HomeMy WebLinkAboutPROJECT INFORMATION-�- wNg'htsoft® Project Summary Date: Mar02, 2018 Enure House I BY: QUICK CALCS, INC 11 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fa 1772-466-6796 Email: QUICKCALCS@AOL.COM For: CHESSER RESIDENCE, GEM BUILDERS 1317 LONE PINE LANE, FORT PIERCE, FL Notes: Weather: I Fort Pierce, FL, US Winter Design Conditions I Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF, Design TD 15 OF Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Structure 33302 Ducts 7328 Central vent (0 cfm) 0 Humidification 0 Piping 0 Equipment load 40630 Infiltration Method S Construction quality Fireplaces Heating Area (ft2) 2393 Volume (W) 24923 Air changes/hour 0.32 Equiv. Avr- torn) IJJ Heating Equipment Summary Sensible Cooling Equipment Load Sizing Structure 29687 Btuh Ducts 1484 Btuh Central vent (0 cfm) 0 Btuh Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 29613 Btuh Latent Cooling Equipment Load Sizing Structure 4176 Btuh Ducts 2839 Btuh Central vent (0 cfm) 0 Btuh Equipment latent load 7016 Btuh Equipment total load 36629 Btuh Req. total capacity at 0.70 SHR 3.5 ton Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTR6042J1 AHRI ref Coil TEM4AOC42S41++TDR AH R I ref 8703699 Efficiency 100,EFF Efficiency 13.0 EER, 16 SEER Heating input 12.4 ikW Sensible cooling 28700 Btuh Heating output 42424 Btuh Latent cooling 12300 Btuh Temperature rise 28 OF Total cooling 41000 Btuh Actual air flow 1367 cfm Actual air flow 1367 cfm Air flow factor 0.034 ;cfm/Btuh Air flow factor 0.044 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.82 C0phi' Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Mar-02 10:04:31 A wrl htsoft° 9 Right -Suite® Universal 2017 17.0.08 RSU08101 Page 1 E:1DocumnetslWrightsoft HVAC\CHESSER RESIDENCE.rup Cale = MJ8 Front Door races: N -�- wrightsoft Right-JO Worksheet Entire House i QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772A66-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM Job: Date: Mar02, 2018 By: 1 Room name Entire House MASTER BEDROOM 2 Exposed wall 246.9 ft 48.0 ft 3 Room height 10.4 ft 11.0 ft heat/cool 4 Room dimensions 1.0 x 378.5 ft 5 Room area 2393.0 ft2 378.5 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2 Load number (Btuh/fVL'F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cwl Gross WP/S Heat Cool Gross WP/S Heat Cool 6 13A-4ocs 2glazing, clrlow-e 2 glazing, clr low-e O.f'43 0.650 0.650 n n n 4.00 18.20 18.20 -1 2.19 14:99 11499 '. 376 20 24 254 0 0 1017 364 437 -556 300 360 0 0 0 0 0 0 0 0 0 0 0 0 11 2 glazing, clrlowoe 2 glazing, clr low-e 0.650 0:650 n n 18.20 18.20 14:99 114.99 24 48 0 0 437 874 360 720 0 0 0 0 0 0 0 0 13A-4ocs 2 glazing, clr low-e 2 glazing, clr low-e 0.143 0.650 0.650 a a a 4.00 18.20 18.20 2.19 30.39 32.08 806 16 8 677 6 1 2709 291 146 1480 486 257 264 16 0 248 3 0 993 291 0 543 486 0 2 glazing, cir low-e 2 glazing, clr low-e 0.650 0.650 a a 18.20 18.20 132.42 32.93 20 21 3 2 364 388 648 702 0 0 0 0 0 0 0 0 2 glazino, cir low-e 13A4ocs 2 glazing, clr low-e 0.650 0.143 0.650 a s s 18.20 4.00 18.20 132.93 , 2.19 14.99 64 580 15 . 6 433 30 1165 1732 273 _ 2107 946 225 0 110 15 0 95 15 0 380 273 0 208 225 2 glazing, cir low-e 2 glazing, cir low-e 0.650 0.650 s s 18.20 18.20 14.99 14.99 40 20 80 41 728 372 600 306 0 0 0 0 0 0 0 0 2 glazing, clr low-e 13A4ocs 2 glazing, cir low-e 0.650 0.143 0.650 s sw sw 18.20 4.00 18.20 14.99 2.19 23.31 72 78 47 144 30 29 1310 122 861 1079 67 1103 0 78 47 0 30 15 0 122 861 0 67 1103 11,V Y-G 13A40cs 2 glazing, cir lower 2 glazing, cIr low-e 0.143 0.650 0.650 w w w 4.00 18:20 18.20. 