EVALUATION REPORT
CertainTeed Corporation
20 Moores Road
Malvern, PA 19355
(610) 651-5847
SCANNED
t� BY
St Lqj'Ie EXTERIOR RESEARCH & DESIGN, LLC.
Certificate of Authorization #9503
353 Christian Street
Oxford, CT 06478
(203) 262-9245
Evaluation Report C40710.12.13-114
FL16709-R4
Date of Issuance:12/02/2013
Revision 4: 09/14/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 6th Edition (2017) Florida Building Code sections noted herein.
DESCRIPTIONS PMEtl tic® Modified Bitumen Roof Systems
LABELING: Labeling s al be in accordance with the' requirements the Accredited Quality Assurance Agency noted'
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity) ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 4, plus 14-page Appendix.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCAANE1983
The facsimile seal appearing was authorized by Robert Nieminen,
P.E on 09/14/2017. This does not serve as an electronically signed
document.
CERTIFICATION OF INDEPENDENCE:
1. Exterior Research St Design, I.I.C. d/b/a Trinity I ERD does not have, nor does it intend to acquire or will it acquire, a financial interest
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, LLC, d/b/a Trinity I ERD is not owned, operated or controlled by any company manufacturing or
distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
l�oQ'TRINIT'y
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Modified Bitumen Roof Systems
Compliance Statement: FlintlasticO Modified Bitumen Roof Systems, as produced by CertainTeed Corporation,
have demonstrated compliance with the following sections of the a Edition (2017) Florida Building Code through
testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and
Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section
Pro a
Standard
Year
1504.3.1
Wind
FM 4474
2011
1504.7
Impact
FM 4470
2012
1507.11.2
Physical Properties
ASTM D6162
2008
1507.11.2
Physical Properties
ASTM D6163
2008
1507.11.2
Physical Properties
ASTM D6164
2011
1507.11.2
Physical Properties
ASTM D6222
2011
1507.11.2
Physical Properties
ASTM D6509
2005
1519.11
Attachment Requirements
RAS 117
1995
3. REFERENCES:
Entity
Examination
Reference
Date
ERD (TST6049)
Physical -properties
C7290.01.08
01/16/2008
ERD (TST6049)
Physical Properties
C10080.09.08
09/04/2008
ERD (TST6049)
FM 4470/4474
C8370.08.08-R1
10/05/2009
ERD (TST6049)
FM 4470/4474
C30310.12.09
12/17/2009
ERD (TST6049)
FM 4470/4474
C30560.03.10
03/18/2010
ERD (TST6049)
FM 4470/4474
3519.12.03-R1
04/15/2011
ERD (TST6049)
Physical Properties
C42110.08.12
08/13/2012
ERD (TST6049)
FM 4470/4474
C46090.11.13-A
11/20/2013
ERD (TST6049)
FM 4470
CTR-SC9920.01.16-111
01/W/2016
FM (TST1867)
FM 4470/4474
3048520
09/19/2013
MTI (TST2508)
Physical properties
DX08C4A
03/22/2004
MTI (TST2508)
Physical properties
DX20E3A
03/22/2004
MTI (TST2508)
Physical properties
DX20E3A-001
01/04/2006
MTI (TST2508)
Physical properties
AX31GBA
08/21/2008
MTI (TST2508)
Physical properties
AX31G8D
09/05/2008
MTI (TST2508)
Physical properties
AX31GBF
06/05/2009
MTI (TST2508)
Physical properties
AX21G8C
01/28/2011
PRI (TST5878)
Physical Properties
CDC-032-02-01
01/16/2008
PRI (TST5878)
Physical Properties
CTC-034-02-01
11/24/2008
PRI (TST5878)
Physical Properties
CTC-066-02-01
08/08/2011
PRI (TSTS878)
Physical Properties
CTC-067-02-01
08/08/2011
PRI (TST5878)
Physical Properties
CTC-068-02-01
08/08/2011
PRI (TST5878)
Physical Properties
CTC-070-02-01
08/08/2011
PRI (TST5878)
Physical Properties
CTC-071-02-01
08/08/2011
PRI(TST5878)
Physical Properties
CTC-093-02-01
08/08/2011
PRI (TST5878)
Physical Properties
CTC-116-02-01
04/03/2012
PRI (TST5878)
Physical Properties
CTC-183-02-01
10/04/2013
PRI (TST5878)
Physical Properties
CTC-259-02-01
12/11/2015
UL, I.I.C. (QUA9625)
Quality Assurance
Service Confirmation, R11656
Exp. 03/09/2020
Exterior Research and Design, LLC.
Evaluation Report C40710.12.13-114
Certificate ofAutharlsatlon 09503
5T" EDITION (2017) FBC NON-HVHZ EVALUATION
FL16709-114
CertainTeed Flintlastic® Modified Bitumen Roof Systems, (610) 651-5847
Revision 4: 09/14/2027
Page 2 of 4
\! TRINITYIQtb
4. PRODUCT DESCRIPTION:
This Evaluation Report covers Flintlastic® Modified Bitumen Roof Systems installed in accordance with CertainTeed
Corporation published installation instructions and the Limitations / Conditions of Use herein. The following
CertainTeed products make up the subject systems.
TABLE 1 ROLL-GOODS;;FOR FLINTLASTIG®'MODIFIED`BITUIVIEN'ROOFSYSTEMS
Type
Product
Specification
Reference
Grade
Type
IlBase Sheets,
Fl)ntlastic S U MBase _.
