty Construction U-value Or HTM Area (W) Load Area (W) Load number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool I Gross WP/S Heat Cool Gross N/P/S Heat Cool 6 W.:., 126-0sw :A 097 %na 2:72, ... 9e8.6 0 -` :0 0 :; "0 Q .. 0• t-G Block Wall 4-1 0.143 ne 4.00 2.97 9 9 36 27 0 0 0 0 11 4A5 2ovd 2glazing dr low e 2;glazing cir low-e, 2 glazing cir lows 0.450 6143 0 450 0450 6 450 ne :'se se sse se 12.60 4.00 12.60 1260 42.60 26.52 2.97 24.18 24a1� 25.20 0 203 0 24 " ` 13 0 0 5 2 0 57 0 , 302 . 169 0 49 .. 0 '- 580:. 338 0 20 0 ' : o 0 9 4 0 ' 0 0 1Block:Wa04 6 252 0 0 0 2 35144 : 48.4 0 = 0 11.D0 ', . .. 0.390 `se 10.92 _r, 12.48 .. , 21 21. 229 '-262 ` 0 0 ' . 0 0 Block Wall 4-1 10D-v 0.143 0.450 sw sw 4.00 12.60 2.97 19.416 9 0 9 0 36 0 27 0 189 0 139 0 557 0 413 0 W "` VVV���lll 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing. cir low-e 12B-0sw Block Wall 4-1 10D-v 2 glazing, dr low-e 0.450 0.450 0.450 0.097, 0.143 0.450 0.450 sw sw sw nw nw nw nw 12.60 12.60 12.60 ... 27.2 4.00 12.60 12.60 24.18 24.1�8 24.1,8 .:.. <1,86 2.97 19.16 26.30 0 0 0 ,:. .. • 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 • ; 0 0 0 0 0 24 26 .'' ,"." .,0 95 0 0 0 5 5 0 58 0 0 0 302 328 ,. 0 231 0 0 0 580 629 ., 0. 171 0 0 C ; ,- 4A5-2ovd `1.6X30-Otd: _ - _ 0.450 0:408 nw. , -:-,. 12.60 :,1:18 26.52 '1;d0 0 ,' ,, 317 0 ' : •::.317, 0 373 0 : -317 37 ; -231 0 231 464 272 977 "': 231 F 22A-tpm ... ., .,_ 1.180 -_- 33.04 0.00 317 25 , ._ 809 0 231 43 1404 . 0. 6 c)AED excursion 127 148 Envelope loss/gain 2532 2105 4126 3868 12 a) Infiltration 576 195 1000 338 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 2 460 0 0 Appliances/other 900 0 Subtotal (lines 6 to 13) I 3109 3660 5126 4206 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 10 8 0 0 14 Subtotal 3118 3668 5126 4206 15 Duct loads 11% 8% 343 289 11% 8% 564 332 F1Total room load 3462 3957 5690 4537 Air required (cfm) 65 185 108 212 to meet all wrightP .8CA' Right -Suite® Universal 2017 17.0 19 RSU17939 2017-Mar-15 1 age 5 Page 5 s1CGA ...LaffontlWorking Drawings\Laffont Load Calcs.rup Caic = MJB; Front Door faces: SE 9 Job: Laffont Residence �R cc, caks Right-J@ Worksh et Date: Mar 13,2017 Entire House By: Tom Platania ProCales, LLC P.O. 13ox882032, Port Saint Lucie, FL34988 Phone: 772-882-5700 Email: tom@pmcales.net Web: wwww.ProCaics.Net License: CAC1815254 RTIN #0105474 1 1 Room name Bedroom 1 AH 2 3 4 5 Exposed wall Room height Room dimensions Room area 8.0 ft 9.0 ft heat1cool 1.0 x 156.5 it 156.5 ft2 0 ft 9.0 ft heat/cool 2.0 x 2.5 ft 5.0 ft2 Ty Construction U-value Or HTM Area (W) Load Area (W) Load number (Btuh/ft3-*F) (Btuh/ft) I or perimeter (ft) (Bt h) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool- Gross N/P/S Heat Cool 6 11 W LBlock G W-. Block Wall 4-1 4A52ovd wocklwan4-i' 2:glazing;-drIow-e, 0.143 0.450 :6,A43 -'0'450, ne, ne ne -se �se 1- 21Z 4.00 12.60 ---4--60 1260 1.86 2.97 26.52 2.97 .-24.18 0 J.- 0- -0. 