AMERICAST GENERATOR CONCRETE PAD
GENERATOR TABLE:
(ON -GRADE APPLICATIONS ONLY)
AMERICAST
wrvw emerEraasnv mfl1.
.•EfAD19�IN.�RIOK:'
FMIAXY'^:.252362 LILMNSEZ994 01S7
53M Pdmene Are, Foot Pierm. FL 3012-
Td: 772-971-1951 F- 77246"M
EMM
HVHZ OR NON-HVHZ
RISK
EXPOSURE (EXP)
RISK
EXPOSURE (EXP)
RISK
EXPOSURE (EXP)
COUNTY
I
C
D
II
C
D
III, IV
C
D
P. BEACH
150 MPH
30.44 Psf
36.94 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
BROWARD
156 MPH
32.92 Psfj
39.95 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
MIAMI-DADE
165 MPH
36.83 Psf
144.69 Psf
175 MPH
141.43 Psf
50.28 Psf
1 186 MPH
46.80 Psf
56.80 Psf
BRAND & MODEL
CAPACITY
WIDTH
LENGTH
HEIGHT
WEIGHT
ALLOWABLE
PRESSURE
COMMENTS
Generac 005871 & 005883
10 KW
25.00 "
48.00 "
29.00 "
387 Ibs
41.43 Psf
EXP C 175 MPH 6 D 156 MPH
Generac 005872 & 005884
14 KW
25.00 "
48.00 "
29.00 "
439 Ibs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 6459, 6461, 6462
16 KW
25.00 "
48.00 "
29.00 "
513 Ibs
47.44 Psf
Generac 006721
16 KW
25.00 "
48.00 "
29.00 "
448 Ibs
47.44 Psf
Generac 005873 & 005885
17 KW
25.00 "
48.00 "
29.00 "
455 Ibs
47.44 Psf
Generac 005874 & 005986
17 KW
25.00 "
48.00 "
29.00 "
421 Ibs
47.44 Psf
Generac 005875 & 005887
20 KW
25.00 "
48.00 "
29.00 "
451 Ibs
47.44 Psf
Generac 006729 & 006730
20 KW
25.00 "
48.00 "
29.00 "
516 Ibs
47.44 Psf
Generac 006551 & 006552
22 KW
25.00 "
48.00 "
29.00 "
526 Ibs
47.44 Psf
Kohler 14RES & 20RES
14-20 KW
26.00 "
48.00"
29.00 "
500 Ibs
47.44 Psf
GE 40323GE & 40324GE
13 KW
35.00 "
39.40 "
39.00 "
540 Ibs
39.09 Psf
EXP
X C 170 MP' H&D156MPH
GE 04038215KW
15 KW
33.00 "
48.00 "
30.S0 "
484 Ibs
43.83 Psf
EXP C 180 MPH & D 156 MPH
-GE-04037817KVV
-17-KW
3.00-"-
48-.00-"-
-3(L50"-
841bs
43.83-Psf-
GE 40330GE & 40331GE
20 KW
33.00 "
48.00 "
30.50 "
600 Ibs
43.83 Psf
Briggs & Stratton 040243-0
10 KW
31.00 "
32.00 "
34.00 "
430 Ibs
43.83 Psf
Briggs & Stratton 040302-2
12 KW
33.75 "
S0.00 "
31.60 "
507 Ibs
41.43 Psf
EXP C 175 MPH & D 156 MPH
Briggs & Stratton 040303-1
15 KW
33.75 "
49.00"
31.60 "
562 Ibs
43.83 Psf
EXP C 180 MPH & D 156 MPH
Briggs & Stratton 040304-1
18 KW
33.75 "
49.00 "
31.60 "
568 Ibs
44.00 Psf
Briggs & Stratton 040305-1
20 KW
33.75 "
49.00 "
31.60 "
570 Ibs
44.00 Psf
Generac 7035, 7036, 7037
16 KW
25.00 "
48.00 "
29.00 "
406 Ibs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 007038 & 007039
20 KW
25.00 "
48.00 "
29.00 "
448 Ibs
47.44 Psf
Generac 007042 & 7043
1 22 KW
25.00 "
48.00 "
29.00 "
466 Ibs
47.44 Psf
GENERATOR MOUNTING CONFIGURATION:
GENERATOR ATTACHMENT BASE
OR SIMPSON A24 ANGLE BRACE
W/ (4) #10 SS 316 SELF -DRILLING
SCREWS
T TO GENERATOR
Q (SEE GENERATOR SPECS)
I I- GENERATOR
(SEE CONCRETE PAD
Lu w SCHEDULE FOR
DIMENSIONS & WEIGHT
= REQUIRED)
4"
EL
�--32" WIDTH+ }54" LENGTH+
m
SIDE VIEW FRONT VIEW
0
`u
0
V THICK GALVANIZED
WASHER& RUBBER
VIBRATION PAD
CONCRETE PAD
6,000 PSI
LIGHTWEIGHT
CONCRETE MIX
ANCHOR TO PAD SCHEDULE:
SUBSTRATE
DESCRIPTION
CONCRETE:
(2)-3/8" 0 TITEN HD
(6000 PSI
OREQUIVALENT,
MIN.)