2.19 . 30.39 32.42 745 8 20 667 3 3 2671 146 364 1459 243 648 77 0 0 62 0 0 248 0 0 136 0 0 2 giazi% or low-e 2 glazing, cir low-e 0.650 0.650 w w 18.20 18.20 32.42 32.42 30 20 4 3 546 364 . 973 648 15 0 1 0 273 0 486 0 C 16A30nid 0.032 0.90 2.24 2392 2392 2143 5357 379 379 339 848 ,. F 22A-tph. 1.358 - 3802 0,00 2392 247 :9389 0 379 48 1825 0 6 c)AED excursion 0 317 Envelope loss/gain 29212 21632 5606 4419 12 a) Infiltration 4090 1096 839 225 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 2 460 0 0 Applianceslother 6500 0 Subtotal (lines 6 to 13) 33302 29687 6445 4643 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 33302 29687 6445 4643 15 Duct loads 22% 5% 7328 1484 22% 5% 1418 232 F1Total room load 40630 31172 7863 4876 Air required (cfm) 1367 1367 265 214 Calculations approved bV ACCA to meet all requirements of Manual J 8th Ed. wrightsci t- RightSuiteO Universal 2017:17.0.08 RSU08101 2018-Mar-02 1 Page 1 E:\Documnets\Wdghtsoft HVACICHESSER RESIDENCE. rup Calc = MJ8 Front Door faces: N -�- wrightsoftm Right-M Worksheet Entire House QUICK CALCS, INCH. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM Job: Date: Mar02, 2018 By: 1 Room name M WIC 1 M WIC 2 2 Exposed wall 12.0 ft 1.0 ft 3 Room height 10.0 ft heaticool 10.0 ft heat/cool 4 Room dimensions 6.0 x 12.0 ft 6.0 x 7.0 ft 5 Room area 72.0 ftz 42.0 ft2 Ty Construction U-value Or HTM Area (ft) Load Area (ft2) Load number (Btuh/ft2- F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat C Gross N/P(S Heat Cool Gross NIP/S Heat Cool 6 11 W 13A4ocs 2 glazing, cir low- 2 glazing, clr low-e 2 glazing, clrlow-e 2 glazing, cir low-e 13A4oes 2 glazing, cir lovo-e 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 plazinp, clr low-e 13A-0acs 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing,_clr low-e - 13A-4ocs 2 glazing, cir low-e 13A4ocs 2 glazing, cir low-e 2 glazing, clr love o A43 0.650 0.650 0.650' 0.65Q 0.143 0.650 0.650 0.650 0.650 0.650 0.143 0:650 0.650 0.650 0.650 0.143 0.650 0.143 0.650 0.650 n n n n n a a a a a _ e s s s s s sw sw w . w w 4.00 18.20 18.20 18.20 18.20 4.00 18.20 18.20 18.20 18.20 18.20 4.00 18.20 18.20 18.20 18.20 4.00 18.20 4.00 18.26 18.20 lool - j 2.19 14.99 114.99 . 114'.99 14.99 2.19 30.39 32.08 32.42 32.93 32.93 12:19 14.99 114.99 14.99 114.99 1 2.19 123.31 3 2.19 130.39 . 132:42 0 0 0 0 0 120 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0_ 120 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 480 0 0 0 0 0 0 0 0 0 0 0 _0 0 0 0 0 0 0 0 0 263 0 0 0 0 .- 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0- 0 0 10 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 22 0 0 VN Y-G 2 glazing, clrlow-e 1 g�lazzi� cir 22A-tph - 0.650 650 0. 1.358 w ,w- . - 18.20 18.2 0 38.02 132.42 3242 . 1 0.00 1 0 0 72 72 0 0. 72 12 0 0 65 - 456 - 0 ,, 0 161 0 0 0 42 42 0 0. 42 1 0 0 38 38 0 0 94 0 C F 6 c)AED excursion -18 -5 Envelope loss/gain 1001 406 116 111 12 a) Irdiftration 190 51 16 4 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other , 0 0 Subtotal Qines 6to 13) 1192 457 132 116 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 443 269 14 Subtotal 1192 457 574 384 15 Duct loads 22% 5% 262 23 22% 5% 126 19 Toted room load 1454 410 701 404 Air required (cfm) 49 21 241 18 Calculations approved bVACCA to meet all requirements of Manual J 8th Ed. 2018-Mar-02 10:04:31 .