0 0 0 0 0 0 0 ----0 0 '0 0 0 .0 0 .0 .0 .0 0 0 0 0 0 0 0 0 .1- 0 0 ,0 0 0 '0 Jo w G glazing,�clr ow 2 -6 Zgjazing 16W-e;r.-' 11DO 0 0.460 Eno se I. sw S6 12.60 -1260 --:24:16 -25 20 12,48 0 :0 0 0 '0 .0 0 0 0'' .0 �-o '0 0 �O 0 0 �0 --G, _Z Block Wall 4-1 1013-v 2 glazing, dr low-e 2 glazing, dr low-e 2 glazing, dr low-e 0.143 0.450 0.450 0.450 0.450 sw sw sw sw sw 4.00 12.60 12.60 12.60 12.60 2.97 19.46 24.19 24.18 24.18 72 0 12 0 0 60 0 3 0 240 0 151 0 0 178 0 290 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 V 12M S-W Block Wall 4-1 -6.691 0.143 nw, nw 2.72 4.00 1.8 2.97 0 0 ...0 ;�' - 0 0 :. -b 0 r - 0 0 0 - 6 0 0 0 --. 0 0 10D-v 2 glazing, dr low-e 4A5-2ovd 16)d0-0td,: 22A-tpM 0.450 0.450 0.450 .-10;406,,'- 1.180 nw mv nw 12.60 12.60 12.60 1 18.1 33.04 19.16 26.30 26.5 .00 0.00 6 0 0 0 157 157 0 0 0 1 ',',157 8 0 0 0 -:,..'184 264 0 0 0 7156 0 0 0 0 .5 0 0 0 6 0 0 0 0 6 0 s 0 0 5 0 C F 6 c) AED excursion 63 0 Envelope loss/gain 840 688 6 5 12 a) Infiltration b) Room ventilation 188 0 64 0 0 0 0 a 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1028 751 6 5 Less external load 0 0 0 0 14 Less transfer Redistribution Subtotal 0 179 1207 0 82 833 0 -6 0 0 -5 0 15 Duct loads 11%1 8% 133 66, 11% 8% 0 0 Total room load Air required (cfm) 1340 25 899 42 0 0 0 01 S a wrights'Oft' Right -Suite® Universal 2017 17.0.19 1 RSU17939 2017-Mar-15 10:28:30 Page 6 ... LafforitlWorking DravAngski-aflont Lead Calos.rup Calc=MJ8 Front Door faces: SE �. p. . I Right-M Worksheet Job: Laffont Residence °='•--�� Enure House Date: Mar 13, 2017 By: Tom Platania ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-8825700 Email: tom(�procalcs.net Web: www.PmCalcs.Net License: CAC1815254 RTIN ft0105474 1 Room name Hall Kitchen 2 Exposed wall 0 ft 15.5 ft 3 Room height 9.0 ft heaUcool 9.0 ft heat/coal 4 Room dimensions 4.5 x 14.5 ft 1.0 x 195.0 ft 5 Room area 65.3 ftz 195.0 ft' Ty Construction U-value Or HTM Area OF) Load Area (ftj Load number (BtuhtWF) (Btuh/ft-) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool I Gross WP/S Heat Cool Gross N/P/S Heat Cool 6 W ;" ;126-0sw:-: "•. 0097 ._net 2:72: 1a16 0 0 :.'; .0 ,`' 0, .,:': 0 ', 0 s0 ..... 0. Block Wall 4-1 0.143 ne 4.00 2.97 0 0 0 0 59 18 73 54 4A5 2ovd 0.450 ne 12.60 26.52 0 0 0 0 40 01. 507 1066 "" ?Block Wall4 1 0:143 .se• 4 00, 2:97 0 0 0 0 0 _ 0 .0 11 2 alazma_;driow�•.. OA90 rse 1260: 24:18 , ;'n n -0 '11DO 0390 se`; "10 c Block Wall 4-1 0.143 sw 4.( 10D-v 0.450 sw 12.E 2 glazing, cir low-e 0.450 sw 12.( 2 glazing, dr lowe 0.450 sw 12.( 2 glazing, dr lowe 0.450 sw 12.E 12B=0sw. ". 0 097 nw,' Z i Block Wall 4-1 0.143 nw 4.( IOD-vglazing, 0.450 nw 12.E 2 2 glazing, clr lowe 0.450 nw 12.E 4A5-2ovd 0.450 nw 12.E C • IOX30'-0td .. _ ;0408 ,.,, i= 1 1 F _ 22A7tpm _ _ - 1"160 - 33.( MI 24As 0 0 0 0 0 '0`261.20 0 0' .12:48 :0 t 0. 0 0 ,' 0 :' . : `0 ' " "0 0 2.97 0 0 0 0 0 0 0 0 19.46 0 0 0 0 0 0 0 0 24.18 0 0 0 0 0 0 0 0 24.18 0 0 0 0 0 0 0 0 24.18 0 0 0 0 0 0 0 0 2.97 0 0 0 0 81 61 244 161 19.16 0 0 0 0 20 0 253 385 26.30 0 0 0 0 0 0 0 0 26.52 0 0 0 0 0 0 0 0 Y00 65 65 195 _' "-1:95 . " -230 195': 0.00. 