HomeMy WebLinkAboutREVISIONGENERAL NOTES 1. DESIGN CRITERIA: APPLICABLE CODES, REGULATIONS & STANDARDS: 1. THE 2017 FLORIDA BUILDING CODE, 6TH EDITION SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CHAPTER 23 WOOD. 2. ASCE 7-10. & SE17 3. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 4. AC1318 CONCRETE REFRENCE MANUAL. 5. PCI PRECAST & PRESTRESSED CONCRETE. 6. AA ASM 35 & AA ADM 1 WIND LOADS: 1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE 1604.5: RISK CATEGORY 1. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 150 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: C 3. SCREENED ROOF ENCLOSURE FBC 2017 CH. 20 TABLE 2002.4 r ALUMINUM SPECIFICATIONS: 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS OTHERWISE SPECIFIED. 2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH #12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. 3. ROOF BRACING SHALL BE A MINIMUM 2"X2"X.050". 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING LLC. FASTNER SPECIFICATIONS: 1.-FASTNERS ARE REQUIRED TO BE SAE GRADE-2 OR BETTER ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS OR BETTER, INSTALLED TO MFG.) 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, AND FASTENERS TO MANUFACTURING SPECIFICATIONS. 3 WHERE WOOD DECK IS PRESENT USE 1/4"X3-1/2" GALV LAG CONCRETE & FOUNDATION DESIGN: 1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE SPECIFIED. REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE 4. 1 "X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST APPLICABLE: A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED A. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE 1/4"X2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS FOLLOWING COMPONENTS: B. FOR WOOD APPLICATION USE #14X2-3/4" WOOD SCREW AT I. PORTLAND CEMENT TYPE 1 - ASTM C 150 24" O.C. AND 6" FROM ENDS. II. AGGREGATES - LARGE AGGREGATE 3/4" MAX. - ASTM C 33 C. FOR ALUMINUM APPLICATION USE #10X1-1/2" SMS OR TEK o III. AIR ENTRAINING +/- 1 /o - ASTM C 260 SCREW AT 24" O.C. AND 6" FROM ENDS "OPEN IV. WATER REDUCING AGENT - ASTM C 494 D. WHERE VX2" INSTALLED THROUGHOUT AN VIEW" V. CLEAN POTABLE WATER SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS VI. OTHER ADMIXTURES NOT PERMITTED MASONRY SPECIFICATIONS: B. METAL ACCESSORIES SHALL CONFORM TO: I. REINFORCING BARS - ASTM A615, GRADE 60 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD II. WELDED WIRE FABRIC - ASTM A1.85 HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED C. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3" ON TYPE M OR S MORTAR. OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT 2. ALL MORTAR SHALL BE TYPE M OR S. -PERMITTED.-- _ 3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE _ D. