REVIEW COMMENTS
e1
Owner(s):
John R Moran
Jurisdiction: SAINT LUCIE COUNTY
Lot#: 85
Stories:
Permit Type: BUILDING RESIDENTIAL (SFR UP TO 2 FLOORS)
CONTRACTOR INFORMATION
Contractor Name:
Business Name:
Business Addr:
City / State / Zip: ,
REVIEWS AND COMMENTS
Block:
Automatic Sprinkler System? No
Fax Number:
Email:
Review Tvae Status Reviewed By Date Started Date Completed Date Released
DOCUMENTS MISSING PENDING Deanna Givens 4/12/2018
4/12/2018 Comment: VEG PERMIT SENT TO ERD.
VEG PERMIT IN DRAWER UNDER "M" MORAN. FEE LOADED
4/12/2018 Comment:
PLUMBING SUB AGREEMENT
4/18/2018 Comment:
MECHANICAL SUB AGREEMENT
4/18/2018 Comment:
E Lt CTRICAL SUB AGREEMENT
4/18/2018 Comment:
ROOF SUB AGREEMENT
ENVIRONMENTAL REVIEW
COMPLETE Lynn Swartzel 4/22/2018 5117/2018 5/17/2018
Comment:
1
FRONT COUNTER REVIEW
COMPLETE Deanna Givens 4/12/2018 4/12/2018 4/12/2018
Comment:
PLANS EXAMINER REVIEW
INCOMPLETE William•Durden 7/10/2018
\ Comment: /
-ALL DOCUMENTS SUBMITTED FOR PERMITTING MUST BE IN DUPLICATE. ANY DOCUMENTS THAT
7/1112011
REQUIRES A SIGNATURE OR SEAL MUST BE SUBMITTED IN DUPLICATE WITH ORIGINAL SEALS AND
SIGNATURES. PLEASE SEE THE 2017 FLORIDA BUILDING CODE CHAPTER 1, SUBSECTION 107.1.
Comment
PLEASE SEE NOTES ON PAGE Al ENERGY EFFICIENCY REQUIREMENTS, NOTE 4. PLEASE SUBMIT THE
7/10/2018 1
PRODUCT INFORMATION SHEETS FOR THE EXHAUST FANS AND LOUVERS. THE SECTION 107 OR 2017
FLORIDA BUILDING CODE.
Comment:
- COULD NOT COMPLETE MY REVIEW DUE TO NO PRODUCT APPROVALS THAT WERE SUBMITTED FOR
7/10/2018 /
REVIEW ARE NOT HIGHLIGHTED SPECIFYING WHICH APPLICATION IS TO BE INSTALLED. PLEASE SEE
1
CHAPTER 1 SECTION [A] 107.2.1 OF THE 2017 FLORIDA BUILDING CODE.
Planning & Development Services
Building & Code Regulation Division,
2300 Virginia Avenue
Fort Pierce, FL. 34982
Phone:(772)462.2172 Fax:(772)462-6443
REVIEW COMMENTS
I
I Page 2
Comment:
• IF SUBMITTING 2 COPIES OF PRODUCT APPROVAL'S (I.E. N.O.A. OR STATE OF FLORIDA APPROVAL) IN
7/10/2018
LUE OF THE PRODUCT APPROVAL AFFIDAVIT DOCUMENTS MUST BE HIGHLIGHTED OR MARKED
IDENTIFYING THE OPENING OR CLADDING COMPONENTS, WITH FASTENERS AND DESIGN PRESSURES.
Comment:
• PLEASE FURNISH THE MANUFACTURES TRUSS PLACEMENT DRAWINGS IN DUPLICATE REVIEWED AND
7/10/2018
APPROVED BY THE DESIGN PERSON OF RECORD IN ACCORDANCE WITH CHAPTER 8 SECTION R802
Comment:
SUBSECTION R802.1.7.1 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE.
• PLEASE FURNISH TR ISS ENGINEERING IN DUPLICATE
7/10/2018
PER CHAPTER 8 SECTION R802 SUBSECTION
R802.1.7.1 OF THE 2017 FLORIDA RESIDENTIAL BUILDING CODE.
Comment:
• THE TRUSS ENGINEERING MUST HAVE THE ORIGINAL SIGNATURE OF THE TRUSS MANUFACTURER'S
ENGINEER. REVIEWEDIAND APPROVED BY THE DESIGN PROFESSIONAL IN CHARGE. PLEASE CORRECT
7/10/2018
AND SUBMIT IN DUPLICATE. IN ACCORDANCE WITH 61G15-30.005 OF THE FLORIDA ADMINISTRATIVE CODE.
