HomeMy WebLinkAboutBUILDING PLAN 16-30DEMOLITION PLAN NOTES: 01 REMOVE EXISTING OVERHEAD DOOR MOTORS. IDENTIFY EXISTING POWER AND CONTROL WIRING AND PULL BACK TO EXISTING WALL WHICH IS TO REMAIN. COIL WIRING FOR FUTURE USE. POWER WIRING: (2) #10. (1) #12 GND. IN 3/4" C. CONTROL WIRING: (5) #16, (1) #16 GND. IN 3/4" C. O REMOVE EXISTING RECEPTACLE AND CONDUIT. PULL BACK WIRING AND COIL FOR FUTURE USE. Q REMOVE DOOR CONTROL JUNCTION BOX AND CONDUIT. COIL WIRING FOR [] O FUTURE USE. b� ® REMOVE PHONE OUTLETS AND CONDUIT. PULL CABLE BACK TO TELEPHONE EQUIPMENT ROOM. Q REMOVE AND DISPOSE OF CEILING MOUNTED LIGHT FIXTURES. IDENTIFY WIRING AND PULL BACK FOR FUTURE USE. © REMOVE AND DISPOSE OF EMERGENCY AND EXIT LIGHTS. IDENTIFY U o WIRING AND PULL BACK FOR FUTURE USE. 0 REMOVE AND DISPOSE OF OUTDOOR LIGHT FIXTURE. IDENTIFY WIRING AND PULL BACK FOR FUTURE USE. Q8 REMOVE EXISTING CAMERA. IDENTIFY EXISTING POWER, SIGNAL AND a o CONTROL WIRING AND PULL BACK TO EXISTING WALL WHICH IS TO REMAIN. EXTEND EXISTING WIRING TO TEMPORARY LOCATION SHOWN ON SHEET E-1. ® u® n DEMO FLOOR PLAN - LIGHTING SCALE: 1/8" = 100" EXISTING / CAMERA EXISTING J CAMERA TO BE TEMPORARILY RELOCATED. PULL BACK TO THIS POINT. COIL WIRING ABOVE CEILING AT THIS LOCATION. H SCANNED By St LUCID rnl inty O EXISTING CAMERA O� PULL BACK TO THIS POINT. COIL WIRING ABOVE CEILING AT THIS LOCATION. EXISTING CAMERA 0� DEMO FLOOR PLAN - POWER/SYSTEMS SCALE: 1 /8" = 1'-0" Z a � 0 Q Q0 U � Fa W M MM a UJ o W- 06 00 CD �U CD OCD wCD Q Z= WMM U M M �a W Za' Lij Q orl /A N w z � U Q o z 00 C) — W �- ry Qn�- �Oz O Q U z w zCD� O � w � oUcn o � Q � cn SHEET NUMBER E- 2 OF 7 MOTOR CONNECTION SCHEDULE Mark Equipment Equip. Voltage Equip. Nema Disconnect Panel & Breaker Feeder Or See Description Load & Phase Location Starter Size at Circuit No. Size Branch Note Size Equipment Wire Size 1 RTU-M 32A 480/3 ROOF WITH 60A-3P FU A/C B- SEE (3)#8,(1)#1OG.-EX. C. 1 EQUIP NEMA 3R 2.4.6 PNL SCH. 2 EF-BOOK 1/30HP 120/1 SEE PLAN WITH M.R.S. B1-18 SEE (2)#12 (1)#12G 1 EQUIP PNL SCH. 3 EF-M 3/4HP 480/3 ROOF 0 : j W/ EQUIP. B0,22,24 (2)#12,(1)#12G. 2 1 1 PNS SCH. 1. INTERLOCK RTU-M AND EF-1. SEE MECHANICAL DRAWINGS. 2. PROVIDE A RELAY FOR FIRE ALARM CONTROL. SCHEDULE OF GENERAL LIGHTING EQUIPMENT AND LAMPS TYPE MANUFACTURER CATALOG NUMBER DESCRIPTION MOUNTING VOLTAGE NOTES A DAY-BRITE 2DG332-FS01-277 (3) 32W T-8 STATIC RECESSED RECESSED 277 1,2 AE DAY-BRITE 2DG332-FS01-277 (3) 32W, T-8 STATIC RECESSED RECESSED 277 1,2,4 B DAY-BRITE WLM-175M-270 M.H. WALL PACK SURFACE 277 3 C DAY-BRITE CLI-175M-27Q-PX 175W M.H. ENT. CANDID. LT. SURFACE 277 3 D CAPRI F6218V2 W/R6200 TRIM 21CF Q 13W 23 RECESSED ON LT RECESSED 277 X MORELITE E-LED-SF-BWM-Ft-RW-277 FURNISHED EXIT SURFACE 277 BU CHLORIDE 4X12N50 FURNISHED EMERGENCY SURFACE 277 LIGHTING FIXTURE GENERAL NOTES: A. PRIOR TO PLACING ORDERS FOR RECESSED FIXTURES, CONTRACTOR SHALL VERIFY THE TYPES OF CEILING AND SUSPENSION SYSTEMS THAT HAVE BEEN APPROVED FOR THE PROJECT AND SHALL ORDER FIXTURES WITH FLANGES AS REQUIRED TO FIT IN THE APPROVED CEILINGS FIXTURE SCHEDULE NOTES: 1. FLUORESCENT LAMPS TO BE 32 WATT T-8. 2, ALL FLUORESCENT ELECTRONIC BALLASTS TO BE 20% THD. 3. PROVIDE QUARTZ RESTRIKE. 4. PROVIDE 1100 LUMEN MIN. EMERG. BATTERY PACK EXISTING PANEL "82" EXISTING PANEL "81 - �TING PANEL "MX" EXISTING PANEL "BE2 EXISTING PANEL "BE1 FLOOR PLAN - LIGHTING SCALE: 1/8" = V-0" NOTE: CONNECT EXIT AND EMERGENCY LIGHTS TO THE HOT LEG OF AN ADJACENT CIRCUIT. LK)FMNG PLAN REFERENCE NOTES - CONNECT LIGHT FIXTURES IN SALLY PORT TO CIRCUIT PREVIOUSLY COILED. EXIST. MX 1 A 4X M U o b o Co b F� U� U i p d .,.4 y a UD 1ti a . m W a* mCh p CV N 0zco (nAb� F e W n as " � ko �kop� U) " g o Z a 0 Q � Q m U rn rR `-/ w w M a w 0- m - 06 1:1) �— co �U;I - CD U wCD Z col m N PI; mcrF I a Z `g w 0I 0, Q C , w z I—UQ o z 00 z � � o Q� � n' o z LL-J (_) Q U � � z w � U z�� 0 W 0 Q� SHEET NUMBER E- 3 OF 7 POWER/SYSTEMS PLAN GENERAL NOTES 1. ALL DEVICES CONNECTED TO FIRE ALARM PANEL SHALL BE UL LISTED FOR USE WITH NOTIFIER AM2020 AND NOTIFIER 5000 FIRE ALARM PANELS. 2. ALL SMOKE DETECTORS, HEAT DETECTORS AND MONITOR MODULES SHALL BE CONNECTED TO NOTIFIER 2020 SIGNALING LOOP CIRCUIT 1_02. 3. ALL STROBE LIGHTS SHALL BE CONNECTED TO THE EXIST. BOOKING STROBE CIRCUIT. 4. ALL SPEAKER/STROBE IN SALLY PORT SHALL BE WEATHERPROOF. 5. ALL SPEAKER/STROBE AND STROBES SHALL BE 80" A.F.F. 6. ALL PULL STATIONS SHALL BE 48" A.F.F. 7. ALL EXIST. DEVICES IN PRESENT BOOKING AREA SHALL REMAIN OPERATIONAL. 8. CONNECT RECEPTACLES TO CIRCUIT SHOWN IN PANEL "B1." 