EVALUATION REPORT
Polyglass USA, Inc. Evaluation Report P12060.02.09-R15
150 Lyon Drive FL5259-1120
Fernley, NV 98408 Date of Issuance: 02/24/2009
Revision 15: 08/25/2014
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been designed to comply with the Florida Building Code, 2010 sections noted herein.
4 QES.CRIPTTON, 12-(. glass RDo 11ndETlaynlents(�
LABELING: Labeling shall be in accordance; with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced j
Quality Assurance documentation changes,1 or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity) ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity IERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection
spection at the job site at the request of the Building Official.
THESE PLANS AND ALL PROPOSED WORK
This Evaluation Report consists of pages 1' through 11. ARE SUBJECT TO ANY CORRECTIONS
REQUIRED BY FIELD INSPECTORS THAT
^ONCEALEO FASTENERS OR ATTACH ►9E'NTIzMAY BE NECESSARY IN ORDER TO
Prepa�F OL��ONI�I� 1 �� T�t� , �t COMPLY WITH ALL APPLICABLE CODES.
OF RECORD - Y
The facsimile seal appearing was authorized
`^ ' G �� by Robert Nieminen, P.E. on 08/25/2014
Robert J.M. Nieminen, P.E. ';��.:'';c?;. This does not serve as anelectronicallysigned 'document.
Florida Registration No. 59166, Florida DCA ANE1983 �S�% "�L��,r• Signed, sealed hardcopies have been transmitted to the
4
Product Approval Administrator and to the named client
CERTIFICATION OF INDEPENDENCE: 0
1. TrinitylERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity] ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
ST. LUCIE COUNTY BUILDIN DI 1. I
REVIEWED FORJ�OMP AN
REVIEWED
REVIEWED Y
DATE. FILE COPY
PLANS AND EMI UST BE KEPT ON JOB
SITE OR NO INSPECTION(S) WILL BE MADE
T�
s ER®
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Underlayment
Compliance Statement: Roof UnderlaymenEs, as produced by Polyglass USA, Inc., have demonstrated compliance with the
following sections of the Florida Building Code through testing in accordance with the following Standards. Compliance is subject
to the Installation Requirements and Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section
Property
Standard
Year
1507.2.3, 1507.3.3, 1507.5.3, 1507.7.3,
Physical Properties
ASTM D226
'2006
1507.8.3,1507.9.3
1507.2.4,1507.2.9.2, 1507.3.3, 1507.5.3
Physical Properties
ASTM D1970
2001
1507.11.2
Physical Properties
ASTM D6164
2005
1507.11.2
Physical Properties
ASTM D6222
2002
1504.6
Accelerated Weathering
ASTM G154
2005
1504.6
Accelerated Weathering
ASTM G155
2005
1504.3.1
Wind'Uplift
FM 4474
2004
1507.3.3
Installation Practice
FRSA/TR107320
2005
1523.6.5.2.1
Physical Properties
TAS 103
1995
3. REFERENCES:
Enti
Examination
Reference
Date
FM Approvals (TST 1867)
Wind Uplift
3004091
01/12/2000
PRI (TST 5878)
Physical Properties
PRI01111
04/08/2002
PRI (TST 5878)
Physical Properties
PUSA-005-02-01
01/31/2002
PRI (TST 5878)
Physical Properties
PUSA-013-02-01
12/23/2002
PRI (TST 5878)
Physical Properties
PUSA-013-02-02
12/23/2002
PRI (TST 5878)
Physical Properties
PUSA-013-02-03
12/23/2002
PRI (TST 5878)
Physical Properties
PUSA-018-02-01
67/14/2003
PRI (TST 5878)
Physical Properties
PUSA-028-02-01
07/13/2005
PRI (TST 5878)
Physical Properties
PUSA-033-02-01
01/12/2006
PRI (TST 5878)
Physical Properties
PUSA-035-02-01
09/29/2006
PRI (TST 5878)
Physical Properties
PUSA-055-02-02
12/10/2007
PRI (TST 5878)
Physical Properties
PUSA-061-02-02
01/28/2008
PRI(TST 5878)
Physical Properties
PUSA-076-02-01
02/22/2008
PRI (TST 5878)
Physical Properties
PUSA-083-02-01
04/14/2008
PRI (TST 5878)
Physical Properties
PUSA-088-02-01
07/29/2009
MTI (TST 2508)
Physical Properties
JX20H7A
04/01/2008
MTI (TST 2508)
Physical Properties
RX14EBA
01/29/2009
ERD (TST 6049)
Physical Properties
11752.09.99-1
02/08/2000
ERD (TST 6049)
Wind Uplift
11757.08.01-1
08/13/2001
ERD (TST 6049)
Wind Uplift
11776.06.02
01/16/2003
ERD (TST 6049)
Physical Properties