65 0 _ 0 0 _. 195 _ 16 512 _. 0 61 c)AED excursion -6 -301 Envelope, loss/gain 77 59 1819 1580 12 a) Infiltration 0 0 365 123 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants Q 230 0 0 1 230 Appliances/other 0 1200 Subtotal (lines 6 to 13) 77 59 2183 3133 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -77 59 0 0 14 Subtotal 0 0 2183 3133 15 Duct loads 11% 8% 0 0 11% 8% 240 247 Total room load 0 0 2424 3381 Air required (cfm) 0 0 46 158 wrightsOft^ Right -Suite® Universal 2017 17.0.19 RSU17939 ACC'Q` ...LaffontlWorking Drawings\Laffont Load Calcs.rup Calc = MJ8 Front Door faces: SE 2017-Mar-15 10:28:30 Page 7 ri Job: Laffont Residence jCS Right-M Worksheet �` Entire House Date: Mar13,2017 ProCalcs, LLC By: Tom Platania P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tomQa procalcs.net Web: www.ProCalcs.Net License: CAC1815254 RTIN #0105474 1 Room name CL 2 3 4 5 Exposed wall Room height Room dimensions Room area 2.5 ft 9.0 ft heatIcool 9.0 x 2.5 ft 22.5 ft2 Ty Construction number U-value (Btuh/ftz "F) Or HTM (Btuh/fo Area (ft2) or perimeter (ft) Load (Btuh) Area or perimeter Load Heat Cool I Gross N/P/S Heat Cool Gross WP/S Heat Cool 6 11 1N = yJ I--G 126 0sw, -... Block Wall 4-1 4A5-2ovd Block Wall 4 1 ' :' 2glazing clrloW-e 2 glazing, ciriow -e. 2 glazing clr.low�e 11 D0' ; :., :: = :.. 0 097 0.143 0.450 0.143 '0450 0.450 .0.450 0 390 ,.. ne ne ne 'se ;se `"se ,-se :.se '2:72 4.00 12.60 4.00 12:60 I2.60 : 12.60 _ 10: 2 2.97, 26.52 2.97, 241$ 24c18 25:20 a2f4.8 0 0 0 0 0 ' : 0 > . 0 0 0 0 0 0 lJ 0.: 0 0 0 0 0 0 0 0 0 0 -;- 0 ` ` -- 0 D c 0 :... '0 , _ '• .: " ;- .: .: . Block Wall 4-1 10D-v 2 glazing, clr low-e 2 glazing, cirlow-e 2 glazing clr low-e 0.143 0.450 0.450 0.450 0.450 sw sw sw sw sw 4.60 12.60 12.60 12.60 12.60 2.97' 19.46 24.19 24.18 24.18 23 0 0 0 0 23 0 0 0 0 90 0 0 0 0 67 0 0 0 0 VII •: _ yyJJ �-G 128 0 Block Wall 4-1 0 0.143 nw ._` 4.00 , 2.97 0 0 .0- 0 0 0 10D-v 2 glazing, cir low-e 4A5-2ovd 0.450 0.450 0.450 nw nw nw 12.60 12.60 12.60 19.1(§ 26.30 26.52 0 0 0 0 0 0 0 0 0 0 0 0 C F . . . 16X30.0td _ 22A-tpm . 0:408 1.180 :_ - ....-. 1:18 33.04 ' ; 1.00 0.00 =;: 23 .-- - 23 - _ 23 3 .. 27 83 ; . 22 _ 0 6 c)AED excursion -10 Envelope loss/gain I 199 80 12 a) Infiltration b) Room ventilation 59 0 20 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13) I 258 100 Less external load 0 0 14 15 Less transfer Redistribution Subtotal Duct loads 11 % 8% 0 258 0 0 0 -100 0 0 FI-- Total room load Air required (cfm) 0 0 0 0 I Calculations approved by ACCA to meet all requirements of Manual J 8th Ed WI'1 htSOft` g 2017-Mar-1510:28:30 Ri ht-Suite® Universal 2017 17.0. 