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE- MAXIMUM COARSE AGGREGATE SIZE OF 3/8". INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3 4. PROVIDE CLEAN -OUTS FOR -REINFORCED -CELLS CONTAINING - INCLUDING HOT WHEATHER RECOMMENDATIONS. REINFORCEMENT WHEN GROUT POUR EXCEEDS 5'-0" IN E. MOIST CURE OR POLYETHYLENE CURING PERMITTED. HEIGHT. F. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE ARE FOR TERMITES IN COMPLIANCE WITH THE MISCELLANEOUS: RECEIVED MAR 2 2 2018 ST. Lucie County, Permittin AWNS , By 2. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND INSURE INSTALLATION HAS BEEN ACCOMPLISHED IN ACCORDANCE. WITH MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH THE ATTACHED DETAILS. 3. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND. FBC. 1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL G. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC BARRIER. R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. FOOTING SIZE: EXISTING CONCRETE SLAB. NO ADDITIONAL 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. PROPOSED CONSTRUCTION IF A MINIMUM 4" CONCRETE IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH SLAB (3000 PSI) IS PROVIDED IN SOUND CONDITION, FREE WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO FROM STRUCTURAL CRACKING, SPALLING & OTHER ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER 3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN CONCRETE SLAB MINIMUM 8"x8" W/ (1) #5 BAR TO BE THE FIELD. VERIFIED BY CONTRACTOR. SEE TYPICAL FOOTING DETAILS 4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR FOR NEW FOOTING DESIGN MINIMUM REQUIREMENTS. SHALL EPDXY TO DECK OR GROUT TO DECK w/3000 PSI 3. WHEN APPLICABLE FOR ATTACHING NEW FOOTER TO EXISTING, GROUT WITH BONDING AGENT. DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1" MIN. 5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE HOLE, EMBED 4 MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED (OR EQUAL) TYP. ALL LOCATIONS. STRUCTURE. 4. WHEN INSTALLING 4" CONCRETE SLAB -ADD ADJACENT TO 6. ALL 2X4 & GREATER ARE TO BE SMB UNLESS OTHERWISE INDICATED EXISTING-DOWELL INTO EXISTING CONCRETE 48" O/C W/8" #5 REBARS- DRILL 3/4" HOLE 4" EMBEDMENT- EPDXY W/ RESPONSIBILITIES: NON -SHRINKING "SIMPSON EPDXY TIE" (OR EQUAL). 1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED 5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHER WISE CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING NOTED. CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. LEGEND: (ALL MAY NOT APPL-p I-CTV- ,r SCR = SCREEN KP = KICK PLATEfE'L�'ED, PW = PICTURE WINDOW i)ATE ,�lj X = HORIZ. SLIDING WINDO A- S -\D O = HORIZ. STATIONARY W�NP)YLNSP DH = DOUBLE HUNG WINDOW' SH= SINGLE HUNG WINDOW SIP = SOLID INSULATED PANEL CT = CABLE TIE SG = SUPER GUTTER CS = CLEAR SPAN KB = KNEE BRACE 1603 -C:63 / L1 TY BUILDNG D V T MUST KEPT 1 WILL E MADE. ALUMINUM