02200.07.03
07/14/2003
ERD (TST 6049)
Wind Uplift
P1740.01.07
01/04/2007
ERD (TST 6049)
Physical Properties
P5110.04.07-1
04/11/2007
ERD (TST 6049)
Wind Uplift
P9260.03.08
03/21/2008
ERD (TST 6049)
Physical Properties
P13450.08.09
08/13/2009
ERD (TST 6049)
Wind Uplift
P30540.11.09-R1
11/30/2009
ERD (TST 6049)
Physical Properties
P11030.11.09-1
11/30/2009
ERD (TST 6049)
Wind Uplift
P11030.11.09-2
11/30/2009
ERD (TST 6049)
Physical Properties
P11030.11.09-3
11/30/2009
ERD (TST 6049)
Physical Properties
P33360.06.10
06/25/2010
ERD (TST 6049)
Physical Properties
P33370.03.11
03/02/2011
ERD (TST 6049)
Physical Properties
P33370.04.11
04/26/2011
ERD (TST 6049)
'Physical Properties
P37300.10.11
10/19/2011
ERD (TST 6049)
ERD (TST 6049)
Physical Properties
P40390.08.12-1
08/06/2012
ERD (TST 6049)
Physical Properties
Physical Properties
P40390.08.12-2
C41420.09.12-3
08/07/2012
09/11/2012
Exterior Research and Design, U.C. Evaluation Report P12060.02.09-R15
Certificate of Authorization #9503
FL5259-R20
Revision 15: 08/25/2014
Page 2 of 11
t
^•S �.TRINITY." ERD
intitt
Examination
Reference
Date
ERD (TST 6049)
Wind Uplift
P39680.03.13
03/04/2013
ERD (TST 6049)
Physical Properties
P45370.04.13
04/26/2013
ERD (TST 6049)
Wind Uplift
P1738.02.07-R2
04/29/2013
ERD (TST 6049)
Wind Uplift
11757.04.01-1-R1
04/30/2013
ERD (TST 6049)
Wind Uplift
P41630.08.13
08/06/2013
ERD (TST 6049)
Wind Uplift
P11751.05.03-Ri
11/26/2013
ERD (TST 6049)
Wind Uplift
P11781.11.03-R1
11/26/2013
ERD (TST 6049)
Physical Properties
P45270.05.14
05/12/2014
ERD (TST 6049)
Physical Properties
P443605C
05/15/2014
ERD (TST 6049)
Physical Properties
P46520.08.14
08/22/2014
ICC-ES (EVL 2396)
IBC Compliance
ESR-1697
09/01/2012
Miami -Dade (CER 1592)
HVHZ Compliance
NOA 12-0713.02
02/14/2013
Polyglass USA
Manufacturing Affidavit
Products Current
02/18/2009
Polyglass USA
P/LAffidavit
Mule -Hide Cross Ltg
03/01/2008
Polyglass USA
Materials Affidavit
Polystick SA Compound
08/18/2011
UL, LLC. (QUA9625)
Quality Control
Service Confirmation, R14571, 2QA
Exp. 08/08/2015
UL, LLC. (QUA9625)
Quality Control
Service Confirmation, MTS PLUS
Exp. 07/01/2017
4. PRODUCT DESCRIPTION:
4.1 Mechanically Fastened Underlavments:
4.1.1 Elastobase is a fiberglass reinforced, SBS modified bitumen base sheet.
4.1.2 Elastobase P is a polyester -reinforced, SBS modified bitumen base sheet.
Self -Adhering Underlavments:
"42.Pol'y�stick MTS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, surfaced
with polyo efmic film surface; meets ASTM D1970 and TAS 103.
4.2.2 Polystick MTS PLUS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced,
surfaced with poly -film surface; meets TAS 103.
4.2.3 Polystick IR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an
aggregate surface; meets ASTM D1970.
4.2.4 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a
polyester fabric surface; meets ASTM D1970 and TAS 103.
4.2.5 Polystick TU P is a nominal 1307mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester reinforced,
with a granular surface; meets ASTM D1970 and TAS 103.
4.2.6 Polystick TU Max is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 170 g/m2 polyester
fabric surface; meets TAS 103.
4.2.7 Polyflex SAP, PolyFlex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester
reinforced, APP modified bitumen cap sheets.
4.2.8 Dual Pro'" is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with
a polyester fabric surface.
4.2.9 Tile Pro" is a nominal 60-mil:hick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a
polyester fabric surface.
4.3 Mechanically Fastened and/or Bonded Underlavments
4.3.1 Elastoflex S6 G and Elastoflex S6 G FR are polyester reinforced, SBS modified bitumen cap sheets.
4.3.2 Polyflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets.
S. LIMITATIONS:
5.1 This Evaluation Report is not for use in the HVHZ.
5.2 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire
ratings of this product.
