HomeMy WebLinkAboutKSM-wSCANNED
KELLER, SCHLEICHE
MARTIN (772) 337-7755 PO.
PALM BEACH (561) 845-7445
FAX (561) 845-8876
C.A.: 5693
R & MacWILLIAM ENGINEERING AND TESTING, INC.
BOX 78-1377, SEBASTIAN, FL 32978-1377 SEBASTIAN (772) 589-0712
www.ksmengineering.net MELBOURNE (321) 768-8488
E-Mail: KSM@KSMENGINEERING.NET ST. LUCIE (772) 229-9093
FAX (772) 589-6469
I
March 8, 2018
Secure Gas, Inc.
13660 77th Drive
Sebastian, Florida 32958
Re: 1000 Gallon Underground Tank
3006 Bent Pine Drive
Ft. Pierce, Florida
KSM Project #: 171550-lpgas
I
Dear Sir:
Please see attached detail for how to tie down the 1000 gallon underground tank
at the referenced site. The following are general notes concerning the attached
drawing.
1. Prior to installing the earth augers, check for underground utilities.
2. Earth auger and cables shown are designed to resist buoyancy forces
from an empty tank fully submerged.
3. Earth augers type and length is dependent of Soil Class. For this site soil
is assumed as Class 4 Soil. If the onsite soils are not Class 4, engineer is
to be notified.
4. Earth auger shall have a tested minimum pull out value of 3000 lbs.
5. Location of tanks are dependent on local codes and are the responsibility
of the persons obtaining the�permit.
Please accept this letter as certification that it is our intent to meet the regulations
as specified in Section 930.07(2)(g) of Indian River County's Land Development
Code
Iestions,
eNse
• o
s
A
Fax to:: ? 0229
please feel free to contact the office.
' � � �,� � - � !j � alai � y •A•(
a f
Ronald G. Keller, P.E.: 37293 / SI Lic. No.: 860 / Julie E. Keller, P.E.: 68366
GROUND LEVEL
`1/4" GALVANIZED VINYL COATED
10 0 0' GAL
C\\ \\\\\ \\\\ \\\ LP G A S
TANK
/ WIRE ROPE W/ CABLE CLAMP,
/ \ (4 REQUIRED)
5/8" x 48" TRAILER ANCHOR
1WITH 6" HELIX
\ \ / (8 REQUIRED)
MY
GROUND LEVEL`,
\/\ 1/4" GALVANIZED VINYL \
COATED WIRE ROPE \/
4 REQUIRED \ \
1000 GAL.
LP GAS 518" x 48" TRAILER ANCHOR \\
TANK WITH 6" HELIX /\
\\ 8 REQUIRED
/\ /\ / //ice//ice//ice. /ice//ice//ice - � •,�� / /j .
ENGINEERS SEAL SHOULD BE BLUE IN COLOR; IF NOT •,,� p` •`�\/\/
\ \ \ CONTACT ENGINEER TO VERIFY SEAL IS AUTHENTIC
PROJECT: SECURE GAS: 3006 Bent Pine Drive, Ft. Pierce Florida
SHEET 1 OF 1 ,_; I %k Aff ENGINE RING AWN BY: JK DESIGNED GNED BY. X
PROJECT NO.: 171550 SCALE: 03NON2E 18