HomeMy WebLinkAboutGENERATOR ADDITION RISER DIAGRAM0 ABBREVIATIONS: AC ALTERNATING CURRENT MDP MAIN DISTRIBUTION PANELBOARD A/C AIR CONDITIONING MTS MANUAL TRANSFER SWITCH AFG ABOVE FINISHED GRADE MLO MAIN LUGS ONLY AL ALUMINUM NEC NATIONAL ELECTRICAL CODE AHU AIR HANDLING UNIT NTS NOT TO SCALE ATS AUTOMATIC TRANSFER SWITCH NEMA NATIONAL ELECTRICAL MANUFACTURERS AMP AMPERE ASSOCIATION AFCI ARC FAULT CIRCUIT INTERRUPTER NFPA NATIONAL FIRE PROTECTION ASSOCIATION ANSI AMERICAN NATIONAL STANDARDS INSTITUTE NON -SE NON SERVICE ENTRANCE RATED C CONDUIT PLCS PLACES (QUANTITY) CU COPPER CONDUCTOR PNL PANEL COVB CITY OF VERO BEACH PVC POLYVINYL CHLORIDE CONDUIT DC DIRECT CURRENT RMC RIGID METAL CONDUIT DISC DISCONNECT RTU ROOFTOP UNIT EXIST EXISTING SE SERVICE ENTRANCE RATED FPL FLORIDA POWER & LIGHT TYP TYPICAL G GROUND TEMP TEMPORARY GFCI GROUND FAULT CIRCUIT INTERRUPTER UG UNDERGROUND IRC INDIAN RIVER COUNTY UL UNDERWRITERS LABORATORY KVA KILOVOLTAMPERE UON UNLESS OTHERWISE NOTED KW KILOWATT V VOLT MC METAL CLAD CABLE VA VOLTAMPERE MCB MAIN CIRCUIT BREAKER W WATT MCC MOTOR CONTROL CENTER XFMR TRANSFORMER (EXISTING) SCANNED By 1 50 AMP150 AMP SE RATED ATS PANELLGENERAC GENERATOR: 10DAMP Em BREAKER GRADE SCOPE OF WORK: • INSTALL 150AMP SE RATED ATS NEXT TO UTILITY METER CAN ON EXTERIOR WALL. • RE -FEED INTERIOR MAIN PANEL, SEPARATE NEUTRALS AND GROUNDS IN MAIN PANEL INSTALL COLD WATER BOND FROM ATS TO NEAREST CU WATER PIPING. • UTILIZE A PRE -FABRICATED GENERATOR PAD. • PROVIDE AND INSTALL (1) 22kW GENERAC LP GAS GENERATOR. • PROVIDE AND INSTALL CONDUIT AND CONDUCTORS FOR FROM ATS TO GENERATOR. • LOAD SHED PER SIZING DATA THIS SHEET. • GENERATOR LP GAS CONNECTION BY FERRELLGAS AS A SUBCONTRACTOR UNDER THIS PERMIT. • NEW LP TANK TO BE PROVIDED AND INSTALLED BY FERRELLGAS UNDER A SEPARATE PERMIT. • NO NEW BRANCH CIRCUIT LOADS SHALL BE ADDED TO HOUSE PANEL UNDER THIS SCOPE OF WORK. ELECTRICAL LEGEND: —F_�_ SURFACE MOUNT 120/204V, 10, 3-WIRE PANELBOARD FLUSH MOUNT 120/204V, 10, 3-WIRE PANELBOARD _L:;� SURFACE MOUNT 277/480V, 30, 4-WIRE PANELBOARD (EXISTING) WATER LINE 0 (EXISTING) 150 AMP METER CAN 120/240 14 FLUSH MOUNT 277/480V, 30, 4-WIRE PANELBOARD UTILITY METER CAN OR METER/MAIN COMBO UNIT SURFACE MOUNT AUTOMATIC TRANSFER SWITCH POINT OF NEW CONNECTION (EXISTING) (2) 5/8" X 8' CU GROUND RODS FRAME SIZE 3NFR 3Rf NEMA RATING NON FUSE. NON -FUSED DISCONNECT FRAME SIZE 3R 3Rf NEMARATING FUSED DISCONNECT V Y - FUSE SIZE GENERATOR AND GENERATOR PAD O= GAS STORAGE TANK GRADE GENERAL NOTES: • THE ELECTRICAL CONTRACTOR SHALL VERIFY AND COORDINATE ALL ELECTRICAL SERVICE ROUGH IN AND INSTALLATION DETAIL WITH THE LOCAL UTILITY POWER COMPANY. • THIS ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 6TH EDITION (2017), LOCAL ORDINANCE, AND THE NATIONAL ELECTRIC CODE THIRTEENTH EDITION NFPA 70 (2014). • ALL ELECTRICAL WORK FOR THE ENTIRE PROJECT SHALL BE PERFORMED IN A NEAT AND CRAFTSMAN LIKE MANNER BY PERSONS SKILLED IN THE ELECTRICAL TRADE, AND SHALL BE DONE UNDER THE SUPERVISION OF A MASTER ELECTRICIAN LICENSED IN THE STATE OF FLORIDA. • THIS ELECTRICAL INSTALLATION SHALL BE PROTECTED FROM PHYSICAL DAMAGE AND SECURELY SUPPORTED AND FASTENED, WITH WORKING SPACE PER NEC 110.26. • PVC SCHEDULE 40 CONDUIT SHALL BE USED UNDERGROUND, IN OR BELOW CONCRETE AND WHERE EXPOSED NOT SUBJECT TO DAMAGE. PVC SCHEDULE 80 CONDUIT SHALL BE USED WHERE EXPOSED, SUBJECT TO