& A - WrightsOTt" Right -Suite® Universal 2017 17.0.08 RSL08101 Page 2 E:\Documnets\WdghtsoftHVAC\CHESSERRESIDENCE.rupj Calc = MJS Front Doorfaces: N I OP m y o e#Tt 3 m � y 0 D ° n O� w M� Mm .Zl mC: c CZmi d m o C' V V N o o C* 11 X K co Ids � -1 O a v 0 O EP N Y_ 0 N to A CD W w n 0 N UTA W N O) W NA WNW ���rtQ� c 3 m �c ' < v D -no V��;= 88 �� ocg yjp o w .1p o 35$ 333 o- 3 n�7•=� y� n 5' 8R 3 X o �+�'fy �N g3m' GNN.N NwN�N NNN�NNNNNWNNNNw ' mmmm m mmmm ammmm mmccm -1' — �n — p 3 CL a_N $ 8 G F! N 7 /`1 N � p—� p—� p-7 ¢—� p� y p� p� FIT •p wryN �N�p�7,N N_ N N_ � N NN _ - ----- ---- 3 A f0 fD'� y- f0 - fC y n f0 y fC 7L g Yn n o gT-. o cZ� �a o �� o c� �� �� a2..a� _. o __ O �CcC C0D � N ci c "a0000000000000o00000000o c ` 00 00 00 OD A OD OD.00 8.b. OD OD 8 A OD 07 Ou A 2 O pA OD OD •8 ,��0pp NO0000 SO S o O O OS O O O O O S O O O O N(O�N WN(A�pp A(ApA a IJ Np Y pONN (NpN (O�N(AtppA (Ap (A�pp SA NN N f0 m > f010.. O S fG0 m W W N Oo f0 m t0 t00 '(O mm Go) O OO A�.A OO 000000 co GOO OO ODOO OO. 00c) � N A O CA ` W �1A 0.000000000.0.0000ON00000` V� x O o WV AW000 W :- O� pGppp N _ N ,6p pNp, .. �. SNOO OG00000000O 00�OOD00000 �O CI r 0- ` O 8 W �,ppj� 0 0 0 0 �j O 00 08 AW N Gi O N pp 0 0 NN coOA00`o 00.0000000089 000• 6 26 O O -u N O N o �O� IAa WpD ,pp -N OO O000000000�00000000000 W W X com _ 0 777p1777 �rn000 ��.0000�0000000000000000�-• �O oD o$ w ID vn 8 ��11 pp ��7p1 ��1p1 W Ap W fps WA OA000 A 00 O8— OODOOOO�OOOOOOOOOOOOfV11000Q i m N CD W PF OOi E Gl N O 0000 - +- wrightsoft Right-M Worksheet Entire House QUICK CALCS, INC. i 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: QUICKCALCS ,AOL.COM Job: Date: Mar 02, 2018 By: 1 Room name LIVING ROOM FOYER 2 Exposed wall I 11.0 ft 8.0 ft 3 Room height 11.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 1.0 x 271.0 ft 271.0 ft2 8.0 x 6.0 ft 48.0 ftz Ty Construction U-value Or HTM Area (ft� Load Area (ft� Load number (Btuh/ft?'F) (Btuwft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A4ocs 2 glazing, cir low-e 2 glazing, cir low-e 0.143 0.650 0.650 n n n 4.00 18.20 18.20 12.19 14.99 114.99 0 0 0 0 0 0 0 0 0 0 0 0 80 0 0 32 0. 0 128 0 0 70 0 0 11 2 glazing, cir low-e 2 glazing, clr low-e 0:650 0.650 n n 18.20 18.20 114.0 114.99 0 0 0 0 0 . 0 0 0 0 48 0 0 0 874 0 720 13AAocs 2 glazing, cir low-e 2 glazing, cir low-e 0.143 0.650 0.650 a a a 4.00 18.20 18.20 1 2.19 130.39 32.08 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazing, clr low-e 2 glazing, clr low-e 0.650 0.650 a a 18.20 18.20 32.42 32.93 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazinq, cir low_-e. - -- 13A-4ocs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, cir low- 13A4ocs 2 glazing, cir low-e 0.650 0.143 0.650 0.650 0.650 0:650 0.143 0.650 a s s s s s sw sw 18.20 4.00 18.20 18.20 18.20 18.20 4.00 18.20 i32.93 12.19 114.99 114.99 ' 14.99 114.99 2.19 123.31 0 121 0 0 0 72 0 0 0 49 0 0 0 72 0 0 0 196 0 0 0 1310 0 0 0 107 0 0 0 1079 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13A-4ocs 2'glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, cir-low-e 0.143 0:650 0.650 0.650 0.650 _ w w w w w 4.00 18.20 18.20 18.20 18.2Q 2.19 # 30.39 32.42 32.42 32.42 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C 16A30md 0.032 0.90 2.24 271 271 243 607 48 48 43 108 t' 22A-tph 1.358 .. 