HomeMy WebLinkAboutENGINEERINGCONTRACTOR: TRI-COUNTY AL.' " wUM, INC. •'DESIGN CRITERIA: Applicable Codes, Regulations, and Standards 1. The 6th Edition (2017) Florida Building Code, specifically Chapter 16 Structural Design, Chapter 20 Aluminum, and Chapter 23 Wood. 2. AA ASM 35 and AA ADMI Specifications for Aluminum Structures, Part 1-A of the Aluminum Design Manual prepared by The Aluminum Association. and the AAF Guide to Aluminum Construction in High Wind Areas. 3. ASCE 7-10. Loading Criteria 1. Live Load: 10 PSF per 6th Edition (2017) Florida Building Code, Appendix I Section 105.1 2. Dead Load:-2 PSF 3. Wind Load: 3.1. Building Occupancy Category, Section 1604.5 and Table 1604.5: Risk Category 1. 3.2. Basic Wind Speed, Figure 1609.3(3), State ofFlorida Debris Region & Basic Wind Speed, Section 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Sp VwT =150 MPH. VAsD =116 MPH 3.3. Exposure Category, Section 1609.4.3: Exposure B 3.4. Screen Enclosure Section 2002.4 4. Building Category for Aluminum Structures, Section 2002.6: Category Type 1- Patio Cover / Screen Room: Non -Habitable, Unconditioned Roof Type 1.RoofType: MONOSLOPE 2. Roof Material: 3" x 12" x 0.019" Four Seasons Building Products Steel Rhino Panel, Florida Product Approval Number FL 18464-111. Foundation Design Existing concrete. No additional concrete footing or slab is required to resist the loads imposed upon the existing slab by the proposed construction if the existing slab is a minimum of 4" thick and in sound condition, free from structural cracking, spalling, or other deterioration. Specifications The following specifications are applicable to this project: 1. All work shall be in accordance with the 6th Edition (2017) Florida Building Code, and any other applicable local codes and regulations. 2. Aluminum extrusions shall be 6005 T5 Alloy. Due to quality control issues, no manufacturer substitution is acceptable without the specific written, signed and sealed authorization of Suncoast Aluminum Engineering, LLC. 3. Screen Material: Design based on 18/14 or 20/20 Better View. Any other material must be approved 4. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc plated to ASTM B633, or coated stainless steel series "300", or uncoated stainless steel series "400". 5. All Self Mating Beam Sections are to be stitched with either #14 screws 6" from ends and 24" center to center or #12 screws 6" from ends and 12" center to center. -6.