HomeMy WebLinkAboutROOFING UNDERLAYMENTFlorida Building Code Onlipe-,
`'e Page 1 or ./
SGANNED
n r rl`
. _G x2ti. �R, n.0 y� ✓ i���.1i e ��7. �.i ��tl
—
BCIS Home s Log In i User Registration - Hot Topics it Submit Surcharge � Stats & Facts
=iiIC3
®/' Product Approval
�� USER: Public User
I
i
Product Approval Menu > Product or App icafion Search > Application List > Application Detail
FL
FL2569-R13
�__j
Application Type
Revision
Code Version
2017
Application Status
I Approved
Comments
Archived
Product Manufacturer
Address/Phone/Email
Authorized Signature
Technical Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email 1
Category i
Subcategory
Compliance Method
Florida Engineer or Architecti Name who developed
the Evaluation Report
Florida license
Quality Assurance Entity
Quality Assurance Contract Expiration Date
Validated By
Certificate of Independence
Referenced Standard and Year (of Standard)
i fi.f ii
w.
Publications FBC Staff : BCIS Site Map Links Search
Soprema, Inc. (Canada)
1640 rue Haggarty
Drummondville, NON -US 00000
(819) 478-2400
memath ieu@sop rema. ca
Marc -Etienne Mathieu
memath ieu@soprema.ca
Marc -Etienne Mathieu
1688 Jean-Berchmans-Michaud
Drummondville, NON -US 00000
(819)478-2400 Ext3327
memath ieu@soprema. ca
Jean -Francois Cote, Ph.D.
1640 rue Haggarty
Drummondville
(888)811-3145
jfcote@soprema.ca
Roofing
Underiayments
RECEIVED
MAR 15 'Z(l18
Permitting Department
St. Lucle Counh
llyon)o�
Tj
BILE COPY
Evaluation Report from a Florida Registered Architect or a Licensed
Florida Professional Engineer
..: Evaluation Report Hardcopy Received
Robert J. M. Nieminen
P E-59166
UL LLC
07/18/2020
John W. Knezevich, PE
i Validation Checklist - Hardcopy Received
EL
2569 R13 COI 2017 01 COI Nieminen.pdf
Standard
ASTM D1970
ASTM D6163
FM 4474
FRSA/TRI April 2012 (04-12)
TAS 110
UL 1897
Year
2015
2008
2011
2012
2000
2012
http://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgsKQFEneIc-B 10... 1/10/2018
Florida Building Code OnlipP
Page 2 of 2
Equivalence of Product Standards
Certified By
Sections from the Code
Product Approval Method
Date Submitted
Date Validated
Date Pending FBC Approval
Date Approved
Method 1 Option D
10/09/2017
10/11/2017
10/15/2017
12/12/2017
FL # Model, Number or Description
Name I
2569.1 Soprema Roof I Self adhering roof underlayments
Underlayments
Limits of Use
Installation Instructions
Approved for use in HVHZ: No I
FL2569 R13 II 2017 10 FINAL ER SOPREMA CA UNDERLAYMENTS FL2569-
Approved for use outside HVHZ: Yes
R13.pdf
Impact Resistant: N/A
Verified By: Robert Nieminen, P.E. PE-59166
Design Pressure: +N/A/-150
Created by Independent Third Party: Yes
other: 1.) Refer to ER Section 5 for
Evaluation Reports
Limits of Use. 2.) The design pressure
FL2569 R13 AE 2017 10 FINAL ER SOPREMA CA UNDERLAYMENTS FL2569_
noted herein pertains to underlayment
R13.pdf
systems used beneath adhesive -set tile
Created by Independent Third Party: Yes
systems. Refer to ER Section 5.6.4 foli
details.
Back N__
Contact Us :: 2601 Blair Stone Road. Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida is an AA/EEO employer. Copyright 7007-2013 State of Florida.:: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida late, email addresses are public records. if you do no[ want your e-mail address released in response to a public -records request, do not send
electronic mail to this entity. Instead, contact the office by phone or,by traditional mail. if you have any questions, please contact 850.487.1395. 'Pursuant to
Seclion 455.275(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 45S, F.S. must provide the Department with an email address If
they have one. The emalts provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to
supply a personal address, please provide the Department with an email address which can be made available to the public. To determine If you are a licensee under
Chapter, 455, F.S., please click ham.