AND CHAPTER 8 SECTION R802 SUBSECTION R802.1.7.1 OF THE 2017 FLORIDA RESIDENTIAL BUILDING
CODE. i
7/10/2018 Comment:
PAGE Al, TERMITE PROTECTION HAS THE 2014 BUILDING CODES SPECIFIED. PLEASE CORRECT AND
RESUBMIT TO THE CURRENT BUILDING CODES. SEE SECTION 107 2017 FLORIDA BUILDING.
Comment:
SUBMIT THE PRODUCT INFORMATION DATA SHEETS FOR THE LIQUID BORATE OR BORA-COR PRODUCT
7/10/2018
AS PER THE PLANS ON PAGE Al TERMITE PROTECTION. SEE SECTION 107 OF THE 2017 FLORIDA
BUILDING CODE
Comment:
r
SEE CONCRETE NOTE SECTION ON PAGE A-2, FOOTING AND FOUNDATIONS, PLANS SPECIFY
COMPACTED FILL MATERIAL LESS THAN 12 INCHES IN DEPTH SHALL BE COMPACTED TO 90% MODIFIED
7/10/201 B
PROCTOR. PLEASEISEE SURVEY PLANS SPECIFY MORE THAN 12 INCHES OF FILL TO BE INSTALLED.
PLEASE PUT ON THE PLANS THE SOIL DENSITY OR SUBMIT GEOTECHNICAL REPORT IN COMPLIANCE
WITH R401 OF THE�2017 RESIDENTIAL BUILDING CODE.
Comment:
A DWELLING UNIT �ATTACHED TO A HANGER MUST HAVE NOT LESS THAN A ONE HOUR FIRE BARRIER
7/10/2018
AND SHALL BE CONTINUOUS FROM THE FOUNDATION TO THE UNDERSIDE OF THE ROOF AND BE
UNPIERCED EXCEPT FOR DOORS AS REQUIRED IN 412.5.1 OF THE FLORIDA BUILDING CODE PLEASE
FURNISH AN APPROVED RATED ASSEMBLY
Comment:
PLEASE SHOW A"SINGLE STATION SMOKE ALARM. IT SHALL BE INTERCONNECTED INTO THE
7/10/2018
RESIDENTIAL SMOKE ALARMS AND BE AUDIBLE IN ALL SLEEPING ROOMS 412.5.2 OF THE 2017 FLORIDA
BUILDING CODE
7/10/2018 Comment:
PLEASE FURNISH PRODUCT APPROVAL FOR THE HANGER DOOR AND LOUVERS AS REQUIRED BY 553.842
OF THE FLORIDA STATUES
7/10/2018 Comment:
PLEASE FURNISH DETAILS FOR GUARDS ON STAIR AND BALCONY MEETING THE REQUIRMENTS OF 312.3
OF THE 2017 FLORIDA RESIDENTIAL CODE
Comment:
I
ELECTRICAL, MECHANICAL AND PLUMBING SHALL INDEPENDENT OF THE SYSTEMS IN THE HANGER THE
7/10/2018
SMOKE DECTOR WIRING AND FEEDERS FOR ELECTICAL SUBPANELS CAN TIE INTO MAIN PANEL BUT CAN
NOT PASS THROUGH FIRE BARRIER INTO HANGER PLEASE SHOW LOCATION OF SUBPLANELS AS
Comment:
REQUIRED IN 412.3 OF THE 2017 FLORIDA RESIDENTIAL CODE
DOORS INTO1A DWELLING UNIT FROM A HANGER MUST BE EQUIPPED WITH SELF CLOSING DEVICES AS
7/10/2018
REQUIRED IN 412.5.1 OF THE 2017 FLORIDA BUILDING CODE.
Comment:
PLEASE ADD THE CUBIC VOLUME OF THE CONDITIONED SPACE TO INFORMATION BLOCK CONTAINING
7/10/2018
THE SQUARE FOOT INFORMATION OR A LETTER FROM THE DESIGN PROFESSIONAL SPECIFYING THE
CUBIC VOLUME OF THE CONDITIONED SPACE. SEE CHAPTER 1 SECTION 107 OF THE 2017 FLORIDA
BUILDING CODE.
Comment:
I
• PLEASE SUBMIT THE ENERGY PERFOMANCE SHEETS OR SUBMIT A THE NFRC FENSTRATION
7/10/2018
MANUFACTURE CERTIFICATE FOR THE U-FACTOR AND THE SHGC FOR EACH GLAZED OPENING SHOWING
COMPLIANCE WITH CHAPTER 4 SECTION 402.1.1 OF THE 2017 ENERGY CODE SIXTH EDITION.