Exterior Research and Design, LLC. Evaluation Report P12060.02.09-R15
Certificate of Authorization #3503 FL5259-R20
Revision 15: 08/25/2014
Page 3 of 11
TRINITY! ERD
5.3 Polyglass Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced
within FBC approval documents. If not listed, a request may be made to the AHJ for approval based on this evaluation
combined with supporting data for the prepared roof covering.
SA Allowable roof covers applied atop the underlayments are as follows:
Underlayment
Asphalt Shingles
Nail -On Tile
Foam -On Tile
Metal
Wood Shakes &
Slate
Shingles
Elastobase
Yes
Yes
No
Yes
Yes
Yes
E4iP
'
Yes
Yes
No
Yes
Yes
Po ystick U 7S
Yes
Yes
No
Yes
r Yes
Yes
olystick NITS PLUS
Yes
Yes
No
es
Yes
Yes
Polystick IR-Xe
Yes
No
No
No
Yes
Yes
Polystick TUP
Yes
Yes
Yes
No
Yes
Yes
See 5.4.1
Polystick TU Plus
I Yes
Yes
Yes
Yes
Yes
Yes
See 5.4.1
Yes
Polystick TU Max
No
Yes
Yes
No
No
_
See 5.4.1
Dual Pro
Yes
Yes
No
Yes
Yes
Yes
Tile Pro
Yes
Yes
es
Yes
Yes
Yes
See
5.Elastoflex
S6 G
Yes
Yes
Yes
No
Yes
Yes
See 5.4.1
Elastoflex S6 G FR
Yes
Yes
No
No
Yes
Yes
I
Polyflex G
Yes
Yes
Yes
No
Yes
Yes
See 5.4.1
Polyflex G FR
Yes
Yes
No
No
Yes
Yes
Polyflex SAP or SAP FR
Yes
Yes
Yes
No
Yes
Yes
_
See 5.4.1
Mule -Hide SA-APP Cap Sheet or SA-
Yes
APP Cap Sheet (FR)
Yes
Yes
See 5.4.1
No
Yes
Yes
5.4.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives unless tensile adhesion / long term aging
data from an accredited testing laboratory is provided.
✓ 3M— 2-Component Roof Tile Adhesive AH-160 (formerly Polyfoam PolyPro AH160): Polystick TU P, Polystick TU
Plus, Polystick TU Max, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet
or Mule -Hide SA-APP Cap Sheet (FR) or Tile Pro.
✓ 3M'" Foam Roof Tile Adhesive RTA-1: Polystick TU P, Polystick TU Plus, Polystick TU Max, Elastoflex S6 G, Polyflex
G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) or Tile Pro
✓ Dow TileBond: Polystick TU P, Polystick TU Plus, Polyflex SAP or Tile Pro
✓ Convenience Products' Touch 'n Seal StormBond Roof Tile Adhesive: Polystick TU Plus, Polystick TU Max
5.5 Allowable substrates are noted below:
Exterior Research and Design, I.I.C. Evaluation Report P12060-02.09-R15
certificate of Authorization #9503 FL5259-R20
Revision 15: 08/25/2014
Page 4 of 12
TRINITYERD
5.5.1 Direct -Bond to Deck:
Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet
(FR) self -adhered to:
➢ New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing
plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern
Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels (designed and installed
to meet wind loads for project).
Note: Polygloss does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or OSB
sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes.
Elastoflex S6 G or S6 G FR in hot asphalt to:
ASTM D41 primed structural concrete.
Polyflex G or G FR torch -applied to:
➢ ASTM D41 primed structural concrete.
5.5.2 Bond -to -Insulation:
Polystick, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to:
ASTM C1289, Type II, Class 1 polyisocyanurate or Type V polyisocyanurate-composite insulation; Dens Deck DuraGuard;
Dens Deck Prime; or SECUROCK Gypsum -Fiber Roof Board.
Elastoflex 56 G or S6 G FR in hot asphalt to:
➢ Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
Polyflex G or G FR torch -applied to:
➢ ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum
requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile
systems, insulation attachment shall be designed by a qualified design professional and installed based on testing of
the insulation/underlayment system in accordance with FM 4470, Appendix K or TAS 114, Appendix J.
5.5.3 Bond to Mechanically Attached Base Laver:
Polystick, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or Tile Pro self -
adhered to:
➢ ASTM D225, Type I or II felt; Elastobase; Elastobase P or Mule -Hide Nail Base.
Elastoflex S6 G or S6 G FR in hot asphalt to:
➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P or Mule -Hide Nail Base.
