ST"LUCIE"COUNTY. PLAN REVIEW
ATTN: Andrew
From: Jason Baran with A&G Concrete Pools
Re: Permit#,1803-0808_ .
Erika;
Per your building comments:
Comment 1: Draw_ ings" reference the outdated fbc and nec, please update:.
Response:
1. " The top right of"the-plan above specifications was updated and circled to reference.the" current. Florida Building Code 2017 61, Edition
for Residential:
2. The pool detail was updated and circled to reference. the current Florida Building Code 2017 a Edition for Residential.
3. Swimout:detail was updated to the current F.R:C. 450'118 and Ansi/NSPI-5-2003
4: Equipotential bonding detail was updated to reflect the N.E.C.'2014 Sec. 680.26 and circled:_
5. " Electrical diagram was -updated fro 2.011 code to reflect 2014.code and -circled,
- Comment 2:' 2 electrical diagrams. are on the drawings, please clarify.
Response;
1: " Bottom diagram was removed."There is only one diag am now.
Comment 3. Please clarify general. note #3, does engineer require a geotechnical report to Verify 2500 psf soil bearing capacity, or is the"2500
psf soil bearing capacity assumed.. Please clarify the note, on. the plans.
Response.`.
1. We changed, the verbiage to state that a:2500 psf load bearing capacity is assumed and circled it.:
Comment 4: Please provide product -data for the alarm.
Response:
A cut sheet of.the alarms was printed and resubmitted) with the revised plans.
Comment 6: Please note on the: plans the pool will conform to the.applicable standard, design, construction, and:workmanship, shall be m" "
conformitywith the requirements of the ansi/apspricc3, ansi/apspficc 4, ansi/apsp/icc 5; ansi/apsp/icc 6, and ansi/apsp/icc.7.
Response::
1. The above verbiage was added to the plan and circled.
Comment 6: Please provide piping diagram:
Response:. :.
1. -Since piping was already shown with applicable piping sizes, we drew the runs all the way to.the equipment pad. There was already a
plumbing legend and equipment layout. �
IF YOU HAVE.ANY QUrESTIONS, PLEASE CALL.ME
:.DIRECT AT 772-678-5632: :.
JASON,BARAN