38.02 0.00 I i I i I i .i 271 11 - - _ 418 0 - 48 8 - 304 0 6 c) AED excursion -164 -35 Envelope loss/gain 2168 1630 1349 sm 12 a) Infiltration 192 51 127 34 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 2500 0 Subtotal (lines 6 to 13) 2360 4181 1476 895 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 596 373 -1476 -896 14 Subtotal 2956 4554 0 0 15 Duct loads 22% 5% 650 228 22% 5% 0 0 Total room load 3606 4782 0 0 Air required (cfm) 121 210 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. Aft � wrightsoft^ RightSuite® Universal 2017 17.0.08 RSU08101 2018-Mar 02 1 Page 4 E:\Documnets\Wrightsoft WAC\CHESSER RESIDENCE.rup Calc = MJ8 Front Door faces: N -�- wrightsofta Right-M Worksheet Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fallc 1772-466-6796 Email: QUICKCALCS@AOL.COM Job: Date: Mar02, 2018 By: 1 Room name DINING ROOM LAUNDRY 2 Exposed wall 14.9 ft 1.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cod 4 5 Room dimensions Room area 1.0 x 138.0 ft 138.0 ftz 8.0 x 13.0 ft 104.0 ft2 Ty Construction U-value Or HTM Area (ft� Load Area M Load number V3tuh/fVk°F) (Btuwft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross WP/S Heat Cool Gross WP/S Heat Cool 6 11 13A-4ocs. 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, cir low-e 13A-4ocs 2 glazing, clr low-e 2 glazing, cir low-e 0.1-43 0.650 0.650. 0.650 0.650 0.143 0.650 0.650 n n n n n a a a 4,00, 18.20 18.20 18.20 18.20 4.00 18.20 18.20 2.19' 14.99 14.99 I14.99 . 14.99 I2.19 30.39 ;32.08 130 , 0 24 24 0 20 0 0 82. 0 0 0 0 20 0 0 328 0 437 437 0 80 0 0 179 0 360 360 0 44 0 0 - 0 0 0 0 0 10 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 40 0 0 0 0 0 0 0 22 0 0 2 glazing, cir low-e 2 glazing, cir low-e 0.650 0.650 a a 18.20 18.20 32.42 32.93 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 glazinq, cir low-e.0.650 13A4ocs 2,glazing, clriow-e 2'glazing, clrlow- 2 glazing, clr low-e 2 glazing, cir low-e 13A4ocs 2 glazing, cir low-e 0.143 0.650 0.650 0.650 0:650 0.143 0.650 a s s s s s sw sw 18.20 4.00 18.20 18.20 18.20 18.20 4.00 18.20 32.93 12.19 14.99 �,14.99 14.99 i 14.99 ' 2.19 123.31 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0_ 0 0 0 0 0 0 0 0 0 0 0 0, 0, 0 0 0 0 0 0 0 0 0 0 t-G 'k 13A4ocs 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, cir low-e 2, glazing, clrlow-e 0.143 0.650 0.650 0.650 0.650 w w w w .w 4.00 18:20 18.20 18.20 18.20 2.19 �30.39 132.42 132.42 132.42. 0 0 0 0 0, 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0_ 0 0 0 0 0 0 0 0 0 0 C F 16A-30md 22A tph 0.032 1.358 - - 0.90 38.02 _ 2.24 ' 0.00 t i I h I 138 , 138 138 15 124 567 - 309 0 104 104 - 104 1 93 38 233 0 - 6 c)AED excursion -68 -29 Envelope loWgain 1973 1183 171 226 12 a) Infiltration 238 64 16 4 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 500 500 Subtotal Vines 6 to 13) 2211 1747 187 730 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 449 283 20 48 14 Subtotal 2660 2030 207 778 15 Duct loads 22% 5% 585 102 22% 5% 46 39 Total room load 1 3245 1 2132 253 1 817 Air required (cfm) 1091 93 8 36 -F- wrightsoft- RightSuite® Universal 2017 17.0.08 RSU08101 E:1DocumnetslWrightsoft HVA=HESSER RESIDENCE.rup I Calc = MJ8 Front Door faces: N 2018-Mar-02 10:04:31 Page 5 -e�- wrightsoft° Right-JO Worksheet Entire House QUICK CALCS, INC I. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM Job: Date: Mar02, 2018 By: 1 Room name HALLWAY IdTCHEN 2 3 Exposed wall Room height 0 ft 10.0 ft heat/cool 0 ft 10.0 ft heat/cool 4 5 Room dimensions Room area 1.0 x 77.0 ft 77.0 ft' 1.0 x 183.0 ft 183.0 ft' Ty Construction number U-value (8tuh/ft2 °F) Or HTM (Btuh/ft�, Area (ft� or perimeter (ft) Load (Btuh) Area (ft� or perimeter (ft) Load (Btuh) Heat C60I Gross WP/S Heat Cool Gross N/P/S Heat Cool 6 11 W 13A-4ocs 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, cir low-e 13A4ocs 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, cir low-e 2 glazirm, cir low-e- 13A-4ocs 2 glazing, clr low-e 2' glazing, cir low-e 2 glazing, cir low-e 2 glazing, cfrlow-e 13A-4ocs 2 glazing, cir low- 13A4ccs 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, clrlow-e 2 glazing, cir law-e 16A30md 22A-tph 0:143 0.650 0.650 0.650 0.650 0.143 0.650 0.650 0.650 0.650 0.650 0.143 0.650 0.650 0.650 0.650 0.143 0.650 0.143 0.650 0.650 0.650 0.650 0.032 1.358 n n n n n a a a a a _ e s s s s s sw sw w w w w w - - 4.00. 18.20. 18.20 18.20 18.20 4.00 18.20 18.20 18.20 18.20 18.20 4.00 18.20 18.20 18.20 18.20 4.00 18.20 4.00 18.20, '18.20 18.20 18:20 0.90 38.02 1 2.19 14.99 [14.99 �14.99 14.99 2.19 30.39 32.08 32.42 32.93 32.93 12.19 14.99 14.99 14.99 14M 2.19 � 23.31 2.19 130.39 32.42 32.42 . 32.42. 2.24 0.00 6 0 0 0 •_ 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 77 77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 77 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 - 0 69 0. 6 0 0 0 0 0 0 0 0 0 0, 6 0 0 0 0 0 0 0 0 0 0 . 0 172 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 183 183 0 0 0 0 0 0 0 0 0 0 0 0 0. 0 0 0. 0 0 0 0 0 0 0 183 0 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ,. , 0 164 - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0, 410- 0 t-G C F 6 c) AED excursion -6 -83 Envelope loss/gain 69 165 164 327 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianceslother 0 1800 Subtotal (fines 6 to 13) 69 166 164 2127 Less e)demal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -69 -166 24 58 14 Subtotal 0 0 188 2184 15 Duct loads 22% 5% 0 0 22% 5% 41 109 Total room load 0 0 229 2294 Air required (cfm) 0 0 8 101 WrlglltsOft^ Right -Suite® Universal 2017 1I A&K 7.0.08 RSU08101 E:1DocumnetslWrightsoft HNACICHESSER RESIDENCE.rupl Calc = MJ8 Front Doorfaces: N 2018-Mar-02 10:04:31 Page 6 wrightsoftRight-J® Worksheet Job: Entire House Date: Mar 02, 2018 By: QUICK CALCS, INI. C 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@,40L.COM 1 Room name I NOOK FAMILYROOM 2 Exposed wall 25.0 ft 49.0 ft 3 Room height 10.0 ft heat/cool 11.0 ft heat/cool 4 Room dimensions 1.0 x 126.0 ft 19.1 x 18.0 ft 5 Room area 126.0 fY 343.5 ft2 Ty Construction number U-value (Btuh/ftz°F) Or HTM (Btuh/ft2), Area (ft� or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat C1I Gross NIP/S Heat Cool Gross N/P/S Heat Cool 6 11 1N 13A4ocs 2 glazing, cir lower 2 glazing, cir low-e 2 glazing, clrlow•e 2 glazing, clr low-e 0143 0.650 0.650 0.650 0:650 n n n n , n 4.00, 18.20 18.20 18.20 18.20 { 2.19. 14.99' 114.99 114[99 14.99 0 0 0 0 0 0 0 0 0 0, 0 0 0 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 13AAocs 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, clr low-e 0.143 0.650 0.650 0.650 0.650 a a a a a 4.00 18.20 18.20 18.20 18.20 2.19 30.39 32.08 32.42 32.93 120 0 0 20 21 79 0 0 1 1 315 0 0 364 388 172 0 0 648 702 132 0 0 0 0 68 0 0 0 0 272 0 0 0 0 149 0 0 0 0 2 glazinq, clr lows- 13A-4ocs 2 glazing, clr low-e 0.650 0.143 0.650 a s s 18.20 4.00 18.20 32.93 2A9 114.99 0 130 0 0 90 0 0 359 0 0 196 0 64 209 0 3 189 0 1165 757 0 2107 414 0 2 glazing, cir low- 2 glazing, cir lower 2 glazing, clr low-e 13A-4ocs 2 glazing, cir low-e 0.650 0.650 0.650 0.143 0.650 s s s sw sw 18.20 18.20 18.20 4.00 18.20 j 14.99 (14.99 114.99 12.19 123.31 20 20 0 0 0 20 20 0 0 0 364 372 0 0 0 300 306 0 0 0 20 0 0 0 0 20 0 0 0 0 364 0 0 0 0 300 '0 0 0 0 V,V L--G 13A■tocs 2 glazing, cir low-e 