Product Approval Accepts:
I Credit Card
I Safe
htti)://www.floridabuildina.org/pr/pr 1/10/2018
_ t EXTERIOR RESEARCH & DESIGN, LLC.
Certificate of Authorization #9503
353 CHRISTIAN STREET, UNIT#13
TRN I ERD OXFORD, CT 06478
t (203) 262-9245
EVALUATION REPORT
Evaluation Report S18010.06.09-R11
Soprema, Inc.
FL2569-R13
1640rue Haggerty
09
Drummondville, QuebecJ2C 5P8 Canada Date of Issuance: /
(819) 478-2400 Revision 11:10/06/20/2017
SCOPE:
This Evaluation Report is issued under Rule 6113k-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 6eh Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: Soprema Roof Underlayments
LABELING: Labeling shall be in accordance with' the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity) ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "TrinitylERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspeIction at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 8.
Prepared by:
I
!
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert
Nleminen, P.E. on 10/06/2017. This does not serve as an
electronically signed document
CERTIFICATION OF INDEPENDENCE:
1. TrinitylERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity' ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity lERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
IIERD
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Underlayment
Compliance Statement: Roof Underlayments, as produced by Soprema, have demonstrated compliance with the
following sections of the 6t11 Edition (2017) Florida Building Code through testing in accordance with the following
Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth
herein.
2. STANDARDS:
Section
1504.3.1
1504.3.1
1507.1.1, T1507.1.1, 1507.2.9.2
1507.3.3
FRSA/TRI April 2012 (04-12)
TAS 110
3. REFERENCES:
Enti
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD(TST6049)
ERD (TST6049)
M-D(CER1592)
ICC-ES (EVL2396)
PRI(TST5878)
Soprema, Inc. (PDM3511)
UL, LLC (QUA9625)
4. PRODUCT DESCRIPTION:
Property
Wind Resistance
Wind Uplift I
Physical Properties
Physical Properties
Physical Properties
Accelerated (Weathering
I
Examination
ASTM D1970 /TAS 110
Physical Properties
ASTM D1970 / TAS 110
Wind Resistance
Wind Resistance
TAS 103 /(TAS 110
ASTM D1970 /TAS 110
ASTM D1970 / TAS 110
Physical properties / Tensile Adhesion
Physical f roperties / Tensile Adhesion
ASTM D1970
ASTM D,1970
Properties / Tensile Adhesion
Properties / Tensile Adhesion
ted Weathering
Wind Resistance
HVHZ, Compliance
2015 IBC Compliance
Physical Properties
Equivalency Declaration
Quality Control
Standard
FM 4474
UL 1897
ASTM D1970
FRSA/TRI April 2012
ASTM D6163
TAS 110
Reference
2968.05.04-2
2757.02.05
2974.03.05-2
2778.07.05
2779.11.05-R1
S7120.11.07-2
S13190.02.09-111
S31370.03.10-1-R1
S11150.05.10-R1
S11150.05.09-R2
S37210.11.11
S40540.02.13-1
543530.02.14-1
SOPC-SC7645.02.15
SOPC-SC8520.14
SOPC-SC 14045.05.17-R 1
15-0508.04
ESR-1524
SOP-064-02-01
SA SMOOTH PLY 40
Service Confirmation
Year
2011
2012
2015
2012
2008
2000
Date
05/14/2004
02/03/2005
05/17/2005
07/15/2005
04/18/2007
11/02/2007
04/01/2010
04/07/2010
09/09/2010
10/05/2010
11/09/2011
02/19/2013
02/21/2014
02/13/2015
04/17/2015
06/07/2017
09/24/2015
03/01/2017
12/03/2013
06/29/2015
Exp.07/18/2020
4.1 Lastobond TU HT is a s6lf-adhering, non -woven polyester fabric surfaced, SBS modified bitumen roof
underlayment; meets ASTM D1970 and FRSA/TRI April 2012 (04-12).