9• CONNECT RECEPTACLES DESIGNATED WITH AN "E" TO CIRCUIT SHOWN IN PANEL "BET." POWER/SYSTEMS PLAN REFERENCE NOTES: 0 PROVIDE (1) 19" RELAY RACK W/CANTILIEVER SUPPORT BASE AND INSTALL IN THE AREA WHERE EXISTING RACKS WERE REMOVED. Q2 RELOCATE EXISTING 12 PORT ETHERNET HUB TO NEW RACK LOCATION. REROUTE EXISTING CABLES TO NEW LOCATION. O3 PROVIDE (3) 16 PORT ETHERNET HUB WITH 10 BASE "T" CONNECTION. INTERCONNECT THE NEW HUBS WITH THE EXISTING HUB USING 10 BASE "T" CONNECTION. ® PROVIDE (5) JUNCTION BOXES SIZED AS NECESSARY FOR CAMERA, INTERCOM, TELEPHONE, DATA AND DOOR LOCK CONTROL WIRING ROUTING. Q LOCATE AND EXTEND EXISTING 3/4" C. FOR DOOR LOCK CONTROLS TO JUNCTION BOX. © PROVIDE (2) JUNCTION BOXES. AT SALLYPORT GATES, (1) FOR POWER AND (1) FOR CONTROL. EXTEND CONDUIT AND WIRING PREVIOUSLY COILED FOR OVERHEAD DOOR MOTOR. PROVIDE LIMIT SWITCHES AS RECOMMENDED BY DOOR MANUFACTURER. COORDINATE W/DOOR CONTRACTOR FOR THE LOCATION OF UPPER AND LOWER LIMIT SWITCHES. ® PROVIDE JUNCTION BOX AND EXTEND EXISTING WIRING TO NEW DOOR LOCATION. (5) #16 IN 3/4" C. ® PROVIDE JUNCTION BOX AND (5) #16 3/4' C. ROUTED TO EXISTING GATE & DOOR CONTROL CABINET. ® PROVIDE NEMA 1 ENCLOSURE SIZED AS REQUIRED INSTALLED ABOVE EXISTING GATE & DOOR CONTROL CABINET. PROVIDE (3) ADDITIONAL CONTROL CARDS BY ICOTECH AND ALL REQUIRED CARD TREMINATION HARDWARE FOR A COMPLETE SYSTEM. NEW CARDS WILL CONTROL (2) VESTIBULE DOORS AND (1) SALLY PORT DOOR. ® MODIFY EXISTING FACILITY DOOR, GRAPHICS DISPLAY CONSOLE LABELS FOR (4) SALLYPORT GATES, (1) SALLYPORT DOOR, & (2) SALLYPORT SLIDING DOORS. PROVIDE PHENOLIC TAGS 1" HIGH LABELING THESE DOORS AS "NEW SALLYPORT." PROVIDE CONTROL BUTTONS AND INDICATION LED'S FOR (2) SLIDING DOORS & (1) SALLYPORT SWING DOOR. MOUNT BUTTONS & LED'S ON A NEMA 1 ENCLOSURE INSTALLED NEXT TO EXISTING CONTROL CONSOLE. ® INSTALL PHONE OUTLET ® 48" A.F.F. EXTEND CONDUIT AND WIRE TO TELEPHONE EQUIPMENT ROOM. Q9 PROVIDE CONTROL RELAY CONNECTED TO THE EXISTING FIRE ALARM PANEL FOR EF-M CONTROL. ROUTE 1" CONDUIT FORM RELAY LOCATION TO THE CENTRAL CONTROL ROOM AND STUB IN A JUNCTION BOX IN THE CEILING SPACE FOR CONNECTION BY THE SECURITY SYSTEM CONTRACTOR. UPON ACTIVATION OF THE FIRE ALARM SYSTEM, RTU-M SHALL STOP AND EF-M SHALL START. ® PROVIDE (2) JUNCTION BOXES AT EACH CAMERA LOCATION. ROUTE POWER FROM PANEL "BE-1." ROUTE SIGNAL CABLE TO CENTRAL CONTROL ROOM. 11 INSTALL CAMERA REMOVED FROM NW CORNER OF SALLY PORT. EXTEND POWER, SIGNAL AND CONTROL WIRING TO THIS LOCATION. © INSTALL CAMERA REMOVED FROM SE WALL OF SALLY PORT. EXTEND POWER, SIGNAL AND CONTROL WIRING TO THIS LOCATION. © INSTALL CAMERA REMOVED FROM SE CORNER OF SALLY PORT. EXTEND POWER, SIGNAL AND CONTROL WIRING TO THIS LOCATION. ® INSTALL CAMERA REMOVED FROM SW CORNER OF SALLY PORT. EXTEND POWER, SIGNAL AND CONTROL WIRING TO THIS LOCATION. ® EXTEND EXISTING POWER AND CONTROL WIRING TO TEMPORARY GATE LOCATION. [POWER = (2) #10, (1) #10 GND. - 3/4" C.; CONTROL = (10) #16 IN 3/4" C.] ® PROVIDE (1) METAL JUNCTION BOX WITH SCREW -ON COVER FOR DIEBOLD SYSTEM POWER. PROVIDE (2) #12. (1) #12 GND, 3/4" C. DOOR STATUS LEDS GREEN = FULLY CLOSED & LOCKED RED = DOOR IN TRANSIT YELLOW = FULLY OPENED & LOCKED 2 POSITION DOOR STATUS LED TOGGLE � GREEN =LOCKED WI CTCH orn — i un nnvrn EXISTING CENTRAL SERVICES SWITCHES FOR NON -RECORDING CAMERAS EXIST. CONDUIT CONNECTING EXIST. SWITCHES 1 EXIST. SP 3/4" C. EXISTING-� CCTV SWITCHES FOR RECORDING CAMERAS J EXIST. TELEPHONE - EXISTING FACILITY & NETWORK EQUIP. RACKS 0 DOOR GRAPHICS BE1-37 DISPLAY CONSOLE NEW BOOKING DOOR CONTROL PANEL EXISTING LEXISTING INTERCOM PANEL "CDP-2C" PANEL EXISTING /A EXISTING CONTROL PANEL PANEL "A/C -Bo ® 1 ® MOMENTARY SWITCH G R Y G R Y G R 000 000 00 CLOSE CLOSE STOP/OFF STOP/OFF OPEN OPEN HALF FULL CYCLE CYCLE INTERIOR INTERIOR NEMA 1 ENCLOSURE PAINTED VESTIBULE VESTIBULE SOUTH TO MATCH EXISTING CONTROL SALLYPORT PANEL. SIZE BOX AS REQUIRED TO ACCOMMODATE BUTTONS LED's AND CONTROL CARDS. BOOKING EXPANSION DOOR CONTROL PANEL 3 POSITION TOGGLE BOOKING DOOR CONTROL PANEL SWITCH COORDINATE WTH TAMPA DETENTION INC. 0 813-264-2802 FLOOR SCALE: 1/8" = 1'-0" , EXISTING PANEL "B2" EXISTING PANEL "B1"� EXISTING PANEL "MX" EXISTING PANEL "BE2" EXISTING PANEL "BE1"� i f - POWER and SYSTEMS n� `r' PHONE PHONE Q u DATA DATA LEVITON QUICK PORT 4 PORT WALL PLATE P/N 41080-41P WITH (2) 8 CONDUCTOR CAT. 5 JACKS P/N 41108-R•5 AND VOICE(2) 6 CONDUCTOR JAC S P/N 411106-R6GRADE PLAN SYMBOL = WS WORKSTATION TELEPHONE & DATA OUTLET TELEPHONE CABLE: BELDEN 9560, 24 AWG, 6 PAIRS COMPUTER CABLE: BELDEN 15858, 24 AWG, 4 PAIRS WORKSTATION OUTLET DETAIL NOT TO SCALE EXIST. GATE & DOOR CONTROL MX CABINET. CONTROL CARDS BY ICOTECH EXIST. 