2 glazing, clr low-e 0.143 0.650 0.650 w w w 4.00 18.20: 18:20 2.19 30.39 32.42 0 0 0 0 0 0 0 0 0 0 0 0 198 0 0 178 0 0 713 0 0 389 0 0 2 glazing, cir low-e 2 glazing, cir low-e 0.650 0.650 w w 18.20 18.20 } 32.42 132.42 , 0 0, 0 0 0 0 0 , 0 0 20 0 1' 0 -, 364 0 648 C 16A-30md 0.032 - 0.90 2.24 126 126 113 282 342 342 306 765 F 22Artph 1.358 - 38.02 - 0.00 I I r i I l I r I 126 25 , 951 0 342 49 1863 0 6 c)AED excursion -102 -188 Envelope loss(gain 3225 2505 5804 4585 12 a) Infiltration 397 106 855 229 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 3622 2611 6659 4814 Less wdernal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 3622 2611 6659 4814 15 Duct loads 22% 5% 797 131 22% 5% 1465 241 Total room load 7 4418 2742 8124 5055 Air required (cfm) 149 120 273 222 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft" Right -Suite® Universal 2017 17.0.08 RSUD8101 2018-Mar 02 1Page 7 Aft E:1DocumnetslWrightsoft HVACICHESSER RESIDENCE.rup Cale = MJB Front Door faces: N -�- wrightsoft® Right-M) Worksheet Job: Entire House Date: Mar02, 2018 By: QUICK CALCS, INC: 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 3 CLST 3 2 Exposed well 12.0 ft 2.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 13.0 x 12.0 ft 156.0 ft2 10.0 x 2.0 ft 20.0 W Ty Construction number LI-value (Btuh/W-°F) Or HTM (Btuh/ft2)I Area (W) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A4acs 2 glazing, clr low-e 2 glazing, cir low-e 0.143 0.650 0.650 n n n 4.00 18.20 18.20 12.19 f14.99 14.99 0 0 0 0 0 0 0 0 0 0' 0 0 0 0 0 0" 0 0 0 0 0 0 0 0 11 2 glazing, clr low-e 2 glazing, cir low-e 0.650 0.650 n n 18.20 18.20 114.09 114.99 0 0_ 0 0 0. 0 0 0 0 0 0 0 0 0. 0 0 - 13A-4oes 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, cir low-e 2 plazirm, cir low-e 13A flocs 2 glazing, cir low-e 2 glazing, cir love 2 glazing, clr low-e 2 glazing, cir low-e 13A-4ocs 2 glazing, cir low-e 13A-4ocs 2 glazing, clr love 2 glazing, cir Iovw a 2 glazing, cir low-e .2 glazing, clrtowe 16A-NkM 0.143 0.650 0.650 0.650 0.650 0.650 0.143 0.650 0.650 0.650 0.650 0.143 0.650 0.143 0.650 0.650 0.650 0.650 0.032 a a a a a a s s s s s sw sw w w w w w 4.00 18.20 18.20 18.20 18.20 18.20 4.00 18.20 18.20 18.20 18.20 4.� 18.20 4.00 18.20 18.20 18.20 18.20 0.90 , 2.19 30.39 32.08 132.42 32.93 '32,93 1 2.19' 114.99 114.99 14.99 I14.99 2.19 ' 23.31 2.19 30.39 32.42 32.42 132.42 2.24 0 0 0 0 0 0 0 0 0 0 0 0 0_ 120 0 20 : 0 - 0 156 0 0 0 0 0 0 0 0 0 0 0 0 0 100 0 1 0 0_ 156 0 0 0 0 0 0_ 0 0 0 0 0 0 0 400 0 364 0 0 140 0 0 0 0 0 0, 6 0 0 0 0 0 0 219 0 648 0 0 349 0 0 0 0 0 - 0 0 0 0 0 0 0 0 20 0 0 0 0 20 0 0 0 0 0 0 0 0 0 0 0 0 0 20 0 0 0 0 20 0 0 0 0 0 0 0 0 0 0 0 0 0 80 0 0 0 0 - 18 0 0 0 0 0 0 0 0 0 0 0. 0 0 44 0 0. 0 0 45 VV L-G W C F 22A-tph- 1.358 - - 38.02 i 0.00 1. i i i I 156 12 456 0 20 2 76 0 6 c) AED excursion 216 -4 Envelope loss/gain 1360 1433 174 85 12 a) Infiltration 190 51 32 8 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 1 230 0 0 Appliances/other 500 0 Subtotal Qines 6 to 13) 1551 2214 206 93 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 107 58 -206 -93 14 Subtotal 1 1658 2271 0 0 15 Duct loads 22% 5% 365 114 22% 5% 0 0 Total room load 2023 2385 0 0 Air required (cfm) 68 105 0 0 .4CLA - Wrigl7tsoft" I2018-Mar-02 1P RightSuite® Universal 2017 17.0.08 RSU08101 age 8 E:\Documnets\Wdghtsoft HVAC\CHESSER RESIDENCE.rupl Calc = MJ8 Front Door faces: N -i - wrightsoftRight-M Worksheet Entire House QUICK CALCS, ING. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM Job: Date: Mar 02, 2018 By: 1 Room name BATH 2 BEDROOM 2 2 Exposed wall 6.0 ft 12.0 ft 3 Room height 10.0 ft heat/cool 10.0 ft heat/cool 4 5 Room dimensions Room area 10.0 x 6.0 ft 60.0 ft' 1.0 x 152.0 ft 152.0 ft2 Ty Construction number U-value (Btuh/ft' °F) Or HTM (Btuh/ft2), Area (ft� or perimeter (ft) Load (Btuh) Area (ft� or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A4ocs 2 glazing, cir low-e 2 glazing, cir low-e 0.143 0.650 0.650 n n n 4.00; 18.20 18.20 12.19 14.99 114.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 0 0 0 0 0 11 2 glazing, cir low-e 2 glazing, cir low-e 0.650, 0.650 n n. 18.20 18.20 i14'.99 114.99 0 0 0 0 0 0 0 0 0 0 0, 0 0 0 0 0 13A4ocs 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazinq, clr low-e 13A-4ocs 2 glazing, clr lower 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, cli low-e 13A40cs 2 glazing, cir low-e 13A-4ocs 2 glazing, cir low-e 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, cir low-e 0.143 0.650 0.650 0.650 0.650 0.650 0.143 0.650 0.650 0.650 0.650 0.143 0.650 0.143 0.650 0.650 0.650 0.650 a a a a a a s s s s s sw sw w w w w w 4.00 18.20 18.20 18.20 18.20 18.20 4.00 18.20 18.20 18.20 18.20 4.00 1.8.20 4.00 18.20. 18.20 18.20 18.20 i 2.19 ;30.39 32.08 i32.42 32.93 32.93 2A9 N4.99 ;14.99 I14.99 I1,14.99 2.19 123.31 ; 2.19 130.39 132:92 i32.42 32.42 0 0 0 0 0 0 0 0 0 , 0 0 0 0 60 8 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 52 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 208 146 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 114 243 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 120 0 0 15 0 0 0 0 0 0 0_ 0 0 0 0 0 0 0 105 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 420 0 0 273 0 0 0 0 0 0 0 0 0 0 0 0 0 0 230 0 0 486 0 1f�1 C 16A-30md 0.032 - 0.90 l 2.24 60 60 54 134 152 152 135 340 f , 22A-tph. 1.358 - 38.02 0.00 i . i i 60 _ 6, 228 - 0 . 152 .. 12 456 0 6 c)AED excursion 107 142 Envelope loss(gain 636 599 1286 1198 12 a) Infiflration 95 25 190 51 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants c@ 230 0 0 1 230 Appliances/other 0 700 Subtotal (lines 6 to 13) 731 624 1476 2179 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 112 68 14 34 14 Subtotal 843 692 1490 2213 15 Duct loads 22% 5% 185 35 22% 51/6 328 111 Total room load T7-1028 727 1818 23fl Air required (cfm) 35 32 61 1 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft" Right -Suite® Universal 2017 17.0.08 RSU08101 2018-Mar-02 1 Pa31 ge ag e 9 E:1DocumnetslWrightsottWACICHESSERRESIDENCE. rupi Calc=MJ8 FrontDoor%ces: N - - wrightsoft9 Right-M Worksheet Job: Entire House Date: Mar 02, 2018 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fa 1772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 2 2 Exposed wall 0 ft 3 Room height 10.0 ft heat/cool 4 Room dimensions 2.0 x 8.0 ft 5 Room area 16.0 ft' Ty Construction U-value Or HTM Area (ft� Load Area Load number (Btuh/ftz°F) (Btuwft� or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 0143 n _' 4:00: 12s1,9 `.::0 ' 0 - 0 0 . 2 glazing, clr low-e 0! 650 n 18.20 14.99 O : 0 0 0 G 2 glazing, clr iow-e 0.650 n 18.20 114.99 . 0 : 0 0 ' :0 , 0 0 '° 11 2 glazir g,;c r love 0650 , n 18. 0' �4.99 0 _ 0 . .. 13A-4ocs 0.143 a 4.00 2.19 0 0 0 0 2 glazing, cir love 0.650 a 18.20 30.39 0 0 0 0 2 glazing, cir low-e 0,650 a 18.20 32.08 0 0 0 0 2 glazing, cir Iou-e 0.650 a 18.20 32.42 0 0 0 0 2 glazing, cir lower 0.650 a 18.20 32.93 0 0 0 0 2alazina, cirlow-e_ 0.650 18.20 32.93 0 0 0 0 W 13k4ocs _ 0.143 _,e s' _. 