4.2 Lastobond Shield is a self -adhering, woven polyethylene surfaced, SBS modified bitumen roof
underlayment available in two widths; 36 and 45 inch; meets ASTM D1970.
4.3 RESISTO SA SMOOTH PLY 40 is a self -adhering, woven polyethylene surfaced, SBS modified bitumen roof
underlayment; available,in 3.3 ft x 65 ft rolls; meets ASTM D1970.
4.4 Lastobond Shield HT N a self -adhering, woven polyethylene surfaced, high temperature, SBS modified
bitumen roof underlayment; meets ASTM D1970.
Exterior Research and Design, LLC. Evaluation Report S18010.06.09-R11
Certificate of Authorization #9503 6' EDITION (2017) FBC NON-HVHZ EVALUATION FL2569-R13
Soprema, Inc. Revision 11: 10105/2017
Page 2 of 8
1
4.5 Lastobond Pro HT-N is a self -adhering, woven polyethylene surfaced, SBS modified bitumen roof
underlayment available in two widths;136 and 45 inch; meets ASTM D1970.
4.6 Lastobond Pro HT-S is a self -adhering, woven polyethylene surfaced, high temperature, SBS modified
bitumen roof underlayment; meets ASTM D1970.
4.7 Lastobond 195 is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified bitumen roof
underlayment; meets ASTM D1970.
4.8 Lastobond Eaves Protection Sheet is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified
bitumen roof underlayment; meets ASTM D1970.
4.9 Lastobond Eco is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified bitumen roof
underlayment; meets ASTM D1970.!
4.10 Lastobond Smooth Seal HT is a self -adhering, glass -mat reinforced, film -surfaced, SBS modified bitumen
roof underlayment; meets ASTM D1970.
4.11 RESISTO LB1236 is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified bitumen roof
underlayment, with a 36-inch sheet width; meets ASTM D1970.
4.12 PrimeSource Grip -Rite Eave & Valley Protector is a self -adhering, glass -mat reinforced, sand -surfaced, SBS
modified bitumen roof underlayment, with a 36-inch sheet width; meets ASTM D1970.
4.13 RESISTO LB1244 is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified bitumen roof
underlayment, with a 44-inch sheet width; meets ASTM D1970.
4.14 Colphene FR GR is a self -adhering, fiberglass reinforced, granule -surfaced, SBS modified bitumen roof
underlayment; meets ASTM D1970 and FRSA/TRI April 2012 (04-12).
S. LIMITATIONS: '
5.1 This is a building code evaluation. Neither TrinityIERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of:this report; refer to current Approved Roofing Materials Directory for fire
ratings of this product.
5.4 Soprema Roof Underlayments'may be used with any prepared roof cover where the product is specifically
referenced within FBC approval documents. If not listed, a request may be made to the Authority Having
Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof
covering.
5.5 Allowable Roof Covers:
TABLE 1: ROOF COVER OPTIONS
Asphalt
Nail -On
Foam -On
Metal
Wood Shakes &
Slate
Underlayment
Shingles
Tile
Tile
Shingles
Lastobond TU HT
Yes
Yes
Yes
See 5.5.1
Yes
Yes.
Yes
Lastobond Shield / Pro HT-N / RESISTO SA
Yes `
-No
'No
No-
Yes -
Yes
SMOOTH PLY 40
Lastobond Shield HT / Pro HT-S
Yes
No
No- ..
Yes
Yes'
Yes
Lastobond Eaves Protection Sheet /
Yes .
