DESIGN CRITERIA:
1. The 6th Edition (2017) Florida Building Code, specifically Chapter 16 Structural Design,
Chapter 20 Aluminum, and Chapter 23 Wood.
2. AA ASM 35 and AA ADMI Specifications for Aluminum Structures, Part 1-A of the
Aluminum Design Manual prepared by The Aluminum Association. and the AAF Guide to
Aluminum Construction in High Wind Areas.
3. ASCE 7-10.
Loading Criteria
1. Live Load: 10 PSF per 6th Edition (2017) Florida Building Code, Appendix I Section
105.1
2. Dead Load: 2 PSF
3. Wind Load:
3.1. Building Occupancy Category, Section 1604.5 and Table 1604.5: Risk Category 1.
3.2. Basic Wind Speed, Figure 1609.3(3), State of Florida Debris Region & Basic Wind
Speed, Section 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Speed: V- =
150 MPH, VA- =116 MPH
3.3. Exposure Category, Section 1609.4.3: Exposure C
3.4. Screen Enclosure Section 2002.4
4. Building Category for Aluminum Structures, Section 2002.6: Category Type 1- Patio
Cover: Non -Habitable, Unconditioned
Roof Type
1. Roof Type: MONOSLOPE
2. Roof Material: 3" x 48" x 0.032" composite panel Elite 2000,1.0# density foam,
Florida Product Approval Number FL 7561-R4.
Specifications
The following specifications are applicable to this project:
1. All work shall be in accordance with the 6th Edition (2017) Florida Building Code, and
any other applicable local codes and regulations.
2. Aluminum extrusions shall be 6005 T5 Alloy. Due to quality control issues, no
manufacturer substitution is acceptable without the specific written, signed and sealed
authorization of Suncoast Aluminum Engineering, LLC.
3. Screen Material: Design based on 18/14 or 20/20 Better View. Any other material must be
approved.
4. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc
plated to ASTM B633, or coated stainless steel series "300", or uncoated stainless steel
series"400".
5. All Self Mating Beam Sections are to be stitched with either #14 screws 6" from ends and
---24" center to center of # 12 screws 6"from ends and 12" center to center.
6. Where concrete specifications are required, whether in the screen enclosure scope or not,
by one or more regulatory agency, the following specifications are applicable:
a. Concrete shall conform to ASTM C94 for the following components:
i. Portland Cement Type 1,- ASTM C 150
ii. Aggregates - Large Aggregate 3/4" max - ASTM C 33
iii. Air entraining +/-1%- ASTM C 260
iv.Water reducing agent - ASTM C 494
v. Clean Potable water
vi. Other admixtures not permitted
b. Metal accessories shall conform to:
i. Reinforcing Bars - ASTM A615, grade 60
ii. Welded wire fabric - ASTM A185
c. Concrete slump at discharge chute not less than 3" or more than 5". Water added
after batching is not permitted.
d. Prepare and place concrete per American Concrete Institute Manual of Standard
Practice, Parts 1, 2, and 3 including hot weather recommendations.
e. Moist cure or polyethylene curing permitted.
f. Prior to placing concrete, treat the entire subsurface area for termites in compliance
with the FBC.
g. Concrete shall be placed over a polyethylene vapor barrier.
h. All aluminum components embedded within concrete shall be coated with a
bituminous paint or epoxy.
7. All flashing and weatherproofing shall be provided by the contractor.
-8. Door location shall be determined by contractor in the field.
9. Use of these plans acknowledges and accepts a limit of liability not to exceed design and
engineering fee.
WIND SP,. ND EXPOSURE HAVE
BEEN DETERMINED USING THE ADVANCED
TECHNOLOGY COUNCIL'S WEBSITE
AND GOOGLE EARTH.
#-- 9'-4• I
3X3XO.093
POST
m
3X3XO.093
POST
�k-- e•-o'
CONCEALED FASTENERS OR ATTACHMENTS
,ARE THE RESPONSIBILITY OF THE
CONTRAC TOR OF RECORD
B'-4J. f- 8'-41.. B'-4t.
2X3
END
BEAM
ST. LITCfE CpL1k I?UTLnt1C SION
REVIEWED FOR COLN2L
RE,AU"WED BY
DATE
PLANS AND PERMIT MUST E KEPT Old,' JOB
OR NO INSPECTION WILL BE ?* Dl,:.
I HE SE PLANS AND ALL PROPOSED WORK
ARE SUBJECT TO ANY CORRECTIONS
REQUIRED BY FIELD INSPECTORS THAT
MAY BE NECESSARY IN ORDER TO
COMM Willi "M140AAW 49001
8'-4t 1 8'-8j
2X3
1.0# DENSITY FOAM
COMPOSITE PANEL S
EASTING ASS
A-2 FRkMED SHED
2x5SMB
EDGE BEAM
1._0.