4.00 j2.10 .0 0 _ .._, - .__ 0 _ 0 2 glazing; cir lower . _ 0.650, s 1820 14:99 0 0 ` 0 0 2 glazing; clr love . , 0.650 s 18.20 14.99 0 0 . 0 0 2 glazing,'clr low-e- °. 0.650 s 18.20 14.99 0 0 _ 0 0 G 2glazirg,:'cirlov�,0-. 0.650. `s... .. 18.20 14.99 0 ,, . `-0 '.. 0 0 ..:_.. -._ 13A-4ocs 0.143 sw 4.00 .19 0 0 0 0 2 glazing, clr low-e 0.650 sw 18.20 23.31 0 0 0 0 13A-06cs> . 0:M ''w 4.00 12.19 0 , 0 '0 2,glazing; cir low-e . 0.650 ;w 18 20 30. 0 0 " .. 0 D 2 glazing, cir lower . 0.650 w 18.20 32:42 . - ' 0 0 _ '; : 0 0 1 = 2 glazing, dr low-e, 0.650 w A&M 32.42 0 0 0 0 2glazing,clr,lowe,:-. D;G50 .,w.., _ 1820 _ 32.42. ,..:0 0 C 16A30md 0.032 - osd 2.24 16 16 14 36 _ F _ 22A4h.:'_°: .. _1.358 -. .. - 38.02 ... 0:00 _-- ,... : . 16 .._ • _ - - . 61 c)AED excursion -1 Envelope loss/gain 14 34 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal (Iines 6 to 13) 14 34 Less external load 0 0 Less transfer 0 0 Redistribution' -14 -34 14 Subtotal 0 0 15 Duct loads 22% 5% 0 0 Total room load 0 0 Air required (drn) 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. A&A -Fid- wrightsoft- Right-Sufte® Universal 2017 17.O.08 RSU08101 E:\Documnets\WrightsoftWAC\CHESSER RESIDENCE.rup Calc = MJ8 Front Doorfaces: N 2018-Mar-02 10:04:31 Page 10 -�- wrightsoft- Duct System Summary Entire House QUICK CALCS, INC.; 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@,40L.COM For. CHESSER RESIDENCE, GEM BUILDERS 1317 LONE PINE LANE, FORT PIERCE, FL External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1367 cfm Job: Date: Mar 02, 2018 By: Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1367 cfm 180 ft Name Design (Btuh) Htg (cfm) Clg (cfm)! Design FR Diam (in) H x W (in) Duct Mad Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 1028 35 32 1.000 5.0 Ox 0 VIFx 12.0 115.0 st1 BEDROOM 2 c 2323 61 102 1.000 7.0 Ox 0 VIFx 15.3 115.0 st1 BEDROOM 3 c 2385 68 105 1.000 7.0 0x0 VIFx 22.9 135.0 st3 DINING ROOM h 3245 109 93 1.000 7.0 Ox0 VIFx 5.8 95.0 FAMILY ROOM h 4062 137 Ili 1.000 7.0 Ox0 VIFx 24.7 135.0 st3 FAMILY ROOM -A h 4062 137 111 1.000 7.0 Ox 0 VIFx 28.8 135.0 st3 KITCHEN c 2294 8 101 1.000 7.0 Ox 0 VIFx 14.2 115.0 st1 LAUNDRY c 817 8 36 1.000 5.0 Ox 0 VIFx 8.2 115.0 st1 LIVING ROOM c 2391 61 105 1.000 7.0 Ox0 VIFx 25.3 115.0 st2 LIVING ROOM -A c 2391 61 105 1.000 7.0 Ox0 VIFx 25.3 115.0 st2 M TOILET h 967 33 21 1.000 5.0 Ox 0 VIFx 44.8 135.0 st4 M WIC 1 h 1454 49 21 1.000 5.0 Ox 0 VIFx 39.8 135.0 st4 M WIC 2 h 701 24 18 1.000 4.0 Ox 0 VIFx 40.3 135.0 st4 MASTER BATH h 4900 165 73 1.000 6.0 Ox 0 VIFx 40.2 135.0 st4 MASTER BEDROOM h 3932 132 107 1.000 7.0 Ox 0 VIFx 24.9 115.0 st2 MASTER BEDROOM -A h 3932 132 107 1.000 7.0 Ox 0 VIFx 37.0 115.0 st2 NOOK h 4418 1 149 1 120 1 1.000 1 7.0 OX 0 VIFx 1 30.7 1 135.0 1 st3 wri htsoft' 2018-Mar-0210:04:33 1. 9 RightSufte® Universal 2017 17.0.08 RSU08101 Page 1 +A E:\Documnets\Wrightsoft HVAC\CHESSER RESIDENCE.rup Calc = MJ8 Front Doorfaces: N Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st4 Peak AVF 270 133 11.000 773 8.0 0 x 0 VinlFlx st2 st2 Peak AVF 656 557 1.000 11.000 835 12.0 0 x 0 VinlFlx st3 Peak AVF 490 446 743 11.0 0 x 0 VinlFlx st1 st1 Peak AVF 602 717 �1.000 777 13.0 0 x 0 VinlFlx Name Grill Size (in) Htg (cfm) Clg (cfm) TEL (ft) i Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox 0 1367 1367 0 0 0 0 0x 0 VIFx A + wrightsoft, Right -Suite® Universal 2017 17.0.08 RSU08101 ZCA E:1DocumnetslWrightsoft HVAMCHESSER RESIDENCE.rup Cale = MJ8 Front Door faces: N S 2018-Mar-02 10:04:33 Page 2