Polyflex G or G FR torch -applied to:
➢ Elastobase; Elastobase P or Mule -Hide Nail Base.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum
codified requirements. For installations under foam -on tile systems, refer to Section 5.5.4 herein and FRSA/TRI
07320/8-05 or RAS 120.
5.5.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI 07320 does not address wind
uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment forms part of the
load -path. The following wind uplift limitations apply to underlayment systems that are not addressed in FRSA/TRI
07320 and are used in foam -on tile applications. Maximum Design Pressure is the result of testing for wind load
resistance based on allowable wind loads. Refer to FBC 1609.1.5 for determination of design wind pressures.
5.5.4.1 Maximum Design Pressure = -90 psf.
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Primer: (Optional) ASTM D41
Underlayment: Polystick TU P, Polystick TU Plus, Polyflex SAP, PolyFlex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP
Cap Sheet (FR), self -adhered.
Exterior Research and Design,LLC. Evaluation Report P12060.02.09-R15
Certificote of Authorization M9503 FL5259-R20
Revision 15: 08/25/2014
Page 5 of 11
`f TO I I r ERD
5.5.4.2
Maximum Design Pressure =-135 osf.
Deck:
Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Primer:
(Optional) ASTM D41 .
Joints:
Min. 4-inch wide strips of Elastoflex SA-V over all plywood joints.
Underlayment:
Polystick TU P, Polystick TU Plus, Polyflex SAP, PolyFlex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP
Cap Sheet (FR), self -adhered.
5.5.4.3
Maximum Design Pressure = -315 osf.
Deck:
Structural concrete to meet project requirements to satisfaction of AHJ.
Primer:
ASTM D41
Underlayment:
Polystick TU P, Polystick TU Plus, Polystick TU Max, Tile Pro, Polyflex SAP, PolyFlex SAP FR, Mule -Hide SA-APP Cap
Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered.
5.S.4.4
Maximum Design Pressure = -622.5 osf.
Deck:
Structural concrete to meet project requirements to satisfaction of AHJ.
Primer:
ASTM 041
Underlayment:
Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
S.5.4.5
Maximum Design Pressure = -30 0 osf.
Deck:
Min. 15/32-inch OSB to meet project requirements to satisfaction of AHJ.
Base Layer:
Elastobase or Mule -Hide Nail Base (poly -film top surface) mechanically attached with 11 ga. x 1.25-inch long x c-
inch head diameter round metal cap nails spaced 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c. at two (2)
equally spaced staggered center rows.
Underlayment:
Polystick TU P, Polystick TU Plus, Polyflex SAP, PolyFlex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP
Cap Sheet (PR), self -adhered.
5.5.4.6
Maximum Design Pressure = -37.5 osf.
Deck:
Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer:
Elastobase or Mule -Hide Nail Base (poly -film top surface) mechanically attached with 11 ga. x 1.25-inch long x f-
inch head diameter round metal cap nails spaced 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c. at two (2)
equally spaced staggered center rows.
Underlayment:
Polystick TU P, Polystick TU Plus, Polyflex SAP, PolyFlex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP
Cap Sheet (FR), self -adhered.
5.S.4.7
Maximum Design Pressure = -37 5 osf.
Deck:
Min. 19/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer:
One (1) or two (2) layers ASTM D226, Type 11 felt mechanically attached with 11 ga. x 1.25-inch long x 1-inch head
diameter round metal cap nails spaced 6-inch o.c. at the 3-inch wide side laps and 12-inch o.c. at two (2) equally
spaced staggered center rows.
Underlayment:
Elastoflex S6 G, applied in full mopping of hot asphalt.
5.5.4.8 Maximum Design Pressure = -45 osf.
Deck:
Min. 19/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer:
One (1) layer ASTM D226, Type 11 felt mechanically attached with 11 ga. x 1.25-inch x 3/8-inch head diameter
annular ring shank roofing nails at 1-5/8-inch diameter tin caps spaced 4-inch o.c. at the 2-inch wide side laps and
two,
4-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment:
Polystick TU P, TU Plus, Polyflex SAP, PolyFlex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP
Cap Sheet (FR), self -adhered or Elastoflex 56 G, applied in full mopping of hot asphalt.
5.5.4.9 Maximum Design Pressure = -45 osf.
Deck:
Min.19/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer:
Two (2) layers ASTM D226, Type II felt mechanically attached with 11 ga. x 1.25-inch long x 3/8-inch head diameter
annular ring shank roofing nails at 1-5/8-inch diameter tin caps spaced 9-inch o.c. at the 2-inch wide side laps and
9-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment:
Polystick TU P, Polystick TU Plus, Polyflex SAP, PolyFlex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP
Cap Sheet (FR), self -adhered or Elastoflex 56 G, applied in full mopping of hot asphalt.