-Where concrete specifications are -required whether in the screen enclosure scope or not, by one or more regulatory agency, the following specifications are applicable: a. Concrete shall conform to ASTM C94 for the following components: i. Portland Cement Type 1,- ASTM C 150 ii. Aggregates - Large Aggregate 3/4" max - ASTM C 33 iiL Air entraining +/- 1% - ASTM C 260 iv. Water reducing agent - ASTM C 494 v. Clean Potable water vi. Other admixtures not permitted b. Metal accessories shall conform to: i. Reinforcing Bars - ASTM A615, grade 60 ii. Welded wire fabric - ASTM A185 c. Concrete slump at discharge chute not less than 3" or more than 5". Water added after batching is not permitted. d. Prepare and place concrete per American Concrete Institute Manual of Standard Practice, Parts 1, 2, and 3 including hot weather recommendations. e. Moist cure or polyethylene curing permitted f. Prior to placing concrete, treat the entire subsurface area for termites in compliance with the FBC. g. Concrete shall be placed over a polyethylene vapor barrier. h. All aluminum components embedded within concrete shall be coated with a bituminous paint or epoxy. 7. All flashing and weatherproofing shall be provided by the contractor. 8. Door location shall be determined by contractor in the field 9. Use of these plans acknowledges and accepts a limit of liability not to exceed design and engineering fee. WIND SPEED AND :' )SURE HAVE BEEN DETERMINE,'--,�JNG THE ADVANCED TECHNOLOGY COUNCIL'S WEBSITE AND GOOGLE EARTH. 10'—o" 3X3XO.090 POST 2X3 KNEE BRACE (TYP) o io 0cli 0 I I 0 1 • i0 3X3XO.090 C'j POST 093—`-mow ST. LUCT_E COUNTY BUILDENG REVIEWED FOR COMPLIANGA DATE 01 (Zia v PLANS AND PERMIT MUST B] OR NO INSPECTION WELL BE B 2x6SMB 2X8SMB pjp 2XSSMB CROSS -CROSS END BEAM 47H WALL BEAM BEAM BEAM 2X3XO.045 2X8SMB 2X8SMB 2X5SMB END CROSS CROSS INT YX12'X0.019' BEAM BEAM BEAM BEAM RHINO PAN A-4 A-4 _ 2X5SMB 2X3XO.050 A-3 EDGE - EDGE BEAM p-3 BEAM A-3 7-1Ok V-10k 7'-10i' 6--* 6'—qk 6--9J* C, ��t�t111i1(/r� R(N co LL ON JOB d- . y.• • F PROP'E�>;Ib{d� ,SEAL 3X3XO.090 POST 1X3 0 2X3GIRT (TYP) .o ro (TYP) io 3X3XO.090 'o POST 1 3X3X0.090 0 POST 0 m 0 2XDJ m 1Ell 2XDJ 3X3XO.090 POST B'-6" WN BY ca 00 THESE PUNS AND ALL PROPOSED WORK ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT MAY BE NECESSARYIN ORDER TO COMPLY WITH ALL APPUCABIE OOAES. 