HomeMy WebLinkAboutDESIGN PRESSURE CALCULATIONSera Aufloo 013nl42 . & TESTING INC. 250 SW'13th A*Pompano Beach,'FL 33069, 09NNVOR.. Phone 954-784-2941.. 800.-848-1919: Pak-' 954-784-7875 fdd-eng.com. ENGINEERING & TESTING Page 2 3/12/18 Flat Wood Deck 753 Altura Drive Port St Lucie, FL Design Pressures: Zone 1 Field: 'Pl.= 26.5*(-1.0 - 0.18).= -31.3 psf Zone 2 Perimeter: P2 _ 26..5*(-1.8 - 0.18) = -52.5 psf Zone 3 Comers: P3 = 26.5*(-2.8 - 0.18) = -79.1 psf Flat Roof Section Attachment Requirements: Based on RAS-117 and F.L. #1654-R22; Table 1G; System Type.F; System No. W-140;.with a, design pressure'of -90 psf; Appendix 1; page'21 of 58, the following system is approved with all layers fully bonded Notes: Comers and perimeterarea dimension shall not be less than a - 4'0" All work shall be in o�ompliance:with the local building code product control notice of acceptance and manufacturer specifications and the Florida -Building Code 2017. Wind. load:calculatiolIns :based on ASCE 7-:10 and information provided by client. All work shall be inspected by our .field engineer or city. inspector to verify compliance with specifications., s _ KeA LeBlanc; P:E. � :2�• � Federal Emgineering &Testing; Inc Florida Reg..,No.59394 . Certifi.cate.of•Authorization #5471 Miami=Dade County Certification 16-'0203.07