MEMBERS DIMENSIONS HOLLOW SECTIONS 2" x2"x0044"--- - - 2 x : 2"x3"x0.044" 2 x 3: -l?ME-PIANSA 3 IUD ALL PROPOSED WORK 2 x 4: 2"x4"0.044" ARE SUBJECT TO ANY CORRECTIONS 2 x 5: 2"x5"0.050" REQUIRED BY F ELD INSPECTORS THAT OPEN BACK SECTIONS MAY EE NEC1111 AIRY IN ORDER TO 1 x 2: 1 "x2"x0.044" OQMRI.Y WITH AIPWOARIA CODES, 1 x 3: 1 "x3"0.044" _ SNAP SECTIONS �ONCF.ALED Ft ENERS ON ATTACHMEM 2 x 2 SNAP: 2"x2"x0.050"2 ARE THEPONSISILP OF THE x 3 SNAP: 2"x3"x0.050" 2 x 4 SNAP: 2"x4"x0.045" CONTACTOR OF RECORD SELF MATING (SMB) 2 x 4 SMB: 2"x4"0.044"0.100" 2 x 5 SMB: 2"x5"x0.050"x0.100" 2 x 6 SMB: 2"x6"x0.050"x0.120" 2 x 7 SMB: 2"x7"x0.057"x0.120" 2 x 8 SMB: 2"x8"x0.072"x0.124" 2 x 9 SMB: 2"x9"x0.082"x0.124" 2 x 10 SMB: 2"x10"0.092"0.398" NOTE: AS INDICATED ABOVE ALL MEMBER PROFILES ARE INDICAT IN INCHES. ff-m I� 1 Y� SR'{, �• x Y � t i .t. r J � m 00J UI co co Zzp o U J_ O U Ooo= W Q LL L N 1 ~ W F-- M C:(D . I z Q F-- ^ _j N L1J d � v- � Q da Q U Ln �Vim- -- d N O O ui a 00 E o N � M u.i rn Lu ca U 0 N 00 0 w U U N_ t` O 00 w J .UJ _l U z w W m J U F- LL U) W LLI C0 LLI _I W I-- Of w � o I U) c� z ¢ imp O U ��Q d U�IL o rt 0 a DESIGN DATE: 3/19/2018 REVISION 1: DATE PAGE: REVISION 2: DATE SCALE: NTS WALL HEIGHT PER PLAN---{—b o I �T F I I \\ I I I \ R N n 1 -CONTRACTOR: PIO- SCREEN PR#JECT APIKESS: _SIDWELL 1626 SWEET BAY CIRCLE ® PALM CITY, L -- 6'-91' , 6'-911 6'-9" -�- 6'-9"----1 N N I 1X3 I w w X X 2X3 N w o c- C W rcn cn W W 1 X3 °0 � I I ------------- I 271-011 I X X 2X8 SMB 15'-2" 2X7 SMB N X 0A, I 13'-511 � I 2X7 SMB i cp I I I I I 11'-911 I 2X6 SMB I I N I X w N I co O=_ ` 3X2 I PROJECT NO. >< 2X6 SMB w co N 6 2X3 w w 00 C-- C-- 1X3 �-—10'-011 -� ■■ W r%)v0 Z7-p�OX 2 �r��zry m — m m cl) co X •e. N ry . D TI o • • ' o� m --I Fu 1211 cn m z -i 0 FLORIDA ENGINEERING LLC 4456 TAMIAMI TRAIL, UNIT B14 PORT CHARLOTTE, FLORIDA 33980 (941) 391-5980 www.fiengineeringlic.com 1807126-2 CA CERT. #30782 E. GundersYn, P.E. #60102 5/16/2018 I —6'-911 —61-911 6'-911 6'-911------- WALL HEIGHT PER PLAN+ . Ap II gy o r i i\ m OT m I I v I A I \\ AO I I I \ m I I I \\ m I I I \ 0 Z z< "'I CC G Z or- x0 n00z >goz m X rm- z0)y �C)> cnr-m cn K0 zz Cl) z m 0 —I o 0 Z m WC o mA x coK c�� m� w On O-A z _0a m p- 0- T 1X3 CO w 2X3 0 0 N y x X N w Cf) cn _ co W 00 E w I W 1X3 I -!--------------- � I I I !' N w 27'-0" 3X2 N D w i � I D 2 W O 2X8 SMB I o Cf) I W X n w i � 16-2 " , c II -------------- i X7 SMB g�_6 m I � 13'-5" w I j 2X7 SMB D O o D �, i = 0 2X6 SMB O 0 x i cn w x I co L= 3X2 w i .