2-3/4' FULL EMBED
0 CONCRETE, 3" MIN
EDGE DISTANCE, 6"
MIN. SPACING TO ANY
ADJACENT ANCHOR.
I
SCANNED
By
I
I
WIND DESIGN REQUIREMENTS-
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION
(2017))
AT -GRADE SIGN METHOD
ULTIMATE DESIGN WIND SPEED Vult = 186 mph
NOMINAL DESIGN WIND SPEED Vasd = 144 mph
RISK CATEGORY = III INTERNAL PRESSURE COEF = N/A
EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR Kd=
0.85
ENCLOSURE CATEGORY ='N/A HEIGHT H = AT GROUND
GUST EFFECT FACTOR = 0.85 PRESSURE AT HEIGHT H qh = 77.56
Ib/ft2
FORCE COEFFICIENT Cf = 1.44
WIND PRESSURE:
P = qh G Cf = 56.80 Ib/ft2 (ASD)
GENERAL NOTES
1. THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED IN
ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE
SIXTH EDITION (2017).
2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR USE WITH
THIS SYSTEM SHALL BE DETERMINED UNDER SEPARATE CERTIFICATION ON A
JOB -SPECIFIC BASIS IN ACCORDANCE WITH THE GOVERNING CODE.
SITE -SPECIFIC LOAD REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH
THE APPLICABLE BUILDING CODE SHALL BE LESS THAN OR EQUAL TO THE
DESIGN PRESSURE "ASD" CAPACITY VALUES LISTED HEREIN FOR ANY
NOTES:
ASSEMBLY AS SHOWN.
1. ANCHOR QUANTITY PER LONG SIDE
3.
DIMENSIONS AND WEIGHT OF UNITS SHALL CONFORM TO SPECIFICATIONS
2. EMBEDMENT AND EDGE DISTANCE
STATED HEREIN.
_.EXCLUDES_EINISHES,_IF
4.
UNITS MUST BE CENTERED ON PAD WITH OPPOSITE SIDES HAVING EQUAL
-A -MINIMUM -DISTANCE -PAD
APPLICABLE.
CLEARANCE. FROM UNIT TO EDGE IS SPECIFIED.
3. ENSURE MINIMUM EDGE DISTANCE
S.
6.
CALCULATIONS MADE.. I US NG LIGHTWEIGHT CONCRETE 125 PCF
THE AREA UNDER CONCERETE SLAB ON GROUND SHALL HAVE ALL
AS NOTED IN ANCHOR SCHEDULE.
VEGETATION, STUMPS, ROOTS, AND FOREIGN MATERIALS REMOVED PRIOR
4. ENSURE MINIMUM SPACING TO
TO INSTALLATION ON COMPACTED SOIL AS VERIFIED BY OTHERS.
ANY ADJACENT ANCHORS.
7.
RESISTANCE TO SLIDING OF THE PAD ON THE GROUND IS NOT PART OF THIS
S. FOLLOW MANUFACTURER'S
DOCUMENT AS SOIL CHARACTERISTICS AND PAD PLACEMENT VARIES.
INSTALLATION INSTRUCTIONS TO
B.
ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY
INSTALL ANCHORS.
OTHERS. ALL MECHANICAL SPECIFICATIONS (CLEAR SPACE, TONNAGE, ETC.)
SHALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE
EXPRESS RESPONSIBILITY OF THE CONTRACTOR.
9.
ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS
SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR, et. al.
INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES
INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM M-T
GENERATOR
IAL
FABRICATION, SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT
ATTACHMENT BASE,
WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES & FROM
VARIES WITH MODEL
DEVIATIONS OF THIS PLAN.
