j EXTERIOR RESEARCH & DESIGN, I.I.C.
�",-,,FTRINITY'
Certificate of Authorization #9503
353 Christian Street
ER® Oxford, CT 06478
(203) 262-9245
EVALUATION REPORT
Polyglass USA, Inc. Evaluation Report P9290.02.08-1120
150 Lyon Drive FL1654-1122
Fernley, NV 89408 Date of Issuance: 02/11/2008
(S70) 384-1230 Revision 20: 09/12/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 6th Edition (2017) FlI orida Building Code sections noted herein.
DESCRIPTION: Polyglass SBS and APP Modified Bitumen Roof Systems
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity) ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of t e Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 6, plus a 58-page Appendix.
Prepared by: `,R'�ttt`tlttr„ter!
Robert J.M. Nieminen, P.E.
,✓,,r11h���iq>>`�~°' The facsimile seal appearing was authorized by Robert Nieminen,
Florida Registration No. 59166, Florida DCA ANE1983 F.E. on 09/12/2017. This does not serve as an electronically signed
document.
CERTIFICATION OF INDEPENDENCE: !
1. Exterior Research & Design, LLC. d/b/a Trinity I ERD does not have, nor does it intend to acquire or will it acquire, a financial interest
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, LLC. d/b/a,Trinity I ERD is not owned, operated or controlled by any company manufacturing or
distributing products it evaluates.
3. Robert Nieminen, P.E. does not have norjwill acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product. !
5. This is a building code evaluation. Neither Trinity[ ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, for previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
TRINITY ERD
ROOFING SYSTEMS EVALUATION:
I
1. SCOPE:
Product Category: Roofing
Sub -Category: Modified Bitumen Roof Systems
Compliance Statement: Polyglass SBS and APP Modified Bitumen Roof Systems, as produced by Polyglass USA,
Inc., have demonstrated compliance with the following sections of the 6th Edition (2017) Florida Building Code
through testing in accordance withlthe following Standards. Compliance is subject to the Installation Requirements
and Limitations / Conditions of Use iset forth herein.
STANDARDS:
Section
1504.3.1
1504.3.1
1504.7
1507.11.2
1507.11.2
1507.11.2
1507.11.2
1507.11.2
3. REFERENCES:
Entity
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD(TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD(TST11294)
Exterior Research and Design; I.I.C.
Certificate of Authorization #9503
I Properties
I Properties
I Properties
I Properties
I Properties
I Properties
Properties
Properties
Properties
Properties
Properties
Properties
Properties
al Properties
al Properties
al Properties
70/4474
al Properties
al Properties
Physical Properties
FM 4470/4474
FM4470/4474
FM 4470/4474
FM 4470/4474
U L 1897
FM 4470/4474
FM 4470/4474/UL1897
FM 474/UL1897/TAS 114
FM �474/UL1897/TAS 114
Standard
FM 4474
UL 1897
FM 4470
ASTM D6162
ASTM D6163
ASTM D6164
ASTM D6222
ASTM D6509
Reference
P10490.10.08-2
P13760.09.09
P13770.09.09
P30540.11.09-R1
P30550.12.09
P33960.12.10
P33970.03.11
P37590.03.13-3A
P39680.03.13
P37590.03.13-1-R1
P37590.03.13-2-R1
P37590.07.13-2
P37590.03.13-5-R1
P37590.07.13-1
P41630.08.13
P45940.09.13
P44370.10.13
P39520.09.14-2
SC6160.11.14
PLYG-P45440SC.03.15-1
SC5170.05.15
SC8085.05.15
SC5170.12.15
SC9455.15
PLYG-SC8905.05.16-1
PLYG-SC8905.05.16-2
PLYG-SC10815.07.16-R1
PLYG-SC12025.10.16
PLYG-SC11475.16
PLYG-SC13235.01.17
PLYG-SC13920.05.17
PLYG-CTL13945.05.17-1
i
6r" EDITION (2017) FBC NON-HVHZ EVALUATION
Polyglass Modified Bitumen Roof Systems; (570) 384-1230
I
i
I
I
Year
2011
2012
2012
2008
2008
2011
2011
2009
Date
10/30/2008
09/10/2009
09/10/2009
11/30/2009
12/02/2009
12/30/2010
03/15/2011
03/06/2013
03/04/2013
06/26/2013
07/01/2013
07/01/2013
07/01/2013
07/02/2013
08/06/2013
09/04/2013
10/04/2013
09/11/2014
11/10/2014
03/31/2015
05/08/2015
05/19/2015
12/29/2015
04/01/2016
05/17/2016
05/17/2016
09/23/2016
10/12/2016
11/17/2016
01/17/2017
05/30/2017
05/30/2017
Evaluation Report P9290.02.08-R20
FL1654-R22
Revision 20: 09/12/2017
Page 2 of 6
4.