DAMAGE. • ALL MATERIAL SHALL BE NEW, FREE FROM DEFECT AND SHALL BE LISTED AND BEAR THE LABEL OF A RECOGNIZED TESTING LABORATORY. • GROUNDING PER NEC ARTICLE 250. • STANDBY SYSTEM INSTALLATION PER NEC ARTICLE 702, AND MANUFACTURER INSTALLATION INSTRUCTIONS, LOAD MANAGEMENT "LCM" LOAD SHED LOAD MANAGEMENT TECHNOLOGY ALLOWS THE LOAD CONTROL MODULE TO MONITOR GENERATOR PERFORMANCE AND ONLY SHED LOADS WHEN ABSOLUTELY NECESSARY BY MONITORING GENERATOR CURRENT AND FREQUENCY. BY ONLY SHEDDING THE NONESSENTIAL CIRCUITS, THE ESSENTIAL CIRCUITS ARE ALWAYS POWERED. LOADS ARE SHED THROUGH INTERRUPTION OF INDIVIDUAL CONTROL CIRCUITS (AHU/AC) AND POWER CIRCUITS (RANGE AND WATER HEATER). NO �A.E GENERATOR ADDITION RISER DIAGRAM GENERAL NOTES: 1. LIGHT LINE WORK REPRESENTS EXISTING TO REMAIN. 2. DARK AND RED LINE WORK REPRESENT NEW EQUIPMENT, CONDUIT, AND WIRE. CONDUIT AND WIRE SCHEDULE SYMBOL DESCRIPTION OA (EXISTING) 2-PVC UNDERGROUND SERVICE FEEDER O (EXISTING) OVERHEAD SERVICE FEEDER © (EXISTING)1/2"PVC #4 BARE CU Op 2-PVC Wl (3) #210 THWN AL O 2-PVC Wl (3) #210 THWN AL, (1) 06 THHN CU GROUND O 14/2"PVC SLEEVE W1 GENERAC CABLE W/ (3) #3 THHN CU, (1) 8 THHN GROUND, (6) #14THHN CU © 1414"PVC WI (3) #3 THHN CU, (1) #8 THHN CU GROUND ® 314"PVC W/ (7) #14 THHN CU Oj 1/2-PVC W1(1)#4 BARE CU COMPLETE ELECTRIC INC. 637 SEBASTIAN BLVD. SEBASTIAN, FL 32958 (772) 388-0533 Sizing Report Rated Nominal Voltage 240 Generator Fuel Choice Propane Sizing Method (NEC 220) Part IV (Part III required for selected circuit Implementation, Both valid for whole house) General Lighting & Receptacles Square Footage Being Covered (ftA2) 1100 Small Appliance Circuits (20 amps) Kitchen Circuits 2 Laundry Circuits 1 GENERAC wammmm Load (kW) 3.3 3 1.5 Managed Estimated Nameplate Fb(ed-In-Place Appliances & Motors Loads (kW) (amps) 240 V Load (k" Microwave - 1.3 1.3 Range -Oven w/Top 8.5 X 8.5 Dishwashe• 1.5 1.5 Freezer Refrigerator We0 Pump Water Healer 0.8 1.5 5.0 0.8 1.5 5.0 Air Conditioning & Cooling Managed Estimated Loads (kW) Nameplate (amps) 240 V Load (kW) 2.5 Ton Unit X 2.5 X 0.0 Managed Estimated Nameplate Heating & Heat Pumps Loads (kW) (amps) 240 V Load (kW) heating element #1 X 0.0 32 X 0.0 Estimated Actual Utilized Transient Requirement (LRA) (LRA) (LRA) Largest Motor's Starling Amps (LRA) 221 67 67 Load NEC Summary NEC Load (kW) Required General Lighting & Receptacles 7.8 Fbed-in-PlaceAppliances & Motors 19.4 Sum of all General Loads 27.2 16.9 Cooling 0 0 Heating (wldemand factors) 0 0 Larger of Heating & Cooling 0 0 Sizing based on requirements of NEC Article 220, Part IV 16.9 Elevation 0 R Minimum size generator for motor starting requirements 9 BTU load required 324000 22 kW Generac Model Generator Recommended Z4S�k�I. oLO (5XN WZMco V a LLLL O WQco ZOOD m.Q W U C/) (0 LLI m O U �E�(D 0- J� U_O J Es-- LU W In LL 0¢ LL WmmU _ D wCo 0=W Omon. LU �O Z LL E1 04/09/2018 Si R' 1 OF 3 2 (NEW) 500 GAL QQV LP TANK LOCATION (NEW)GENERATOR PAD LOCATION MIN. (NEW) ATS LOCATION O (EXISTING) UTILITY METER LOCATION 3•-0•• MIN. (EXISTING) INTERIOR HOUSE PANEL CAR I I I h PORT COVERED PATIO • • 4 DRIVEWAY . do19 . '00. 0 SINGLE FAMILY RESIDENCE 7802 HIBISCUS RD. FORT PIERCE. FL 34951 SHED 1 N 10'_o. GENERATOR SITE PLAN W +XXE S Z'sUN � Lo 0) 04 04 RzMch LU u- 9 m WQQami m W U) co m coco LLI 0 U � \ Uo �U o �Jww� CD Ixc gO J j LL Wmm_Lj U w0=W Amc-jon. f U.,m z O E2 04/09/2018 2OF3