12 PORT ETHERNET HUB EXIST. TTB (2) 4" C. FOR PHON LINES (2) 4" C. FOR DATA LINES EXIST. SPARE 3/4" C. T O a Z IC ❑ O IC 4 27 (2) 4" C. FOR CCTV (2) 4" C. FOR INTERCOM N 5 ,as 0 29 4 BE1- 3 PJ2 TO TEMP GATE IC CAMERA CONNECTION SCHEDULE CAM. RECORDING NON -RECORDING TYPE HOUSING LENS NO. BURLE BURLE BURLE 1 X TC552A TC9303 TC9902 BURLE BURLE BURLE 2 X TC552A TC9340A TC9902 BURLE BURLE BURLE 3 X TC552A TC9302SH-LC TC9702 BURLE BURLE BURLE 4 X TC552A TC9302SH-LC TC9702 BURLE BURLE BURLE 5 X TC552A TC9302SH-LC TC9702 BURLE BURLE BURLE 6 X TC552A TC9350 TC9702 BURLE BURLE BURLE 7 X TC552A TC9350 TC9702 BURLE BURLE BURLE 8 X TC552A TC9350 TC9702 BURLE BURLE BURLE 9 X TC552A TC9350 TC9902 BURLE BURLE BURLE 10 X TC552A TC9350 TC9902 BURLE BURLE BURLE 11 X TC552A TC9350 TC9702 BURLE BURLE BURLE 12 X TC552A TC9350 TC9702 BURLE BURLE BURLE 13 X TC552A TC9350 TC9702 X BURLE BURLE BURLE 14 TC552A TC9350 TC9702 15 X EXISTING EXISTING EXISTING BURLE BURLE BURLE 16 X TC552A TC9350 TC9702 BURLE BURLE BURLE 17 X TC552A TC9350 TC9702 18 X EXISTING EXISTING EXISTING 19 X EXISTING EXISTING EXISTING 20 X EXISTING EXISTING EXISTING NOTE: MOUNT CAMERAS 6" BELOW CEILING HEIGHT UNLESS OTHERWISE NOTED. ETEq EWH E'R"fW§1 ©WE 34 34 34 34 t 0 aco 0 20 ® 20 b 22 22 22 5E tE tE 08' AFG 19 ®IC 0 J OJ �418 07' AFG J ® ® 14 1 �J ,,, 17 J � v v 12 31 Ol O22Tf K E p© 11 If J 1022 E 20� 16 34 I{ ® IC E UY �22 ® m�IC IC �0 81-3 20r�Tf0 U /10 ® E J 31 9 33_Q UJ ,. 20 ❑F ® GF1I 249 38' Q 8 0 BOOKING INTERCOM © E E 33 � MASTER STATION &20 ® B1-1 34 (ON ROOF) IC EF-BOOK J ® r WP 36 (ON ROOF) /C-B:22,24.26 i� i �1�tFL�IE 3 z F2)#10, 9 S J (ON (1)#10 GND, 3/4"C. 3ROOF)16 EWH-1 m [.� ® 16 ,W ® =0 16 E M 16 t(O 2Q [�J BE2-20,22,24 � (ON ROOOF) 09 6 J 13 J 6 J 16 J E�3J IC J J J 07' ® ,0 IG J ®� 15 AFG 08' AFG TO TEMP. CALL BOX SEE SHET E-1 Z� a Q Qo w� c� a 0 w c a r w I ^ L O m 06 a) co �UCD O CD O W Cl). vJ F- Q Z m U m N N M a: zw z W �I I- Q sg v / N w z Q 0 C) 0 zULL_ LLJ �oz LLJ U CD Q U � z ,_, U CD z C) �— LLJ U cj-) Q SHEET NUMBER E- 4 OF 7 1/2" x 24" — (MAX. WITHOUT SUPPOR ALUMINUM AIR TERMINAI ALU SUR ALUMINUM LOOP CABLE CLIP W/STAINLESS STEEL SCREW NOTE: CLASS I SHOWN CONDUCTOR G FLAT MOUNT AIR TERMINAL NOT TO SCSALE 20' OF LESS MAIN SIZED CABLE SPLICER / STATIC GROUNDING RECEPTACLE WITH CHAIN ATTACHED COVER. CADWELD B165R OR EQUIV. 2- 5/8"x10' COPPERWELD GROUND ROD EMOVABLE 3/4"0 BALL EXOTHERMIC WELD CONNECTIONS TO CABLE & ROD. CADWELD TYPE BG-GR OR EQUIV. 4-1/2" MAIN SIZED CABLE TO LOCAL COUNTERPOISE NOTE: PROVIDE MATCHING GROUND CLAMP EX THERMICALLY WELDED TO ONE END OF A NO. 4 FLEXIBLE WELDING CABLE & WITH AN APPROPRIATELY SIZED GROUNDING CLA P ON THE OTHER END DEPENDING ON ITEN TO BE CONNECTS . LENGTH OF CABLE TO BE SELECTED FOR SPECIFIC INSTALLATION CONDITIONS. eSTATIC C E-4 NOT TO SCALE ROOF TOP MECHANICAL EQUIPMENT — METAL LESS THAN 3/16" THICK — NOT IN ZONE PROTECTION — CLASS II CONNECTIONS SHOWN eROOF TOP MECHANICAL EQUIPMENT E-4 AIR TERMINAL DETAILS NOT TO SCALE 20' OR LESS N LEGEND OLIGHTNING PROTECTION AIR TERMINAL --��i GROUN� ROD LIGHTNING PROTECTION CONNECTION POINT LIGHTNING PROTECTION CONDUCTOR PRESSURE TYPE "TEE" SPLICER WITH STAINLESS STEEL BOLTS. HEAVY DUTY STRAIT SPLICER WITH STAINLESS STEEL BOLTS SYSTEM CABLE HEAVY DUTY PARALLEL CLAMP WITH STAINLESS STEEL BOLTS CABLE END SHALL FACE IN DIRECTION OF NEAREST DOWNLEAD SYSTEM CABLE C S W/Y CO W CLMMn E-4 Morro e LUMNING PROTECTION REFERENCE NOTES: O1 CONNECT TO EXISTING MAIN CONDUCTOR. DOWN CONDUCTOR. A E-4 (TYPICAL) 5•------------ ----------- // I / I / I I � I CONNECT TO EXIST. LIGHTNING PROTECTION SYSTEM , ----------- - - - - - - - - - � i I -�------- I I I I I I I I I D �--- D E-4 E-4 RMU EF CONNECT TO EXIST. I D e0ox I C I LIGHTNING PROTECTION I E-4 I EF I E-4 (TYPICAL) , SYSTEM I I M I I I I I J I I 2 2 -----------d----------�--------- -----------fir / B E-4 LIGHTNING PROTECTION PLAN U to b 0 o m rn Z a � S � N CwJ � f`R W M M L.V a � W CL o m - 00 O CD CDW U co Z mU m N W HQ s o co 101 w z I—UQ o z 0 zoo oW � o z LLJU� o U Q z LLJ U CD zU 0 � W U � 0 � Q SHEET NUMBER E- 5 OF 7 SCALE: 1/4' = 1'-0" EMERGENCY POWER PoSER LEGEND EXISTING EQUIPMENT/WIRING ETC. TO REMAIN M\ a ❑AlDQ TELEPHONE RISER DIAGRAM NOT TO SCALE 'AIRS 9566 (TYP.) (2) 4 PAIRS CAT 5 BELDEN 15858 JUNCTI BOX C. NEW BOOKING AREA 4" -------------- C. - - EXIST. PHONE ROOM NEW 12 POR / ETHERNET 4 HUBS -------- ____ EXIST. 12 PORTJ `�' ETHERNET Il HUB COMPUTER LAN 225A 3P REPLACE EXISTING CIRCUIT BREAKER WITH (1) 225A, 3P 100% RATD BREAKER NORMAL POWER RISER LECND 13 EXISTING EQUIPMENT/WIRING ETC. TO REMAIN OAU-1 NEW EQUIPMENT/WIRING ETC. POWER RISER DIAGRAM NOT TO SCALE I I I CAT 5 BELDEN A115858 (TYP.) I I I I i EXISTING INTERCOM STENTOFON P9600 INTERCOM SYSTEM (CENTRAL CONTROL) JUNCTION BOX 4" C. 4" C. (1) 2 WIRE INTERCOM SYSTEM TWISTED SHEILD INTERCOM MASTER STATION CABLE (NEW BOOKING) JI TO COMPUTER -- - ROOM SERVER -- - - - - - - I I EXISTING CABLE I I I I r tic IC IC IC IC IC TEMPORARY INSTITUTIONAL CALL STATION PUSHBUTTON STATION (TYPICAL) (5) 2 WIRE TWISTED SHIELDED CABLE BELDEN 6342FE (TYP.) INTERCOM RISER DIAGRAM NOT TO SCALE 14 QAU-2 EXISTING PELCO VIDEO SWITCHER AT CENTRAL CONTROL. (2) 4" C. JUNCTION BOX (5) RG-59/U- BELDEN 82241 LOAD SUMMARY: MAIN SWITCHBOARD "MDP-i" EXISTING CONNECTED DEMAND LOAD = 1,328KW NEW DEMAND LOAD = 1,353KW 1,353KW =(480x r3) = 1,630amps 3000AMP RATED MAIN FUSED SWITCH DISTRIBUTION BOARD "CDP-2A" EXISTING CONNECTED DEMAND LOAD = 484KW 864KW _ (480xr 3) = 1040amps 1200AMP RATED FUSED SWITCH DISTRIBUTION BOARD EXISTING CONNECTED "CDP-2C" DEMAND LOAD = 464KW NEW DEMAND LOAD = 498KW 498KW _ (480xv-3) = 589amps 800AMP RATED FUSED SWITCH EMERGENCY GENERATOR EXISTING ACTUAL MEASURED LOAD = 120KW NEW DEMAND LOAD = 130KW 13OKW 830 KW EMERGENCY GENERATOR (8) RG-59/U BELDEN 82241 EXISTING PELCO VIDEO SWITCHER AT COMPUTER ROOM 16 CAMERA B&W VIDEO MULTIPLEXER AT CENTRAL CONTROL 4 CAMERA B&W VIDEO MULTIPLEXER AT CENTRAL CONTROL (9) RG-59/U BELDEN 82241 R R R R R R R R R vmv■o■o■m R R R R R mmummonsip NR NR R R R CCTV RISER DIAGRAM NOT TO SCALE NOTE: CAMERAS SHALL BE POWERED FROM SAME PHASE PHASE AS CENTRAL CONTROL MONITORS. Y R = RECORDING NR = NON -RECORDING m U 0 q 0 co rn o w > = z Z a g Q c� o 4i � U � 0 W M a UJ IL O W 06 (j) TO O CD CD Vw � Q Z = �N � c \ • U CON M N_ cI V Z!