�'JI� TI conN v -n Nv - 10' - 011 cn I O � -i m �c�N nzm Wcm � m = D �D N G x m ccnn 2X6 SMB 00 �T cn --I x w w 0) = N N 2X3 W W 0 0 L 1X3 10'-011 C ig E. Gunderson, P.E. #60102 DATE: 3/19/2018 FLASHING 1'W" FASTEN TO COL. (INTERNAL) W/(2) #10xl-1/2" SMS, FASTEN TO EAVE RAILS ABOVE W/#10X7-1/2" SMS 24" O.C. AND 6" FROM END. TABLE D BEAM QTY EACH SIDEIS17E 2x3 4/12 2 x 4 8110 2x5 8/10 2 x 6 10/10 2 x 7 12/10 2x8 8/14 2x9 9/14 2 x 10 9/14 MAINTAIN MIN, OF 5/8" SEPERATION FROM EDGE OF BEAM SMS O.C. DETAIL E - UPRIGHT TO BEAM CONNECTION SCALE: NTS 'HORIZONTAL OR SLOPED BEAM PER PLAN NOTCHED TO RECEIVE COLUMN WITHIN SMS, (EACH SIDE) QTY PER TABLE D NOTCH PROFILE MAY VARY TO PERMIT CORRECT # SMS COLUMN PER PLANS NOTE: WHERE PAVERS ARE PRESENT USE 5/16" TAPCON XL (RED HEAD MFG.) MASONRY ANCHORS TO PENETRATE UNDERLYING CONCRETE FOOTING 2-1/4" (MIN.) -ALTERNATELY 5" x 1/4" QUICKSETS 2-114" EMBEDMENT (2) #10r INTO BE BEAM INSTAL TO COF SELF -MATING OR 1/8"x2"x2"x ANGLE SNAP SECTION TYP. 5032 H-32 ANGLE PER PLAN - I 2 - #10 SMS INTO COLUMN - - Vx2" O.B.-BASE PLATE-TYP. 1/4"MASONRY ANCHOR EACH P "I ANGLE - EACH SIDE COL. 0 0 1-1/4" MIN. CONC. ANCHOR EMBEDMENT 2" MIN. INCREASE DISTANCE MIN 4" SLAB 3000 PSI WHEN GREATER THAN 2x4 CONC. w/FIBERMESH UPRIGHT IS USED CONC. FOOTING BELOW SIDE VIEW 1/4" MASONRY ANCHOR AT EACH ANGLE 2 - #12 SMS I I 24 " TAPCON 1x2 BASE L (RED HEAD MFG. OR EQUAL) 2 @ SLAB (BEYOND) 1'S2" BASE PLATE ANCHORED TO CONC w/ 1/4" MASONRY ANCHOR 6" MAX EACH SIDE OF POST AND 24" O.C. MAX CONC. FOOTING BELOW FRONT VIEW `NOTE: FDETAIL "B" - 2"x4" TO 2"x7" SELF MATING FOR AND GREATER SEE DETAIL ON PLAN VIEW UPRIGHT TO DECK DETAILS SCALE: NTS (2) #10x3" SMS INTO SCREW BOSSES FOR EDGE MEMBER EDGE MEMBER / � , OR PURLIN EDGE MEMBER OR PURLIN ;E 0,0625" 6063-T6 FLAT PLATE w/(8) #10x3/4" SMS, MIN. 1/2" EDGE DISTANCE, PLATE MAY BE FASTENED INTERNALLY TO BRACE DETAIL "D"- ROOF BRACING CONNECTION DETAIL SCALE: NTS 'ALL MEMBERS PER PLAN �MFMRFPC \/ARV PFR PI AN ALUMINUM INTERNAL OR EXTERNAL RECEIVING CHANNEL w/(4) #10x75" INTO GIRT OR PURLIN & (2) #14x75" INTO BEAM OR UPRIGHT 0.062 ANGLE CLIPS MAYBE USED > PURLIN op, UPRIGHT, BEAM -SNAP, SELF MATING, OR HOLLOW III S MEMBER DETAIL "C" - GIRT OR PURLIN TO BEAM OR POST DETAIL SCALE: NTS DOORJAMB PER PLAN #10x2" SMS INTO REW BOSSES 2"x2"x.063" - DIM. TO MATCH PURLIN SIZE RECEIVING CHANNEL (2) #12 SMS INTERNAL TO EAVE RAIL (3) #12 EACH SIDE INTO PURLIN EAVE RAIL - SEE PLAN-- 1x2 OPEN BACK/ EXTRUSION (2) #10x2" SMS THRU 1x2 INTO EAVE RAIL EACH SIDE OF COLUMN - -- FASTEN HEADER w/(2) #10xT' / INTO SCREW BOSS OF HEADER it DETAIL "G" - SLOPED PURLIN � ALTERNATE HEADER CONNECTION it CONNECTION SCALE: NTS WHEN Z-BAR IS USED - FASTEN Z-BAR TO COUHEADER AT EACH CORNER AND 18" O/C (12) #12x1" SMS @ 1" SPACING II II ALTERNATE BASE PLATE CONNECTION it u 2'W" EDGE BEAM ATTACH MEMBER TO BASE PLATE ii u (INTERNAL) w/(2) #10x2" SMS o ATTACH BASE PLATE TO MEMBER ii II (2) #10x3" SMS - w/(2) #10x3" SMS INTO SCREW ii a INTO SCREW BOSSES BOSS OF BASE PLATE p CONNECTING EDGE o BEAM TO PURLIN I I I I I I 1/4" TAPCON (RED HEAD MFG. OR EQUAL) WITHIN 6" OF COLUMN 1-1/2" PENETRATION INTO