HomeMy WebLinkAboutNOA - MODIFIED BITUMENT ROOF SYTEMFILE COPY SCANNED RECEIVED Rt i I tP fP;�'lt��f�� MAR g 1Q18 EXTERIOR RESEARCH & DESIGN, I.I.C. 3, x'—•% Certificate of Authorization#9503 - f) �� i E E� (permitting Department 353 Christian Street K,r i i E I St. Lucie County Oxford, CT 06478 (203)262-9245 EVALUATION REPORT Polygiass USA, Inc. Evaluation Report P9290.02.08-1120 150 Lyqn Drive FL1654-R22 Fernley, NV 89408 Date of Issuance: 02/11/2008 (570) 384-1230 Revision 20: 09/12/2017 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. he documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Buijding Code. The product described herein has been evaluated for compliance with the 6u' Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: Polyglass SSS and APP Modified Bitu (men Roof Systems LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is va Quality Assurance documentation changes, or prov this Evaluation Report by the named client consl changes or the referenced Quality Assurance docui Evaluation Report relative to updated Code require ADVERTISEMENT: The Evaluation Report number pre advertising literature. If any portion of the Evaluati INSPECTION: Upon request, a copy of this entire Eval its distributors and shall be available for inspection until such time as the named product(s) changes, the referenced ms of the Code that relate to the product change. Acceptance of ites agreement to notify Robert Nleminen, P.E. if the product ntation changes. Trinityl ERD requires a complete review of this ants with each Code Cycle. Jed by the words "Trinity I ERD Evaluated" may be displayed in Report is displayed, then it shall be done In its entirety. tion Report shall be provided to the user by the manufacturer or the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 6,1 plus a 58-page Appendix. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCAANE1983 CERTIFICATION Of INDEPENDENCE: I. Exterior Research & Design, LLC, d/b/a Trinity I E in any company manufacturing or distributing prc 2. Exterior Research & Design, LLC. d/b/a Trinity distributing products it evaluates. 3. Robert Nieminen, P,E, does not have nor will acq which the evaluation reports are being issued. 4. Robert Nleminen, P.E. does not have, nor will ac( product, S. This is a building code evaluation. Neither Trini,. project on which this Evaluation Report, or prevli specifically for that purpose. CONCEALED FASTENERS OR Ai TACHMM ARE THE RESPONSIBILITY OF THE CONTRACTOR OF RECORD THESE PLANS ANC ARE SUBJECT M ) REQUIRED BY FIEL MAY BE NECESSAF 6AMPhY WITH The facsimile seal appearing was authorized by Robert Nieminen, P.P. on 09/12/2017. This does not serve as an electronically signed document. and to acquire or will It acquire, a financial Interest or controlled by any company manufacturing or )mpany manufacturing or distributing products for then entity involved in the approval process of the :. are, in any way, the Designer of Record for any for permitting or design guidance unless retained ST. LIVE COUNTY BUII. D ION R.EVTFV%']ED FOR CO, REVIEWED BY DATE &-12-fy___-- — PLANS AND PEI7MIT T RE KEPT ON JOB OR NO INSPECTION WML BE MADE. N",,JTR11T(J ERD ROOFING SYSTEMS EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Modified Bitumen Roof Systems Compliance Statement: Polyglass SBS and APP Modified Bitumen Roof Systems, as produced by Polyglass USA, Inc., have demonstrated compliance with the following sections of the 6th Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Propert Standard Year 1504.3.1 Wind I FM 4474 2011 1504.3.1 Wind UL 1897 2012 1504.7 impact I FM 4470 2012 1507.11.2 Physical Properties ASTM D6162 2008 1507,11.2 Physical Properties ASTM D6163 2008 1507.11.2 Physical Properties ASTM D6164 2011 1507,11.2 Physical Properties ASTM D6222 2011 1507.11.2 Physical Properties ASTM D6509 2009 3. REFERENCES: Entity Examination Reference Date ERD (TST6049) Physical Properties P10490.10.08-2 10/30/2008 ERD (TST6049) FM 4470/4474 