VALUATION REPORT
ICP Adhesives and Sealants, Inc. Evaluation Report 02768.02.06-116
12505 NW 44th Street ��� Q 'fP,ce0 FL6276-R6
Coral Springs, FL 33065 Date of Issuance: 03/21/2006
(888) 774-1419 Revision 6:10/12/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The docume tation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Cod . The products described herein have been evaluated for
compliance with the 61h Edition (2017) Florida Building Coclle sections noted herein.
DESCRIPTION: ICP Adhesives Polyset° RTA-1
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions o the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity) ERD requires a complete review of this
Evaluation Report relative to updated Code requirements . vith each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire EvaluationJReport shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 8.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
CERTIFICATION OF INDEPENDENCE:
1. Exterior Research & Design, LLC. d/b/a Trinity I ERD does not
in any company manufacturing or distributing products it eval
2. Exterior Research & Design, LLC. d/b/a Trinity I ERD is n
distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a finan
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a fina
product.
5. This is a building code evaluation. Neither Trinityl ERD nor
project on which this Evaluation Report, or previous versions
specifically for that purpose.
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. on 10/12/2017. This does not serve as an
electronically signed document.
nor does it intend to acquire or will it acquire, a financial interest
of owned, operated or controlled by any company manufacturing or
cial interest in any company manufacturing or distributing products for
ncial interest in any other entity involved in the approval process of the
Robert Nieminen, P.E. are, in any way, the Designer of Record for any
thereof, is/was used for permitting or design guidance unless retained
FILE Copy
f
\I I KINIlYIfRD � v
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Roof Tile Adhesive
Compliance Statement: ICP Adhesives Polyset® RTA-1, as produced by ICP Adhesives and Sealants, Inc., has
demonstrated compliance with the 6th Edition (2017) Florida Building Code through testing in accordance with the
Standards set forth herein. Compliance is subject to the Installation Requirements and Limitations / Conditions of
Use set forth herein.
2. STANDARDS:
Sections Property Standard Year
1504.2.1.1 Overturning resistance SSTD 11 1997
3. REFERENCES:
Entity
Examination
Reference
Date
ERD (TST6049)
Static Uplift —SSTD 11
E42730.08.13
08/23/2013
ERD (TST6049)
Static Uplift —SSTD 11
ECM-SC6795.12.14-2
02/27/2015
Miami -Dade (CER 1592)
HVHZ compliance •
16-0315.03
04/07/2016
PRI (TST5878)
Static Uplift —SSTD 11
PFI-006-02-01
05/09/2005
PRI (TST5878)
Static Uplift —SSTD 11
PFI-008-02-03
12/14/2005
PRI (TST5878)
Static Uplift —SSTD 11
PFI-008-02-04
12/14/2005
PRI (TST5878)
Static Uplift —SSTD 11
FOP-009-02-02 Rev1
03/24/2015
PRI (TST5878)
Static Uplift —SSTD 11
FOP-009-02-01 Rev1
03/24/2015
PRI (TST5878)
Static Uplift —SSTD 11
FOP-009-02-03 Rev1
03/25/2015
PRI (TST5878)
Static Uplift —SSTD 11
FOP-009-02-04 Rev1
03/25/2015
PRI (TST5878)
Static Uplift —SSTD 11
FOP-009-02-05 Rev2
06/01/2015
UL, LLC. (QUA9625)
Quality Assurance
Service Confirmation
Exp. 06/05/2018
4. PRODUCT DESCRIPTION:
4.1 ICP Adhesives Polyset® RTA-1 is a single component polyurethane foam roof tile adhesive distributed in
factory, pre -mixed canisters.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire classification is not part of this evaluation. Refer to a current Roofing Materials Directory for fire ratings
of this product and FBC 1505.2.
5.4 ICP Adhesives Polyset® RTA-1 can be used with flat, low and high profile tiles or any rigid, discontinuous roof
assembly having a current Florida Statewide Product Approval or approved on a local -level by the Authority
Having Jurisdiction.
5.5 Minimum underlayment shall be per FRSA/TRI April 2012 (04-12) or having a current Florida Statewide
Product Approval or approved on a local -level by the Authority Having Jurisdiction for use with ICP
Adhesives Polyset® RTA-1.
Exterior Research and Design, I.I.C. Evaluation Report 02768.02.06-R6
Certificate ofAuthori:ation #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL6276-116
ICP Adhesives Polyset® RTA-1; (888) 774-2419 Revision 6: 10/12/2017
Page 2 of 8
5.6 Field tiles, meeting the limitations of FBC 16(
projects having an Aerodynamic Uplift Moment
2A and 2B of FRSA/TRI April 2012 (04-12), not
values. Refer to Section 10 and ICP Adhesiv(
Adhesive Paddy Placement details.
