EVALUATION REPORT
Manufacturer:
Manufacturing Location
Quality Assurance:
SCOPE
FLORIDA BUILDING CODE, 6T"j EDITION (2001177)) �--
L
MID -STATES ASPHALT AND CANT STRIP, INC. Issued October 11, 2�}}l
1637 51s` Street ST. LUCIE COUNTY BUILDINGeDIVI,Tuscaloosa, AL 35401 REVIEWED FOR COMPLIANCE
I(800) 489-2391 REVIE D BY
www.msaroof.com DATE
PLANS ND PERMIT MUST BE KEPT ON JOB
Tuscaloosa, AL SITE OR NO INSPECTION(S) WILL BE MADE
UL LLC (QUA9625)
Category:
Roofing
Subcategory:
Underlayments
Code Sections:
1504.3.1, 1507.1.1
Properties:
Physical properties
PRODUCT DESCRIPTION AND LIMITS OF USE
III:
WORK
REQUIRED BY FIELD INSPECTORS THAT
COMPLY WIT HALL APPLICABLE CODES.
QUIKStick Ice & Water QUIK-Stick Ice & Water Granular is an ASTM D 1970 self-adhesive underayment
Granular constructed from SBS modified asphalt, a fiberglass mat reinforcement and surfaced
with granules. The product is supplied in 2-sq. rolls with nominal dimensions of 3-ft x
66.8-ft and has a nominal thickness of 50 mils.
QUIK-Stick Ice & Water Granular is permitted to be used as prescribed in FBC Section
1507.1.1 for mechanically attached roofing coverings. Exposure on the roof deck shall
be limited to a maximum 30 days.
QUIK-Stick Ice & Water QUIK-Stick Ice & Water Sand is an ASTM D 1970 self-adhesive underlayment
Sand constructed from SBS modified asphalt with a fiberglass mat reinforcement and surfaced
with sand. The product is supplied in 2-sq. rolls with nominal dimensions of 3-ft x 66.8-ft
and has a nominal thickness of 50 mils.
QUIK-Stick Ice & Water Sand is permitted to be used as prescribed in FBC Section
1507.1.1 for mechanically attached roofing coverings. Exposure on the roof deck shall
be limited to a maximum 30 days.
QUIK-Stick HT QUIK-Stick HT is an ASTM D 1970 self-adhesive underlayment constructed from SBS
(High Temperature) modified asphalt with a fiberglass mat reinforcement and poly -fabric surface. The
product is supplied in 2-sq. rolls with nominal dimensions of 3-ft x 66.8-ft or 3-ft 3-in x 61-
ft and has a nominal thickness of 60 mils.
QUIK-Stick HT is to be used as prescribed in FBC Section 1507.1.1. QUIK-Stick HT is
permitted to be used with adhered clay or concrete tile roofing using either ICP
Adhesives Polyset AH-160 (ICP Adhesives and Sealants, Inc.). Exposure on the roof
deck shall be limited to a maximum 90 days.
The maximum roof slope shall be 6:12 when used with clay or concrete tile installations
without battens. Tile shall be stored on battens for roof slopes greater than 6:12. Tiles
shall not be stacked greater 10 tiles per stack. CONCEALED FASTENERS OR ATTACHMENTS
ARE THE RESPONSIBILITY OF THE
CONTRACTOR OR RECORD
MSA17001 FL17401-R4 Page 1 of
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
FILE COPY
CREEK MID -STATES ASPHALT AND CANT STRIP, INC
Self -Adhering Underlayments
TECHNICAL SERVICES, LLC
QUIK-Stick HT Pro QUIK-Stick HT Pro is an ASTM D 1970 self-adhesive underlayment constructed from
(High Temperature) SIBS modified asphalt with a fiberglass mat reinforcement and poly -fabric surface. The
product is supplied in 2-sq. rolls with nominal dimensions of 3-ft x 66.8-ft and has a
nominal thickness of 60 mils.
QUIK-Stick HT Pro is permitted to be used as prescribed in FBC Section 1507.1.1 for
mechanically attached roofing coverings. Exposure on the roof deck shall be limited to a
maximum 30 days.