9 RSU17939 e` At...LaffontlWorking DrawingslLaffont Load Calcs.rup Calc = MJ8 � Front Door faces: SE Page 8 The following pages summarize ft ACCA Manual J8 calculation pros given to ProCalcs in the form of di ProCalcs may make assumptions accurate for the location of concer contractor to verify the design con Any load calculations provided in i provided by the party submitting a does not independently verify that and any calculations made by Pro third parties. ProCalcs makes no c complete. ProCalcs, LLC. DISCLAIMER heat gain and heat loss of the building using the lure. The calculations are based on the information Kings, sketches, and interviews. In certain cases, 3out design conditions that may or may not be It is the responsibility of the installing HVAC Lions before equipment purchase and installation. following pages are based upon information articular project to ProCalcs. ProCalcs has not and ie data provided to ProCalcs is correct or complete, 3Ics are based upon the information provided by iim that the information given to us is correct or ProCalcs utilizes WrightSoft Residential 15.0 which is an ACCA Certified and ASHRAE recommended computer program to determine the heating and cooling loads presented in this report, and is therefore veryaccurate. If the information given to ProCalcs is accurate, and the building is built as per the plans submitted, then the load calculations presented in this report can be assumed to be accurate. A licensed mechanical contractor may use these calculations as a starting point in system sizing and selection. ProCalcs does not provide archite or for use by contractors or constr ProCalcs works with architectural connection with their designs of hi layout installed on -site DOES NO" ProCalcs, then ProCalcs cannot a duct design. All branch ducts Ml delivery to each room. Final HV/ HVAC contractor. Many factors be to final system selection and desic availability and selections, system distribution and cycling, Uniform 8 requirements, and many other sta Society of Heating, Refrigeration, ProCalcs therefore assumes nc system design. Various modific may have occurred after this Di would require that this Design accurate. After reviewing ProCc- installation, please inform ProC assumptions and tural or engineering plans or diagrams for the public ation companies as final "construction documents". nd engineering firms and with contractors in. rting and air conditioning systems. If the HVAC duct match the Manual D duct design prepared by d will not guarantee the performance of any altered ;T have adjustable dampers to ensure proper air sizing and selection should be done by a licensed and the scope of this report must be considered prior i, such as: exact equipment :ontrols and location of controls, system air ilding Code requirements, Uniform Mechanical Code lard design conventions as listed by the American id Air Conditioning Engineers (ASHRAE). liability for final equipment selection or final ations to the information provided to ProCalcs sign Support information was prepared, which oupport information be modified in order to be Ics report, and prior to any system purchase or alcs in writing of any changes which may alter the calculations contained in this report._