� W N I Qn O C/) N W w z = W I—UQ CD o z CD Q CD W ��i _ Q cn- z CDCD � U � Q � U CCD z ICI U LLJ �U(n 0 � Q SHEET NUMBER E- 6 OF 7 n 120/208 VOLTS 3 PHASE 4 WIRE PANEL B1 100 AMPS MLO OPTIONS: 100 AMP BUS AIC EXISTING SURFACE MTG NEMA 1 TYPE NEHB KVA PHASE I KVA OTHER REC LTG LOAD BK JPL A B CIPLI BK LOAD LTG REC OTHER MECH. RMS. LTG. 1 20 1 X 2 1 20 STRIP SEARCH LTG. RECEPT 1120 3 X 4 t 20 RECEPT. RECEPT. t 20 5 X 6 1 20 RECEPT. RECEPT. 1 20 7 X 8 1 20 RECEPT. RECEPT 1 20 9 X 10 1 20 RECEPT. RECEPT, 1120 11 1 X 12 1 20 RECEPT. RECEPT t 20 13 1 X 114 1 20 LOBBY WATER FOUNT. RECEPT. 1 20 15 1 X 1 16 t 20 RECEPT. 1.08 1.00 RECEPT. 1 20 17 1 XI 18 1 20 EF-BOOK 0.10 3.00 EWH-1 1 20 19 X RECEPT. 1.08 21 X1321C 23 25 X 27 X29 31 X 33 X 34 35 36 37 X38 39 IX 40 SPACE 41 42 ISPACE 3.00 1.00 1 0.00 1 SUB TOTALS 0.00 2.16 0.10 TOTAL CONN. KVA 6.26 TOTAL DEMAND KVA 6.26 CONNECTED KVA 0.00 3.16 3.10 VOLTAGE 480 DEMAND FACTOR 1.25 1.0 1.0 DEMAND AMPS - -- 7_53 DEMAND KVA i 0.00 3.16 3.10 ♦.u„ uv[fu sfuuL,u .1 &K"o t"RVJGVI. 277/480 VOLTS 3 PHASE 4 WIRE PANEL 82 100 AMPS MLO OPTIONS: 100 AMP BUS AIC EXISTING SURFACE MTG NEMA 1 TYPE NEHB KVA PHASE I KVA OTHER REC LTG LOAD BK PL A B C PL I BK LOAD LTG REC OTHE SALLY PORT LTG. 1 20 1 XI 2 1 20 SPARE SALLY PORT LTG. 1 20 3 X 4 1 20 BOOKING LTG. ELECT. RM. LTG. 1 20 5 X 6 1 20 PERS. PROP. LTG. PROPERTY STOR. LTG. 1 20 7 X 8 1 20 HALL #2 LTG. CLASSRM. LTG. 1 20 9 X 10 1 20 LIBRARY LTG. EXTERIOR BLDG. LTG. 1 20 11 X 12 1 20 EXIT LIGHTS HALL #3 LTG. t 20 13 X 14 1120 BOOKING ADDITION LTG 0.58 SPARE 1 20 15 X 16 1 20 BOOKING ADDITION LTG 0.98 SPACE 17 X1 18 1 SPACE 19 X 20 211 X 22 23 X 24 25 X 26 27 X 28 29 X 30 31 X 32 33 X 34 35 IX136 37 X 38 39 X 40 SPACE 41 1 IX142 ISPACE 0.00 0.00 0.00 I SUB TOTALS 1.55 0.00 0.00 TOTAL CONN. KVA 1.55 TOTAL DEMAND KVA 1.94 CONNECTED KVA 1.55 0.00 0.00 VOLTAGE 480 DEMAND FACTOR 1.25 1.0 1.0 DEMAND AMPS 2.33 DEMAND KVA 1.94 0.00 0.00 '11Z" LVe A VL kj 114 1R1J rlcujLul. 277/480 VOLTS 3 PHASE 4 WIRE PANEL BE2 100 AMPS MLO OPTIONS: 100 AMP BUS AIC EXISTING SURFACE MTG NEMA 1 TYPE NQOB KVA PHASE I KVA OTHER REC LTG LOAD BK PL AlB IC PL I BK LOAD LTG REC OTHER 0.62 SALLYPORT LTG. 1 20 1 X 2 1 20 BOOKING HOLD CELL LTG. HALL #2 LTG. 1 20 3 1XI 4 1 20 HALL #3 LTG. BOOKING LTG. 1 20 5 X 6 t 20 EXTERIOR BLDG. LTG. 0.53 PERIMETER LTG. 1 20 7 X 8 1 20 PERIMETER LTG. PERIMETER LTG. 1 20 9 X 10 1 20 PERIMETER LTG. PERIMETER LTG. 1 20 11 X 12 1 20 PERIMETER LTG. PERIMETER LTG. t 20 13 IX 14 1 20 PERIMETER LTG. HALL #3 LTG. 1 20 151 X 1 16 t 20 SPACE 0.86 BOOKING ADDTION LTG. 1 20 17 1 1 IX 18 t 20 BOOKING ADDITION LTG. 0.58 19 1XI 1 20 3 20 EF-M 0.44 21 1 1XI22 --- ---- 0.44 231 1 IX 24 -- ---- 0.44 251XI 26 27 IX 28 29 X 30 31 X 32 33 X 134 35 X 36 37 X 38 39 X 40 SPACE 41 X 42 0.00 1 0.00 F 1.49 SUB TOTALS 1.10 0.00 1.32 TOTAL CONN. KVA 3.91 TOTAL DEMAND KVA 4.55 CONNECTED KVA 2.59 0.00 1.32 VOLTAGE 480 DEMAND FACTOR 1.25 1.0 1.0 DEMAND AMPS 5.48 DEMAND KVA 3.23 0.00 1.32 -AZ" LVAD AUUY:IJ 114 '1H1J Vl{UJEU'1'. 120/208 VOLTS 3 PHASE 4 WIRE PANEL BE1 100 AMPS MLO OPTIONS: 100 AMP BUS AIC EXISTNG SURFACE MTG NEMA 1 TYPE NQOB KVA IPHASE I KVA OTHER REC LTG LOAD BK PL AlBICI PL BK LOAD LTG REC OTHER ARMORY LTG 1 20 1 X 1 1 2 3 20 SALLYPORT R U G #2 SALLYPORT R U G #1 3 20 3 X 4 -- ----- ----- -- 5 X 6 ----- ----- -- 7 X 8 3 20 SALLYPORT R U G #4 SALLYPORT R U G #3 3 20 9 X 10 -- ----- ----- 11 X 12 ----- -- 13 X 14 1 20 ISMOKE EVAC. UNIT SMOKE EVAC. UNIT 1 20 15 IX 16 t 20 SMOKE EVAC. UNIT SMOKE EVAC. UNIT 1 20 171 1 X 18 1 20 SMOKE EVAC. UNIT SMOKE EVAC. UNIT t 20 19 X1 20 1 20 RECEPT. 1.08 LTG. RELAY PANEL 1 20 21 IX 22 1 20 RECEPT. 1.08 SPARE 1 20 23 1 X 24 t 20 MINIPLEX POWER 0.01 CCTV CAMERAS 1 20 25 XI 26 1 20 CCTV CAMERA 0.01 CCTV CAMERAS 1 20 27 IX, 28 t 20 CCTV CAMERA 0.01 CCTV CAMERAS 1 20 29 1 IX 30 1 20 CCTV CAMERA 0.01 CCTV CAMERAS i 20 31 X 32 1 20 CCTV CAMERA 0.01 CCTV CAMERAS 1 20 33 X 34 1 20 RECEPT. 1.08 1.20 DIE BOLD SYSTEM 1 20 35 X 36 1 20 RECEPT. 0.36 GATE CONTROL PANEL 1 20 37 X 38 39 X 40 L.86O6 SPACE 41 X 42 SPACE 0.00 0.00 SUB TOTALS 0.00 3.60 0.00 TOTAL CONN. KVA 5.46 TOTAL DEMAND KVA 5.46 CONNECTED KVA 0.00 3.60 1.86 VOLTAGE 480 DEMAND FACTOR 1.25 1.0 1.0 DEMAND AMPS 6.57 DEMAND KVA 6.00 3.60 1.86 -Ncn LUAU AU1Jt51J 1N '1'H1J YRUJECT. 