P13760.09.09 09/10/2009 ERD (TST6049) FM 4470/4474 P13770.09.09 09/10/2009 ERD (TST6049) FM 4470/4474 P30540.11,09-R1 21/30/2009 ERD (TST6049) FM 4470/4474 P30550.12.09 12/02/2009 ERD (TST6049) Physical Properties P33960.12.10 12/30/2010 ERD (TST6049) FM 4470/4474 P33970.03.11 03/15/2011 ERD (TST6049) Physical Properties P37590.03.13-3A 03/06/2013 ERD (TST6049) FM 4470/4474 P39680.03.13 03/04/2013 ERD (TST6049) Physical Properties P37590.03.13-1-R1 06/26/2013 ERD (TST6049) Physical Properties P37590.03.13.2-R1 07/01/2013 ERD (TST6049) Physical Properties P37590.07.13-2 07/01/2013 ERD (TST6049) Physical Properties P37590.03.13-5-R1 07/01/2013 ERD (TST6049) Physical Properties P37590.07.13-1 •07/02/2013 ERD (TST6049) FM 4470/4474 P41630.08.13 08/06/2013 ERD (TST6049) Physical Properties P45940.09.13 09/04/2013 ERD (TST6049) Physical Properties P44370.10.13 10/04/2013 ERD (TST6049) Physical Properties P39520.09.14-2 09/11/2014 ERD (TST6049) FM 4470/4474 SC6160.11.14 11/10/2014 ERD (TST6049) Physical Properties PLYG-P454405C.03.15.1 03/31/2015 ERD (TST6049) Physical Properties SC5170,05.15 05/08/2015 ERD (TST6049) FM 4474 SC8085.05.15 05/19/2015 ERD (TST6049) Physical Properties SCS170.12.15 12/29/2015 ERD (TST6049) FM 4470/4474 SC9455.15 04/01/2016 ERD (TST6049) FM 4470/4474 PLYG-SC8905.05.16.1 15/17/2016 ERD (TST6049) FM 4470/4474 PLYG-SCS905.05.16-2 05/17/2016 ERD (TST6049) FM 4470/4474 PLYG-SC10815.07.16-R1 09/23/2016 ERR (TST6049) UL 1897 I PLYG-SC12025.10.16 10/12/2016 ERD (TST6049) FM 4470/4474 I PLYG-SC11475,16 11/17/2016 ERD (TST6049) FM 4470/4474/UL1897 PLYG-SC13235.01.17 01/17/2017 ERD (TST6049) FM 4474/U L1897/TAS 1114 PLYG-SC13920.05.17 05/30/2017 ERD(TST11294) FM 4474/U L1897/TAS, 14 PLYG-CTL13945.05.17-1 05/30/2017 i Exterior Research and Design, LLC. Evaluation Report P9290.02,08-R20 Certificate of Authorization#9504 6"' EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-R22 Polyglass Modified Bitumen Roof Systems; (570) 384.1230 Revision 20: 09/12/2027 Page 2 of 6 Entity ERD (T5T11294) ERD (TST6049) ERD (TST6049) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) FM Approvals (TST1867) PRI(TST5878) PRI(TST5878) PRI(TST5878) PRI (TST5878) PRI(TST5878) PRI(TST5878) PRI(TST5878) PRI(TST5878) PRI (TST5878) Miami -Dade (CER1592) Miami -Dade (CER1592) UL LLC (QUA9625) TR.INIT ' I. ERD Reference AS 114 PLYG-CTL13945,05,17.3 PLYG-SC13945,05.17 PLYG-SC15760.09,17 2W7A7.AM OD3A3.AM 2DOAO.AM 2DSA9.AM 3006646 3001334 3001334 3000857 3004091 3006115 3012321 3014692 3014751 3007170 3019317 3020703 3018332 3023368 3024594 3023458 3030668 3032172 3049631 3057029 PUSA-062-02-01 PUSA-061-02-02 PUSA-064-02-02 PUSA-062-02-02 PUSA-188-02-01 PUSA-188-02-02 l PUSA-188-02-03 PUSA-202-02-01 l PUSA-202-02-02 Various NOAs w 10-0823 ty n Service Confirmation, R14571 Exp. 10/06/2018 4. PRODUCT DESCRIPTION: I This Evaluation Report covers Polyglass Modified Bitumen Roof Systems installed in accordance with Polyglass USA, Inc. published installation instructions and the Limitations / Conditions of Use herein. The following Polyglass membranes make up the subject systems. Examination FM 4474/UL1897(T FM 4474/UL1897I FM 4474/TAS 11�} FM 4470 FM 4470 FM 4470 FM 4470 FM 4470 FM 4470 FM 4470 FIVI 4470 FM 4470 FM 4470 FM 4470 FM '4470 FM 4470 FM 4470 FM 4470 FM 4470 FM 4470/4474 FM 4470/4474 FM 4470/4474 FM 4470/4474 FM 4470/4474 FM 4470/4474 FM 4470/4474 FM 4470/4474 Physical Properties Physical Properties Physical Properties Physical Properties TAS 114 TAS 114 TAS 114 TAS 114 TAS 114 HVHZ Compliance Proposal for Revie nl n Co trot Date 05/30/2017 05/30/2017 09/11/2017 08/04/1994 04/04/1997 12/23/1998 06/22/1999 01/04/2000 01/25/2000 02/15/2000 01/12/2000 01/12/2000 05/02/2001 07/29/2002 08/05/2003 08/27/2003 01/13/2004 06/30/2004 07/30/2004 01/31/2006 03/20/2006 05/23/2006 07/18/2006 09/12/2007 06/12/2009 04/21/2014 02/02/2017 22/04/2007 01/28/2008 02/27/2008 12/04/2008 02/08/2017 02/08/2017 02/08/2017 05/17/2017 05/17/2017 Various 10/12/2010 :.vt,:,.is /..,�. r: :�-. rr<.