No. --.•
No
'No
Yes
Yes
Lastobond 195
Lastobond ECO / RESISTO L61236, Grip -
Rite Eave & Valley Protector / RESISTO
Yes
No
No
No
Yes
Yes
i
LB1244
Exterior Research and Design, LLC. Evaluation Report S18030.06.09-R11
Certificate of Authorization #9503 Of EDITION (2017) FBC NON-HVHZ EVALUATION FL2569-1113
Soprema, Inc. Revision 11: 10/06/2617
Page 3 of 8
i
A TRINITY1 ER®
• - - .TABICE 1: ROOF. COVER OPTIONS ,
Asphalt
Nail -On
Foam -On
Metal
Wood Shakes &
Slate
Underlayment
Shingles
Tile
Tile _
Shingles
, Yes }
Yes
' Yes y
L st3honm oflthTSealiHii
Na{:
t� fir::. �.�r
(Llo
_
Colphene FR GR
p
Yes-
Yes
Yes
See 5.5.1. .
No '
Yes
Yes
5 5 1 "Fnam-nn Tile" is limited to use of following Approved tile adhesives / underlayment combinations.
TABLE 1A:: ALLOWABLE TILE ADHESIVE / UNDERLAYMENT COMBINATIONS)
Adhesive
Florida Product Approval
Underlayments
Dow TileBond-
; FL22525
Lastobond TU HT
ICP Adhesives PolysetO AH-160
FL6332
Lastobond TU HT or Colphene FR GR
5.6 Allowable Substrates:
5.6.1 Direct -Bond to Deck:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond
Pro HT-S, Lastobond TU HT, Lastobond Eaves Protection Sheet, Lastobond 195, Lastobond ECO, RESISTO
LB1236, Grip -Rite Eave & Valley Protector, RESISTO LB1244 or Lastobond Smooth Seal HT applied to:
➢ Plywood; ASTM D41 primed, plywood; OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41
primed Southern Yellow Pine; ASTM D41 primed structural concrete.
Colphene FR GR applied to:
➢ Plywood; ASTM D41 primed plywood; ASTM D41 primed structural concrete.
Note:
➢ While not required over plywood, OSB or Southern Yellow Pine substrates, Soprema recommends
priming with Elastocol Stick or Elastocol 600c if the final roof cover is not slated for installation within
24 hours.
Soprema requires tongue -and -groove board decking be covered with plywood or OSB prior to
installation of the self -adhering underlayment.
5.6.2 Bond -to -Insulation:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond
Pro HT-S, Lastobond TU HT, Lastobond Eaves Protection Sheet, Lastobond 195, Lastobond ECO, RESISTO
LB1236, Grip -Rite Eave & Valley Protector, RESISTO 1_61244, Lastobond Smooth Seal HT or Colphene FR
GR applied to:
➢ Dens Deck Prime; SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per
minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations
under foam -on tile system s�(Lastobond TU HT only), insulation attachment shall be designed by a qualified
design professional and installed based on testing of the insulation/underlayment system in accordance
with FM 4474, Appendix D; Testing Application Standard TAS 114, Appendix J or UL1807.
1 Refer to Tile Manufacturer's orAdhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
Exterior Research and Design, LLC.
Certificate of Authorization 0503
'6"' EDITION (2017) FBC NON-HVHZ EVALUATION
Soprema, Inc.
I
I
I
Evaluation Report S18010.06.09-R11
FL2569-R13
Revision 11: 10/06/2017
Page 4 of 8
`i
TRINrry E D
5.6.3 Bond to Mechanically Attached Base Ll er:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond Pro
HT-S, Lastobond TU HT, Lastobond Eaves Protection Sheet, Lastobond 195, Lastobond ECO, RESISTO
LB1236, Grip -Rite Eave & Valley Protector, RESISTO LB1244, Lastobond Smooth Seal HT or Colphene FR GR
applied to:
ASTM D226, Type I or II felt; Sopra-G; Modified Sopra-G.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirements. For installations under foam -on tile systems (Lastobond TU HT only),
base layer shall be attached in accordance with FRSA/TRI April 2012 (04-12).
5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12)
does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where
the underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment
systems that are not addressed injiFRSA/TRI April 2012 (04-12) and are used in foam -on tile applications.
Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads,
and reflects the ultimate passing Ipressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has
already been applied). Refer to FRSA/TRI April 2012 (04-12) or FBC 1609 for determination of design wind
pressures.