`J TRINITY I ERD
19.5.3, using ICP Adhesives Polyset® RTA-1 are limited to
Ma), determined in accordance with FBC 1609.5.3 or Tables
greater than the following Allowable Overturning Moment
s and Sealants, Inc. published installation instructions for
TABLE 1: FIELD TILES IN ICP.-A
DHESIVES POLYSET® RTA-1
ALLOWABLE OVERTURNING MI
MENT PERFORMANCE DATA `
4 To 1 MARGIN 0S' AF.TYALREADYAPPLIED
Tile (FBC 1609.5.3)
Adhesivo
Paddy Placement
Allowable
Overturning
Type
Profile
Placement
Contact Area
Moment
(ft-lbf)
Interdependent, Cross Bond Tile Application:
On Underlayment: One (1) -5-inch long x -9 g am oblong shaped bead on
underlayment at strengthening rib closest to I. nderlock side starting -4-inch below the
the course line working up towards the ridge, ontinuing 1-inch above the tile course
Tile Underside:
2
3r
-',
ISOnerete
VF.latf ;`
line and place the tile.
8 to 10 in
Tile Head Lap:
51.8
y, ^ 1-inc the
At'Tile Headlap: Continue on top of the exposed portion of underlayment-
10 in
bead and onto the head of the lower course title and carry the adhesive bead
minimum 4.5-inches horizontally across the h2ad of the lower course tile.
See Section 10, Placement Detail #1.
Interdependent, Cross Bond Tile Application:
On Underlayment: One (1) -5-inch long x -9 gram oblong shaped bead on
underlayment at strengthening rib closest to ttnderlock side starting -4-inch below the
tile course line working up towards the ridge, continuing 1-inch above the tile course
Tile Underside:
6 to 8 in 2
Concrete
Medium
line and place the tile.
Tile Head Lap:
44.0
At Tile Headlap: Continue on top of the -1-in h exposed portion of the underlayment-
10 in
bead and onto the head of the lower course t le and carry the adhesive bead
minimum 4.5-inches horizontally across the h ad of the lower course tile.
See Section 10, Placement Detail #2.
Interdependent, Cross Bond Tile Application:
On Underlayment: Two (2) -6-inch long x -12
gram oblong shaped beads on
Concrete
High
underlayment, side -by -side, where the pan p
rtion of the tile is to be located starting
36.2
-5-inch below the tile course line working up
towards the ridge, continuing 1-inch
Tile Underside:
above the tile course line and place the tile.
At Tile Headlap: Continue on top of the -1-inch
exposed portion of the underlayment-
12 to 16 in'
Tile Head Lap:
beads and onto the head of the lower course
ile and carry the adhesive bead
18 in'
Clay
High
minimum 10-inches horizontally, or the entir
width of the file, across the head of the
33.5
lower course tile.
See Section 10, Placement Detail #3.
Pan Tile to Underlayment: Two (2) ^7-inch long x -6 gram oblong shaped beads on
underlayment, side -by -side, where the center of the pan tile contacts the deck
starting ^2 to 3-inches from the eave end of the pan tile.
Tile Underside:
Cap Tile to Pan Tile: One (1) -7-inch long x-61gram oblong shaped bead at each long
35 to 40 in
Clay
Ca & Pan
p
(Barrel)
edge of the cap tile, % to 1-inch from each edge, starting -2 to 3-inches from the eave
Long Edge of
162.2
end working towards the ridge. Turn cap tile over and install onto pan, butting the
Cap Tile:
second course pan tile eave end on underlay ent, side -by -side, where the center of
20 to 25 in
the pan tile contacts the deck starting "2 to inches from the eave end of the pan tile.
See Section 10, Placement Detail #4.
5.6.1 Data in Table 1 relates to installation over a '3
2012 (04-12). Alternate underlayment systei
Approval and/or approved on a local -level by
Adhesives Polyset0'RTA-1.
Exterior Research and Design, I.I.C. '
Certificate ofAutharization #9503 6TH EDITION (2017) FBC I
ICP Adhesives Polyset®
0' underlayment system, as detailed in the FRSA/TRI April
include those having a current Florida Statewide Product
! Authority Having Jurisdiction specifically for use with ICP
Evaluation Report 02768.02.06-116
HZ EVALUATION FL6276-116
(888) 774-1419 Revision 6:10/12/2017
Page 3 of 8
F)o
\I I KINITiIERD
5.6.2 Tile roof systems using tile types or profiles other than those listed above acquiring acceptance for use with
ICP Adhesives Polyset® RTA-1 shall be tested in accordance with SSTD 11 or Testing Application Standard
TAS 101. For the interdependent multi -paddy method, an additional 2-to-1 margin of safety above that
specified in SSTD 11 or Testing Application Standard TAS 101 shall be applied in determining the 'allowable
overturning moment'.
5.7 Hip and ridge tiles using ICP Adhesives Polyset® RTA-1 are limited to projects having hip/ridge design
pressure requirements, determined in accordance with Table 1A of FRSA/TRI April 2012 (04-12), not greater
than the following values. Refer to ICP Adhesives and Sealants, Inc. published installation instructions for
Adhesive Paddy Placement details.
TABLE 2. Hlf?.&RIDGE TILES IN„ICP ADHESIVES POLYSET®:RTA 1 °.
k
•ALLOWABLE U0LIFY1,kESIsTANCE,Pi2kFORPAAhCE DATA
2 TO 1 MARGIN'OFSAFEI YALREADYAPPLIED FOR INDEPENDENT PLACEMENT r
IJ
4 T01 MARGIN4FSAFETYAIREADYAPPLIED FOR INTERDEPENDENT PLACEMENT
Allowable
Tile
Substrate
Attachment Method
Design Pressure
(psf)
Clay or
Interdependent: Head: One (1) #10 x 2%" screw;
Concrete
2x PT ridge board
Overlap: 1x6-inch x —10.5 gram
186.5
See Section 10, Placement Detail #5
r.
Hip &Ridge Channel Metal (FB7 FL5374
Independent: Tile -to -metal, centered along tile: 3x6-
�omerete
*r r.�gwrp
.galv�gnizeed only yy �; JJ
inch x —30 gram, starting 3-inch from the tile head.
122.6
See Section 10, Placement Detail #6
Hip & Ridge Channel Metal (FBC FL5374):
Independent: Tile -to -metal, centered along tile: 3x6-
Clay
galvanized only
inch x ^30 gram, starting 4-inch from the tile head.
251.2
See Section 10, Placement Detail #6
Trim Lock (FBC FL5394): aluminum
Interdependent:
Clay or
or
On Trim -Lock'"' metal: One (1) ^7-inch long x —10 gram
93
Concrete
Trim Lock'"" Plus (FBC FL5394): aluminum,
oblong shaped paddy centered on metal.
galvanized, Galvalume® or stainless steel
At Tile Headlap: One (1) ^7-inch long x —10 gram
oblong shaped bead at tile headlap.
Clay or
Trim Locklm (FBC FL5394): galvanized,
Concrete
Galvalume® or stainless steel
See Section 10, Placement Detail W.
110
6. INSTALLATION:
6.1 ICP Adhesives Polyset® RTA-1 and the tile roof assembly shall be installed in accordance with FRSA/TRI April
2012 (04-12) and ICP Adhesives and Sealants, Inc. published installation instructions, subject to the
limitations outlined in Section 5.
6.2 Hip and ridge boards or hip/ridge metal shall be installed in accordance with the FRSA/TRI April 2012 (04-
12). Proprietary hip and ridge metal shall be installed in accordance with the manufacturer's Florida Product
Approval.
6.3 Installation shall be performed by applicators that hold a valid Qualified Applicator Card presented by ICP
Adhesives and Sealants, Inc.
6.4 All tiles must be set in adhesive prior to tack free time (approximately 2 to 3 minutes).
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
Exterior Research and Design, I.I.C. Evaluation Report 02768.02.06-116
Certificate of Authorization #9503 6EDITION (2017) FBC NON-HVHZ EVALUATION F1.6276-116
ICP Adhesives Polyset® RTA-1; (888) 774-1419 Revision 6: 10/12/2017
Page 4 of 8
H. MANUFACTURING PLANTS:
Norton, OH
9. QUALITY ASSURANCE ENTITY:
UL, LLC.—QUA9625; (847) 664-3623; LeAnna.Gr
10. PADDY PLACEMENT DETAILS (FROM ICP ADHESIVES AND
10.1 Detail #1: Flat Profile Tile:
EaveooLrse
Exterior Research and Design, I.I.C.
Certificate of Authorization #9503
k
INC. PUBLISHED LITERATURE):
,acted to paddy
math fie
start ovedock side
`pac* at lie a xime line.
Start Ltij Iiodca paddy
amrowrmtely 1" abawe file
e EDITION (2017) FBC �ON-HVHZ EVALUATION
ICP Adhesives Polyset RTA-1; (888) 774-1419
\I TRINI7YJ ERD
Evaluation Report 02768.02.06-116
FL6276-R6
Revision 6:10/12/2017
Page S of 8
TRINITY JERD
10.2 Detail #2: Low/Medium Profile Tile:
10.3 Detail #3: High Profile Tile:
Exterior Research and Design, I.I.C. Evaluation Report 02768.02.06-116
Certiftate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL6276-116
ICP Adhesives Polyset® RTA-1; (888) 774-1419 Revision 6:10/12/2017
Page 6 of 8
10.4 Detail #4: Two Piece Barrel (Cap & Pan) Tile:
\
�+}l3
e�1
\I TRINITY ERD
10.5 Detail #5: Hip and Ridge (interdependent with screw):
Adhere•starter•
tile•withra? r'-x•7"
Paddy,•placed-3"�
downmcorri-hed&
ofitile�j .
Exterior Research and Design, U.C.
Certificate of Authorization #9503
6' EDITION (2017) FBC P
ICP Adhesives Polyset®
7,Fuc g
1"•)(;V'•8ead-of'ICP+
•Adliesiies, •
P,.olyiset`RTA-lrrpof•
ii1e•adhesiver•4
Code:Approy' ..
-Fastener:
Evaluation Report 02768.02.06-116
'HZ EVALUATION FL6276-116
(888) 774-1419 Revision 6:10/12/2017
Page 7 of 8
�l TRINITY I ERD
10.6 Detail #6: Hip and Ridge (independent placement):
:_r 1
,.�.'
3" x 6" Paddy
10.7 Detail #7: Hip and Ridi:e (interdependent placement):
- END OF EVALUATION REPORT -