+i....a,+.,.. �..:...::::s:_:-4:`.�.�:':v�_.:4:':.r.:.;.'.u�n:..: _:a.; �.,..i-:�i.,;.i.: ��,:., .• ::n:TE D lY�L�3S:�2TODt'� R i'3S - - a...: Type Product Specification Reference Grade Type Base Sheets Polyglass G2 Base ASTM D4601 N/A 11 Polyflex SA Base ASTM D4601 N/A 11 Polyglass APP Base ASTM D6509 N/A N/A Exterior Research and Design, LLC. Certificate of Authorization #9503 6TH EDITION (2017)IFBC NON-HVHZ EVALUATION Polyglass Modified Bitumen Roof Systems; (570) 384-2230 Evaluation Report P9290.02.08-R20 FL1654-R22 Revision 20: 09/12/2017 Page 3 of 6 \ TRINITY j ER® 4: .3 '.�d :�- ... � �+v Pdi<� .�S:fVti7iJ��(�t3�i� :'Fill; :5y �;� :>�:..::a...�.•,:::.�,�:.: P am. .,.p . Type Product Specification Reference Grade Type SBS Membranes Polyglass HT Base 650 ASTM D6162 S iII Elastobase ASTM D6163 5 1 Elastoflex V ASTM D6163 S 1 Elastoflex SA V Bdse ASTM D6163, Table 2 S I Elastoflex SA V FR Base ASTM D6163, Table 2 S i Elastoflex SA V Plus ASTM D6163 S 1 Elastoflex SA V Plus FR ASTM D6163 S I Elastobase Poly ASTM D6164 5 I Elastoflex S6 ASTM D6164 S I Elastoflex S6 T pel II ASTM D6164 S II Elastoflex VG ASTM D6163 G I Elastoflex VG FR ASTM 06163 G I SBS Membranes Elastoflex S6 G ASTM D6164 G I Elastoflex S6 G FR ASTM D6164 G I Polyfresko G SBS (sand or poly -film backed) ASTM D6164 G I Polyfresko G SBS FR (sand or poly -film backed) ASTM D6164 G I Elastoshield TS G ASTM D6164 G I Elastoshield TS G Fit ASTM D6164 G I Elastoflex SAP ASTM D6164 G 1 blastoflex SA P FR ASTM D6164 G I Polyreflect ASTM D6164 S I APP Membranes Polyflex ASTM D6222 S I Polyflex G ASTM D6222 G i Polyflex G FR ASTM D6222 G I Polyfresko G I ASTM D6222 G 1 Polyfresko G FR ASTM D6222 G I Pol bond ASTM D6222 S I Polybond G ASTM D6222 G I Polyflex SA P ASTM 06222 G I Polyflex SA P FR ASTM D6222 G I Polyfresko G SA ASTM D6222 G I Poiykool ASTM D6222 S I 5. LIMITATIONS: 5.1 This is a building code evaluation. Neither Trinity J ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose, 5.2 This Evaluation Report is not for use in FBC HVHZjunsdictions. 5.3 Refer to a current Approved Roofing Materials Directory for fire ratings of this product. 5.4 For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance with FBC 2603.4 unless the exceptions sated in FBC 2603.4.1 and 2603.6 apply. 5.5 The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be .In accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the rool f deck shall be documented through proper codified and/or FBC Approval documentation. 5.6 For recover installations, the existing roof shall be examined in accordance with FBC 1511. Exterior Research and Design, I.I.C. Evaluation Report P9290.02.08-1120 Certificate of Authorization #9503 6TM EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-RZZ Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Revision 20: 09/12/2017 Page 4 of 6 5.7 5.8 For mechanically attached insulation for the selected assembly shall mee FBC Chapter 16. Zones 2 and 3 professional to resist the elevated p Prevention Data Sheet 1-29, Roofin 137. Assemblies marked with an a Prevention Data Sheet 1-29 (January For assemblies with a!I components assembly shall meet or exceed critic rational analysis is permitted for thes 10 .' TR1N1TY 1 ERD a or membrane or strip -bonded insulation, the maximum design pressure t or exceed the Zone 1 design pressure determined in accordance with shall employ an attachment density designed by a qualified design ressure criteria. Commonly used methods are ANSi/SPRI WD1, FM loss g Application Standard RAS 117 and Roofing Application Standard RAS sterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss i 2016) for Zone 2/3 enhancements. (fully bonded in place, the maximum design pressure for the selected al design pressure determined in accordance with FBC Chapter 16. No e systems. 5.9 For mechanically attached insulation or membrane over existing roof decks, fasteners shall be tested In the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard I AS 105. 