277/480 VOLTS 3 PHASE 4 WIRE PANEL A C-B 225 AMPS MLO OPTIONS: 225 AMP BUS AIC EXISTING SURFACE MTG NEMA 1 TYPE SIEMENS ITE KVA PHASE I KVA OTHER REC LTG LOAD BK PL AlBICIPLI BK LOAD LTG REC OTHER 5.50 RTU-A 3 35 1 X 1 2 3 35 RTU-B 9.10 5.50 ---- -- 3 X 1 4 -- - - - - 9.10 5.50 ---- -- 5 XI 6 -- - - - - 9.10 5.20 RTU-L 3 35 7 X 1 8 3 35 RTU-D 6.60 5.20 ---- -- 9 X 110 -- ---- 6.60 5.20 - - - - 11 X 12 -- ---- 1 6.60 6.60 RTU-3 3 35 13 X 14 3 35 RTU -F 6.60 6.60 ---- -- 151 IX 16 -- ---- 6.60 6.60 ---- -- 17 X 18 -- ---- 6.60 19 X 20 1 20 SPARE 21 X 22 3 35 RTU-M 8.60 23 IX 24 -- ---- 8.60 25 X 26 -- ---- 8.60 27 X 28 29 X 30 31 X 32 33 X 34 35 X 36 37 X 38 39 X 40 41 X 42 51.90 0.00 0.00 SUB TOTALS 0.00 0.00 92.70 TOTAL CONN. KVA 144.60 TOTAL DEMAND KVA 144.60 CONNECTED KVA 0.00 0.00 144.60 VOLTAGE 480 DEMAND FACTOR 1.25 1.0 1.0 DEMAND AMPS 173.93 DEMAND KVA 0.00 0.00 144.60 'NEW LUAU ADDED 1N THIN YROJECI'. EXTENDED EXISTING CIRCUITS (10) #16 - (TYP EACH DOOR) SALLYPORT SLIDING DOORS EXISTING CONTROL PANEL (2) #12, (1) #12 GND, 3/4" C. NEW CONTROL PANEL BE1-37 (27) #14 IN 1" C. NEW - EXISTING MX CONTROL PANEL JUNCTION BOX (10) #14 - 47TT (7) #14 IN 3/4" C. IN 3/4" C. VESTUBLE SLIDING SALLYPORT DOORS SWING DOOR EXISTING SALLY PORT GATE CONTROL CIRCUITS (10) #16 IN 1"C. (TYP. EACH GATE) UPPER LIMIT SW SALLYPORT LOWER SWING DOOR LIMIT SW (TYP) EXISTING SALLY PORT - GATE POWER CIRCUITS * (3) #10 IN 3/4"C. (TYP. EACH GATE) 8F10,12) 9F(11,13) 2F4,6) 3F5,7) NEW SALLY PORT GATE OPERATORS DOOR CONTROL RISER DIAGRAM NOT TO SCALE EXISTING FIRE ALARM CONTROL PANEL "FACP" (SUPPLY DUCT) EF-M TO REMAINING SMOKE DETECTORS. TO REMAINING FIRE ALARM PULL STATIONS i FIRE ALARM RISER DIAGRAM NOT TO SCALE GENERAL FIRE ALARM RISER NOTE5• 1. THIS DRAWING IS FOR REFERENCE ONLY FOR TYPICAL ARRANGEMENT. (RETURN DUCT) Z a 0 Q 12 �a w� �a 0 F M W cc FL r w I o m� 0 co co F- Oo CD U W - Q mUmN m cM r zw LLIy I a og cl) w z = W I-UQ 0 C) 00 o�-'L� L� < Cr� o z IL-L-JU� 0 _j Q�-U z LLJ = U zCD� 0 ~ W U 0 � Q SHEET NUMBER E- 7 OF 7 U n 0 �+ o r� rncn 3/4" 8w 4" RWLA EXIST. RD HB REMOVE EXISTING HOSE BIBB AND CAP PIPING BELOW GRADE. EXIST. RD ^8• Z--8rr 4" RWL REMOVE EXISTING J 7- STORM PIPING ABOVE CEILING AND CAP BELOW GRADE. CO �8" 4" CO DEMO FLOOR PLAN - PLUMBING SCALE: 1 /Bw = 1'-Ow rn rn I ID N I 0 5 a w o It In Z m e Q IL c w u 'R Uc fr - J W \Mw/ a MW (L 0 W R� w z = w 0 o z � 00 z � � o Qryr� � o z LUG o > U Q � o C) U 0 � Q � V) SHEET NUMBER P-1 O 3 PLUMBING FIXTURE SCHEDULE: LAVATORY L-1 (WALL HUNG FIXTURE: ELKAY #ELV-2219, TYPE 302, SEAMLESS 18 GAUGE STAINLESS STEEL, 8" CENTERS, WALL MOUNTED WITH BACKSPLASH. FAUCET: CHICAGO 404A-317-E12VP CHROME PLATED BRASS FAUCET, VANDAL PROOF AERATOR. P-TRAP: McGUIRE 8872 HEAVY CHROME PLATED CAST BRASS, 1-1/4" ADJUSTABLE P-TRAP, CLEANOUT, SLIP NUT, 17 GA. TUBULAR BRASS WALL BEND AND BRASS FLANGE, SUPPLIES: McGUIRE H2165 SERIES, HEAVY CHROME PLATED BRASS ANGLE STOP WITH (LOOSE KEY OPERATOR), CHROME PLATED RISER AND FLANGE. DRAIN: McGUIRE 155-A CHROME PLATED BRASS FLAT GRID STRAINER AND 1-1/4" TAILPIECE. DOMESTIC WATER SPECIALITIES• INSTANTANEOUS WATER HEATER EWH-1, CHRONOMITE S-30LP, 3.0 KW, 208V, 10, 60Hz. Lee ST. LUCIE CO. CORRECTION CENTER No.: 98003 Sims Wilkerson Engineering, Inc. BY: R.D.P. 1556 Howell Branch Road, Suite A-1 DATE: 5/5/99 Winter Park, Florida 32789 SCALE: 1 8"=1'-O" (407) 645-1586 FAX (407) 645-2399 DWG. No. P-2(SK-2) EXISTING ` ROOF DRAIN 4" RWL DOWN' TO BELOW GRADE EXISTING ROOF DRAIN CONNECT NEW- 4" RWL INTO EXISTING ABOVE CEILING. 4"RWL DOWN TO BELOW GRADE. 4" RWL UP- 1/2" TO 4" RD SAN SAN CONNECT NEW 1/2" CW INTCNSTANTANEOUS WATER -/ EXIST. ABOVE CEILING. FIELD WH1 UNDER LAVATORY VERIFY EXACT LOCATION 0 1 CONNECT NEW 3' SANITARY LINE INTO EXIST. BELOW GRADE. FIELD VERIFT EXACT LOCATION CONNECT NEW 3/4" CW LINE INTO EXISTING BELOW GRADE FIELD VERIFY EXACT LOCATION CONNECT NEW 4" RWL INTO 8" BELOW GRADE FIELD VERIFY EXACT LOCATION EXISTING CLEAN -OUT TO REMAIN. L-1 1/2" CW DN WITH 1/2" CW TO LAV. & 1/2" CW TO EWH-1 4" 4" CONNECT NEW 4" RWL INTO EXISTING BELOW GRADE. FIELD VERIFY EXACT LOCATION OFLOOR PLAN - PLUMBING SCAM: 1 /8" = 1'-0" 4" RWL UP TO 4" RD (TYP. OF 4) U c a a Cr �N b U .. L �U�yy FI � ,y y O � W O mm n C N N 0P4`' U �o'+ � rl oaf max,, �' U) t mm 0 w Y a W 0 U TIm F—CC �U O W� U C� Q Z_= � MU m W w m of of Z W � A N C) z�LL_ o III o z C) Q � U C:6 = U zQ� 0 U Q F-- SHEET NUMBER P- 2 OF 3 O fo/ 4" RD PLUMBING ROOF PLAN SCALE: 1/4" = 1'-0' EXIST. RD EXIST. RD 4" RD l / 4" RD 4" RD 4" RD 4" RD Z 0 Q � �a L o U � W M M cc a W Uj (L o m 06 ca 00 ~OV o U W� m�-Q Z gN my M ti m I �� W F— Q s g %1 N w z �z-UQ 0 o zrK 00 z�LL- o Qr� woz O Q \ U � C U zCD� 0 i=-w� oU � � Q cn SHEET NUMBER P- 3 OF U o q � ►-4 c N b H U� Q I y 00 w m o NCc, go CN N 0Ki M I q o04 w mw � ko ,p.4 to r- U)l or 5 EXISTING MAIN PIPING TO REMAIN r'APPING AT IN (TYPICAL) EXISTING SPRINKLER `RISER TO REMAIN .t I REMOVE EXISTING SPRINKLER PIPING AND HEADS IN THIS AREA. DEMO FLOOR