DtSIGN CRITERIA:
Applicable Codes, Regulations, and Standards
1. The 6th Edition (2017) Florida Building Code, specifically Chapter 16 Structural Design,
Chapter 20 Aluminum, and Chapter 23 Wood.
2. AA ASM 35 and AA ADMI Specifications for Aluminum Structures, Part 1-A ofthe
Aluminum Design Manual prepared by The Aluminum Association. and the AAF Guide to
Aluminum Construction in High Wind Areas.
3. ASCE 7-10.
Loading Criteria
1. Live Loa& 10 PSF per 6th Edition (2017) Florida Building Code, Appendix I Section
105.1
2. Dead Load: 2 PSF
3. Wind Load:
3.1. Building Occupancy Category, Section 1604.5 and Table 1604.5: Risk Category 1.
3.2. Basic Wind Speed, Figure 1609.3(3), State of Florida Debris Region & Basic Wind
Speed, Section 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Speed:
VwT =150 MPH, VASD =116 MPH
3.3. Exposure Category, Section 1609.4.3: Exposure C
3.4. Screen Enclosure Section 2002.4
4. Building Category for Aluminum Structures, Section 2002.6: Category Type 1- Screen
Room: Non -Habitable, Unconditioned
Scope of Work:
Does not include analysis of remaining existing structure.
Roof Type
1. Roof Type: EXISTING
2. Roof Material: EXISTING
Foundation Design
Existing concrete. No additional concrete footing or slab is required to resist the loads
imposed by the proposed construction if the existing slab is a minimum 4" thick with an
8" x 8" thickened slab edge and in sound condition, free from structural cracking,
spelling, or other deterioration.
Specifications
The following specifications are applicable to this project:
1. All work shall be in accordance with the 6th Edition (2017) Florida Building Code, and any
other applicable local codes and regulations.
2. Aluminum extrusions shall be 6005 T5 Alloy. Due to quality control issues, no
manufacturer substitution is acceptable without the specific written, signed and sealed
authorization of Suncoast Aluminum Engineering, LLC.
3. Screen Material: Design based on 18/14 or 20/20 Better View. Any other material must be
approved.
4. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc plated
to ASTM B633, or coated stainless steel series "300", or uncoated stainless steel series
"400".
5. All Self Mating Beam Sections are to be stitched with either #14 screws 6" from ends and
24" center to center or # 12 screws 6" from ends and 12" center to center.
6: Where concrete specifications are required; whether in the screen enclosure scope ornot, by
one or more regulatory agency, the following specifications are applicable:
a. Concrete shall conform to ASTM C94 for the following components:
i. Portland Cement Type 1,- ASTM C 150
ii. Aggregates - Large Aggregate 3/4" max - ASTM C 33
iii. Air entraining +/- 1 % - ASTM C 260
iv.Water reducing agent - ASTM C 494
v. Clean Potable water
vi. Other admixtures not permitted
b. Metal accessories shall conform to:
i. Reinforcing Bars - ASTM A615, grade 60
ii. Welded wire fabric - ASTM A185 . .
c. Concrete slump at discharge chute not less than 3" or more than 5". Water added
after hatching is not permitted.
d. Prepare and place concrete per American Concrete Institute Manual of Standard
Practice, Parts 1, 2, and 3 including hot weather recommendations.
e. Moist cure or polyethylene curing permitted
f. Prior to placing concrete, treat the entire subsurface area for termites in compliance
with the FBC.
g. Concrete shall be placed over a polyethylene vapor barrier.
IL All aluminum components embedded within concrete shall be coated with a
bituminous paint or epoxy.
7. All flashing and weatherproofing shall be provided by the contractor.
8. Door location shall be determined by contractor in the field
9. Use of these plans acknowledges and accepts a limit of liability not to exceed design and
engineering fee.
WIND SPEED A , ;XPOSURE HAVE
BEEN DETERMINED USING THE ADVANCED
TECHNOLOGY COUNCIL'S WEBSITE
AND GOOGLE EARTH.
{
RECEIVED
MAR 2 2 i �'15
ST. Lucie County, Permitting
EXISTING
4TH WALL
EXISTING
2
6SMB
EXISTING
2X3SMB
EXISTING
RISEN
PAN
-
ROOF
EXISTING
2X6SMB
EXISTING
2X3PB
it —on
(003 —0(0*!;05
EXISTINCST. LUCT' COLN'TY BLTILD-11 r SION
f 2X3PS RUMNN ED FOR COMT
d REVIEVVED/BY
DATE
PLANS AIND PERMIT' MUS BE KEPT ON JOB
OR NO LNNsPEETION WIL BE NUDE.