#1 Maximum Design Pressure = -45.0 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Primer: (Optional) Elastocol Stick, Elastocol 600c or RESISTO EXTERIOR PRIMER
Underlayment: Lastobond TUI HT or Colphene FR GR, self -adhered.
#2 Maximum Design Pressure = -67.5 psf:
Deck: Structural concrete to meet project requ(rements'to satisfaction of Authority Having
Jurisdiction.
Primer: Elastocol600c
Underlayment: Lastobond TU HT or Colphene FR GR, self -adhered.
#3 Maximum Design Pressure =-1I50.0 psf:
Deck: Min. 15/322inch APA-rated BCX plywood (may be installed C-side up) to meet project
requirements to satisfaction of Authority Having Jurisdiction.
Deck Preparation: Plywood shall be thoroughly cleaned to remove dust and debris that may inhibit
adhesion. All sheathing fasteners shall be driven flush with the surface. All sharp
splinters and wood projections shall be removed/sanded.
Primer: (Optional),'RESISTO EXTERIOR PRIMER
Underlayment: Lastobond TU HT, self -adhered, shall be thoroughly roll using hand roller and/or
weighted roller to ensure there are no voids, and ensure there are no voids/bridging at
side and end -laps.
#4 Maximum Design Pressure:;, -60.0 psf:
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Base Sheet: Sopra-G,or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1) and tin
caps (FBC 1517.5.2) spaced 6-inch o.c. at the 4-inch laps and 6-inch o.c. in three (3),
equally spaced rows in the center of the sheet.
Underlayment: Lastobond TU HT or Colphene FR GR, self -adhered
5.6.4.1 All other direct -deck, adhered Soprema underlayment systems beneath foam -on tile systems carry a
Maximum Design Pressure of -45 psf.
Exterior Research and Design, LLC. II Evaluation Report S18010.06.09-Rii
Certificate of Authorization#9503 6n'EDITION(2017)FBC NON-HVHZEVALUATION FL2569-1113
I Soprena, Inc. Revision 11, 10/06/2017
Page 5 of 8
5.6.4.2 For mechanically attached Base Shee�, the maximum design pressure for the selected assembly shall meet
or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1
design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an
attachment density designed by a qualified design professional to resist the elevated pressure criteria.
Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing
Application Standard RAS 217. Assemblies marked with an asterisk* carry the limitations set forth in
Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
5.7 Exposure Limitations:
Lastobond Eaves Protection Sheet, Lastobond 195,Lastobond Eco, Lastobond Smooth Seal HT, RESISTO
LB1236, Grip -Rite Eave & Valley P iotector or RESISTO LB1244 shall not be left exposed for longer than 30-
days after installation.
Lastobond Shield, Lastobond Pro PT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT or Lastobond
Pro HT-S shall not be left exposed Ifor longer than 90-days after installation.
Lastobond TU HT or Colphene FR PR shall not be left exposed for longer than 180-days after installation.
5.8
When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall
be as follows. These slope limitations can only be exceeded by using battens during loading of the roof
tiles.
TABLE 2::TILE SLIPPAGE LIMITATIONS FOR DIRECT-DECKTILE INSTALLATIONS .
Maximum
Underlayment
Tile Profile
Staging Method
Slope
I Flat
Max. 10-tile stack
6:12
Lugged
Max. 10-tile stack
5:12
Max. 10-tile stack (bottom 2-tile stack
I
shall be inverted, followed by 8 tiles high
6:12
on slope, as shown below)
Lastobond TU HT
Lugged
Flat
Max. 10-tile stack
5:12
Colphene FR GR
Lugged
Max. 10-tile stack
6:12
Exterior Research and Design, LLC. Evaluation Report S18010.06.09-R31
Certificate of Authorization #9503 6" EDITION (2017) FBC NON-HVHZ EVALUATION F1.2569-1113
I Soprema, Inc. Revision 11: 10/06/2017
Page 6 of 8
i
nnpn
6. INSTALLATION:
6.1 Soprema Roof Underlayments shall be installed in accordance with Soprema published installation
requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debris prior,to application, and prime the substrate with Elastocol Stick, Elastocol
600c or RESISTO EXTERIOR PRIMER (if applicable).