3'X48'XO.032'
COMPOSITE PANEL1
2X3 KNEE
BRACE(TYP)
-
A-2
3X3X0.093
POST
3X3XO.093
POST
3X3X0.093
POST
'3X3XO.093
POST
3X3XO.093
POST
3X3XO.093 l
POST m
A-3
D
8'-4+;'
8'-4k
B'=4
B'-4J
ELITE 2000 COMPOSITE PAWL- (FPA:FL7581-R4)
150MPH/EXP C
3'x48'4.032' (1.0# DENSITY FOAM)
MAX SPANA-rL = 14-5'
a3��,,�
N
�(/ .•
•�
t�?�
�.p J�
_ co
Q' Z=
V.-t� .
i0
■
o
w
W
L)
a
UCJ
tr
�
m
-� o
rL
Z a
� m
uJ Es
5
Q coJ
cc
m
uJ
Lu
z
p Z
Z
N
�Z
�-
QZ
u
ZO U
Z
=
W
H�
OCiL
3X3XO.093 ;
POST 0Z
U
Iw
µit
_
#--- B'-1Q�
J $
Q Z N
Z op
I- cc n 5
g
Q LiJ J CDW CP
C) W rM Cis ra
Z
N UJ ,�mut2 o
N
t/f
W
w
W_ Z Q W
O 2
a6tzL-Li
MW
DATE DRAWN
03/31 /18
REVISION
SHEET NO:
A-1
ALUMINUM MEMBERS DIMEN (S
.HOLLOW SECTIONS
2x2: 2"x2"x0.046"
• •
2 x 3: 2" x 3" x 0.050"
\Y i
2x4: 2"x4"x0.050"
Q�
u
2x5: 2"x5 x0.050"to
OPEN BACK SECTIONS
#14x47/8"SMSW/
- ; W
-
4
1 x 2: 1" x 2" x 0.040"
1 1/2" DIA. NEOPRENE
FLASHING
- i7
�'. i) O 0
(A
1 x 3: 1" x 3" x 0.045"
FACED WASHER @ 6" O.C.
,
SNAP SECTIONS
TE
�jO•
. •
2 x 2 Snap:2" x 2" x 0.045"
2 x 3 Snap: 2" x 3" x 0.050"
- "��°' �'=`tin;
;.;��;,���, • � . ;�y.��,,✓,,,r ;�k�. ,�:�c• '"•
3 ROOF PANIEL
.
�`
2 x 4 Snap: 2" x 4" x 0.045"
SELF MATING (SMB)
'�s%ws•.'�an r'';� �.: <su, u�, `�!.�#� ti =�t;s°r.,�,,Ya. ,
�w'S�'w'S.f4Y 9.ti .:',Y";i];'.3 <?.^;1..*•Y�. s.:}a. Air ry
.,r,\ .. t;�'p'�' � �'
� M�.e, ,",�",,,{.±4.°�k ;��
;
Pddt�
$IpgL1,L1 EIAL
2 x 4 SMB: 2" x 4" x 0.044" x 0.100"
3" COMPOSITE
5 SMB: 2" 5" 0.050" 0.100"
2 x x x x
ROOF PANEL
2 X 6 SMB: 2" x 6" x 0.050" x 0.120"
3" x 0.062" ALUM ;
#14 x 4 7/8" SMS W/
2 x 7 SMB: 2" x 7" x 0.057" x 0.120"
RECEIVING CHANNEL
1 1/2" DIA. NEOPRENE EXISTING f
FACED WASHER 6" O.C. BUILDING{'
O
W W
a a
2 x 8 SMB: 2" x 8" x 0.072" x 0.124"
W/ #10 x 3/4" TOP AND ; (3) 3/8" DIA.
@
U
2 x 9 SMB: 2" x 9" x 0.072" x 0.124"
2 10 SMB: 2" 10" 0.092" 0.398"
BOTTOM AS END CAP THRU BOLTS
(3) 3l8DIA I
W
pe
CD"
,D
x x x x
THRU BOLTS
ILL
Z W m
MINIMUM FASTENER EDGE DISTANCE: 1/2"
MINIMUM FASTENER SPACING: 3/4"
2" x 5"SMB
x 0.093"
2"x5"SMB i
3" x 3" x 0 09T I
W
aC
Q w LLI
-i w
a m . i
POST
POST f
Lu
I
I i
Z
Q W W
CONCRETE SCREW ANCHOR:
Q
SIMPSON TITEN HD OR EQUIVALENT
I I
W W
O u Z u
SHEET METAL SCREWS (SMS):
-
Z
W
= =1 O
~
ITW / BUILDEX OR EQUIVALENT
S COMPOSITE ROOF TO POST CONNECTION
S', COMP. ROOF TO POST 4TH WALL DETAIL
A_2 SCALE: NTS
G
A_2 SCALE: NTS
Z V
..n
Z o$gg a
� 6O
QQ
ta m
W
W t;W
U Z NN W
r,P4
u
Z (9 .I!
