Request for 30-
5333 Emerson A
g & Development Services
i & Code Regulation Division
rginia Ave
�rce, FL 34982
t-2165 Fax 772-462-6443
Temporary Power Release
Permit Number:
1803-0756
Ft. Pierce, FI. 34951
THE UNDERSIGNED HEREBY REQUEST RELEASE IOF ELECTRICAL POWER TO THE ABOVE DESCRIBED
PROPERTY, FOR A PERIOD NOT TO EXCEED THIRTY (30) DAYS, FOR THE PURPOSE OF TESTING SYSTEMS
AND EQUIPMENT IN PREPARATION FOR A FINAL11 INSPECTION. IN CONSIDERATION OF APPROVAL OF THE
REQUEST WE HEREBY ACKNOWLEDGE AND AGREE AS FOLLOWS:
1. This temporary power release is requested
occupancy of any type, other than that per
2. As witness by our signatures, we hereby a(
including Building Division Policy, which is
3. All conditions and requirements listed in th
Power for Testing" have been fulfilled and
4. All requests for an extension beyond 30 da
the reason for the request. Power may be
the Final Inspection has not been approve(
the Stop Work Order.
for the above stated purpose only, and there will be no
miffed by construction during this time period.
Iree to abide by all terms and conditions of this agreement,
ncorporated herein by reference.
attached document entitled "Requirements for 30 Day
the premise is ready for compliance inspection.
1ys must be made in writing to the Building Official stating
removed from the site and/or a Stop Work Order issued if
Ilwithin 30 days. A fee of $100.00 will be required to lift
WE HEREBY RELEASE AND AGREE TO HOLD HARMLESS, ST. LUCIE COUNTY, AND THEIR EMPLOYEES FROM
ALL LIABILITIES AND CLAIMS OF ANY TYPE OF NATURE WHICH MAY ARISE NOW OR IN THE FUTURE OUT
OF THIS TRANSACTION, INCLUDING ANY DAMAGE WHICH MAY BE INCURRED DUE TO THE
DISCONNECTION OF ELECTRICAL POWER IN THE EVENT OF VIOLATION OF THIS AGREEMENT.
0 N TU "� I DATE
CTOR SIGNATURE DATE
70 41' (1? (= — ( t.
ELECTRICA CONTRACTOR SIGNATURE DATE
I.
II.
St. Lucie County
Building and Zoning Department
Requirements for 30 Day Power for Testing
Form entitled "Request for 30-Day porary Power Release" must be fully executed and posted in
the Building Department record files prior to inspection.
Inspection Requirements:
1. Address numbers shall be posted per county Ord. No. 7.05.09.
2. All entrances, exits, windows and garage doors must be lockable.
3. All circuits on exterior shall be terminated in a box with weatherproof cover. The same applies
to a disconnect. If circuits are at or above 7'6" from grade they may be capped with wire nuts
and taped.
4. All breakers must be installed. Any blank space must be closed by a breaker or approved filler
plates.
5. Interior Wiring: All receptacles, light fixtures and fans must be trimmed. Any fixture below
7'6" from the floor or mezzanine that is not available at the time of inspection must have an
Inviso plate installed. Fixtures ai or above that height may be capped with wire nuts and taped.
6. All smoke detectors must be installed.
7. Kitchen cabinets must be installed; any exception for special conditions or circumstances must
have an approval prior to schedul d inspection.
8. Sewer and water connections mu t be complete. Only well pumps are excluded from this
requirement.
9. Exterior construction must be complete and weather tight, including stucco, siding, roof and
soffit.
10. Permit work shall be substantially completed except for back orders, paint on exterior, carpet
and/or floor covering, pumps, airconditioners and driveway.