UNDERLYING FOOTING ALTERNATE DETAIL "G" SLOPED DETAIL "I"' - DOOR JAMB & HEADER PURLIN CONNECTION SCALE: NTS CONNECTION SCALE: NTS PURLIN o I I UPRIGHT I I I I 1-1/2"x 1/16" PLATE (TOP OR BOTTOM) V52" FASTENED TO COLUMN w/(2) #10xl-1/2" SMS INTO SCREW BOSSES FOR SMB OR SNAP COLUMN Vx2" SNAP NOTCH COLUMN AS REQ'D. COLUMN PER PLAN J C) J m m UI co co Zz o 0 O U U W — W < LL Lo ,� -- a) (DF- 5 ai z WQ��m O � 0 _ Q �. = U F_ O � 1J N O 0 co 4t LLI ci c 00 ti O N � M W rn W N 00 F` 0 M F-- W U U CD CD 00 T_ b Z -U W W _1 U U J J 0!f Z U W i- m Of U J LL (A W }: U) J >w F- W o W cf)j� U 0 Z a U p � 0NQ Ul 0 ��a- Z OO O a DESIGN DATE: 3/19/2018 REVISION 1: DATE PAGE: REVISION 2: DATE SCALE: NTS GIRT FASTENED INTERNALLY AT EACH END w/#10xl.5" EACH SCREW GROOVE. FASTEN TO BEAM wl 2x2xl25 ANGLE (2) #12 SMS INTO BEAM & (2) #10xl-1/2" THRU ANGLE INTO GUTTER WHERE NO GIRT IS PRESENT, ATTACH ANGLE DIRECTLY TO GUTTER 2"x2"xl/8" ANGLE w/(2) #12 SMS EACH LEG FOR BEAMS ABOVE 2x8 INSTALL GUTTER BRACE AT MIDPOINT BETWEEN BEAMS & INCLUDE 2" GUTTER BRACE AT EACH BEAM LOCATION BEAM 0 11 1(2) #12 SMS �� vtll- SCREW 18" OpOD 0 0 CLOSE BOTTOM OF o 0 BEAM WHEN TRIMMED 044 RECEIVING CHANNEL, FASTEN w/(2) #12 SMS EACH SIDE OF B #10 SMS WITHII OF BEAM & 24" FOR BEAM OVER 2x5 044 RECEIVING CHANNEL FASTEN TO STRUCTURAL GUTTER INTERNALLY w/(2) #12 SMS ALTERNATELY 2x2xl/8" ANGLE BELOW GIRT, (2) #14 SMS INTO BEAM & (2) #12 SMS INTO STRUCTURAL GUTTER SIDE VIEW FASTEN GUTTER TO FASCIA w/ #14x2" WOOD SCREW 18" O.C. (2) #12 SMS 2x2xl/8"ANGLE EA SIDE OF BEAM EA- SIDE W OD S WOOD SCREW w/(2) #12 SMS EACH LEG EACH SIDI?Z�i FASCIA (2"x6" MIN. EXISTING) STRUCTURAL GUTTER TOP VIEW *ALTERNATELY SEE PAGE 5 - — - - - DETAIL "H" - SCALE: NTS NOTE F INSTALL FASTENERS ALONG PERIMETER OF GUSSET -BEAM JOINT 3/8" MIN, FROM EDGE. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 FASTENER PATTERN MAY APPEAR DIFFERENT FROM ILLUSTRATION. MAINTAIN 1/2" SEPARATION BETWEEN FASTENERS. MAINTAIN 3/8" MIN, FASTENER SEPARATION FROM BEAM JOINT OR EDGE OF BEAM LAP FASTENERS MAY BE EVENLY SPACED AROUND EDGE OF GUSSET WITHIN 3/8" OF BEAM JOINT. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 5052-H32 GUSSET TABLE B-1 BEAM SIZE COL. TO BEAM ON SMS/ SIDE OF COL. BEAM TO BEAM CITY SMS/ FACEISIDE 2 x 4 (5) #12 (9) #12 2 x 5 (5) #12 (9) #12 2 x 6 (7) #12 (9) #12 2 x 7 (10) #12 (10) #12 2 x 8 (12) #12 (14) #12 2 x 9 (14) #14 (14) #14 2 x 10 (16) #14 (15) #14 DETAIL "K" GUSSET CONNECTION SCALE: NTS .050" GUTTER STIFFNER FASTEN TO FASIA w(2) #12x2" WOOD SCREW FASTEN TO GUTTER w(2) #12 SMS \-- "ALTERNATELY SEE PAGE 5 —V — DETAIL "M" BEAM & PURLIN TO GUTTER CONNECTION SCALE: NTS (2) #12 SMS 2x2xl/8" ANGLE w/(2) GIRT \ #12 SMS EA. LEG SMB ° 1/8"&'x4" STRAP (2) #12 SMS INTO BEAM (2) #12 SMS INTO GUTTER WHEN BEAM & PURLIN HIT ON CORNER - FASTEN OUTSIDE