5.5.4.10 Maximum Design Pressure = -45 osf.
Deck:
Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer:
Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
mechanically attached with Simplex MAXX Cap Fasteners spaced 9-inch o.c. at the 2-inch wide side laps and 18-inch
o.c. at two (2) equally spaced staggered center rows.
Underlayment:
Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
Exterior Research and Design, LLC. Evaluation Report P12060.02.09-1115
Certificate of Authorization N9503
FL5259-R20
Revision 15: 08/25/2014
Page 6 of 11
5.5.4.11 _Maximum Design Pressure = -52 5 osf.'
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Lay&: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
mechanically attached with Simplex MAXX Cap Fasteners spaced 9-inch o.c. at the 2-inch wide side laps and 12-inch
o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
5.5.4.12 Maximum Design Pressure = -52 5 osf.
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer: Elastobase or Mule -Hide Nail Base (poly -film top surface) mechanically attached with Simplex Original Cap Nails
spaced 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows.
Underlayment: Polystick TU P, Polystick TU Plus, Polyflex SAP, PolyFlex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP
Cap Sheet (FR), self -adhered.
5.5.4.13 Maximum Design Pressure = -52 5 osf.
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
mechanically attached with Simplex Original Cap Nails spaced 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c.
at four (4) equally spaced staggered center rows.
Underlayment: Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
5.5.4.14 Maximum Design Pressure = -60 osf.
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
mechanically attached with 11 ga. x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at.1-
5/8-inch diameter tin caps spaced 8-inch o.c. at the 4-inch wide side laps and 8-inch o.c. at three (3) equally spaced
staggered center rows.
Underlayment: Elastoflex S6 G, applied In full mopping of hot asphalt or Polyflex G, torch -applied.
5.5.4.15 Maximum Design Pressure = -60 osf.
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
mechanically attached with OMG #12 Standard Roofgrip with OMG Flat Bottom Metal Plates spaced 12-inch o.c. at
the 4-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
5.5.4.16 Maximum Design Pressure = -90 osf.
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
mechanically attached with Simplex MAXX Cap Fasteners spaced 6-inch o.c. at the 2-inch wide side laps and 6-inch
o.c. at two (2) equally spaced staggered center rows.
Underlayment: Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
5.5.4.17 Maximum Design Pressure = -90 osf.
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
mechanically attached with OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates
or OMG Flat Bottom Metal Plates spaced 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally
spaced staggered center rows.
Underlayment: Elastoflex S6 G,, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
5.5.4.18 Maximum Design Pressure = -90 osf.
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer: Elastobase (sanded top surface) mechanically attached with Trufast #12 DP or Trufast #14 HD with Trufast 3" Metal
Insulation Plates spaced 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered
center rows.
Underlayment: Elastoflex S6 G, applied in full mopping of hot asphalt.
5.5.4.19 _Maximum Design Pressure = -97 5 osf.
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer: Elastobase or Mule -Hide Nail Base (poly -film top surface) mechanically attached with 11 ga. x 1.25-inch x 3/8-inch
head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps spaced 4-inch o.c. at the 4-inch wide
side laps and 4-inch o.c, at four (4) equally spaced staggered center rows.
Underlayment: Polystick TU P„ Polystick TU Plus, Polyflex SAP, PolyFlex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP
Cap Sheet (FR), self -adhered.
Exterior Research and Design, LLC.
Certificate of Authorizotron #9503 Evaluation Report P12060.02.09-R15
FL5259-R20
Revision 15: 08/25/2014
Page 7 of 11
TRINITY: ER®
5.5.4.20 Maximum Design Pressure = -105 psf.
Deck:
Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer:
Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
mechanically attached with Simplex MAXX Cap Fasteners spaced 6-inch o.c. at the 2-inch wide side laps and 6-Inch
o.c. at three (3) equally spaced staggered center rows.
Underlayment:
Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
5.5.4.21 Maximum Design Pressure = -112 5 psf.
Deck:
Min. 19/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer:
Elastobase or Mule -Hide Nail Base (poly -film top surface) mechanically attached with 11 ga. x 1.25-inch x 3/8-inch
head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps spaced 6-inch o.c. at the 4-inch wide
side laps and 6-inch o.c. at four (4) equally spaced staggered center rows.
Primer:
PG100 or ASTM D41 primer at all tin -caps
Underlayment:
Polystick TU P, Polystick TU Plus, Polyflex SAP, PolyFlex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP
Cap Sheet (FR), self -adhered.
5.5.4.22 Maximum Design Pressure = -120 psf.
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction ofAH1.