Comment:
• PLEASE FURNISH ENEGRY CALULATIONS AND MANUAL J IN ACCORDANCE WITH SECTIONS 402 AND 403
7/10/2018
OF THE 2017 FLORIDA ENEGRY CODE FIFTH EDITION. NOTE ONLY; ENERGIES MUST HAVE ORIGINAL
SIGNATURE OF PREPARER
Comment:
PLEASE SEE PAGE D1 ENGINEERING DATA, INCORRECT BUILDING CODE. • PLEASE FURNISH DESIGN
CRITERIA INCLUDING BUT NOT LIMITED TO WIND LOAD,DESIGN PRESSURES, EXPOSURE CATEGORY, RISK
7/10/2018
CATEG YAND DESIGN CODES IN ACCORDANCE WITH SECTION 301 OF THE FLORIDA RESIDENTIAL
CODE
�
7/10/2018 Comment:
• PLEASE ADD TO THE PLANS THE CLIMATIC AND GEOGRAPHIC DESIGN CRIERIA WEATHERING AND
TERMITE AREA IN ACCORDANCE WITH TABLE 301.2.(1)
7/10/2018 Comment:
• PLEASE SHOW FLAME SPREAD INDEX AND SMOKE DEVELOPED INDEX FOR WALL AND CEILING FINISHES
IN ACCORDANCE WITH SECTION 302.9 OF THE 2014 FLORIDA RESIDENTIAL CODE
Comment:
• PLEASE SHOW THE FLAME SPREAD AND SMOKE DEVELOPED INDEX FOR THE INSULATION AS
7/10/2018
REQUIRED IN SECTION 302.10 OF THE 2014 FLORIDA RESIDENTIAL CODE
I
1
Planning& Development Services ' REVIEW COMMENTS
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL. 34982
Phone:(772)462-2172 Fax:(772)462-6443
Page 3
7/10/2018 Comment: • PLEASE SHOW GYPSUM BOARD MATERIALS ARE IN ACCORDANCE WITH 702.3.1 OF THE 2017 FLORIDA
RESIDENTIAL CODE
Comment: • SHOW FLASHING DETA10N PLANS FOR ALL EXTERIOR WINDOWS AND DOORS. SEE SECTION R612.10
7/10/2018 FLASHING, SEALANTS, AND WEATHER STRIPPING, AND R703.8 FLASHING OF THE 2017 FLORIDA
RESIDENTAL BUILDING CODE.
I
Comment: • PLEASE FURNISH A INTERIOR STAIR DETAIL SHOWING STAIR WIDTH, HEADROOM, RISER HEIGHT,
7/10/2018 TREAD DEPTH, HAND RAILIHEIGHT AND GRIP SIZE IN ACCORDANCE WITH SECTION R311.7 AND R312 OF
THE 2017 FLORIDA RESIDENTIAL CODE
7/10/2018 Comment: • PLEASE FURNISH DETAIL FOR EXTERIOR GUARD RAILS BEING IN ACCORDANCE WITH SECTION 312 OF
THE 2017 FLORIDA RESIDENTIAL CODE
1
7/10/2018 Comment: • PLEASE FURNISH A INTERIOR WALL DETAIL SHOWING STUD SPACING, STUD SIZE, AND WALL FINISH IN
ACCORDANCE WITH 602.2� OF THE 2017 FLORIDA BUILDING CODE
1
7/10/2018 Comment: • PLEASE SHOW ON PLANS DOOR FROM GARAGE TO HOUSE MEETING THE REQUIREMENTS OF R302.5 OF
THE 2017 RESIDENTIAL BUILDING CODE. DOOR MUST BE SELF -CLOSING.
I
7/10/2018 Comment: • PLEASE FURNISH PLUMBING RISER DIAGRAM BEING IN ACCORDANCE WITH 3004 AND 3005 OF THE 2017
FLORIDA RESIDENTIAL CODE.
1
7/10/2018 Comment: • PLEASE FURNISH A DUCT PLAN SHOWING A BALANCED SYSTEM, DUCT SIZE, GRILL SIZE, AND ROOM BY
ROOM CFMS PER 107.2.1 OF THE 2017 FLORIDA BUILDING CODE
I
7/10/2018 Comment: • PLEASE COMPLETE THE GAS PIPING SCHEMATIC WORK SHEET
7/10/2018 Comment: • SUBMITTED DOCUMENT S MUST BE IN DUPLICATE. SEE SECTION 107.1 OF THE 2017 FLORIDA BUILDING
CODE.
Comment: • PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE
7/10/2018 SUBMITTED DOCUMENTS. ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED
DOCUMENTS.
ZONING REVIEW INCOMPLETE Angela Huff 4/18/2018
4/19/2018 Comment: THE FLORIDA BUILDINGICODE CONSIDERS AN AIRPLANE HANGAR OVER 2000SF TO BE COMMERCIAL;
BECAUSE OF THE SIZE OF THIS HANGAR A GENERAL CONTRACTOR MUST PULL THIS PERMIT.