PLAN - FIRE PROTECTION SCALE: 1/8" = l'-0" Z a 0 �a Lo wLo U m r� V W M a UJ W •- 0 00 �U O CD U w� C1) f- Q Z= MN iMm W z p za Lij V) Q _ 0 � n C/ / N w z = w H- U Q 0 o z � 00 z t W Q � H— n, o z � U � O Q U � z LLJ zCDJ 0 w� U % SHEET NUMBER F-1 OF 2 EXISTING TO REMAIN EXISTING TO REMAIN .er FLOOR PLAN - FIRE PROTECTION SCALE: 1/4' = 1'-0' u 0 0 U rD 0 0 00 I y� t tw y tj y W co Co. t` C N N Oa"' m m qb, jy U •[ n 4 ml rl i N P-4 J o a wi o CD m I 04 N i M 5 a w o cr Z o Q � Qton U � `J w a w CL o m 06 � cv O CD CD C) W C1) a Z mU m N n z� W N� Qo 0 o V_ `^ / w z 0 o z � 00 z~� o� w � CD LLJ o Q�U � � U zCD� 0 U � � Q H— SHEET NUMBER -2 2 STa L OCO1��ECTfONf�L CENTER STo L i E COUNTY, FLO 'I DA E)T, LUCIE COUNTYI [30ARD OF COMMISSIONERS JOHN P,, [3RUHN, P15TRICT 1 DOUG COWAgP) P15T1ZICT 2 F'AULA A. LEV/15, P15TR FP--.ANNIE HUTCHIN50N, P15TR CLIFF ICT .5 ST. LUCIE COUNTY IRE DISTRICT FO, �aR COMPL, I� E +p— >rF_ r�TT S�FIN L, F_ Z] T DTI-01v BATE: COmplfanca to: 1. NAP.A. 101 -w-+: 2. Standard Building Code S. State Fire Marshal Rules . 4. Local Fire Codes SEE ATTACHED DEPARTMENT WRITE UP ARCHITECT AND ENGINEER5 2400 RFIDDE ISLAND AVE. TELEPHONE: (561) 462.2312 FT. P=QE, FL 34950 -. FAX: (561) 462-2325 [3ARN5) 5TEDDIN5, SCOTT & DERGM ARCHITECTS, F.A. CULFEFTER & TERFENING, I CIVIL ENGENEERS D15TR N, O'DONNELL, NACCARATO & MIGNOGNA, STRUCTURAL ENGINEERS C. SIMS WILr,.ER50N ENGINEERING, INC., MECHANICAL, ELECTRICAL ENGINEERS INDEX TO PKI ,�'. CIVIL 1 OF i PAVING 4ND DRAINAGE - smucrLw 5-i oP 4 F<)UF 4Tk N PI.AN 52 OF 4 ROOF, :2AMI➢ ti PLAN '-30- NO,E5,I-Fr"!L5 5.4OF4 WALL5t ;iOHi ARCHrRCr�s, 1-2 OF s FLOOF' '°LAN _ A-3 OF 12 FURNITURE PLAN A-4OF 12 ROOM FINl-z�,H SCHEDULE. EXTERIOr1 A-5 OF 12 INTFr (1r E W A.TIONA. FiENCH 9F'# A 6 OF 1^. !':TERf 't ELLV,1'.TION5. CABINET Df A OF'? COO? A 'D W�: ,�`CIW 5CHEDULE, X A-NF')F i2 J OL<nE,AP5 A-9')F t° WA,,. Er.:TION5 A-10 jr !2 Wr'.i L 5ECT;ON5 A-1 - 12 A : 5FCTION. A-1 r l WP'-L :,E 7ON-a ".? All 3 a1FCHA1111- FLOCK. PLAN M2 aFy ivtECY,.ANIG'AL ROO!, F' AN SGn. ' M•u OF •` .ZCHANICAL 5MU GHELES. rk _ ELECTKXPn E-1 OF 7 '', ELFC:' AL . PLAN E-2 OF } I ,,LECTkICAL DF'AO:ITION FLOOR PLA,. E-3 01 "1 LIGH (ItJG FI OOtr PALN `4 \- 7 POV:-E2. AN"3Y5TEM5 FLOOR PLAN E-5 O1- 7 4G"TIN," PROTECTION PLAN, DETAIL5 E-6 OF 7 PR9t ER R15ER CAr+.0 KAM E-7 OF r -A JI BOARD 5CHEOULES PLUMBING P ' 3 .UMBIJG r)C4, )51TION FLOOR PLAN5 P-2 OF d PLUMBING FWnP PLAN P 3 OF ? PLOMOING r..)OF PLAN FIRE PROTECTION F-1 QF .' FIRE ' .OTECTION DEMOLITION FLOOR PI Ak F-2 OF c 4IRE Pk V';' 71C" FLOOR PLAN st. wcm oourrn a UX4wnaa+ Rt . 1 11 8 5 roe cm rm"mrvv"ww INDIAN RIVER COUNTY V) 2 HOLES FOR NO. 5 BARS 12" FROM EACH END 2" 45'0'0" 2- 3 BARS, 5-6- LONG 6„ NO. 4 BARS. 18" LONG (2) EMBEDDED IN PAVEMENT A - A WHEEL STOP DETAIL PARKING STALL - 6' A A TYPICAL PARKING STALL e I N SLOPE -6' CEMENTED COQUINA BASE COAC T TO 9811 OF MAXIMUM DENSITY AS PER MSMPHTO ISO 6" STABILIZED SUBGRADE (MIN. 75 P.S.I., F IS V.) COMPACTED TO 98% OF MAXIMUM DENSITY PER AASHTO T-180 TEMPORARY ROAD SECTION SECTION "A -A" 8" 6" -I3 4" R d JOINT SEAL to 2" R ° PAVEMENT ° SECTION d d d co ° BASE d d ° 1/2" EXP. JOINT ° °� d SUBGRADE d d JOINT FILLER WHEEL STOP "D" CURB GENERAL NOTES All paved areas shall meet the requirements of AASHTO Specifications, FDOT and St. Lucie West Utilities and shall be constructed to the typical sections as shown on the plans. The Contractor shall retain the services of an Independent testing laboratory to conduct all required testing and retesting to comply with these Specifications. The Owner shall bear the cost of Initial testing and the Contractor shall correct any deficient work at his own expense. A. Asphaltic Concrete: Asphaltic concrete materials and construction methods shall meet the requirements of FOOT Sections 300, 320, 330 and 331 and shall be Type S with a 2" thickness. Prime Coats shall meet the requirements of FDOT Sections 300-1 through 300-7 and shall have an application rate of 0.10 gallons per square yard, unless a variation rate Is approved by the Engineer. Asphalt shall be placed in two (2) lifts. The first lift shall consist of 1-1/4" of Type S-1(mod). The second lift shall consist of 3/4" Type S-III. B. Base: The base course shall be 8 Inches of compacted Ilmerock for the loop road, residential road and the cul-de-sac as shown on the typical sections on the plans. The base shall be compacted to 98 percent of the maximum density as determined by AASHTO T-180. I for C. Subgrade: The subgrade shall be 12 Inches thick o the loop road residential road and the cul-de-sac and shall extend six inches beyond the edge of the base course within the limits shown on the plans. Subgrade shall be compacted to 98 percent of the maximum density as determined by AASHTO T-180. If normal compaction methods do not meet the required densities, the subgrade shall be stabilized as directed by the Engineer. D. Type "D" Curb: Concrete type "D" curb shall meet the requirements of FDOT Section 520 and shall be constructed to the typical section as shown on the plans. E. 8' Concrete Sidewalk: 8' concrete sidewalk shall meet the requirements of FOOT Section 522 and shall be constructed to the typical section shown on the plans. F. Painted Traffic Striping: Painted traffic stripes shall meet the requirements of FOOT Section 710. 