Base Layer: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap)
mechanically attached with OMG #12 Standard Roofgrip or CMG #14 Heavy Duty with OMG 3" Round Metal Plates
or CMG Flat Bottom Metal Plates spaced 6-inch o.c. at the 4-inch wide side laps and 6-Inch o.c. at five (5) equally
spaced staggered center rows.
Underlayment: Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied.
5.5.4.23 Maximum Design Pressure = -120 psf;
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Layer: Elastobase (sanded top surface) mechanically attached with Trufast #12 DP or-Trufast #14 HD with Trufast 3" Metal
Insulation Plates spaced 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered
center rows.
Underlayment: Elastoflex S6 G, applied in full mopping of hot asphalt.
5.5.4.24 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on tile systems carry a Maximum Design
Pressure of -45 psf.
5.6 Exposure Limitations:
S.6.1 Elastobase, Elastobase P or Polystick MTS PLUS shall not be left exposed for longer than 30-days after installation.
5.6.2 Polystick IR-Xe, Polystick TU Max, Dual Pro or Tile Pro shall not be left exposed for longer than 90-days after
installation.
5.6.3 Polystick MTS, TU P or TU Plus shall not be left exposed for longer than 180-days after installation.
5.6.4 Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure
limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30
days.
5.6.S Elastoflex S6 G or 56 G FR or Polyflex G or G FR does not have an exposure limitation, unless the prepared roof
covering is to be adhesive -set tile (Elastoflex S6 G or Polyflex G), in which case the maximum exposure is 180 days.
5.7 For tile roof installations governed by the FRSA/TRI 07320/8-05 Installation Manual, Fourth Edition, use is limited to
the following. Reference is made to the FRSA/TRI Technical Brief titled "Florida High Wind Roof Tile Self -Adhered
Underlayment Requirements as of 02/14/2011" for limitations for self -adhering underlayments used beneath tile roof
systems.
;C{LE:Sy57ENfOPTIONSPERFRSA�l07,•320�8-'05•.;� ,"::�'.'•-••� •. r(.r:: ':`.`::
System
Underlay
Option
Sectiori
Reference
Product(s)
1
3.02A
Batten onlyModified
Cap sheet
Elastoflex 56 G or Elastoflex 56 G FR; Polyflex G or G FR
System One:
2
3.028
No. 30/Modified Cap Sheet
Base Layer: Elastobase; Elastobase P
Mechanically Fastened
Top Layer: Elastoflex S6 G or Elastoflex 56 G FR; Polyflex G or G FR
Tile, Unsealed or
4
3.02D
No. 30
Elastobase; Elastobase P
Sealed Underlayment
System
S
3.02E
Self -Adhered Underlayment
Polystick MTS; MTS PLUS; TU P; TU Plus; TU Max;,Polyflex SAP orSAP FR; Mule -
Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR); Dual Pro; Tile Pro
6
3.02E
No. 30 / Self -Adhered
Base Layer: ASTM 0226, Type 11; Elastobase; Elastobase P; Mule -Hide Nail Base
Underlayment
Top Layer; Polystick MTS; MTS PLUS; TU P; TU Plus; TU Max; Polyflex SAP or SAP
FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR); Dual Pro; Tile Pro
Exterior Research and Design, LLC-
Certificate of Authorization #9503
Evaluation Report P12060.02.09-1115
FL5259-RZO
Revision 15: 08/25/2024
Page 8 of 11
S
TRINITY1 ER®
1
3.02A
Batten only
Modified Cap Sheet
Elastoflex S6 G or Elastoflex S6 G FR; Polyflex G or G FR
system Two;
2
3.02B
No. 30 / Modified Cap Sheet
Base Layer: Elastobase; Elastobase P
Mechanically Fastened
Top Layer: Elastoflex S6 G or Elastoflex S6 G FR; Polyflex G or G FR
Tile, Sealed
4
3.020
Self -Adhered Underlayment
Polystick TU P; TU Plus; TU Max; Polyflex SAP or SAP FR; Mule -Hide SA-APP Cap
Underlayment System
Sheet or SA-APP Cap Sheet (FR); Dual Pro; Tile Pro
S
No. 30 / Self -Adhered
Base Layer: ASTM D226, Type il; Elastobase; Elastobase P; Mule -Hide Nail Base
3.02E
,Underlayment
Top Layer: P01ystick TU P; TU Plus; TU Max; Polyflex SAP or SAP FR, Mule -Hide
SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro; Tile Pro
1
3.02A
Modified Cap Sheet
Elastoflex S6 G or Polyflex G
System Four •
2
3.02B
No. 30 / Modified Cap Sheet
Base Layer: Elastobase; Elastobase P
Top Layer; Elastoflex S6 G or Polyflex G
Adhesive -Set Tile,
le
Unsealed or Sealed