\\JTRINITYIERN,
Entity
Examination
Reference
Date
ERD(TST11294)
FM 4474/UL1897/TAS 114
PLYG-CTL13945.05.17-3
05/30/2017
ERD(TST6049)
FM 4474/UL1897
PLYG-SC13945.05.17
05/30/2017
ERD(TST6049)
FM 447i4/TAS 114
PLYG-SC15760.09.17
09/11/2017
FM Approvals (TST1867)
FM 4470
2W7A7.AM
08/04/1994
FM Approvals (TST1867)
FM 4470
OD3A3.AM
04/04/1997
FM Approvals (TST1867)
FM 4470
2DOAO.AM
12/23/1998
FM Approvals (TST1867)
FM 4470
2D5A9.AM
06/22/1999
FM Approvals (TST1867)
FM 4470
3006646
01/04/2000
FM Approvals (TST1867)
FM 4470
3001334
01/25/2000
FM Approvals (TST1867)
FM 4470
3001334
02/15/2000
FM Approvals (TST1867)
FM 4470
3000857
01/12/2000
FM Approvals (TST1867)
FM 4470
3004091
01/12/2000
FM Approvals (TST1867)
FM 4470
3006115
05/02/2001
FM Approvals (TST1867)
FM 4470
3012321
07/29/2002
FM Approvals (TST1867)
FM 4470
3014692
08/05/2003
FM Approvals (TST1867)
FM 44;70
3014751
08/27/2003
FM Approvals (TST1867)
FM 4470
3007170
01/13/2004
FM Approvals (TST1867)
FM 4470
3019317
06/30/2004
FM Approvals (TST1867)
FM 4470
3020703
07/30/2004
FM Approvals (TST1867)
FM 4470/4474
3018332
01/31/2006
FM Approvals (TST1867)
FM 4470/4474
3023368
03/20/2006
FM Approvals (TST1867)
FM 4470/4474
3024594
05/23/2006
FM Approvals (TST1867)
FM 4470/4474
3023458
07/18/2006
FM Approvals (TST1867)
FM 4470/4474
3030668
09/12/2007
FM Approvals (TST1867)
FM 4470/4474
3032172
06/12/2009
FM Approvals (TST1867)
FM 4470/4474
3049631
04/21/2014
FM Approvals (TST1867)
FM 4470/4474
3057029
02/02/2017
PRI(TST5878)
Physical Properties
PUSA-062-02-01
12/04/2007
PRI(TST5878)
Physical Properties
PUSA-061-02-02
01/28/2008
PRI(TST5878)
Phys ical Properties
PUSA-064-02-02
02/27/2008
'PRI(TST5878)
PhyslicalProperties
PUSA-062-02-02
12/04/2008
PRI(TST5878)
TAS 114
PUSA-188-02-01
02/08/2017
PRI(TST5878)
TAS1114
PUSA-188-02-02
02/08/2017
PRI(TST5878)
TAS1114
PUSA-188-02-03
02/08/2017
PRI(TST5878)
TASI114
PUSA-202-02-01
05/17/2017
PRI(TST5878)
TAS 114
PUSA-202-02-02
05/17/2017
Miami -Dade (CER1592)
HVHZ Compliance
Various NOAs
Various
Miami -Dade (CER1592)
Proposal for Review
10-0823
10/12/2010
UL LLC (QUA9625)
Quality Control
Service Confirmation, R14571
Exp. 10/06/2018
PRODUCT DESCRIPTION:
This Evaluation Report covers Polyglass Modified Bitumen Roof Systems installed in accordance with Polyglass USA,
Inc. published installation instructions and the Limitations / Conditions of Use herein.
The following Polyglass
membranes make up the subject systems.
" TABLE 1 ROLLASOODS>FOR POLYGLASSMODIFIED IBITUMENROOF SYSTEMS
Type
! Product
Specification
Reference
Grade
Type
Base Sheets
Polyglass G2 Base
ASTM D4601
N/A
II
Polyflex SA Base
ASTM D4601
N/A
II
Polyglass APP Base
ASTM D6509
N/A
N/A
Exterior Research and Design, U.C. Evaluation Report P9290.02.08-R20
Certificate of Authorization tl9503 a EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-1122
Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Revision 20: 09/12/2017
Page 3 of 6
r
I
i
i
T�RINITYJERD
aJL
u ,TABLE 1(CONTINUEO�, ROLL GOODS FOR POLYGLASS MODIFIED
,.. _..,
BITUMEN ROOF SYSTEMS
Yp
Type
i Product
Specification
Reference
Grade
Type
SBS Membranes
Polyglass HT Base 650
ASTM D6162
S
III
Elastob'ase
ASTM D6163
S
I
Elastoflex V
- ASTM D6163
S
I
Elastoflex SA V Base
ASTM D6163, Table 2
S
I
Elastoflex SA V FR Base
ASTM D6163, Table 2
S
I
Elastoflex SA V Plus
ASTM D6163
S
I
Elastoflex SA V Plus FR
ASTM D6163
S
I
Elastobase Poly
ASTM D6164
S
I
Elastoflex S6
ASTM D6164
S
I
Elastoflex S6 Type II
ASTM D6164
S
II
Elastoflex VG
ASTM D6163
G
I
Elastoflex VG FR
ASTM D6163
G
I
SBS Membranes
Elasto,,'flex S6 G
ASTM D6164
G
I
Elastoflex S6 G FR
ASTM D6164
G
I
Polyfresko G SBS (sand or poly -film backed)
ASTM D6164
G
I
Polyfresko G SBS FR (sand or poly -film backed)
ASTM D6164
G
I
Elastoshield TS G
ASTM D6164
G
I
Elastoshield TS G FR
ASTM D6164
G
I
Elastoflex SA P
ASTM D6164
G
I
Elastoflex SA P FR
ASTM D6164
G
I
Palyreflect
ASTM D6164
S
I
APP Membranes
Polyflex
ASTM D6222
S
I
Polyflex G
ASTM D6222
G
I
Polyflex G FR
ASTM D6222
G
I
Polyfresko G
ASTM D6222
G
I
Polyfresko G FR
ASTM D6222
G
I
Polybond
ASTM D6222
S
I
Polybond G
ASTM D6222
G
I
Polyflex SA P
ASTM D6222
G
I
Polyflex SA P FR
ASTM D6222
G
I
Polyfresko G SA
ASTM D6222
G
I
Polykool
ASTM D6222
S
I
S. LIMITATIONS:
5.1 This is a building code! evaluation. Neither Trinity) ERD nor Robert Nieminen, P.E. are, in any 'way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used
for permitting or design Iguidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Refer to a current Approved Roofing Materials Directory for fire ratings of this product.
5.4 For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance
with FBC 2603.4 unlessithe exceptions stated in FBC 2603.4.1 and 2603.6 apply.
5.5 The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural
members shall be in ;accordance with FBC requirements to the satisfaction of the Authority Having
Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC
Approval documentation.
5.6 For recover installations, the existing roof shall be examined in accordance with FBC 1511.
i
i
Exterior Research and Design, I.I.C. Evaluation Report 139290.02.08-1120
Certificate of Authorization #9503 6- EDITION (2017) FBC NON-HVHZ EVALUATION F1.1654-1122
i Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Revision 20: 09/12/2017
Page 4 of 6
I
I �
I
TR1N111Y ER®
5.7 For mechanically attached insulation or membrane or strip -bonded insulation, the maximum design pressure
for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with
FBC Chapter 16. Zones 2 and 3 shall employ an attachment density designed by a qualified design
professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss
Prevention Data Sheet 1-29! Roofing Application Standard RAS 117 and Roofing Application Standard RAS
137. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss
Prevention Data Sheet 1-291(January 2016) for Zone 2/3 enhancements.
5.8 For assemblies with all components fully bonded in place, the maximum design pressure for the selected
assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No
rational analysis is permitted for these systems.
5.9 For mechanically attached insulation or membrane over existing roof decks, fasteners shall be tested in the
existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison
to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI
FX-1 or Testing Application!Standard TAS 105.
1
5.10 For bonded insulation or membrane over existing substrates in a re -roof (tear off) or recover installation, the
existing deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If
any surface conditions exist that bring system performance into question, field uplift testing in accordance
with ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS
124 shall be conducted on mock-ups of the proposed new roof assembly.
5.11 For bonded insulation or (membrane over existing substrates in a recover installation, the existing roof
system shall be capable of resisting project design pressures on its own merit to the satisfaction of the
Authority Having Jurisdiction, as documented through field uplift testing in accordance with ASTM E907, FM
Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
5.12 Metal edge attachment (except gutters), shall be designed and installed for wind loads in accordance with
FBC Chapter 16 and testedifor resistance in accordance with ANSI/SPRI ES-1 or Roofing Application Standard
RAS 111, except the basic wind speed shall be determined from FBC Figure 1609.3(1), 1609.3(2) or
1609.3(3). 1
I
5.13 All products in the roof assembly shall have quality assurance in accordance with FAC Rule 611320-3.
I
6. INSTALLATION:
6.1 Polyglass Modified Bitumeln Roof Systems shall be installed in accordance with Polyglass UISA;Inc. published
installation instructions, subject to the Limitations / Conditions of Use noted herein.
6.2 System attachment requirements for wind load resistance are set forth in Appendix 1. "MDP" = Maximum
Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects
the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been
applied). Refer to FBC 1609 for determination of design wind loads.
I
I
I
I
I
Exterior Research and Design, I.I.C. i Evaluation Report P9290.02.08-R20
Certificate of Authorization #9503 1 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-1122
Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Revision 20: 09/12/2017
Page 5 of 6
7.
8.
9.
\ ",�TRINITYJERD
6.3 Any of the following FBC Approved coatings may be applied to the top roof membrane without adverse effect
on the system wind load performance. Refer to current Roofing Materials Directory for fire ratings associated
with coating usage.
➢ PG200 Non-Fibered Roof Coating;
➢ PG300 Fibered Roof Coating;
➢ PG600 Non-Fibered Aluminum Roof Coating;
➢ PG650 Fibered Aluminum Roof Coating;
➢ PG700 High Quality Elastomeric Roof Coating or KM Acryl 25;
➢ PG700QS (Quick -Set.) High Quality Elastomeric Roof Coating or KM Acryl 25-QS (over granule -surfaced
APP or SBS only);
➢ PG800 Asphalt Emulsion Roof Coating;
➢ Polyplus 60 Premium Non-Fibered Aluminum Roof Coating;
➢ Polyplus 65 Premium Fibered Aluminum Roof Coating;
➢ Polybrite 70 Premium Grade Elastomeric Roof Coating or KM Acryl 15;
➢ Polybrite 70QS (Quick -Set) Premium Grade Elastomeric Roof Coating or KM Acryl 15-QS (over granule -
surfaced APP or SBS only);
➢ Polybrite 90 High Slolids Silicone Roof Coating;
➢ Polybrite 95 Silicone Roof Coating.
BUILDING PERMIT REQUIREMENTS:
As required by the Building Offii ial or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
MANUFACTURING PLANTS:
Contact the noted Q4 agency for information on product locations covered for F.A.C. Rule 61G20-3 QA
requirements
QUALITY ASSURANCE ENTITY: I
UL LLC—QUA9625; (314) 578-i406, k.chancellor@us.ul.com
- THE 58-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT -
I
i
I
I
Exterior Research and Design, U.C. ' Evaluation Report P9290.02.08-R20
Certificate of Authorization #9503 6' EDITION (2017) FBC NON-HVHZ EVALUATION FL1654-1122
Polyglass Modified Bitumen Roof Systems; (S70) 384-1230 Revision 20: 09/12/2017
Page 6 of 6
"TA'BLEIF- WOOD DECKS NEW CONSTRUCTION, t AbOPAP-0`06RRE'C`0VEA
7
A SA*((�Oitkw4kA 0QNDE"QQF�,C
COVER
fcALp kk�
System
Base Sheet --- Roof Cover (Note 25)
MD
Deck (Note 1)
No.
Type
Fasten Attach Base Ply
Cap
(Psf)
M'
i�� A "
"01 1� -"\E"',Q
A"Po""'IL4
5 ;15"a W
E,
14 pt
W
i 4 4
-,, J"k""'v""�h �
7""i 44 A
S
A
Min. 19/32-
Elastobase, Elastobase P
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14
12-inch o.c. in 4-inch lap and 12-inch o.c. in two
SBS-SA, APP-SA, SBS-
W-136
inch plywood
(poly -film top)
or Trufast 3" Metal Insulation Plate with Trufast HD
(2), equally spaced, staggered center rows
SBS-SA
TA, APP-TA
-52.5*
W-137
Min. 19/32-
Elastobase, Elastobase P
Dekfast Hex (aka, Dekfast PLT-H-2-7/8) with Dekfast #14
12-inch o.c. in 4-inch lap and 12-inch o.c. in two
Polyflex SA Base
APP-TA
-S2.5*
inch plywood
(poly -film top)
or Trufast 3" Metal Insulation Plate with Trufast HD
(2), equally spaced, staggered center rows
W-138
Min. 19/32-
Elastobase, Elastobase P
OMG Flat Bottom Plates (square) with Roofgrip #12
12-inch o:c. in 4-inch lap and 12-inch o.c. in two
SBS-SA
SBS-SA, APP-SA, SBS-
_60.0*
inch plywood
(poly -film top)
(2), equally spaced, staggered center rows
TA, APP-TA
-Min. 19/32--
Elastobase,.Elastobase-P_
_OMG-Flat-Bottom-Plates (square)-with.Roofgrip-#12
12-inch o.c. in 4-inch lap and 12-inch o.c. in two
Polyflex SA Base
APP-TA
I
.0*
inch plywood
(poly -film top)
(-2);-equally-spaced,-staggered center rows _
TABLE 6 Wcb4stk6cTib" 'k "6 Y", X, DECKS , 000, CONSTRUCTION TEAR� IFF
'4 E YPk,�' E OF, VEW," %
SYST W17 N�� ,N�Q�AT�D P
System
Deck (Note 1)
Primer
Roof Cover (Note 15)
MDP (psf)
Joint Treatment,Base
_Ply—
� Ply
Cap Ply
No.
ljogf
I'M `SL>g"\
re
v" w mr%
Q
A�
narra a t�
1-5 S
—S
*AUW
�
T
P.-
W, -k
W-141
Min. 15/32-
(Optional) PG100
None
Polyflex SA Base
(Optional) APP-TA
APP-TA
-90.0
inch plywood
W-142
Min. 15/32-
PG100
None
SBS-SA
(Optional) SBS-SA, SBS-
SBS-SA, APP-SA, SBS-
-97.5
inch plywood
TA, APP-TA
TA, APP-TA
Min. 15/32-
Plywood joints are covered with 4-Inch wide strips of Elastoflex SA Plus, rolled into
Elastoflex SA V Base or
(Optional) SBS-SA, SBS-
SBS-SA, APP-SA, SBS-
97.5
W-143
inch plywood
(Optional) PG100
place to create continuous bond.
Elastoflex SA V FR Base
TA, APP-TA
TA, APP-TA
-
W-144
Min. 15/32-
WB-3000
None
SBS-SA
(Optional)
SBS-SA, APP-SA, SBS-
-105.0
inch plywood
TA, APP-TA
Min. 15/32-
Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus, rolled into
Elastoflex SA V Plus or
(Optional) SBS-SA, SBS-
SBS-SA, APP-SA, SBS-
inch plywood
(Optional) PG100
place to create continuous bond.
Elastoflex SA V Plus FR
TA, APP-TA
TA, APP-TA
-135.0
Min. 15/32-
(Optional) PG100
Plywood joints are covered with 4-Inch wide strips of Elastoflex SA V Plus, rolled into
Polyflex SA Base
(Optional) APP-TA
APP-TA
135.0
I
inch plywood
,
place to create continuous bond.
Exterior Research and Design, LLC. d/b/a Trinity I ERD Evaluation Report P9290.02.08-R20 for FL1654-1122
Certificate of Authorization #9503 EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/12/2017
Prepared by: Robert Nieminen, PE-59166 Polyglass Modified Bitumen Roof Systems; (570) 384-1230 Appendix 1, Page 21 of 58