QUIK-Stick FS QUIK-Stick FS is an ASTM D 1970 self-adhesive underlayment constructed from SBS
(Film Surface) modified asphalt with a fiberglass mat reinforcement and textured film surface. The
product is supplied in 2-sq. rolls with nominal dimensions of 3-ft x 66.8-ft and has a
nominal thickness of 45 mils.
QUIK-Stick FS is permitted to be used as prescribed in FBC Section 1507.1.1 for
mechanically attached roofing coverings. Exposure on the roof deck shall be limited to a
maximum 30 days.
PRODUCT APPLICATION
Min. Roof Slope:
2:12 or in accordance in with the FBC
Application:
All underlayments shall be installed in accordance with the FBC.
Deck substrates shall be clean, dry, and free from any irregularities and debris. All
fasteners in the deck shall be checked for protrusion and corrected prior to underlayment
application. Prior to beginning installation, the underlayment shall be unrolled and
allowed to relax for a minimum of 3-5 minutes.
The underlayment shall be installed with the release backer removed and pressed firmly
into place to ensure complete contact with the deck. The underlayment shall be installed
with the roll length parallel to the eave, starting at the eave, and with minimum 3" side
laps and minimum 6" end laps staggered min. 6-ft.from preceding course.
It is permissible to back nail the underlayment 12-inches on -center as needed (nails shall
be installed perpendicular to deck with the nail heads flush to the top surface of the
underlayment).
Min. Application
40°F; Contact the manufacturer when installing at temperatures below the minimum
Temperature:
application temperature.
WIND RESISTANCE
The Maximum Design Pressures shown below were calculated using a 2:1 margin of safety per FBC Section 1504.9.
Underlavment System No.1 — QUIK-Stick HT only
Roof Deck:
Min. 15/32-inch CDX plywood attached to wood supports spaced a maximum 24" o.c.
Underlayment:
QUIK-Stick HT shall be fully adhered to the optionally primed plywood deck.
Maximum Design
-52.5 psf
Pressure:
MSA17001 FL17401-R4 Page 2 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
GENERAL LIMITATIONS
MID -STATES ASPHALT AND CANT STRIP, INC
Self -Adhering Underlayments
1) This evaluation report is not use in the HVHZ.
2) Fire Classification is not within the scope of this evaluation.
3) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturer's published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
4) The roof deck shall be constructed of closely fitted plywood sheathing for new or existing construction.
5) The space under the deck area shall be properly ventilated in accordance with the FBC requirements.
6) All side lap seams shall be installed to shed water from the deck.
7) The underlayment may be used as described in other current FBC product approval documents.
8) Design wind load pressures shall be determined for components and cladding in accordance with FBC
1609.
9) The roof deck shall be designed by others in accordance with FBC requirements to resist the design wind
load pressures for components and cladding.
10) Maximum Design Pressures for a given underlayment shall meet or exceed the design wind loads
determined for the roof assembly.
11) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
REFERENCES
Eflifty
Report No.
Standard
Year
PRI Construction
Materials Technologies (TST5878)
BWR-514-02-01
ASTM D 1970
2015a
PRI Construction
Materials Technologies (TST5878)
BWR-522-02-01
ASTM D 1970
2015a
PRI Construction
Materials Technologies (TST5878)
BWR-533-02-01
TAS 103
1995
PRI Construction
Materials Technologies (TST5878)
BWR-534-02-01
ASTM D 1970
2015a
ASTM D 4798
2011(2016)
PRI Construction
Materials Technologies (TST5878)
BWR-543-02-01
ASTM D 1970
2015a
PRI Construction
Materials Technologies (TST5878)
WRMI-011-02-01
ASTM D 1970
2015a
PRI Construction
Materials Technologies (TST6049)
MSA-007-02-01
UL 1897
2012
PRI Construction
Materials Technologies (TST6049)
MSA-026-02-01
ASTM D 1970
2015a
MSA17001 FL17401-R4 Page 3 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
COMPLIANCE STATEMENT
MID -STATES ASPHALT AND CANT STRIP, INC
Self -Adhering Underlayments
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 6t' Edition (2017) as evidenced yin the referenced documents submitted by the named manufacturer.
11%J u u 1 i il,�i
R.
6.
No 74021
-o '. STATE OF 44/�
unt
CERTIFICATION OF INDEPENDENCE
2017.10.11
11:41:31
04f00f
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
MSA17001 FL17401-R4 Page 4 of 4
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.