6.3 Lastobond'TU H.T Lastobond;Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH.PLY-40, Lastobond•Shield
Hi, Lastobond-Pro HT-S, Lastobond Eaves Protection Sheet, Lastobond 19%_ Lastobond'Eco,.Lastobond
Smooth:Seal'.HT,-RESISTO•LB1236, Grip=Rite Eave & Valley,Protector,' RESISTO L61244 or. Colphene.FR GR:
6.3.1 Shall be installed in compliance with the requirements Tor HSIIVI UiyiU unaenayrnenL ui rD%- 101i C
1507.1.1 for the type of prepared roof covering to be installed.
6.3.2 Non -Tile Applications: I
While priming is optional, Soprema recommends priming with Elastocol Stick, Elastocol 600c or RESISTO
EXTERIOR PRIMER if the final roof cover is not slated for installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3
ft of release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel -off the release film diagonally while holding the
membrane tight. Firmly roll the membrane into place to achieve a bond.
Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6-
inches and staggered not less than 2-ft from vertical seams in the course below. All over -granule end -laps
shall be sealed using either heat -welding or hot air welding techniques.
When installing at slopes above 8:12, Soprema recommends back -nailing in the overlap area at the top of
the sheet at 12-inch o.c.
For Valleys and Ridges: Cut ulnderlayment into 4 to 6 foot lengths. Peel the release paper and center sheet
over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in
each direction. For valleys, alpply the sheet starting at the lowest point and work upward.
6.3.3 Tile Applications (LastobondlTU HT orTile Applications HT or Colphene FIR GR onlylFR GR only):
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the
instructions noted above as a guideline.
For foam -on tile applications, reference is made to Section 5.6.4 herein for wind resistance limitations that
fall outside the scope of FRSA/TRI April 2012 (04-12).
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the
underfayment. See Table,2 herein, and Soprema published requirements for tife staging.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
Exterior Research and Design, I.I.C. Evaluation Report 518010.06.09-Ril
Certificate of Authorization #9503 6" EDITION (2017) FBC NON-HVHZ EVALUATION FL2569-1113
Soprema, Inc. Revision 11: 10/06/2017
Page 7 of 8
J\
8.
I .y
MANUFACTURING PLANTS:
Contact the noted QA agency for information o product locations covered for F.A.C. 61G20-3 QA requirements.
The following plants have qualified products under their respective physical properties specifications.
Plant
Saecificatiori
.Products . _..
Shield, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT,
ILastobond
Lastobond Pro HT-N, Lastobond Pro HT-S, Lastobond 195, Lastobond
Drummondville,
ASTM D1970 I
Eaves Protection Sheet, Lastobond Eco, Lastobond Smooth Seal HT,
QC (Canada)
I
RESISTO L131236, PrimeSource Grip -Rite Eave & Valley Protector,
RESISTO LB1244
ASTM D1970 & FRSA/TRI 04-12
Colphene FR GR
Lastobond 195, Lastobond Eaves Protection Sheet, Lastobond Eco,
Wadsworth, OH
ASTM D1970 I
Lastobond Smooth Seal HT, RESISTO LB1236, PrimeSource Grip -Rite
Eave & Valley Protector, RESISTO LB1244
ASTM D1970 & FRSA/TRI 04-121
LastobondTU HT; Colphene FIR GR
Lastobond 195, Lastobond Eaves Protection Sheet, Lastobond Eco,
Gulfport, MS
ASTM D1970 I
Lastobond Smooth Seal HT, RESISTO LB1236, PrimeSource Grip -Rite
Eave & Valley Protector, RESISTO L81244
9. QUALITY ASSURANCE ENTITY:
UL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com
- END OF EVALUATION REPORT -
i
I
I
I
I
i
Exterior Research and Design, LLC.
Certificate of Authorization #9503
i
6.. EDITION (2017) FBC NON-HVHZ EVALUATION
Soprema, Inc.
Evaluation Report S18010.06.09-1312
FL2569-R13
Revision 11: 10/06/2017