OF BEAM & PURLIN w/ 1/8"x2'SC2" ANGLE & (4) #12 SMS EACH LEG FASTEN INSIDE CORNER (BEAM TO PURLIN) w/ 1/8"x2"x2" ANGLE w/(2) #12 SMS INTO EA MEMBER (BEAM & PURLIN) #14 WOOD SCREWS '0 FASCIA 18" O.C. o GIRT SIDE VIEW ' STRUCTURAL GUTTER (2) GUTTER BRACES EACH w/(2) #12 SMS INTO GUTTER & (2) #14 WOOD SCREWS INTO FASCIA GIRT " 1/8"x2"x4" STRAP (2) #12 SMS INTO BEAM GIRT (2) GUTTER BRACES (2) #12 SMS INTO GUTTER FASCIA EACH w/(2) #12 SMS INTO GUTTER & (2) #14 WOOD SCREWS INTO FASCIA 2x2xl/8" ANGLE w/(2) o #12 SMS EA. LEG o (2) #12 SMS o o SMB 1/8"&'x4" STRAP (2) #12 SMS INTO BEAM GIRT (2) #12 SMS INTO GUTTER STRUCTURAL GUTTER TOP VIEW DETAIL "L" CORNER CONNECTION SCALE: NTS (9) #104" Sn 1/8" PLATE ON 45° ANGLE OR 1/8"x2"x2" ANGLE w/(4) #12 SMS INTO EACH INTERSECTING MEMBER PERIMETE FRAMING DETAIL 1-2" CABLE CONNECTION AT CORNER SCALE: NTS N 0 o ' LLI 00 c ti 0 m O • � N ' U M rn LU ! 0 U (EBOLTFOR 4BLE TENSION 1/8" STAINLESS STEEL BRAIDED CABLE 1/8" STAINLESS STEEL 3000 PSI GONG. 40° MIN. BRAIDED CABLE 6x6 WWM OR OR FIBERMESH 60 MAX. 4" MIN. SLAB w/FOOTING 3/8" DIA x 3" EMBED GONG. SCREW ANCHOR (TAPCON OR EQUAL) 3000 PSI GONG. 6x6-10x10 40° MIN. WW IBE M H i. "W IIIII • m Am 4" MIN. SLAB/ \ WFOOTING 1.5"x5.5"ALUM. STRAP w/(2) 1/4" DIA x 2-1/4" MASONRYANCHOR (TAPCON OR EQUAL) DETAIL 14' CABLE CONNECTION AT FOUNDATION SCALE: NTS r� CD CO 0 co0o 0-)cl) co z 0 v ¢ of p U U W J O oo a, W V co O Z r W < Qrn� Q 0 F- U � � N O a �- 0o r O Z w O W U J U J J � Z U Of U ED LJL I— fA D" w y._ U) JLL1�_ U o W W z (�j� 0 U Q D_ w (n 1 0- DESIGN DATE: 3/19/2018 REVISION 1: DATE PAGE. REVISION 2: DATE SCALE: NTS 3/16" 5052-1-132 GUSSET 2" X PURLINS ATTACH TO BEAM WITH MIN (4) #10 X 1 1/2" SMS PLACE WASHER UNDER SCREW IN GUSSET CORNER 1 1/4" (TYPICAL) o0 0 0 51ar #14 SMS @ 1 1/4" O.C. / a o 0 0 0 0 0 0 0 0 0 23j8� „ �231 B 6 /8 NOTES: 1. GUSSET DIMENSION ARE MINIMUM (2) REQ'D (1) EA SIDE OF BEAM - MAYBE INTERNAL OR EXTERNAL 2. AS BEAM SIZE CHANGES, ADD OR SUBTRACT SCREWS TO MAINTAIN 1-1/4" C/C SPACING 3. GUSSET LENGTHS REMAIN CONSTANT WIDTHS CHANGE TO MATCH BEAM SIZE. 2"X2"X1/8" ANGLE X4" LONG PROVIDE #14 X 1" INTO EACH MEMBER AS INDICATED BELOW PROVIDE INTERIOR ANGLE ABOVE AND BELOW CHAIRRAIL EXTERIOR PLATE CORNER POST EAVE RAIL 1" x 2" O.B. PATIO SECTION 3" x 3" x 0.050" MIN., 6063-T6 ALLOY PLATE DR STRONGER (ONE SIDE) WITH (3) - #12 x 3/4" S.M.S. EACH SIDE AS SHOWN (318" MIN. PLATE EDGE DISTANCE & C-C FASTENER SPACING) x2x0.0 DACE (TYP. K-BRACE LATERAL "W'-BRACING CONNECTION DETAILS 1" X 2" O.B. FASTENED TO CORNER POST W/ #12 X 1 1/2" SMS AT 6" FROM ANGLE TOP & BOTTOM RAILS TYPICALLY @ 24" O.C. 1" INTO EACH DICATED BELOW 1/8" X 2" X 2" EXTRUDE ANGLE 5052 H-32 ALLOY EA CORNER W/ (2) #14 X 2" SMS INTO POST & (1) CORNER POST CONCRETE SCREW ANCHOR INTO CONCRETE 6' (2) #10 X 1 1/2" SMS I THRU SCREW BOSSES 