March 23, 2018
Re: Van Leeuwen Re -Roof
10725 S. Ocean Drive Lot 72
Jensen Beach, FL 34957
ie, FL 34984
785 - 9888
SCOPE OF.WORK:
Remove existing roofing and install new 5-V Crimp Metal Roof (Gulf Coast Supply & ;
Manufacturing FL # 11651.13) at above referenced residence address over new underlayment
and existing plywood sheathing. i
DESIGN CRITERIA:
FBC 2017
ASCE7-10
PROJECT DATA:
BUILDING HIEGHT =12'
A= 3'
MEAN ROOF HIEGHT = <20'
ROOF ANGLE = 3:12 '
SHAPE = PITCHED, GABLE
RvfPROTANCE FACTOR = 1.00 J
WIND VELOCITY V ult = 165 MPH
WIND VELOCITY V asd =124 MPH
EXPOSURE = D r
ENCLOSURE CLASS = ENCLOSED BUILDING
INTERNAL PRESSURE COEFFICIENT = -0.18
APPLIED UPLIFT DESIGN PRESSURES ON SLOPED ROOF (Dst):
ZONE 1 (Field) = -44.7
ZONE 2 (Perimeter/ Ridge) = =75,.5
ZONE 3 (Comers) = -110.8 ,
Paul Welch Inc.
I aul. Welch P.E. Reg. No. 29945
I March 23, 2018
10725 S. Ocean Drive Lot 72 Jenseni8each, FL 34957 1 of 4
�i
i
Metal roofing to be attached with #9 -15 x 1
plywood sheathing) Woodgrip screws with v
ZONE 1(Field):
Fasteners through ribs (Type 1 per l
ZONE 2 (Perimeter/ Ridge):
Fasteners through ribs (Type 1 per I
ZONE 3. (Corners):
Fasteners adjacent to ribs both sides
long (minimum- V4" penetration through
ier sealing washers spacing as follows:
approval) at 16" O.C.
approval) at 16" O.C.
2 per product approval) at 16" O.C.
Zones 1,.& 2 Design uplift Pressure: -94.25,E psf
Zone 3 Design uplift Pressure: - 131.0 psf
Zones 1 &2: 94.25 > 75.5 > 44.7
Zone 3: 131.0 > 110.8
NOTE: CONTINUOUS APPROVED
SIDELAPS FOR SLOPES LESS THL
O.K.
O.K.
►P SEALANT MUST BE USED AT ALL PANEL
3:12.
UNDERLAYMENT:
Underlayment shall lie Tri-Built Roofing Products FL# 16048'.1 "Tri-Built S/A HT TU'..
While priming is optional, TRI-BUILT recommends priming the deck if the final roof cover is
not slated for installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 10'ft of membrane and peel back
the first 3 ft of release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel -off the release film diagonally while
holding the membrane tight. Firmly roll the membrane into place to achieve a bond. Horizontal
seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6inches
and staggered not less than 2-ft from vertical seams in the course below. All over -granule end -
.laps shall be sealed using either heat -welding ors hot air welding techniques. For Valleys and
Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet over
valley or ridge. Drape and press sheet!into'place, working from the center of the valley or ridge
in each direction. For valleys; apply the sheet starting at the lowest point and work upward.
Paul Welch Inc.
Paul Welch P.E. Reg. No. 29945
March 23, 2018
10725 S. Ocean Drive Lot 72 Jensen Beach, FL 34957 2 of 4
I
I
DECK INSTALLATION:
Re -nail all plywood sheathing (15/32" thick minimum) with 8D ring -shank nails at 4" O.C.
perimeter and 6" O.C. field for all zones.
!
All work to be in compliance with product approval (FL # 11651.13),'(FL# `16048.1),
manufacturer's specifications, and the Florida Building Code 2017.
i
10725 S. Ocean Drive Lot 72 Jensen Beach, FL 34957
i
Paul -Welch Inc.
Paul Welch P.'E.'Reg. No. 29945
March 23, 2018
3 of 4
r
OR
ROOF �ZQNE PLAN
A=3'
Q (D, ZONE DESIGNARON (TYPICAL)
NOTE: CONTINUOUS APPROVED LAP SEALANT MUST BE USED AT ALL PANEL
SIDELAPS FOR SLOPES LESS THAN 3:12.
Paul Welch Inc.
-Paul Welch'P.-E. Reg.. No. 29945
March 23, 2018
10725 S. Ocean Drive Lot 72. Jens6A Beach, FL 349157 4 of 4