ASTM D4601
N/A
II
Glasbaser" Base Sheet
ASTM D4601
N/A,
II
All Weather/Empire- Base
ASTM D4601
N/A
11
FlexiglasT" Base
ASTM D4601
N/A
II
Flintlastic' Base 20
ASTM D4601
N/A
II
Flintlastic Poly SMS Base Sheet
ASTM D4601
N/A
II
Yosemite®, Venting Base
ASTM D4897
N/A
II
PI Sheets
y
Flintglas® Ply 4
ASTM D2178
N/A
IV
Flintglas® Premium Ply 6
ASTM D2178
N/A
VI
Base/Ply Membranes (APP)
Flintlastic® APP Base T
ASTM D6509
N/A
N/A
Flintlastic® STA
ASTM D6222 '
S
I
Flintlastic® STA Plus
ASTM D6222
S
Cap Membranes (APP)
Flintlastic® STA
ASTM D6222
S
I
Flintlastic® STA Plus
ASTM D6222
S
I
Flintlastic® GTA
ASTM D6222
G
I
Flintlastic° GTA CoolStar-
ASTM D6222
G
I
Flintlastic® GTA-FR
ASTM D6222
G
I
Flintlastic® GTA-FR CoolStarlm
ASTM D6222
G
I
Base/Ply Membranes (SBS)
Flintlastic SA PlyBase
ASTM D1970
N/A
N/A
Black Diamond° Base Sheet
ASTM D1970
N/A
N/A
Flintlastic SA Mid Ply
ASTM D6163
S
I
Flintlastic Ultra Glass SA
ASTM D6163
S
I
Flintlastic Base 20
ASTM D6163
S
I
Flintlastic- Base 20 T
ASTM D6163
S
I
Flintlastic Ultra Poly SMS Base Sheet
ASTM D6164
S
I
Cap Membranes (SBS}
Flintlastic FR Dual Cap
ASTM D6162
G
I
Flintlastic SA Cap FR
ASTM D6163
G
I
Flintlastic SA Cap FR CoolStar""
ASTM D6163
G
I
Flintlastic Cap 30
ASTM D6163
G
I
Flintlastic Cap 30 CoolStar'"
ASTM D6163
G
I
Flintlastic FR Cap 30
ASTM D6163
G
I
Flintlastic FR Cap 30 CoolStarTM'
ASTM D6163
G
I
Flintlastic FR Cap 30 T
ASTM D6163
G
I
Flintlastic,�FR Ca _30 T CoolStarTM
ASTM D6163
G
I
F intlastit SA Cap
ASTM 06164
G
Flintlastic SA Cap-C-007Star"
ASTM D6164
G
I
Flintlastic FR-P
ASTM D6164
G
I
Flintlastic FR-P CoolStarl
ASTM D6164
G
I
Flintlastic GMS
ASTM D6164
G
I
Flintlastic GMS CoolStar"
ASTM D6164
G
I
Flintlastic GTS
ASTM D6164
G
II
Flintlastic GTS CoolStarTM
ASTM D6164
G
II
Flintlastic GTS-FR
ASTM D6164
G
II
Flintlastic GTS-FR CoolStarTM'
ASTM D6164
G
II
Flintlastic Premium FR-P
ASTM D6164
G
II
Flintlastic Premium FR-P CoolStarTM'
ASTM D6164
G
li
Exterior Research and Design, I.I.C. Evaluation Report C40710.12.13-114
Certif ate ofAuthorizotion #9503 6'" EDITION (2017) FBC NON-HVHZ EVALUATION FL36709-R4
CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-5847 Revision 4: 09/24/2017
Page 3 of 4
'\,JTRInJITY I ERD
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity) ERD nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for
permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions..
5.3 Refer to a current Roofing Materials Directory for fire ratings of this product.
5.4 The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural
members shall be in accordance with FBC requirements to the satisfaction of the Authority Having
Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC
Approval documentation.
5.5 For recover installations, the existing roof shall be examined in accordance with FBC 1511.
5.6 The maximum design pressure 'for the selected base assembly shall meet or exceed the Zone 1 design
pressure determined in accordance with FBC Chapter 16. This is already addressed in the Appendix tables via
"N/A" reference if the baseline system is "Not Applicable" to Zone 1 design pressure requirements.
5.7 For mechanically attached insulation or membrane over existing roof decks, fasteners shall be tested in the
existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison
to the minimum requirementsfor the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-
1 or Testing Application Standard TAS 105.
5.8 Metal edge attachment (except gutters), shall be designed and installed for wind loads in accordance with FBC
Chapter 16 and tested for resistance in accordance with ANSI/SPRI ES-1 or Roofing. Application Standard RAS
111, except the basic wind speed shall be determined from FBC Figure 1609.3(1),1609.3(2) or 1609.3(3).
5:9 All products in the roofassembly shall have quality assurance in accordance with FAC Rule 611320-3.
6. INSTALLATION:
6.1 Flintlastic° Modified. Bitumen Roof Systems shall be installed in accordance with CertainTeed Corporation
published installation instructions, subject to the Limitations / Conditions of Use herein.
6.2 System attachment requirements for wind -load resistance are set forth in Appendix 1. System listings are
based on allowable wind loads per FBC 1609 and a 2 to 1 margin of safety per FBC 1504.9.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
8. MANUFACTURING PLANTS:
Contact the named QA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 QA requirements.
9. QUALITY ASSURANCE ENTITY:
UL, LLC. — QUA9625; (414) 248-6409, karen.buchmann@us.ul.com
- THE 14-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT -
Exterior Research and Design, I.I.C. Evaluation Report C40710.12.13-R4
Certificate of Authorization #9503 6' EDITION (2017) FBC NON-HVHZ EVALUATION F1.16709-114
CertainTeed Flintlastic® Modified Bitumen Roof Systems, (610) 65145847 Revision 4: 09/14/2017
Page 4 of 4