PLANS EXAMINER REVIEW INCOMPLETE Jpi, Inc 4/9/2018 , ( REVISIONS MADE 5-25-2018 )
4/9/2018 Comment:1) POOL IS IN A FLOOD ZONE, PLEASE NOTE PER SECTION (R322.3.6) OF THE FBCR
REQUIRES -THE CONSTRUCTION DOCUMENTS SHALL INCLUDE DOCUMENTATION ... THAT THE DESIGN
AND METHODS OF CONSTRUCTION TO BE USED MEET THE APPLICABLE CRITERIA OF THIS SECTION.
I
FLOOD -RESISTANT CONSTRUCTION. ( NOTED ON BOTTOM RIGHT OF PAGE 1 POOL PLAN)
4/9/2018 Comment: 2) MECHANICAL EQUIPMENTISERVICING THE POOL SHOULD BE ELEVATED ABOVE
THE BFE. EQUIPMENT SHALL BE LOCATED AT OR ABOVE THE ELEVATION REQUIRED IN SECTION R322.2
OR R322.3. (R322.1.6) ( NOTED ON BOTTOM RIGHT OF PAGE 1 POOL PLAN 1
4/9/2018 Comment: 3) PLEASE PROVIDE PRODUCT DATA FOR CHILD BARRIER.
(' INCLUDED CHILD BARRIER DATA SHEET)
4/9/2018 Comment: 4) PLEASE SHOW ON DRAWINGS THE REQUIRED BONDED PARTS PER (E4204.2)
(;ADDED RIGHT SIDE PAGE 3 POOL PLAN)
4/9/2018 Comment: 5) PLEASE SHOW ON DRAWINGS THE BONDING OF THE POOL WATER. (E4204.3)
1 ADDED CENTER OF PAGE 2 POOL PLAN)
4/9/2018 Comment: 6) PLEASE PROVIDE SOIL DESIGN PARAMETERS- SOIL BEARING CAPACITY
&COMPACTION REQUIREMENTS. (R401.2)
RI
4/9/2018 Comment: 7) PLEASE PROVIDE DETAIL AT WATERFALL DROP. ([A] 107.2.1)
( ADDED CENTER OF PAGE 2 POOL PLAN )
4/9/2018 Comment: 8) PLEASE PROVIDE A SOIL BORING TEST & REPORT TO DETERMINE THE SOIL'S
CHARACTERISTICS. THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN APPROVED
METHOD. (R401.4) ( INCLUDED SOIL REPORT & ENGINEERS LETTER)
4/9/2018 Comment: 9) PLEASE ENLARGE ELECTRICAL DETAIL TO BE LEGIBLE. ([A] 107.2.1)
( ENLARGED ON RIGHT SIDE OF PAGE 3 POOL PLAN)
( SUBMIT PLUMBING SUB-APP SIGNED BOTH LOCATIONS AND NOTARIZED )
i
( SUBMIT UPDATED ELECTRICAL SUB-APP SIGNED AND NOTARIZED)