HomeMy WebLinkAboutPLAN EXAMINER REVIEWii`.'�:J
08-08-18
City of Port St. Lucie
Building Department
Plan Review Div.
RE: Oakland Lake (Lot 71) 1833 Model
[PLANS EXAMINER REVIEW]
ARCHITECTS
Design
Group Inc.
CHANGES TO THE STRUCTURE AND FENESTRATION.
PLEASE FURNISH REVISED ENERGY CALCULATIONS AND MANUAL J IN ACCORDANCE WITH SECTIONS 402
AND 403 OF THE 2017 FLORIDA ENERGY CODE FIFTH EDITION. NOTE ONLY; ENERGIES MUST HAVE
ORIGINAL SIGNATURE OF PREPARER.
Provided
SUBMIT THE PRODUCT APPROVALS, IN DUPLICATE OR PRODUCT REVIEW AFFIDAVIT COMPLETE WITH
FLORIDA PRODUCT APPROVAL OR N.O.A. NUMBER WITH INSULATION INSTRUCTIONS AND SIGNED SEALED
AND DATED BY THE DESIGN PERSON OF RECORD FOR ALL COMPONENTS AND CLADDING IN ACCORDANCE
WITH 553.842 OF THE FLORIDA STATUTES. PRODUCT APPROVAL'S MUST BE HIGHLIGHTED OR MARKED
IDENTIFYING THE OPENING OR CLADDING COMPONENTS, FASTENERS AND DESIGN PRESSURES.
See signed Product Approvals included with this submission.
PLEASE FURNISH THE REVISED MANUFACTURERES TRUSS PLACEMENT DRAWINGS IN DUPLICATE
REVIEWED AND APPROVED BY THE DESIGN PERSON OF RECORD IN ACCORDANCE WITH CHAPTER 8
SECTION R802 SUBSECTION R802.1.7.1 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE.
These truss drawings have been reviewed and approved Vpv'&".\ "i 'WN %viN,a\ 'pe' VVz%-t C'Jov":AA3�
PLEASE FURNISH REVISED TRUSS ENGINEERING IN DUPLICATE PER CHAPTER 8 SECTION R802 SUBSECTION
R802.1.7.1 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE.
Provided v�a�a7v� �`e1���A\ �Q�trv.:� t�d'�o�ev.`��1C.� .
PLEASE SUBMIT A DETAIL FOR THE INFILL OF THE REMOVED WINDOW. SEE SECTION 107 OF THE 2017
FLORIDA BUILDING CODE.
See repair letter included with this submission.
1441 N. Ronald Reagan Blvd. • Longwood, FL 32750 • Phone: (407) 774-6078 • Fax: (407) 774-4078
AA0003325
www.abdesigneroun.com
PLEASE FURNISH THE REVISED MANUFACTURERES TRUSS PLACEMENT DRAWINGS IN DUPLICATE
REVIEWED AND APPROVED BY THE DESIGN PERSON OF RECORD IN ACCORDANCE WITH CHAPTER 8
SECTION R802 SUBSECTION R802.1.7.1 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE.
These truss drawings have been reviewed and approved.
CHANGES TO THE STRUCTURE AND FENESTRATION.
PLEASE FURNISH REVISED ENERGY CALCULATIONS AND MANUAL J IN ACCORDANCE WITH SECTIONS 402
AND 403 OF THE 2017 FLORIDA ENERGY CODE FIFTH EDITION. NOTE ONLY; ENERGIES MUST HAVE
ORIGINAL SIGNATURE OF PREPARER.
Provided
Should you have any questions regarding this letter, do not hesitate to call me.
Sincerely,
Jame Cayh�well
Flo (chitect #12079
August 8, 2018
City of Apopka Building Department
120 E. Main Street
Apopka, FL 32703
ph: 407.703.1700
Orchid Estates (Lot 71)
To Whom It May Concern:
This letter is in reference to the left an Id right side windows at the front entry.
• The window on the left of the entry increased in size from a 35-SH to (2) 25-SH. The
original bond beam was cut out and a new opening was created with (1) #5 retrofitted on
each side of the opening. A poured in place concrete beam with (1) #5 bar was put over
the new window opening with a new bond beam on top of the concrete beam.
• The window on the right of theentry decreased in size from a 35-SH to a 25-SH. Each
side of the window was form and poured with (1) #5 bar drilled and epoxied into the
adjacent block on each side of the opening before pouring.
These repairs for both the left and right'; window are structurally adequate.
Should you have any questions regarding this letter, do not hesitate to call me.
I
Sincerely,
AUG 0 9 2018
Ryan P. Howard, P.E.
License # 67403
1441 N. Ronald Reagan Drive • Phone: (407)774-6078 • Fax: (407)774-4078
www. abdesigngroup.com