6" wide white stripes shall be used for the centerline and edge -of -pavement. G. Stop Sign and Bar: Stop signs and bars shall meet the requirements of FDOT Section 700 and the Manual of Uniform Traffic Control Devices and shall be constructed in the locations as shown on the plans. H. Clearing and Grubbing: Clearing and grubbing shall meet the requirements of FOOT Section 110 and shall be performed within the limits of the project work. This work shall include, but is not limited to, the removal of existing trees, brush stumps, roots and other objectionable material to a depth of 18 inches below the natural ground or design grade, whichever Is lower. The areas to be cleared and grubbed generally consist of rights -of -way, utility easements, water management tracts, and portions of the lots as detailed on the plans. The Contractor shall confirm with the Owner the removal of any trees on the lots for possible preservation. All material shall be removed from the site of the project and shall be disposed of in accordance with local, regional, State and Federal laws, regulations and ordinances. There shall be absolutely no clearing and grubbing or placement or removal of material from within the area designated as "Wetland Preserve" or their buffers. 1. Rough Grade: The Contractor shall grade the rights -of -way and lots to meet the requirements of FDOT Sections 110 and 120 and shall conform to the lines, grades, and typical sections as shown on the plans. J. Fine Grade: The Contractor shall fine grade the roadway to meet the requirements of FOOT Sections 110 and 120 and shall conform to the lines, grades and typical sections as shown on the plans. K. Sod: Sad shall meet the requirements of FDOT Section 570, 575, and 981 and shall be placed adjacent to the curbing for a minimum width of 24 inches. L. Seed and Mulch: Seed and mulch shall meet the requirements of FOOT Sections 570, 575, and 981 and shall be placed in the rights -of -way and all disturbed areas. EXISTING FENCE TO EXISTING FENCE TO REMAI KI TYPE "D" CURB %-1 1/2" TYPE S-1 ASPHALTIC CONCRETE 8" CEMENTED COQUINA BASE COMPACTED TO 98% OF MAXIMUM DENSITY AS PER AASHTO T-180 12" STABILZED SUBGRADE (MIN. 75 P.S.I., F.B.V.) COMPACTED TO 98% OF MAXIMUM DENSITY AS PER AASHTO T-180 TYPICAL ROAD SECTION SECTION "B-B„ EXISTING BUILDING e- 66, 1.00% 1 1.00% mmmmmmommmi— 1-6 `t" TYPE S-1 ASPHALTIC CONCRETE 6" CEMENTED COQUINA BASE COMPACTED TO 982 OF MAXIMUM DENSITY AS PER AASHTO T-190 8" STABILIZED SUBGRADE (MIN. 75 P.S.I., F.B.V.) COMPACTED TO 98% OF MAXIMUM DENSITY AS PER AASHTO T-180 TYPICAL PARKING LOT SECTION SECTION "C-C" AW CUT EXISTING PAVEMENT AND MATCH EXISTING GRADE / EXISTING ASPHALT AND CURB TO BE REMOVED --r ENTRANCE / EXISTING ISTING SALLY PORT 1 NEW SALLY PORT F.F.E. 22.00 V 1 1 /2" STEP -DO 7 21.87 �\ EXISTING FIRE REMAIN RANT TO / / ' /' \ \ ryO NG 7_ �P /Pv/ 'Lc6/ /+\/ i a0. i \ °22.QOi i x TO REMAIN x � � x x NEW ENTRANCE TO S/ EXISTING FENCE TO REMAIN (SEE SECTION B- TEMPORARY ROCK ROAD (SEE SECTION A -A) x APPROXIMATE LOCATION OF BACK FLOW PREVENTER VERIFY LOCATION AND RELOCATE IF NECESSARY PROPOSED PAVEMENT ELEVATION --X- ---X— --ir X --X X —X— mac— EXISTING FENCE TO REMAIN x _EXISTING 6" PVC WATER MAIN / I— � EXISTING PVCJ_RE MAIN 1.87 x d u � 4CONSTRUCT NEW x\ j TEMPORARY FENCE x I Ij / j (BY OTHERS - NOT A / PART OF THIS CONTRACT) 50' R. EXISTING FENCE TO BE OVED BY OTHERS - NOT A PART OF THIS CONTRACx I 1 \ 'x 1 x X \ \ 30 x ` \ P 21.7 x- EW FENCE BY OTHER- x— x NOT A PART OF THIS CON ACT —! -- — \ I rya \ x x - \ v�i EXISTING GATE L,um ru ILK FILE REF. FIELD BK./PG. 8967ADD DWG CULPEPPER & ............ ........ I .................. ...... C .. . .... TERPENING,INC. ..... .............................. ... .... I ...... E 140 SAW CUT EXISTING PAVEMENT AND MATCH EXISTING GRADE 21.50 TT-1 F TT \t�21. / SAW CUI EXISTING PAVHMENT / AND MATCH EXI TING G ADE \\/1 EXISTING PARKING LOT Xv- \ k2l $_ SAW CUTI EXISTING PAVEMENT LOCATION MAP EXISTING TYPE "C" INLET TOP EL. 20.97 S. INV. 17.11 7.11 . N. INV. 17.10 18" RCP //qD MAT H EXIS NG GRR DE _. EXISTING TYPE "I" INLET JJ�_ _I L_ I TOP EL. 21.62 S. INV. 17.39 N. INV. 17.36 EXISTING PAVEMENT ELEVATION 18" RCP �.29 (TYPICAL) 2? j7 _ EXISTING TYPE "I" INLET 22.08 TOP EL. 21.62. \ , 24' 22.00 S. INV. 17.— 1\YIL-/ N. INV. 17.26 26 & PAVEMENT ELEVATION (TYPICAL) 18 RCP I-T�I- II I I I I I U I + z15 21.55 EXISTING TYPE "C" INLET TOP EL. 21.27 / ❑ N. INV. 17.80 �V MATCH EXISTING EXISTING PARKING LOT PAVEMENT ELEVATION L� I - BENCHMARK TOP OF GRATE EXISTING CATCH BASIN ELEV. - 21.27 —�_ X CONSULTING ENGINEERS - R E V I S 1 0 N S - BY DATE IBY DATE SALLY PORT PAVING AND DRAINAGE PLAN DESIGNED R L 12-30-98 & CALCS. ............ FOR LAND SURVEYORS .. ........ DRAWN D.F. 12-30-98 2980 SOUTH 25th STREET FORT PIERCE, FLORIDA 34982 ..._.... .... DETAILED .. ._ .. ST. LUCIE COUNTY CORRECTIONAL FACILITY (561) 464-3537 CHECKED R L 1-4-99 APPROVED rDATE:12-30-9820' SHEET OF 1 SEE NOTE #1 DRILL & EPDXY HORIZ. REINF 6" INTO EXISTING FTG. (TYP) SEE NOTE 1 SEE ARCH'L DWGS FOR EXISTING WALLS BEING REMOVED 32'-8" 3'-4" 10'-0" 1'-4" 3'-4" 1'-4" EXISTING FTG SEE NOTE 1 3'-4" 8" 5'-4" 8" 5'-4" EXISTING FTG 8" 5'-4" 0 I SEE NOTE #4 SEE NOTE #4 SEE NOTE #4 ao N 4" t CONC SLAB OVER EXISTING 6" SLAB ON GRADE W/ 6x6- W1.4xW1.4 WWF OVER ROUGHENED SURFACE & BONDING AGENT a APPLIED TO EXISTING. a 8" 3'-4" 4% 'a LD I N F N 5 - SEE NOTE 1 5, - 4» EXISTING 2'-4'xt'-O" FTG 0 I o OD I Z I w • °0 0 I 4'-0" 8" 2'-8" I -t 8'-B" `O a I J w a1 O Z z n uj vWi EXISTING FTG 10'-0" 3'-4" SEE NOTE 1 FTG 0 co S. 4'-B" 1 5'-4" 33'- 4" 1'-4" 4'-0' 1'-4" 10'-8" 2'-8" SEE NOTE t� ----_.1------- .- ----------------�1. • ----_ -- --- I —— — — — — — — — — — — — — — T.E. T.E. F24.12 DRILL & EPDXY HORIZ. REINF _ — 6" INTO EXISTING FTG. � I s-a I w I 0 1 _x I I N I co z i In N 5 I I 3 m I o I �2 10'-0" I'SLa - I I _ I • I I SEE NOTE 1 6" CONC SLAB ON GRADE I w/ 6x6, W1.4 x W1.4 WWF - � ON 6 MIL VAPOR BARRIER N SEE NOTE 1 ? ON COMPACTED TREATED c SUB -SOIL (TYPICAL) C14 EXIST NIG 2'- x-0 TG rJ I I DRILL & EPDXY HORIZ. REINF. I I I I 6" INTO EXISTING FTG. I II 218 I , 1,-4" 3'-4„ e» 1 IIn "' L 75-1 201 0 4" CONC SLAB ON GRADE . ` o z w/ 6x6, W1.4 x W1.4 WWF I- I II _ w ON 6 MIL VAPOR BARRIER S-a 1 T1 "1 m i� ON COMPACTED TREATED I II SUB -SOIL (TYPICAL) I II I I I I co 1 I I• I I o —TS-' I I � Co ---- . — I I I — --------- I I I "k I rI I N I I w I I I I 1 ♦ s-a I I I I I of 1 In I IN I I o j I 6 I I~ of I I~ 7 I I s_a I S-3 I I 00 4 EXISTING SEE NOTE 1__— — FTG I 1 I I I I F24.12 _J L_ -J • T.E. T.E. T.E. °° — — — — — — — — — — -------------- *'--I TIT �1I1 1 ---------------------------------------- — ---- —-------- --- --- I I I I I F24.12 2-8" _ _ _ _ _ 10'-B» _ _ _ _ _ -4 4'-0" -4' 0'-8" 2'-8° ' SEE NOTE 1 33'- 4" 00 I I I I i I I m 4v ry l l 1 1 NI �I r l I I I cl I I DRILL & EPDXY HORIZ. REINF. 6" INTO EXISTING FTG. 1 L—_ F24.12_J I I L_ I I I sa 1 I TS-1 OVER STEM WALL L- _ _ _ _ _ _ _ _ _ _ _ J &STRIP FOOTING. FOUNDATION PLAN 9' - 4" SEE NOTE 1 fOUNDATION NOTES: 1.) PROVIDE MIN. 16ga CORRIGATED MASONRY TIES O 16" O,C. ATTACHED TO EXISTING MASONRY W/ (1) 3/16"x1 1/4" TAPCON. ALTERNATE W/ HORIZ. A REINF. TYP. AT INTERSECTION OF EXISTING MASONRY AND NEW MASONRY. 2.) DRILL AND EPDXY MASONRY WALL REINFORCING 6" (4" THRU NEW TOPPING + 2") INTO EXISTING WHERE NEW MASONRY SITS ABOVE EXISTING SLAB ON GRADE. 3.) ALL MASONRY TO BE W-1 (U.N.0) 4.) INTERIOR NON LOAD BEARING WALLS ADJACENT g OPENINGS WITH ONLY 8" OF MASONRY BETWEEN TO HAVE CONTINUOUS "U" BLOCK LINTELS W/(2) #5 BARS. EXTEND TO CONTINUE UNTIL 8" BEARING EACH END IS ACHIEVED. (MAX. CLEAR OPENING 6'-0"). USE 16" DEEP "U" BLOCK W/(2) #5 BOTTOM, (1) #5 TOP FOR CLEAR OPENINGS UP TO 10'-0". — O'DONNELL, NQOCG RATO &NO STRUCTURAL ENGINEERS- k1b 1665 PALM BEACH LAKES BLVD. SUITE 800 WEST PALM BEACH, FLORIDA 33401 (561) 471 - 5166 JOB # 436.043� Z a :E 0 cc W a E.., �h U W H IA � W U z a � d m `W VI g� a L� w = U Q ~ J OQ� z O__j z i= LL O U F=- Li >= Q ry — cl.,- Q�_'z LLJ �QO J Q � U C�d z U O O U cr) D Q SHEET NUMBER S-'I l OF 4 SEE ARCH'L DWGS FOR EXISTING WALLS BEING REMOVED 0 I M SLAB THICKNESS ® EXISTING = 8" /- EDGE OF SLAB s8a ---- i THICKNESS = 6" �______________� r--r ---, II II II II II II I! II II II II II II II II II II H II n II II I fI II n II II n II II n II II II II II II SEE NOTE F- T- - - 4 - N- II II - I -SEE NOTE �j4 II SEE NOTE p4J i II II I I I I I I s-4 v cj LJ --Tn---- —Z�-`-17 —C�-- --� ;-------- � I I I /l'� il, /i•, I I N II �i II w I I I II II I I Il I I I—i II I I II i t u II II II II 2 II II II II � II I I jT_ S-a I I I LI I I L----------- I i I----- L_.-------- L __..— — _— _— I — —7 1eK6 I I I I II I ® 4'-0" O.C. I I II II a II III II II a -- -- ----- II II T °� ----=--�1 ------�-7 I I (�j""_ ` co i t -,-,---� I I Cr I .l N I _Y- I I - -- ----------- — — — — J__LJ L_ — — — — — — ------------� ---------- ----'- 18K6 L I ® 4'-0" O.C. F-_----� _ 4 r._—..----. I I I I s7a I Lj s- a , - - - - - - - - - -------- - - - - - - - LJ-L----------L--7 -------�-----r=l �s _CZ- ---� --- 1_ -- --___ ROOF PLAN 32'-0" I8"I 33.-4. ROOF DECK: 1 1/2" TYPE "B" 229a GALVANIZED DECK ATTACHED TO JOIST W/ 5/8"0 PUDDLE WELD AT 36/4 PATTERN AND PROVIDE (2) #10 TEK SCREW SIDE LAP FASTENERS. TYP. U.N.O. STRUCTURAL ENGINEERS 1665 PALM BEACH LAKES BLVD. SUITE 80C a WEST PALM BEACH, FLORIDAkll (561) 471 - 5166 A JOB # 436.043 ally A �e z 0 W - m� a cc E, co U p ow V V E� w� /A U z = W co) o� ww = U Q ~ J 0 O `L BOO z F -- O U w Q�� w0� �U01 U Q � F—w D zO� O U w �— D U 0 Q SHEET w'UMBER S-2 OF 4