5.10 For bonded insulation or membrane olver existing substrates in a re -roof (tear off) or recover installation, the existing deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If any surface conditions exist that bring system performance into question, field uplift testing in accordance with ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124 shall be conducted on mock-ups o the proposed new roof assembly. 5.11 For bonded insulation of membrane over existing substrates in a recover installation, the existing roof system shall be capable of resisting project design pressures on Its own merlt to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124, 5.12 Metal edge attachment (except gutters), shall be designed and installed for wind loads in accordance with FBC Chapter 16 and tested for resistance in accordance with ANSI/SPRI ES-1 or Roofing Application Standard RAS 111, except the basic wind speed shall be determined from FBC Figure 1609.3(1), 1609.3(2) or 1609.3(3). 5.13 All products in the roof assembly shall 6. INSTALLATION: quality assurance in accordance with FAC Rule 61G20-3. 6.1 Polyglass Modified Bitumen Roof Systems shall be installed in accordance with Polyglass USA, Inc. published installation instructions, subject to the Limitations / Conditions of Use noted herein. 6.2 System attachment requirements for wi II d load resistance are set forth in Appendix 1. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FBC 1609 for determination of design wind loads. Exterior Research and Design, LLC. Evaluation Report P9290.02.08-R20 Certificate of Authorization #9503. 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-R22 Polyglass Modified Situ en Roof Systems; (570) 384-1230 Revision 20: 09/12/2017 7 Page 5 of 6 6.3 Any of the following FBC Approved co< on the system wind load performance. with coating usage, ➢ PG200 Non-Fibered Roof Coati ➢ PG300 Fibered Roof Coating; ➢ PG600 Non-Fibered Aluminumli ➢ PG650 Fibered Aluminum Roof ➢ PG700 High Quality Elastome4 ➢ PG700QS (Quick -Set) High Qua APP or SBS only); ➢ PG800 Asphalt Emulsion Roof ➢ Polyplus 60 Premium Non-Fibe ➢ Polyplus 65 Premium Fibered P ➢ Polybrite 70 Premium Grade El ➢ Polybrite 70QS (Quick -Set) Prei surfaced APP or SBS only); ➢ Polybrite 90 High Solids Silicone ➢ Polybrite 95 Silicone Roof Coat 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Autho this product. 8. MANUFACTURING PLANTS: Contact the noted QA agency for requirements 9. QUALITY ASSURANCE ENTITY: UL LLC—QUA9625; (314) 578-3406, - THE 58-PAGES THAT TRIM d i { ERD tings may be applied to the top roof membrane without adverse effect Refer to current Roofing Materials Directory for fire ratings associated ng; Roof Coating; Coating; Roof Coating or KM Acryl 25; lity Elastomeric Roof Coating or KM Acryl 25-QS (over granule -surfaced pating; red Aluminum Roof Coating; luminum Roof Coating; astomeric Roof Coating or KM Acryl 15; nium Grade Elastomeric Roof Coating or KM Acryl 15-QS (over granule - Roof Coating; Having Jurisdiction in order to properly evaluate the installation of on on product locations covered for F.A.C. Rule 61G20-3 QA )lr@us.ui.com /i FORM PART OF THIS EVALUATION REPORT - Exterior Research and Design, LLC. Certificate of Authorization #9503 6rH EDITION (2017) FBC NON-HVHZ EVALUATION Polyglass Modified i3itumen Roof Systems; (570) 384-1230 Evaluation Report P9290.02.08-R20 FL1654-R22 Revision 20: 09/12/2017 Page 6 of 6 -�. TRIilY ERa Table Deck Application Type Description Page 1A Wood New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 5 1B-1 Wood New or Reroof (Tear -off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 5-9 1B-2 Wood New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 10-11 IC Wood New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 11 1D Wood New, Reroof (fear -off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 12-13 1E Wood New, Reroof (Tear -Off) or Recover