4W
-Adhered Underlayment
Polystick TU P; TU Plus; TU Max; Polyflex SAP or SAP FR; Tile Pro; Mule -Hide SA -
Underlayment System
APP Cap Sheet or SA-APP Cap Sheet (FRI
S
30 / Self -Adhered
Base Layer: ASTM D226, Type 11; Elastobase; Elastobase P; Mule -Hide Nail Base
erlayment
Top Layer: Polystick TU P; TU Plus; TU Max; Polyflex SAP or SAP FR; Tile Pro;
yf
Mule -Hide SA-APP Cap Sheet or SA4,PP Cap Sheet (FR)
1
30 /Modified Cap Sheet
Base Layer: ASTM D226, Type 11; Elastobase; Elastobase P
System Four "B":Top
Layer: Elastoflex S6 G or Polyflex G
Adhesive -Set Tile,
3
Adhered Underlayment
Polystick TU P; TU Plus; TU Max;Polyflex SAP or SAP FR; Tile Pro; Mule -Hide SA -
Sealed UnderlaymentAPP
Cap Sheet or SA-APP Cap Sheet (FR)
System
0 / Self -Adhered
Base Layer: ASTM D226, Type 11; Elastobase; Elastobase P; Mule -Hide Nail Base
4
rlayment
Top Layer: Polystick TU P; TU Plus; TU Max; Pol ex SAP or SAP FR; Tile Pro;
Polyflex
Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR)
6. INSTALLATION:
6.1 Polyglass Roof Underlayments, shall be installed in accordance with Polyglass published installation requirements
subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove
any dust and debris prior to application, and prime the substrate (if applicable).
6.3 Elastobase, Elastobase P or Mule -Hide Nail Base-
6.3.1 Shall be installed in compliance with the codified requirements for ASTM D226, Type II underlayment in FBC Sections
1507 for the type of prepared'roof covering to be installed.
6.3.2 For use in non -tile applications:
6.3.2.1 Reference is made to the current edition of the NRCA Steep -slope Roofing Manual and ARMA recommendations for
installing shingle underlayments and flashings
6.3.2.2 Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polystick, Polyflex SAP or SAP FR,
Mule -Hide SA-APP Cap Sheet. or SA-APP Cap Sheet (FR), Dual Pro or Tile Pro, self -adhered, Elastoflex S6 G or S6 G FR
in hot asphalt or Polyflex G or G FR, torch applied.
6.3.3 For use in tile applications, reference is made to Polyglass published installation instructions in conjunction with
FRSA/TRI 07320/8-05 Installa,'tion Manual, Fourth Edition, Table 2 herein and Section S.5.4 herein.
6.4 Polystick MTS, MTS PLUS IR-Xe, TU P. TU Plus TU Max Polyflex SAP or SAP FR Mule Hide SA APP Cap Sheet or SA
APP Cap Sheet fFIR Dual Pro or Tile Pro:
6.4.1 Shall be installed in compliance with the codified requirements for ASTM D1970 underlayment in FBC Sections 1507
for the type of prepared roof covering to be installed.
6.4.2 For non -tile applications:
6.4.2.1 All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule -Hide SA-APP Cap
Sheet or SA-APP Cap Sheet (FR) should be back -nailed in selvage edge seam in accordance with Polyglass / Mule -Hide
Back Nailing Guide. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 1-inch diameter
metal disk or Simplex -type metal cap nail, at a minimum rate of 12" D.C. Polystick TU Plus should be back -nailed
using the above noted fasteners and spacing, in area marked "nail area, area par@ clavar" on the face of membrane.
The head lap membrane is to cover the area being back -nailed
Exterior Research and Design, LLC-
Certificate of Authorization #9503
Evaluation Report P12060.02.09-R15
FL5259-R20
Revision 1S: 08/25/2024
Page 9 of 11
6.4.2.2 All seal -lap seams (selvage laps) must be firmly
rolled with a minimum 28 lb. hand roller to
ensure full contact and adhesion. For Dual Pro
and Tile Pro, align the edge of the top sheet to
the end of the glue pattern (the sheet will overlap
the fabric).
View of Ovelap Seam of Dual Pro and Tile Pro
TRINITY ; ER®
6.4.2.3 All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyglass Polyplus 55 Premium
Modified Flashing Cement, Polyglass Polyplus 50 Premium MB Flashing Cement, Polyglass PG500 MB Flashing
Cement, Polystick TU Plus Tile Underlayment Flashing Cement, Mule -Hide 241 Premium Modified Flashing Cement,
Mule -Hide 251 Premium Wet/bry Electrometric Flashing Cement, or Mule -Hide 421 Mod Bit Flashing Adhesive
Trowel Grade mastic, applied in between the application of the lap.
6.4.2.4 Polystick TU Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys,
or exposed roof to wall details
6.4.2.5 Repair of Polystick membranes is to be accomplished by applying Polyglass Polyplus 55 Premium Modified Flashing
Cement, Polyglass Polyplus 50 Premium MB Flashing Cement, Polyglass PG500 MB Flashing Cement, Polystick TU Plus
Tile Underlayment Flashing Cement, Mule -Hide 241 Premium -Modified Flashing Cement, Mule -Hide 251 Premium
Wet/Dry Elastomeric Flashing Cement, or Mule -Hide 421 Mod Bit Flashing Adhesive Trowel Grade mastic to the area
in need of repair, followed by a minimum 6 x 6 inch patch of the Polystick material of like kind, set and hand rolled in
place over the repair area. Patch laps, if needed, shall be installed in a water shedding manner.
6.4.2.6 All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a
minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 40-lbs of load applied
for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28 lb roller) or small areas of
the roof that are not accessible to a large roller or broom.
6.4.3 For tile applications (not allowed for Polystick IR-Xe):
6.4.3.1 Reference is made to Section 6.4.2 herein in conjunction with FRSA/TRI 07320/8-05 Installation Manual, Fourth
Edition, Table 2 herein and Section 5.5.4 herein, using the instructions noted above as a guideline.
6.4.3.2 For nail -on tile systems over Polystick MTS, battens are required for loading / staging of the tile.
6.4.3.3 For nail -on tile systems over Polystick MTS PLUS:
➢ Battens are required for loading/staging of lugged tile regardless of slope.
➢ Battens are required for loading/staging of flat tile at slopes in excess of 5:12.
6.4.4 Two (2) Ply Underlayment Systems:
6.4.4.1 Polystick MTS or MTS PLUS followed by Polystick MTS, TU P, TU Plus, TU Max, TilePro or Polyflex SAP is allowable for
use under mechanically attached prepared roof systems. Limits of use are those associated with the top -layer
material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired.
6.4.4.2 Polystick MTS PLUS followed by Polystick TU P, TU Plus, TU Max, TilePro or Polyflex SAP is allowable for use under
foam -on tile systems. Limits of use are those associated with the top -layer material. This is not a requirement, but is
allowable if a 2-ply underlayment system is desired.
6.5 Elastoflex S6 G or 56 G FIR:
6.5.1 Elastoflex 56 G or S6 G FR shall be installed in compliance with current Polyglass published installation requirements.
For use in tile applications, reference is made to FRSA/TRI 07320/8-OS Installation Manual, Fourth Edition, and Table
2 herein.
Exterior Research and Design, LLC. Evaluation Report P12060-02.09-R15
Cerrificote of Authorization a9503
FL5259-R20
Revision 15: 08/25/2014
Page 10 of 11
7.
8.
9.
� I
TRINITY: ERD
6.5.2 Elastoflex 56 G or S6 G FR shall be fully asphalt -applied to the substrates noted in Section 5.5. Side laps shall be
minimum 3-inch and end -laps minimum 6-inch wide, and off set end -laps minimum 3 feet from course to course.
Side and end laps shall be fully adhered in a complete mopping of hot asphalt with asphalt extending approximately
3/8-inch beyond the lap edge.
6.6 Polyflex G or G FR:
6.6.1 Polyflex G or G FR shall be installed in compliance with current Polyglass published installation requirements. For use
in tile applications, reference is made FRSA/TRI 07320/8-05 Installation Manual, Fourth Edition, and Table 2 herein.
6.6.2 Polyflex G or G FR shall be fully torch -applied to the substrates noted in Section 5.5. Side laps shall be minimum 3-
inch and end -laps minimum 6-inch'wide, and off set end -laps minimum 3 feet from course to course. Side and end
laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the
lap edge.
6.7 Tile Staging:
6.7.1 Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. Refer to
Polyglass published requirements for tile staging.
6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI 07320/8-05 must be used on all
roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or nail -boards, to
prevent tile sliding and/or damage to the underlayment during the loading process.
6.7.3 For nail -on tile systems over Polystick MTS, battens are required for loading / staging of the tile.
6.7.4 For nail -on tile systems over Polysti'ck MTS PLUS:
➢ Battens are required for loading/staging of lugged tile regardless of slope.
➢ Battens are required for loading/staging of flat tile at slopes in excess of 5:12.
6.7.5 The minimum cure time after installation of self -adhering membranes and before loading of roofing tiles is forty-
eight (48) hours.
BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or AuthorityiHaving Jurisdiction in order to properly evaluate the installation of this product.
MANUFACTURING PLANTS:
Contact the noted CIA agency for information on product locations covered for F.A.C. Rule 61G20-3 CIA requirements.
QUALITY ASSURANCE ENTITY:
UL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com
- END OF EVALUATION REPORT -