1�. LE COP-Y OONORALEO PASTENERS OR ATTACHMENTS ARE THE RESPONSIBILITY OF THE CONTRACTOR OF REOOn ui u i OV d d W LL.Cr. 0 Zv WCC LLI ,000 � am Wm W (A Z Qc W W G Z Q Z Z x= O� W F— -- CC 0 ZUo W J J . v Q Z O r t7 m Q W -,-P8 O LLl g "' m m ZTC �v,E Z 3 �pQNN h 3 n n :3 Z e� l LA W diwLL EL F- W O W O Z �ZLU ZW _ mtboDDoo O ZW~rn M a 00aLLL DRAWN BY GD DATE DRAWN 02/17/18 REVISION SHEET NO: A-1 60 0 ALUMINUM MEMBERS DIMEN"'__'fS \0�� HOLLOW SECTIONS 2x2:2"x2"x0,046" 2x3: 2"x3"x0.050" .J 1 2 x 4: 2" x 4" x 0.050" Q; � c+� w � 2x5: 2"x5"x0.050" - p O co w OPEN BACK SECTIONS Z- ` 1x2: 1"x2"x0.040" I (j);> 0 z'' 1 x 3: 1" x 3" x 0.045" rl SNAP SECTIONS ��OLL• • . !•:(� 0.045" , ''' 2 x 2 Snap: 2" x 2" x 2 x 3 Snap: 2" x 3" x 0.050" 3" 3" 0.0991 2 x 4 Snap: 2" x 4" x 0.045" I T' x 8" x 0.090" x x POST I li)) PROFE _ POST SIa NALSREAL U SELF MATING (SMB) (2) 318" DIA CONCRETE I a 2 x 4 SMB: 2" x 4" x 0.044" x 0.100" SCREW ANCHORS c 2 X 5 SMB: 2" x 5" x 0.050" x 0.100" (3" CONC. EMBED) ( (2) 3/8" DIA CONCRETE qq qq 3 i 2 X 6 SMB: 2" x 6" x 0.050" x 0.120" SCREW ANCHORS 0 2 x 7 SMB: 2" x 7" x 0.057" x 0.120" (T' CONC. EMBED) INTERNALIEXTERNAL y,j Li C 2 x 8 SMB: 2" x 8" x 0.072" x 0.124" 1" x 3" OB W/ 1/4" CONCRETE INTERNAL/EXTERNAL ( 3" x 3" x 118" EXTRUDED Q _ 2 x 9 SMB: 2" x 9" x 0.072" x 0. IX' SCREW ANCHOR V' 3" x W x 1/8" EXTRUDED POST BASE W/ (2) 3/8" W z 2 x 10 SMB: 2" X 10" X 0.092" X 0.398" FROM UPRIGHT 8 @ £ POST BASE W/ (2) 3/8" DIA. THRU BOLTS �. ,h c ¢ 2N' O.C. (MIN. 3" EMBED.) 1 DIA THRU BOLTS N u MINIMUM FASTENER EDGE DISTANCE: 1/2" 1 LL Q� p MINIMUM FASTENER SPACING: 3/4" — i 1 OC a 15 m Lu m z LL LLJ CONCRETE SCREW ANCHOR: LLI SIMPSON TITEN HD OR EQUIVALENT z Q z SHEET METAL SCREWS (SMS): a '° ,< • '. 4 e — ITW / BUILDEX OR EQUIVALENT �a'. k - k a ;� Z = O j j W F— cz LL v C z 5 LL ` C. B B' l 3" x 3" POST TO CONCRETE CONNECTION DETAIL z_ ., c 3" x 3" POST TO CONCRETE CONNECTION DETAIL /� SCALE: NTS C V a A _2 SCALE: NTS /'1-2 c r" a J g •y LLa la— Z Z0 10.ceo S z k v� CC tmo8 a Q W "'ILL TT64A ai N I If1 Q W `•• K Ym1 W z =��� LL = U u 1/8"x2"x2"EXTRUDED Z (7 C ANGLE 5052 H-32 ALLOY • • (4) #14 x 3/4" SMS • �_ INTO DJ m W s �/)_W_,,.u_�,, ?� � —� Fm a a a z •'•' e, e.: @ a tL • 211r MIN CONC SLAB /FOOTING ` a .iwCHON USEDMEW 4 i SEE PLAN ':6 6 d N 0. � LL L • 1 '9 ea'. "'` ''• CHAIR RAIL MEMBER 3 1 ¢ � O Z w e LL SIDE VIEW 0 z Z U a FS� a 1 J J :j - C z (1) 3/8" DIA CONCRETE 1"x 1"x l/8"ANGLE W/ W m � Goo SCREW ANCHORS I UPRIGHT 1/4" CONC. EMBED) (2) #14 x 5/8" EACH FLANGE Z 0 F 0) Z M (2PRE -HUNG DOOR JAMB EACH SIDE OF UPRIGHT 0.090' LUW IY a O LJL PST POST — - — _ DRAWN BY a .. GD BASE PLATE ° DATE DRAWN ANCHORED TO CONC W/ 1/4" ' . a', ' a' a d a 02/17/1 8 CONCRETE SCREW ANCHOR a : 4 a REVISION (MIN. 1 IK'EMBED) �. . 