D Prelim. Attached insulation, Mech. Attached Base Sheet, Bonded Roof Cover 14-15 IF-1 Wood New or Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet (nails), Bonded Roof Cover 16-18 1F-2 Wood New, Reroof (rear -Off) or Recover E Non -insulated, Mech. Attached Base Sheet (screws & plates), Bonded Roof Cover 19-21 SG Wood New or Reroof (Tear -Off) F Non -Insulated, Bonded Roof Cover 21 2A Steel or Structural concrete New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 22-24 26 Steel or Structural concrete New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 25-28 2C Steel or Structural concrete New, Reroof (Tear -Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover 29-31 3A Structural concrete New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 32-40 36 Structural concrete New or Reroof (rear -Off) F Non -Insulated, Bonded Roof Cover 40 4A LWIC _ New -or-Reroof -(Tear-OfQ A-- Bonded Insulation, Bonded Roof Cover 41-42 4B LWIC New or Reroof (Tear -off) A-2 Mech. Attached Anchor Sheet Bonded Insulation, Bonded Roof Cover 43 4C LWIC New or Reroof (Tear -Off) E Non -insulated, Mech. Attached Base Sheet, Bonded Roof Cover 44-46 SA CWF New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 47 5B CWF New, Remo€ (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet; Bonded Insulation, Bonded Roof Cover 48 5C CWF New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 49 5D CWF New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 49 SE CWF New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 49 6A Gypsum Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 50-52 6B Gypsum Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 52 6C Gypsum Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 53 6D Gypsum Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 53 7A Various Recover A-1 Bonded Insulation, Bonded Roof Cover 54-58 7B Various Recover F Non -Insulated, Bonded Base Sheet, Bonded Roof Cover 58 The following notes apply to the systems outlined herein: 1. The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be in accordance with FEC requirements to the satisfaction of the Authority Having Jurisdiction Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. Insulation / base sheet fasteners shall be of sufficient length for the following deck engagement: ➢ Wood: Minimum 0.75-Inch penetration. ➢ Steel: Minimum 0.75-inch penetration and engage the top flute of the steel deck. ➢ Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturers published installation instructions. Unless otherwise noted, insulation may be any one layer or combination of polylsocyanurate, polystyrene, wood fiberboard, perlite, gypsum -based roof board -or mineral -wool -roof board that meets the CIA requirements of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover. Exterior Research and Design, U.C. d/b/a Trinity[ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization #9503 67 EDITION (2017) FBC NON-H VH2 EVALUATION -Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-2230 Appendix 1, Page 1 of 58 4 `TRINITY t ERD Minimum 200 psi, minimum 2-Inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover), whereby the base sheet fasteners are installed through the LWIC to engage the structural steel or concrete deck The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 5. Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016). Unless otherwise noted, insulation adhesive application rates areas follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted In the manufacturer's published instructions. ➢ Hot asphalt (HA): Full coverage at 25-30 Ibs/square. ➢ Dow INSTA STIK Ctuik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1-inch wide ribbons, 12-Inch o.c. ➢ Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0-25 to 0.5-inch wide ribbons,l2-inch o.c. ➢ Millennium PG-1 Pump Grade Adhesive (M-PGl): Continuous 0.25 to 0.5-inch wide ribbons, 1-2-inch o.c. ➢ OMG OlyBond 500 (08500): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c. (PaceCart or SpotShot). Note: 0ly8ond Green may be used where OlyBond 500 is referenced. ➢ OiyBond Classic (OB Classic): Full coverage at 1 gal/square. ➢ ICP Adhesive & Sealants CR-20: Continuous 25-3.5-inch wide ribbons,12-inch o.c. ➢ Note. When multiple loyers(s) of insulation and/orcoverboard are installed in ribbon -applied adhesive, board joints shall be staggered. ➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one -boy' the specked ribbons spacing. Unless otherwise noted, all insulations are flat -stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following Maximum Design Pressure (MDP) limitations- In no case shall these values be used to `increase' the MDP listings in the tables; rather if MDP listing below meets-or_exceeds-that listed-for-a-particGlarsystem in the tables, then the thinner board listed below may be used as a drop -in for the equivalent -thicker -material -listed -in the tattle: ➢ Millennium PG-1 Pump Grade Adhesive (M-PG1): ➢ OMG OlyBond 500 (OBS00): ➢ OMG OlyBond 500 (06500): ➢ OMG OlyBond 500 (OB500): ➢ OMG OlyBond 500 (OB500): ➢ ICP Adhesives & Sealants CR-20: MDP -iS7.5 psf (Min. 0.5-inch thick) MDP -1575 psf (Min.0.5-inch thick) MDP -45.0 psf (Min. 0.5-inch thick Multi -Max PA-3) MDP -187.5 psf (Min. 0.5-inch thick ISO 95+ GL) MDP -315.0 psf (Min. 0.5-inch thick ENRGY 3) MDP -487.5 psf (Min. 0.5-inch thick ACFoam II) MDP -117.5 psf (Min. 1.0-inch thick) 8. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft. 9. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC -Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk' carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements- 10. For fully bonded assemblies, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no rational analysis is permitted. 11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysisshall be in accordancewith ANSI/SPRI FX-1 or Testing Application Standard TAS 105. 12. For existing substrates in a bonded recover or re -roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the existing roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing In accordance with ANSt/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124. 13. For Recover Applications using System Type D, the Insulation is optional; however, the existing roof system shall be suitable for a recover application. 14. Lightweight Insulating Concrete (LWC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced, refer to current LWC Product Approval for specific deck construction and limitations. For systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. in all cases, the minimum top -coat thickness is 2-inches. For LWC over structural concrete, reference is made to FBC Section 1917.4A, Point 1. Exterior Research and Design, LLC. d/b/a Trinity( ERD Evaluation Report P9290.02.08-R20 for FL1654-R22 Certificate of Authorization N9503 6n' EOrrm (2017) FBC NON.HVHZ EVALUATION Revision 20: 09/12/2017 Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 2 of 58 15. Unless otherwise noted, refer to the followine references for bonded base. olv or can sheet aoolications .. _. .. .... .... .,.... t ­777- ... ........ .. .. ....., :. _,::io."4 hi' -:a:' `*7:771 Reference Layer Material Application BP -AA Base Ply One or more plies Polyglass G2 Base, FBC Approved ASTM D4601, Type If (Base and Ply sheets, Asphalt- Ply One or more plies Polyglass Ply IV, Polyglass Ply VI, FBC Approved ASTM 02178, Type IV or VI Hot Asphalt at 20-40 Applied) PP ) Nate: Asphalt -applied sheets or insulation shall not be applied to poly -film surfaced membranes. Ibs/square Base Ply One ply Elastobase (sand/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 Type 11, Polyglass HT Base 650 SBS-CA1 Cap Ply Eiastoflex VG, Elastoflex VG FR, Elastoflex S6, Elastoflex S6 Type 11, Elastoflex S6 G, Elastoflex S6 G FR, Elastoshield T5-G, Elastoshield PG350 at 1.5-2-0 gal/square TS-G FR, Polyfresko G SSS (sand -backed), Polyfresko G SBS FR (sand -backed) Base Ply One ply Elastobase (sand/sand), Elastoflex V, Elastoflex S6, Elastoflex S6 Type 11 SBS-CA2 Cap Ply Elastoflex VG, Elastoflex VG FR, Elastoflex S6, Elastoflex S6 Type 11, Elastoflex S6 G, Elastoflex S6 G FR, Elastoshield TS-G, Elastoshield Polyplus 35 at 1.5-2.0 gal/square TS-G FR, Polyfresko G SBS (sand -backed), Polyfresko G SBS FR (sand -backed) Base Ply or Ply One or more plies Elastobase (sand/sand or poly/sand), Elastobase P (sand/sand or poly/sand), Elastoflex V, Elastoflex S6, Elastoflex SBS S6 Type 11, Polyglass HT Base 650 AA Hot As at 20-40 (SBS, Asphalt -Applied) Cap Ply Elastoflex V, Elastoflex VG, Efastoflex VG FR, Elastoflex S6, Elastoflex S6 Type 11, Elastoflex S6 G, Elastoflex S6 G FR, Elastoshield TS-G, Ibs/square Elastoshield TS-G FR, Polyfresko G SBS (sand -backed), Polyfresko G SBS FR (sand -backed) Note: Asphalt -applied sheets or Insulation shall not be applied to poly -film surfaced membranes. _ or more plies Elastobase (sand/poly), Elastobase (poly/poly), Elastoflex V, Elastoflex S6, ElastoflexS6 Type-Il,-Polyglass HT Base SBS TA Base Ply or Ply 650 (SB5, Torch=Applied)_ -- Cap Ply -Efastoflex V, Elastoflex VG, Elastoflex VG FR, ElastoflexSG, Elastoflex 56 Type 11, Elastoflex S6 G, Elastoflex 56 G FR, Elastoshield TS-G, Torch -Applied Elastoshield TS-G FR, Polyfresko G SBS (poly -film backed), Polyfresko G SBS FR (poly -film backed) Base Ply One or more plies Elastoflex SA V Base, Elastoflex SA V FR Base, Elastoflex SA V Plus, Elastoflex $A V Pius FR SBS-SA Cap Ply Elastoflex SA P, Elastoflex SA P FR, Polyreflect (SBS, Self -Adhering) Unless otherwise noted, permissible membrane substrates forsBS-SA are limited to the SBS-SA Base Ply options herein, Self -Adhering Now' Elostobase (poi /san or Elostobase of Y d1 (P Y/PoIY)• APP-CAI Cap Ply Polyflex G FR PG350 at 15-2.0 gal/square APP-TA Base Ply or Ply One or more plies Polyglass APP Base, Polyflex, Polybond (APP, Torch -Applied) Cap Ply Polyflex, Polyflex G, Polyflex G FR, Polybond, Polybond G, Polyfresko G, Polyfresko G FR Torch -Applied APP-SA Cap Ply Polyflex SA P, Polyflex SA P FR, Polyfresko G SA, Polykoal (APP, Self -Adhering) Note: Unless otherwise noted, permissible membrane substrates forAPP-SA are limited to the SBS SA Base Ply options herein, Self -Adhering Elostobase(poly/sand) or Elostobase (poly/poly). 16. Any of the following FBC Approved coatings maybe applied to the top roof membrane without adverse effect on the system wind load performance. associated with coating usage. D PG20D Non Fibered Roof Coating; ➢ PG3011 Fibered Roof Coating; D PG600 Non-Fibered Aluminum Roof Coating; ➢ PG650 Fibered Aluminum Roof Coating; ➢ PG700 High Quality Elastomeric Roof Coating or KM Acryl25; D PG700QS (Quick Set) High Quality ElastomericRoof Coating or KMAcryl 2S-QS (forgranuie-surfaced APP orSRS only); D PG800 Asphalt Emulsion Roof Coating; ➢ Polyplus 60 Premium Non-Fibered Aluminum Roof Coating; D Polyplus 65 Premium Fibered Aluminum Roof Coating; D Polybrite 70 Premium Grade Eiastomeric Roof Coating or KM Acryf 15; ➢ Polybrite 70QS (Quick Set) Premium Grade Elastomeric Roof Coating or KM Acryl 15-QS (for granule -surfaced APP or SSS onyj; D Polybrite 90 Nigh Solids Silicone Roof Coating or Polybrite 95 Silicone Roof Coating. Exterior Research and Design, LLC. d/b/a TrinitylERD Certlficate of Authorization #9503 6TM EDITION (2017) FBC NON-HVHZ EVALUATION Prepared by: Robert Niernmen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1730 Refer to current Roofing Materials Directory for fire ratings Evaluation Report P9290.02.08-R20 for FL1654-RZZ Revision 20: 09/12/2017 Appendix 1, Page 3 of 58 "1 -° j T RINITYIERD 17. Dens Deck shall be field -primed with PG100 prior to self -adhering membrane application. Refer to tables herein for other priming requirements. 18. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Design Pressure (MDP) limitations. The lesser of the MDP listings below vs. those in Table 3A applies: y A ..... � 4 N3 STD cfuRn o u oN.P .A 0i1 �.. T P .. .... lid R .. .. .... ...... � .JtiS • Option # Primer Vapor Barrier Insulation Adhesive MDP (psf) Type Attach VB-L PG100 Elastoflex SA V Plus Self -Adhering Inta-Stik or CR-20,12-inch o.c. -60.0 VB-2_ PG300 Polyglass APP Base Torch -applied Inta-Stik or CR-20, 12-inch o.c. -75.0 VB-3. PGI00 Efastoflex SA P Self -Adhering Insta-Stik, 12-inch o.c. -75.0 VB-4. PG100 Elastoflex SA P Self -Adhering Millennium One Step Foamable Adhesive, 12-Inch o.c. -157.5 VB-S. PG300 Elastoflex SA P Self -Adhering CR-20,12-inch o.c. -270.0 VB-6. PG100 Elastoflex SA V Base, Elastoflex SA V FR Base, Elastoflex SA V Plus, Elastoflex SA V Plus FR Self -Adhering Millennium One Step Foamable Adhesive, Millennium PG-1 Pump Grade Adhesive, OlyBond 500 or CR-20,12-inch o.c. -290.0 19. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads. Exterior Research and Design, LLC. d/b/a Trinity I ERD -Evaluation Report P9290.02.08-R20 for FL1654-RZZ Certificate of Authorization #9503 67" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017 Prepared -by: Robert Nfeminen, PE-59166 Polyglass Modified Bitumen Roof Systems, (570) 384-1230 Appendix 1, Page 4 of 58 MI.] TRINITY !ERD YR. NA System Dark (Note 1) Base Sheet Roof Cover .1. 15) MOP No. Type Fasten Attach Base Ply Cap (psf) c2l", 0 W-136 Min. 19 2- Elastobase, Elastobase P Dekfast Hex (aka, Dekfast PLT-il-2-7/8) with Dekfast #14 12-inch ci.c. in 4-inch lap and 12-Inch o.c. in two SBS-SA, APP-SA, SBS- inch plywood (poly -film top) or Trulast 3' Metal Insulation Plate with TrUfast HD (2), equally spaced, staggered center rows SOS -SA TA, APP-TA W-137 Min. 19/32- Elastobase, Elastobase P Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14 12-Inch o.c. In 4-inch tap and 12-inch o.c. In two inch plywood (poly -film top) or TrufaA 3" Metal Insulation Plate with Trufast HD (2). equally spaced, staggered center rows Polyflex SA Base APP-TA -52.5* W-138 Min'19/32- inch Elastobase, Elastobase P top) OMG Flat BPlates Bottom (square) with Roofgrip #12 12-inch o-c- in 4-inch lap and 12-Inch o.c. in two SBS-SA SBS-SA, APP-SA, SBS- -60.0* plywood (poly -film (2), equally spaced, staggered center rows TA, APP-TA W-139 Min. 19/32- inch plywood Elastobase, Elastobase P (poly -film top) OMG Flat Bottom Plates (square) with Roofgrlp #12 12-Inch o.c. in 4-inch lap and 12-Inch o.c. in two Polyflex SA Base APP-TA 60.0 (2), equally spaced, staggered center rows -J, System Deck (Note 1) Primer Roof Cover (Note 15) JointTreatment base Ply _—Mly— No. MDP (psf) mKolin-IFIS I , 585- SBS- 0"T mchNone w1-pi �A Min. 15/32- ram— J W-141 inch plywood (Optional) PG100 None Polyflex SA Base (Optional) APP-TA APP-TA -90.0 W-142 Min. 15/32- PG100 None SBS-SA (Optional) SBS SA, SBS- SBS-SA, APP-SA, SOS- Inch plywood TA, APP-TA TA, APP-TA -97.5 W-143 Min. 15/32- (Optional) PG100 Plywood joints are covered with 4-Inch wide strips of Elastoflex SA V Plus, rolled into Elastoflex SA V Base or (Optional) SBS-SA, SBS- SBS-S& APP-SA, SBS- Inch plywood place to create continuous bond. Elastoflex SA V FR Base TA, APP-TA TA, APP-TA -97-5 W-144 Min. 15/32- Inch WB_3 000 None SBS-SA (Optional) SBS-SA, APP-SA, SBS- -105.0 plywood TA, APP-TA W-145 Min. 15/32- (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled Into Elastoflex SA V Plus or (Optional) SBS­SA, SBS- SBS-SA, APP-SA, SBS- inch plywood place to create continuous bond. Elastoflex SA V Pius FR TA, APP-TA TA, APP-TA -135-0 W-146 Min. 15/32- (Optional) PG100 Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled into I inch plywood , I place to create continuous bond. Polyflex SA Base (Optional) APP-TA APP-TA - 135.0 Exterior Research and Design, LI.C. d/b/a TrinitVj ERD Certificate of Authorization #9503 Prepared by: Robert Nieminen, PE-59166 e" EDITION (2017) FBC NON-HVHZ EVALUATION Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Evaluation Report P9290.02.08-R20 for 171.1654-1122 Revision 20:69/12/2017 Appendix i, Page 2.1 of 58