SEE GENERATOR SPECS
10.
WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL
RESPONSIBILITY OF THE INSTALLING CONTRACTOR. CONTRACTOR SHALL
GENERATOR %e' SIMPSON TITEN HD,
ENSURE THAT ANY REMOVED OR ALTERED WATERPROOFING MEMBRANE IS
SEE ANCHOR SCHEDULE
RESTORED AFTER FABRICATION AND INSTALLATION OF STRUCTURE
2"x3"x3/e" GALV. STEEL
PROPOSED HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
WASHER
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
RUBBER VIBRATION PAD
WATER -TIGHTNESS SHALL BE THE FULL RESPONSIBILITY OF THE INSTALLING
CONTRACTOR.
11.
THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF SPECIALTY
ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE
"
ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE
INTEGRITY OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL
BE COORDINATED BY THE PERMITTING CONTRACTOR.
Z
12.
THIS DOCUMENT IS GENERIC AND DOES NOT PERTAIN TO ANY SPECIFIC
CONCRETE PAD <
in
PROJECT SITE. INFORMATION CONTAINED HEREIN IS BASED ON
6,000 PSI
„I
-
CONTRACTOR -SUPPLIED DATA AND MEASUREMENTS. ENGINEERING EXPRESS
SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS
LIGHTWEIGHT
X CONCRETE MIX j j jj j jjj j jj j j jj j j j//
�I1
aOR
INACCURATE DATA OR MEASUREMENTS. DIMENSIONS R
ILLUSTRATE DESIGN FORCES AND OTHER DESIGN VARY
CRITER ATHEY MAY
` MASTERFIBER MAC 100 /j///j//j///j///j//
SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS SPECIFIED HEREIN,
WORK SHALL BE FIELD VERIFIED BY
%/////�
OTHERS PRIOR TO CONSTRUCTION.
& ROAD MESH /j%
ENGINEERING EXPRESS SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO
REEVALUATE OUR WORK UPON DISCOVERY OF ANY INACCURATE
2"
INFORMATION PRIOR TO MODIFICATION OF EXISTIN
FOAM CORE G F IELD CONDITION.
NOTES: AND FABRICATION AND INSTALLATION OF MATERIALS. ALTERATIONS OR
1. Y DISTANCE DEPEND ON GENERATOR BASE LENGTH, NO LESS THAN 2". ADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR
2. X DISTANCE 3" FROM UNIT EDGE TO CLIP. CERTIFICATION.
3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN 13. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS
ANCHOR REQUIREMENTS OR AFFIRMATIONS ARE INTENDED.
VK L. BENNAFPO, P.E.
0046549
03;�
CMECKED,C Fl7NG P.E. APPE5R5 BELOW
RDON M DIBATTISTO, P.E.
NATURE ON SHEET 1, THIS
EET IS PART OF A DIGITALLY
MED FILE, SHALL REMAIN IN
iITAL FORMAT, & PRINTED
PIES OF THIS DOCUMENT
E NOT CONSIDERED SIGNET
D SEALED. IF THERE IS NO
:ITAL SIGNATURE ON SHEET 1
THIS SHEET DOES NOT
NTAIN AN ENGINEER'S
[GINAL SIGNATURE & SEAL,
U ID N
Z o
'T 0
uJ
� M V, w 0
WUJ U'U) W X �A
WTI' O Lu Lu S�Fi
�wax
Z I- > U R Lu
l.J '<Q W w0
II1,11. OLmoz+z~
W W O N -1m w W U
O,4UJ'0-
� UL 0
U) ct =
oLu uj
W w
� Q
rn Q z
O d- 0
J ~
LLI
C7 O
Z LU
Q LL Ln
Q_ 0 .
ri-
Y x
N I-
NM -x
U Lu 1
w
Wp
W
cc) 00 2
0
LU a�ri
ozu
g
C cn O [�
W ..
z
Q m
Y � �
W
ti m
Ln
Lu Q a
d
O
W
a a OJ � NOZZ
CI g�gCF
z
Y.n
W co[O R. U O
= U J J OwpF
zog
0 0 O oizo¢
o�5g wWw==
w
�oW
0
co
w Qo w'o-�z
Y w o > >zc�iy�
K Q U oC
o m g
w w Noi2
z 0 N -1a31.
COPYRIGHT ENGINEERING EXPRESS e
17-3961.1
SCALE: NTS UNLESS NOTED
OF