3" COMP ROOF PANEL SELF -MATING BEAM
o-
N W S
-' - - -- --- - - ---------
- -- - -
- --_ - _ - ___
Y:'Sl�M.�1_t�="•:. �LviR^?S�"a`�i,W" y,Ytw:4 ��.Y'x`2 "S�lKgi �i+F°•t: ki
`� i w'" arY, ,tirtr3.''h`'•�ro '+q• `'%'..'Y'''aC..�T• K-,,y,.'d+�:+T'-'•
a"-��Y� °s'%b:'yj•'+"�.N:a� �Lti T..«�=-`'-''*..'.ri+ c' "`s..r`:�i+, a.��s
---
tom„. 4.hc,�.�q�,.,o�vV w£P' c• s: .S°..t h.tta�t+. ,n:a`C
s'
#14 x 4 7/8" SMS W/
a+'�s 'v.-%r�`,N,��3+ii.`a'6 .ir..S. f•�J°'j i:+.� .n i'i .
i;¢iak
11/2"DIA. NEOPRENE
FLASHING
#14x47/8"SMSW/
1 1/2" DIA. NEOPRENE 3" COMPOSITE
b x•,s z'r, ,%: , zvs' ,su;.,•,. >_,� ..n,._'.
- - - -
i
FACED WASHER @ 6" O.C.
FACED WASHER @ 6" O.C. ROOF PANEL
1
3" COMPOSITE
ROOF PANEL
K�>'••`o,,w.y''ss' ias it§Lr.i S }4 .
�, ,�"�'.rr�.r' :1°,;;,.nc•r:�,Lt'"�.,.., a'- wr. f•..2.
1
� a ....y ;pyr..'•: 8sa.�'"r��- 2'e�S^�.��
•fir>> tih�''. "'.`,�^ar� �' y++s.°'gviz. e�(.,�.;.�+,�*(4
N t��.xn.a:'�:�;�.4ev-:. r��'�,•z.�^*,a1•.
• • • � I
(✓%
W
.a,°y'uch�'i'� !.sy3t• `Sk gy,�''d7xt`v+%
�xi$v
;.'` ?,�'•K 'v`a:F4�$ F•lr. • f-3'"?Sf� sw..` °},�" #�
g°'"t
P,��'„.x' 4a.,±£
_ f
•,I« $%`'A°i ���• ��^ia'�?'Y�c'A.)f zl• ^,S„�'y'tM"
a. :"°*.^a.R�i"s y%,5,;4�yyr�q•^pi �.Fh, a�sa�ytvv '� •'
�j'�''•*�'`:*�'ck+,'�,a:� S;.:ss"a'�c,}�'i:•rTc>".•�n•`ia.,.a.Wr. "''�'l'
4"
.i?:ro?;�Y`�.yyr.,.w'n{w4: S'° @'<:^i
_ • _ _� �-_
� V
\ \ i
2" x 3" x 0.050" •
END BEAM •
I
EXISTING
BUILDING
{ •
3" x 0.062" ALUM • _
I I
�' \ i
\ \ EE
W
U
W Z Q� 0)
-
RECEIVING CHANNEL
t
3/4" TOP AND (
i
\ 12^
\
I QJ W�
-
_ -
W/ #10 x
\
=1
1 1/2" x 21/8" x 1 1/2" x 0.062" x 3" LONG I
I
BOTTOM AS END CAP 11/2"x21/8"x1112"x0.062"x3"LONG
ALUM RECEIVING CHANNEL W/ 3
2" x 5" SMB ()
2"x3"x0.046" \ I UPRIGHT
KNEE BRACE
\
d O L~L LL
ALUM RECEIVING CHANNEL W/ (3)
)
( #14 x SMS EACH SIDE
\ • i
#14 x 3/4" SMS EACH SIDE OF
& ( BOLTS
BEAM 8 (3) 3/8"DIA THRU BOLTS
\ •
DRAWN BY
BEAM & (2) 3/8" DIA. THRU BOLTS I
( INTO POST
i
INTO POST
3"x3"x0.093"
11/ "x21/8"x11/2"x \
MW
(3) 3/8" DIA THRU BOLT
II
2" x 5" SMB I
I
I
POST
0.062" x 3" LONG ALUM
RECEIVING CHANNEL W/ (3) ! !
#1(3) #12 x 3/4" INTO POST i !
DATE DRAWN
03/30/18
3" x 3" x 0.093"
- -
-
REVISION
POST
I
0
0
S-2
S-3 COMPOSITE ROOF TO POST CORNER CONNECTION
S-4 KNEE BRACE CONNECTION DETAIL
SHEET NO:
COMP. ROOF TO CORNER POST 4TH WALL DETAIL
SCALE: NTS
SCALE: NTS
A-2
A-2 SCALE: NTS
A_2
A-2