21/4• NCHOF SLAB/FOOTING NOTES: SEE PLAN 1. CONNECTION DETAIL AT EAVE RAIL SIMILAR , GUSSET PLATE PER E-SERIES SELF MATING PURLIN CONTRACTOR TO INSTALL (2) #14 X 2" SMS THRU BRACE INTO BEAM THRU GUSSET PLATE CORNER POST 3" x 2" x 0.050" MIN., 6063-T6 ALLOY PLATE DR STRONGER (ONE SIDE) CORNER K-BRACE DETAIL SCALE: N.T.S. (4) #14 X 3/4" SMS INTO POST 1" X 2" BASE PLATE ANCHORED TO CONC W/ 1/4" CONCRETE SCREW ANCHOR (MIN. 1 1/4" EMBED) 6" MAX EACH SIDE OF POST AND 24" O.C. MAX FRONT VIEW E ,-- _ CORNER POST W/ 1" X 2" @ BACKSIDE 3/8" X LENGTH AS REQUIRED FOR 2 1/4" EMBED CONCRETE SCREW ANCHOR INTO CONCRETE CP-1 CORNER POST TO CONCRETE DETAIL A-4 SCALE: NTS (3) - #12 x 3/4" S.M.S., 6" x 5" x 0.050" EACH SIDE AS SHOWN 6063-T6 ALLOY PLATE (1/2" MIN. PLATE EDGE K-BRACE (ONE SIDE) OR STRONGER DISTANCE & C-C FASTENER SPACING) K-BRACE x 2 x 0.093 BRACE (TYP 2 x 3 x 0.070 CHAIR RAIL Oj O ®. j �I 3/8" 0 CONCRETE ANCHOR (2 PLATES) FOUNDATION IN LIEU OF TYP. 1/4" 0 CONCRETE SCREWS FOR CORNER COLUMN LATERAL "W'-BRACING CONNECTION DETAILS K-BRACE 2x2x0.093 BRACE (TYP.) N O O m LLI O (D M W U d COLUMN I :O O `, O �I O O i O GIRT (CHAIR RAIL) I _ __ I O O O ' O I 2x2x0.093 BRACE (TYP.) (11 TOTAL) - #12 x 3/4" S.M.S. AS SHOWN (1/2" MIN. PLATE EDGE DISTANCE & LATERAL 'W-BRACING C-C FASTENER SPACING) CONNECTION DETAILS U J t O 00 N co 0 ~ co UI z z O Q U U 0 W —� O 00 ao W Q LL Lo ' L.L � " a) ( ~ I-- M w< -j y-- Q LO � N O LL co T- O z U W O a_ W J U U J J � Z U 0� m LJL W 66 W [IfW JWI-- o W Z W�U a U 04 Q a- W � 5 � d DESIGN DATE: 3/19/2018 REVISION 1: DATE PAGE. 5 REVISION 2: DATE SCALE: NTS 1311/4" DIA MACHINE BOLTS w/ 3/4" DIA WASHERS THRU CARRIER BEAM & POST 0 Q CARRIER BEAM 0 1 POST VARIES 1"x2" MEMBER FOR SCREENING HORIZONTAL BEAM ON ITS SIDE (IF REQUIRED) 2'XL"x0.062" RECEIVING CHANNEL OR ANGLE EACH SIDE (6) #104.75" SMS EACH SIDE (12) #104.75" SMS 2 ROWS OF (6) FOR RECEIVING CHANNEL OR (6) EACH ANGLE BEAM TO POST DETAIL SCALE: NTS 2" FOR SINGLE HORIZONTAL BEAM 4" FOR DOUBLE HORIZONTAL BEAM OR 4"x4" (2) 3/8" DIA EXPANSION BOLTS SEE NOTE #1 THIS PAGE FOR BOLT PLACEMENT � ZW" FASTENED TO CARRIER BEAM w/(2) #10xl-1/2" SMS INTO SCREW BOSSES EACH END, CARRIER (3) 1/4" DIA MACHINE BOLTS w/ 3/4" DIA, WASHERS THRU CARRIER BEAM & POST � 1"x2" MEMBER FOR SCREENING #10xl-1/2" SMS @ 24" O.C. MAX CONNECTING TO Vx2" CARRIER BEAR #10xl1/2" SMS @ 24" O.C. MAX CONNECTING TO Vx2" POST 2"xZW.062" RECEIVING CHANNEL ROOF BEAM (SLOPED OR FLAT) NOTE USE SIMILAR DETAIL FOR NOTCHED UPRIGHT CONNECTIONTO CARRIER BEAM /(5) #12x3/4" SMS (TYP. EACH SIDE) (2) ROWS OF (5) #12x3/4" SMS NOTE: FOR DOUBLE OR TRIBLE CARRIER BEAM, OUTSIDE WEBS SHALL OVERLAP 4x4 POST OR NOTCH POST AS ABOVE FOR 6x6 POST. ALL CASES, CONNECT USING MACHINE BOLTS DECRIBED ABOVE. CARRIER BEAM TO POST CONNECTION DETAI SCALE: NTS (2) 1/2" DIA EXPANSION