EXISTING
n, nr-n n a n 1
2'-0"
THESE PLANS AND ALL PROPOSED WORK
ARE SUBJECT TO ANY CORRECTIONS
REQUIRED BY FIELD INSPECTORS THAT
MAY BE NECESSARY IN ORDER TO
COMPLY WITH Ail, A-PPWCARIS 00090,
CONCEALED FASTENERS OR ATTACHMENTS
ARE THE RESPONSISILP OF THE
--- — CONTRACTOR OF RECORD — — —
kLUMINUM
'LATE(TYP)
ram.: � ;. ,�,n rr� �,�: ,"•r, � -
_
El
ui Ui
0 d a
w d
�m —QC)
Ucc
z Lu e
tY Qm Jm
UJ d =
Z Q W W
2z Qz
Z == OU
W F- -_ cc
ZU4
J
J
Z z$ 1. m
Qcc
W JcP8
OZ=���
Z (D �3^^
Z
to W NUFLL
to
W
Z
En
g
W
�
Y
Q
0O U
0 J
In
LU
W�F..U3
<Ntl�c�
WaoatJi
d
DRAWN BY
GD
DATE DRAWN
02/28/18
SHEET NO:
t
S,
A-1
ALUMINUM MEMBERS DIMENSIC
/
KICK PLATE NOTES:
HOLLOW SECTIONS
1.
0.024 ALUM
2x2: 2"x2"x0.046"
2.
SCREW ALL CORNERS
2 x 3: 2" x 3" x 0.050"
3.
100 B -120 B WIND ZONES
2 x 4: 2" x 4" x 0.050"
USE #8 x 5/8" SMS @ 12" O.C.
2x5: 2"x5"x0.050"
4.
120 C - 140 B WIND ZONES
USE #8 x 5/8" SMS @ 8" O.C.
5.
140 C -150 B WIND ZONES
OPEN'BACK SECTIONS
USE #8 x 5/8" SMS @ 6" O.C.
1 x 2: 1" x 2" x 0.040"
6.
150 C & ABOVE WIND'ZONES
1 x 3: 1" x 3" x 0.045"
USE #12 x 5/8" SMS @ 6" O.C.
7.
SCREW GIRT, BOTTOM RAIL
SNAP SECTIONS
i
& BOTH SIDES
2 x 2 Snap: 2" x T' x 0.045"
( 3' x x 0.093"
8.
MAX KICK PLATE HT = 36'
2 x 3 Snap: 2" " "
p x 3x 0.050
T
POST
I � OPTION 2:
2x4Snap: 2"x4"x0.045"
(2) 3/8" DIA CONCRETE
SCREWANCHORS
�
0.040"x11/8"x2"x11/8"
I I
(3" CONC. EMBED)
!!
t
OPTION 1:
INTERNAL OR EXTERNAL
PROFES
IONAL SEAL
SELF MATING (SMB)
ALUM RECEIVING CHANNEL
x 2" x 1/8" ALUM ANGLE I I W/ (3) #10 x 3/4" INTO
2 x 4 SMB: 2" x 4" x 0.044" x 0.100"
W// (4) #10 x 5/8" EACH SIDE
I I GIRT EACH FACE & (3)
2 X 5 SMB: 2" x 5" x 0.050" X 0.100"
2 x 6 SMB: 2" x 6" x 0.050" x 0.120"
V x 2" OB Wl 1/4" CONCRETE
(
EE INTERNAL/EXTERNAL
I #10 x 3/4" INTO UPRIGHT
2 x 7 SMB: 2" x 7" x 0.057" x 0.120"
SCREW ANCHOR V'
i 3" x 3" x 1/8" EXTRUDED
_ _ _
FROM UPRIGHT & @
POST BASE W/ (2) 3/9'
I I
W LLI
2 X 8 SMB: 2" x 8" x 0.072" X 0.124"
24" O.C. (MIN. 3" EMBED.)