6" MAX EACH SIDE OF POST ' ... • q• , AND 24" O.C. MAX z - s a < `• C CHAIR RAIL TO POST CONNECTION DETAIL FRONT VIEW A-Z SCALE: NTS SHEET NO: DJ-1 UPRIGHT TO CONCRETE8 PRE -HUNG A-2 DOOR LOCATION DETAIL SCALE: NTS A-2 ����,` #14x314- W/ ,.������.� •9�'�, NEOPRENE FACED WASHER @ 4" O.C. •- / ,/ 3" RHINO PANEL L�� i I 914x3/4"SMSW/ Q; LL �• r NEOPRENEFACED UJ -- l WASHER @ 4„ O.C. _- - EL : ll1 yy T H Q JJ • #14x3/4"SMSW/ 3"x12"RHINO �%••, i ! �� Q' NEOPRENEFACED PAN PANEL �- •, • 2' x 8' WASHER @ 4" O.C. r •!• J ` 2"x3"x0.050"TOP RAIL- ANGLE REQUIRED • CROSSBEAMNO • ��O •••, � /,���� ,.• •. �G/ � UNLESS SPLICED OR (��i !! — P�O� �\` ( • • —� //! CORNER -ATTACH w/(4) 111110\\ ! #10 x 4" LG ? �! 1 • 3" x 12" RHINO • PROFE iSIONAL SEAL j i� �- PAN PANEL �� I • - y r �I r 11/2"x21/8"x11/2"x1/81x lie a li • UPRIGHT 8" LONG ALUM RECEIVING 3/8" DIA. THRU BOLTS (4) TOTAL „ • �• ❑ CHANNEL W/ (7) #14 x 3/4" i I SMB ( 2" x 6" SMB INTO THE UPRIGHT AND • • END BEAM (7) #14 x 3/4" SMS INTO EACI i ; • ui u,I SIDE OF BEAM 2" x 5" SMB • II 0 p: C 2"xWx0.050"TOP ;� • 1 (� • LLI RAIL w/ (4) #10 x 4' 3" x 3" x 0.090" _ — 1= m o SMS INTO POST POST 2"x5"SMB y ILLZw w� 2" x 2" x 3" LG ` i 2" x 2" x 3" LG -- — 1 1!2" x 21/8" x 1 1/2" x 8" x 0.062"ALUM I 3" x 3" x 0.090" 1 1/2" x 2118' x1 1/2" x 6" x 0.062" ALUM O Q w w W m x 1/8"ANGLE x 1 /B" ANGLE RECEIVING CHANNEL W/ (7) POST RECEIVING CHANNEL W! (5) W • J co C 2 #14 x 3/4" SMS EACH SIDE OF #14 x 3/4" SMS EACH SIDE OF W 0 - BEAM & (4) 3!8" DIA THRU BOLTS INTO POST BEAM & (3) 3f8" DIA THRU BOLTS Z y J W (4) #10 x 31M' (4) #10 x 3/4"_�] INTO POST (D Z = u O u z u SMS INTO 33 SMS INTO LLISCREW I -- SCREW BOSSES i SCREW BOSSES (2) INTO TOP RAIL (2) INTO TOP RAIL ) (2) INTO POST (2) INTO POST S-2 RHINO CONNECTION AT CORNER CONNECTION AT SPLICE S-1 HINO PAN ROOF TO POST CONNECTION PANEL TO CORNER POST CONNECTION A-3 SCALE: NTS A_3 SCALE: NTS Z S X 3 TOP RAIL CONNECTION TO 3 X 3 UPRIGHT ? J A-� SCALE: NTS z F- 4 Q UJI 9 ai W'i m m z O u 03^^ Z C7 o #14x3/4"SMSW/ NEOPRENEFACED #14 x 3/4" SMS Wf FLASHING WASHER @ 4" O.C. 3" x 12" RHINO NEOPRENEFACED WASHER @ 4" O.C. #14 x 3/4" SMS W/ NEOPRENE FACED FLASHING [PANPANEL 3" RHINO PANEL WASHER @ 4" O.C. 2" x 3" TOP RAIL w/ (4) #10 x 4" SMS 3" RHINO PANEL INTO POST — __ — — — - - — — 2"x2"x3"LG N Q W • x 1/8" ANGLE — W V Z — — _ • ... .... Q c Q • E • EXISTING — — ~ • (4) #10 x 3!4" SMS INTO Z Z LLI a BUILDING • EXISTING„ • t I t SCREW BOSSES J 2"x8"SMB • BUILDING _ _ pt(2) INTO TOP CROSSBEAM • • 1 (2) INTO POSTAL W m H (~- Cj I END BEAM 2" x 5" SMB Z 0 0) • 1 • Q Z W • 1 j 1 1/8" x 2" x 1 1/8" x 5" x 0.067' yS m O J • I I ALUM RECEIVING CHANNEL G. 7 co a LL • _ W/ (4) #14 is 3/4" SMS INTO - a----" EACH SIDE OF BEAM & (4) DRAWN BY 1 1/2" x 2118" x1 1/2" x 6" x 0.06Z' #14 x I" SMS INTO CORNER POST GD 1 1/2" x 21/8" x1 1 /2" x 0.06Z' ALUM RECEIVING CHANNEL W/ (5) #12 x 3/4" SMS EACH ! 2" x 5" SMB 1 DATE DRAWN ALUM RECEIVING CHANNEL _ _ W/ (7) #12 x 3/4" SMS EACH SIDE OF BEAM & (3) 3/8" DIA. 02/17/18 SIDE OF BEAM & (4) 318" DIA. 2" x 5"SMB THRU BOLTS INTO THE POST - _ i 3" x 3" POST REVISION THRU BOLTS INTO THE POST 3" x 3" x 0.090" AK-- POST S-3 HINO PANEL TO CORNER POST 4TH WALL DETAIL S-5 SCALE: NTS A-3 S-4 PANEL TO CORNER POST WALL DETAIL HINO PANEL ROOF TO POST CONNECTION HIND 0 4TH A_3 SCALE: NTS SHEET NO: A-3 SCALE: NTS A-3 t 3" RHINO PAN I .40 T, i7. LL ROOF PANE L cli 0 0, Zyy W SELF -MATING BEAM -\I 1 3" x Wx 0.090" POST PROFESSIONAL SEAL c MB - Z, x S, SMB 2 Ll lb El (c 1 1/Z'x 2 1/8" x 11/2" x 6' x 2 1/8"x 11 lz'x 6' 1 ir 0 w Ld RECEMNG CHANNEL RECEIVING CHANNEL #12 314'SMS EACH 2"x 3" W/ (4) #12 x 3/4" SMS EACH x W1 H (4) LLJ KNEE BRACE UPRIGHT SIDE INTO UPRIGHT & (2) 30 SIDE INTO UPRIGHT & (2) 3/8 I= a to DIA. THRU BOLTS DIA. THRU BOLTS INTO POST INTO POST LL 0 z w 1! Lu0 1 112" x 2 1/8" x 1 11Z' x LIJ LU CL 2 .2 0.062'x Z' LONG ALUM Lu RECEIVING CHANNEL W/ (3) z uJ 2z #12 x 3/4" SMS EA. FACE& FD w W (3) #12 x 3/4" INTO POST z Z u u = 0 - LLI = i— rS 7 MULTIPLE BEAMS TO POST CONNECTION �SCALE: NTS 4 rS 6NNEE BRACE CONNECTION DETAIL SCALE: �4 z U 0 -j gn -j Zoe 9 Z N a 00 cp 91 0 Lu — u Znn ;4 N C4 z Q <0 z (4) #14 x 3/4" SMS W/ o--FLASHING -FACED NEOPRENE 1 1i2'x21i8'x1 I/2'x0.062' WASHER EA. PANEL BEAM DEPTH CHANNEL Wl (4) #14 x 3/4" SMS INTO 3" RISER PANEL BEAM EACH SIDE & (4) #14 x 3/4" SMS INTO CROSS END BEAM CL F- cl)QQ LA w LA 0 LLI 0 Z 2'x 5" SMB Lu EXISTING z Z BEAM • BUILDING Lu b C-4 ca 1 1/Z'x 2 liff'xl IIZ'x Wx 0.06Z' z O Z LU ALUM RECEIVING CHANNEL 3 I cl) 20 W/ (3) #12 x 3/4" SMS EACH 00 CIL u- SIDE OF BEAM & (2) 318" DIA. THRUI BOLTS INTO THE POST DRAWN BY —\,—OR Z, x 61 SMB—/ GD 2" x 9' SMB CROSS BEAM DATE DRAWN 3"x3"POST 02/17/18 2" x 61 SMB END BEAM REVISION rs 9 PANEL TO CORNER POST (cD 4TH WALL DETAIL INT BEAM TO CROSS I END BEAM ATTACHMENT SCALE:NTS �4 SCALE:NTS SHEEr NO: