HomeMy WebLinkAboutENGINEERINGCONTRACTOR: KING CARTER ALU11_ `M INC. DESIGN CRITERIA: 1. The 6th Edition (2017) Florida Building Code, specifically Chapter 16 Structural Design, Chapter 20 Aluminum, and Chapter 23 Wood. 2. AA ASM 35 and AA ADMI Specifications for Aluminum Structures, Part 1-A of the Aluminum Design Manual prepared by The Aluminum Association. and the AAF Guide to Aluminum Construction in High Wind Areas. 3. ASCE 7-10. Loading Criteria 1. Live Load: 10 PSF per 6th Edition (2017) Florida Building Code, Appendix I Section 105.1 2. Dead Load: 2 PSF 3. Wind Load: 3.1. Building Occupancy Category, Section 1604.5 and Table 1604.5: Risk Category 1. 3.2. Basic Wind Speed, Figure 1609.3(3), State of Florida Debris Region & Basic Wind Speed, Section 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Speed: V- = 150 MPH, VA- =116 MPH 3.3. Exposure Category, Section 1609.4.3: Exposure C 3.4. Screen Enclosure Section 2002.4 4. Building Category for Aluminum Structures, Section 2002.6: Category Type 1- Patio Cover: Non -Habitable, Unconditioned Roof Type 1. Roof Type: MONOSLOPE 2. Roof Material: 3" x 48" x 0.032" composite panel Elite 2000,1.0# density foam, Florida Product Approval Number FL 7561-R4. Specifications The following specifications are applicable to this project: 1. All work shall be in accordance with the 6th Edition (2017) Florida Building Code, and any other applicable local codes and regulations. 2. Aluminum extrusions shall be 6005 T5 Alloy. Due to quality control issues, no manufacturer substitution is acceptable without the specific written, signed and sealed authorization of Suncoast Aluminum Engineering, LLC. 3. Screen Material: Design based on 18/14 or 20/20 Better View. Any other material must be approved. 4. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc plated to ASTM B633, or coated stainless steel series "300", or uncoated stainless steel series"400". 5. All Self Mating Beam Sections are to be stitched with either #14 screws 6" from ends and ---24" center to center of # 12 screws 6"from ends and 12" center to center. 6. Where concrete specifications are required, whether in the screen enclosure scope or not, by one or more regulatory agency, the following specifications are applicable: a. Concrete shall conform to ASTM C94 for the following components: i. Portland Cement Type 1,- ASTM C 150 ii. Aggregates - Large Aggregate 3/4" max - ASTM C 33 iii. Air entraining +/-1%- ASTM C 260 iv.Water reducing agent - ASTM C 494 v. Clean Potable water vi. Other admixtures not permitted b. Metal accessories shall conform to: i. Reinforcing Bars - ASTM A615, grade 60 ii. Welded wire fabric - ASTM A185 c. Concrete slump at discharge chute not less than 3" or more than 5". Water added after batching is not permitted. d. Prepare and place concrete per American Concrete Institute Manual of Standard Practice, Parts 1, 2, and 3 including hot weather recommendations. e. Moist cure or polyethylene curing permitted. f. Prior to placing concrete, treat the entire subsurface area for termites in compliance with the FBC. g. Concrete shall be placed over a polyethylene vapor barrier. h. All aluminum components embedded within concrete shall be coated with a bituminous paint or epoxy. 7. All flashing and weatherproofing shall be provided by the contractor. -8. Door location shall be determined by contractor in the field. 9. Use of these plans acknowledges and accepts a limit of liability not to exceed design and engineering fee. WIND SP,. ND EXPOSURE HAVE BEEN DETERMINED USING THE ADVANCED TECHNOLOGY COUNCIL'S WEBSITE AND GOOGLE EARTH. #-- 9'-4• I 3X3XO.093 POST m 3X3XO.093 POST �k-- e•-o' CONCEALED FASTENERS OR ATTACHMENTS ,ARE THE RESPONSIBILITY OF THE CONTRAC TOR OF RECORD B'-4J. f- 8'-41.. B'-4t. 2X3 END BEAM ST. LITCfE CpL1k I?UTLnt1C SION REVIEWED FOR COLN2L RE,AU"WED BY DATE PLANS AND PERMIT MUST E KEPT Old,' JOB OR NO INSPECTION WILL BE ?* Dl,:. I HE SE PLANS AND ALL PROPOSED WORK ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT MAY BE NECESSARY IN ORDER TO COMM Willi "M140AAW 49001 8'-4t 1 8'-8j 2X3 1.0# DENSITY FOAM COMPOSITE PANEL S EASTING ASS A-2 FRkMED SHED 2x5SMB EDGE BEAM 1._0. 3'X48'XO.032' COMPOSITE PANEL1 2X3 KNEE BRACE(TYP) - A-2 3X3X0.093 POST 3X3XO.093 POST 3X3X0.093 POST '3X3XO.093 POST 3X3XO.093 POST 3X3XO.093 l POST m A-3 D 8'-4+;' 8'-4k B'=4 B'-4J ELITE 2000 COMPOSITE PAWL- (FPA:FL7581-R4) 150MPH/EXP C 3'x48'4.032' (1.0# DENSITY FOAM) MAX SPANA-rL = 14-5' a3��,,� N �(/ .• •� t�?� �.p J� _ co Q' Z= V.-t� . i0 ■ o w W L) a UCJ tr � m -� o rL Z a � m uJ Es 5 Q coJ cc m uJ Lu z p Z Z N �Z �- QZ u ZO U Z = W H� OCiL 3X3XO.093 ; POST 0Z U Iw µit _ #--- B'-1Q� J $ Q Z N Z op I- cc n 5 g Q LiJ J CDW CP C) W rM Cis ra Z N UJ ,�mut2 o N t/f W w W_ Z Q W O 2 a6tzL-Li MW DATE DRAWN 03/31 /18 REVISION SHEET NO: A-1 ALUMINUM MEMBERS DIMEN (S .HOLLOW SECTIONS 2x2: 2"x2"x0.046" • • 2 x 3: 2" x 3" x 0.050" \Y i 2x4: 2"x4"x0.050" Q� u 2x5: 2"x5 x0.050"to OPEN BACK SECTIONS #14x47/8"SMSW/ - ; W - 4 1 x 2: 1" x 2" x 0.040" 1 1/2" DIA. NEOPRENE FLASHING - i7 �'. i) O 0 (A 1 x 3: 1" x 3" x 0.045" FACED WASHER @ 6" O.C. , SNAP SECTIONS TE �jO• . • 2 x 2 Snap:2" x 2" x 0.045" 2 x 3 Snap: 2" x 3" x 0.050" - "��°' �'=`tin; ;.;��;,���, • � . ;�y.��,,✓,,,r ;�k�. ,�:�c• '"• 3 ROOF PANIEL . �` 2 x 4 Snap: 2" x 4" x 0.045" SELF MATING (SMB) '�s%ws•.'�an r'';� �.: <su, u�, `�!.�#� ti =�t;s°r.,�,,Ya. , �w'S�'w'S.f4Y 9.ti .:',Y";i];'.3 <?.^;1..*•Y�. s.:}a. Air ry .,r,\ .. t;�'p'�' � �' � M�.e, ,",�",,,{.±4.°�k ;�� ; Pddt� $IpgL1,L1 EIAL 2 x 4 SMB: 2" x 4" x 0.044" x 0.100" 3" COMPOSITE 5 SMB: 2" 5" 0.050" 0.100" 2 x x x x ROOF PANEL 2 X 6 SMB: 2" x 6" x 0.050" x 0.120" 3" x 0.062" ALUM ; #14 x 4 7/8" SMS W/ 2 x 7 SMB: 2" x 7" x 0.057" x 0.120" RECEIVING CHANNEL 1 1/2" DIA. NEOPRENE EXISTING f FACED WASHER 6" O.C. BUILDING{' O W W a a 2 x 8 SMB: 2" x 8" x 0.072" x 0.124" W/ #10 x 3/4" TOP AND ; (3) 3/8" DIA. @ U 2 x 9 SMB: 2" x 9" x 0.072" x 0.124" 2 10 SMB: 2" 10" 0.092" 0.398" BOTTOM AS END CAP THRU BOLTS (3) 3l8DIA I W pe CD" ,D x x x x THRU BOLTS ILL Z W m MINIMUM FASTENER EDGE DISTANCE: 1/2" MINIMUM FASTENER SPACING: 3/4" 2" x 5"SMB x 0.093" 2"x5"SMB i 3" x 3" x 0 09T I W aC Q w LLI -i w a m . i POST POST f Lu I I i Z Q W W CONCRETE SCREW ANCHOR: Q SIMPSON TITEN HD OR EQUIVALENT I I W W O u Z u SHEET METAL SCREWS (SMS): - Z W = =1 O ~ ITW / BUILDEX OR EQUIVALENT S COMPOSITE ROOF TO POST CONNECTION S', COMP. ROOF TO POST 4TH WALL DETAIL A_2 SCALE: NTS G A_2 SCALE: NTS Z V ..n Z o$gg a � 6O QQ ta m W W t;W U Z NN W r,P4 u Z (9 .I! 3" COMP ROOF PANEL SELF -MATING BEAM o- N W S -' - - -- --- - - --------- - -- - - - --_ - _ - ___ Y:'Sl�M.�1_t�="•:. �LviR^?S�"a`�i,W" y,Ytw:4 ��.Y'x`2 "S�lKgi �i+F°•t: ki `� i w'" arY, ,tirtr3.''h`'•�ro '+q• `'%'..'Y'''aC..�T• K-,,y,.'d+�:+T'-'• a"-��Y� °s'%b:'yj•'+"�.N:a� �Lti T..«�=-`'-''*..'.ri+ c' "`s..r`:�i+, a.��s --- tom„. 4.hc,�.�q�,.,o�vV w£P' c• s: .S°..t h.tta�t+. ,n:a`C s' #14 x 4 7/8" SMS W/ a+'�s 'v.-%r�`,N,��3+ii.`a'6 .ir..S. f•�J°'j i:+.� .n i'i . i;¢iak 11/2"DIA. NEOPRENE FLASHING #14x47/8"SMSW/ 1 1/2" DIA. NEOPRENE 3" COMPOSITE b x•,s z'r, ,%: , zvs' ,su;.,•,. >_,� ..n,._'. - - - - i FACED WASHER @ 6" O.C. FACED WASHER @ 6" O.C. ROOF PANEL 1 3" COMPOSITE ROOF PANEL K�>'••`o,,w.y''ss' ias it§Lr.i S }4 . �, ,�"�'.rr�.r' :1°,;;,.nc•r:�,Lt'"�.,.., a'- wr. f•..2. 1 � a ....y ;pyr..'•: 8sa.�'"r��- 2'e�S^�.�� •fir>> tih�''. "'.`,�^ar� �' y++s.°'gviz. e�(.,�.;.�+,�*(4 N t��.xn.a:'�:�;�.4ev-:. r��'�,•z.�^*,a1•. • • • � I (✓% W .a,°y'uch�'i'� !.sy3t• `Sk gy,�''d7xt`v+% �xi$v ;.'` ?,�'•K 'v`a:F4�$ F•lr. • f-3'"?Sf� sw..` °},�" #� g°'"t P,��'„.x' 4a.,±£ _ f •,I« $%`'A°i ���• ��^ia'�?'Y�c'A.)f zl• ^,S„�'y'tM" a. :"°*.^a.R�i"s y%,5,;4�yyr�q•^pi �.Fh, a�sa�ytvv '� •' �j'�''•*�'`:*�'ck+,'�,a:� S;.:ss"a'�c,}�'i:•rTc>".•�n•`ia.,.a.Wr. "''�'l' 4" .i?:ro?;�Y`�.yyr.,.w'n{w4: S'° @'<:^i _ • _ _� �-_ � V \ \ i 2" x 3" x 0.050" • END BEAM • I EXISTING BUILDING { • 3" x 0.062" ALUM • _ I I �' \ i \ \ EE W U W Z Q� 0) - RECEIVING CHANNEL t 3/4" TOP AND ( i \ 12^ \ I QJ W� - _ - W/ #10 x \ =1 1 1/2" x 21/8" x 1 1/2" x 0.062" x 3" LONG I I BOTTOM AS END CAP 11/2"x21/8"x1112"x0.062"x3"LONG ALUM RECEIVING CHANNEL W/ 3 2" x 5" SMB () 2"x3"x0.046" \ I UPRIGHT KNEE BRACE \ d O L~L LL ALUM RECEIVING CHANNEL W/ (3) ) ( #14 x SMS EACH SIDE \ • i #14 x 3/4" SMS EACH SIDE OF & ( BOLTS BEAM 8 (3) 3/8"DIA THRU BOLTS \ • DRAWN BY BEAM & (2) 3/8" DIA. THRU BOLTS I ( INTO POST i INTO POST 3"x3"x0.093" 11/ "x21/8"x11/2"x \ MW (3) 3/8" DIA THRU BOLT II 2" x 5" SMB I I I POST 0.062" x 3" LONG ALUM RECEIVING CHANNEL W/ (3) ! ! #1(3) #12 x 3/4" INTO POST i ! DATE DRAWN 03/30/18 3" x 3" x 0.093" - - - REVISION POST I 0 0 S-2 S-3 COMPOSITE ROOF TO POST CORNER CONNECTION S-4 KNEE BRACE CONNECTION DETAIL SHEET NO: COMP. ROOF TO CORNER POST 4TH WALL DETAIL SCALE: NTS SCALE: NTS A-2 A-2 SCALE: NTS A_2 A-2