BOLTS SEE NOTE #2 THIS PAGE FOR BOLT PLACEMENT\ 2' FIR DG_E_ iC O If2" FROM EDGE OF SLAB ` OF SLAB TOP VIEW (2) 1/4" DIA MACHINE BOLTS w/ WASHERS C3 3"x"x0.125" POST (2) 3/8" DIA EXPANSION BOLTS SEE NOTE #1 THIS PAGE FOR BOLT PLACEMENT `-3"x3"x0.125 ANGLE CONC. FOOTING BELOW FRONT VIEW 3"x3" POST CONNECTION DETAI SCALE: NTS BOLTS w/ WASHE SS (2) 1/2" DIA EXPANSION BOLTS SEE NOTE #2 THIS PAGE FOR BOLT PLACEMENT TOP VIEW 125" POST 2"x SMB (SEE SHEET S-2 FOR SIZE) (3) 1/4" DIA MACHINE BOLTS w/ 3/4" DIA, WASHERS THRU CARRIER BEAM & POST,, ---._ (3) 1/4" DIA MACHINE BOLTS w/ 3/4" DIA, WASHERS THRU CARRIER TOP VIEW BEAM & POST 0 / CARRIER BEAM CARRIER BEAM 1 0 (3) 1/4" DIA MACHINE BOLTS w/ 3/4" DIA WASHERS THRU CARRIER BEAM & POST (3) 1/4" DIA MACHINE BOLTS/ POST w/ 3/4" DIA, WASHERS THRU CARRIER BEAM & POST FRONT VIEW CORNER CARRIER BEAM CONNECTION DETAI SCALE: NTS (4) 3/8"x4" TAPCON THRU BOTTOM LEG OF ANGLE INTO CONC. 3-314" FROM EDGE 3-3/4" FROM EDGE OF SLAB (TYP.) OF SLAB STITCH w/(2) #12X3/4" SMS @ 12" O.C. (3) 1/4" DIA MACHINE SMB BOLTS wMASHERS\ SHEET S-2 SIZE) (4) 3/8'W" TAPCON i 2"x4"x0.125 ANGLE THRU BOTTOM LEG OF ANGLE INTO CONC CONC. FOOTING BELOW FRONT VIEW 4"x4" POST w/ 2x SMB CONNECTION DETAIL SCALE: NTS NOTES: 1. 3x3 POST TO HAVE 3/8" RED HEAD - TRUBOLT WEDGE ANCHORS (STAINLESS STEEL, PROVIDE MINIMUM 2" FROM EDGE OF SLAB AND PROVIDE MINIMUM 2" SPACING TO ANY OTHER CONNECTOR. SEE MFG. NOTES FOR INSTALLATION REQUIREMENTS. THREADED ROD REQUIRES 3" MINIMUM EDGE DISTANCE. 2. 4x4 POST TO HAVE 1/2" RED HEAD -TRUBOLT WEDGE ANCHORS (STAINLESS STEEL, PROVIDE MINIMUM 3-3/4" FROM EDGE OF SLAB AND PROVIDEBMINIMUM 3-3/4" SPACING TO ANY OTHER CONNECTOR. SEE MFG. NOTES FOR INSTALLATION REQUIREMENTS. 3. WHERE PAVERS ARE PRESENT ANCHOR LENGTH SHALL BE INCREASED BY THICKNESS OF PAVER NOT TO EXCEED 2-1/2" FOR PAVER THICKNESS MORE THAN 2-1/2" SPECIFICATIONS SHALL BE REQUIRED. PAVERS SHALL BE BONDED TO UNDERLYING CONCRETE FOUNDATION. 4. WHERE RETURN WINDOW BEAM MEETS MASONRY WALL USE 1/8" U-CHANNEL W/ (3) 2-1/4" TAPCONS INTO WALL AND #12 x 3/4" INTO BEAM E/S QUANITY= BEAM SIZE TOP VIEW (2) 1/2" DIA EXPANSION BOLTS SEE NOTE #2 THIS PAGE FOR BOLT PLACEMENT\ _If�ll;.o 3-3/4" FROM EDGE 3-3/4" FROM EDGE OF SLAB (TYP.) OF SLAB (TYP.) TOP VIEW COLUMN PER PLAN (3) 1/4" DIA MACHINE BOLTS w/ WASHERS 1/8"x2"x2"x33/4" (LENGTH) ANGLE (INTERNAL) (2) 1/2" DIA EXPANSION BOLTS SEE NOTE #2 THIS PAGE FOR BOLT PLACEMENT CONC. FOOTING BELOW FRONT VIEW ALT. COLUMN BASE ATTACHMENT DETAIL SCALE: NTS 4'W'W.125" POST "2"x4"x0.125 ANGLE CONC. FOOTING BELOW FRONT VIEW 4"x4" POST CONNECTION DETAIL SCALE: NTS v .J m co J V rn M Zzo 0 p U U W -J 0 00 W V/ J � LL. L -` 11..IV.. �— LL r' L a) a) r— v — co �-- z20�� W < 0 Lo o LL U J J Z W W w U W W Z O 'o1 DESIGN DATE: REVISION 1: REVISION 2: SCALE: _N O 00 r 3/19/2018 PAGE: NTS