A. TI-J BOLTS
DILAJ
O
d d
2x9SMB:2"x9"x0.072"x0.124"
_- --
----
u
2 x 10 SMB: 2" x 10" x 0.092" x 0.398"
MINIMUM FASTENER EDGE DISTANCE: 1/2"
ai ti ,;a • v
CHAIR RAIL MEMBER
I I
O
Z w
MINIMUM FASTENER SPACING: 3/4"
- '
2X PATIO
I I
cc
Q wW w
m m
< •
EXTRUSION
W
a
CONCRETE SCREW ANCHOR:
''
z z
SIMPSON TITEN HD OR EQUIVALENT
J
mz Qz
SHEET METAL SCREWS (SMS):
O u Z u
ITW / BUILDEX OR EQUIVALENT
W
:30
B 3" x 3" POST TO CONCRETE CONNECTION DETAIL
A
SCALE: NTS
0
_rf
/1 L
z ..y
c-),PURLIN OR GIRT TO BEAM OR POST DETAIL
0
J
A_2
GG
SCALE: NTS
F �
Q z O- a
z m s
a W �;cPg W
W " � C4 z
O re u
z =
1"x 2" O.B. FASTENED TO CORNER
_
(� n n :3
POSTW/#12x11/2"SMS AT6"FROM
z (D
TOP & BOTTOM RAILS. TYPICALLY @
I
mq
24" O.C.
1/8" x 2" x 2" EXTRUDED
in W ti U O
ANGLE 5052 H-32 ALLOY
•• 4 #14 x 3/4"SMS
( )
• • INTO DJ
_ 1 /6" x 2" x 2" EXTRUDED ANGLE 5052
CORNER POST
H-32 ALLOY EA CORNER W/ (2) #f4 x 2"
- I- - --_
SMS INTO POST & (1) 3/8" DIA.
I6„ CONCRETE SCREWANCHOR INTO
CONCRETE
,
(2) #10 x 1 112" SMS2
aUCH
THRU SCREW BOSSES
_
SLAB / FOOTINGBEDMENT#10
IW MIN CONC
•BFDMWDDD:
2 1/4"MIN CONC
SEE PLAN°`UJIA,
ZFROM
x 3" WOOD SCREWS, 6"
ANCHOR EMBEDMENT
"'
GIRT & @ 12" O.C.
a .m
N
CONC:
SLAB / FOOTING
W Y
1/4" DIA x 3" CONCRETE
SEE PLAN
ea 4 ': a,
` "
w w
SCREW ANCHOR, 6"®
FROM GIRT & @ ZV O.C.
SIDE VIEW
(4) #10 x 1 1/2" INTO
BOSS
SIDE VIEW
Q O U
- -SCREW
2 CORNER POST W/ 1"x 2" @
}b'
�+LLI W H Lo
(4) #14 x 3/4" SMS
BACKSIDE
D_
1 L!J ~ Nr
1
INTO POST
(1) 318" DIA ANC CONCRETE
2" x 4" DJ
cc
--
I 3/8" x LENGTH AS REQUIRED
FOR 21/4" EMBED CONCRETE
(21/4" CONC. EMBED)
10_
Q v O J
SCREW ANCHOR INTO
DRAWN BY
�2"
_ I CONCRETE
_ I
x 2" OR 2" X 3" HOLLOW
1" x 2" BASE PLATE
-
GD
(
SECTION GIRT
ANCHORED TO CONC W/ 1/4"
°�.: •
CONCRETE SCREW ANCHOR
` 3
DATE DRAWN
1"x 2"
(MIN. 1 1/4' EMBED)
6" MAX EACH SIDE OF POST
a e• a a °
1" x 2" BASE PLATE
' '
q 4
'
02/28I1$
AND 24" O.C. MAX
'
ANCHORED TO CONC W/ 1/4"
` . " 'e• a a e
a
REVISION
CONCRETE SCREW ANCHOR
r ? •,
° •
1
a ., „
(MIN.11/4"EMBED) s n
•
d
W MAX EACH SIDE OF POST
AND 24" O.C. MAX
° ..
6"'
m
1X2 TO HOST STRUCTURE DETAIL
FRONT VIEW
FRONT VIEW
SHEET NO:
A_rf
G
SCALE: NTS
CP-1 CORNER POST TO CONCRETE DETAIL
DJ-1 DOOR JAMB TO CONCRETE DETAIL
A-2
SCALE: NTS
A_2
SCALE: NTS
A-2