EVALUATION REPORT
ICP Adhesives and Sealants, Inc.
12505 NW 44th Street
Coral Springs, FL 33065
(888) 774-1419
APR 18 2018
2T.��I.Jae Coi
` - fnty, nm...�
EXTERIOR RESEARCH & DESIGN, I.I.C.
Certificate of Authorization r'l9503
353 CHRISTIAN STREET, UNIT 13
OXFORD, CT 06478
(203)262-9245
Evaluation Report 02768.03.06-RS
FL6332-R8
Date of Issuance: 08/08/2008
Revision 8: 10/12/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 a d the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 6th Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: ICP Adhesives PolysetO AH-160
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity) ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number precede by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 9.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
CERTIFICATION OF INDEPENDENCE:
1. Exterior Research & Design, LLC. d/b/a Trinity I ERD does not
in any company manufacturing or distributing products it eval
2. Exterior Research & Design, LLC. d/b/a Trinity I ERD is n<
distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a finar
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a final
product.
5. This is a building code evaluation. Neither Trinity I ERD nor
project on which this Evaluation Report, or previous versions
specifically for that purpose.
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. on 10/12/2017. This does not serve as an
electronically signed document.
have, nor does it intend to acquire or will it acquire, a financial interest
sates.
t owned, operated or controlled by any company manufacturing or
:ial interest in any company manufacturing or distributing products for
cial interest in any other entity involved in the approval process of the
tobert Nieminen, P.E. are, in any way, the Designer of Record for any
thereof, is/was used for permitting or design guidance unless retained
rA
1,71
ROOFING COMPONENT EVALUATION:
1.
3.
SCOPE:
Product Category: Roofing
Sub -Category: Roof T)IeAdhesives
Compliance Statement: ICP Adhesives Polyset®
demonstrated compliance with the 6th Edition (201
Standards set forth herein. Compliance is subject
Use set forth herein.
STANDARDS:
Sections
1504.2.1.1
REFERENCES:
Entity
ERD (TST 6049)
ERD (TST 6049)
ICC-ES (EVL2396)
Miami -Dade (CER 1592)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
PRI (TST 5878)
UL LLC (QUA 9625)
4. PRODUCT DESCRIPTION:
Property
Overturning resistance
Examination
Static Uplift —SSTD 11
Static Uplift —SSTD 11
2012 IBC Compliance
HVHZ compliance
Static Uplift —SSTD 11
Static Uplift —SSTD it
Static Uplift —SSTD it
Static Uplift —SSTD 11
Static Uplift —SSTD 11
Static Uplift —SSTD 11
Static Uplift —SSTD 11
Static Uplift —SSTD 11
Static Uplift —SSTD 11
Static Uplift —SSTD 11
Static Uplift —SSTD 11
Static Uplift —SSTD it
Static Uplift —SSTD 11
Static Uplift —SSTD 11
Static Uplift —SSTD it
Static Uplift —SSTD 11
Static Uplift —SSTD 11
Static Uplift —SSTD it
Static Uplift —SSTD 11
Quality Assurance
1-160, as produced by ICP Adhesives and Sealants, Inc., has
Florida Building Code through testing in accordance with the
the Installation Requirements and Limitations / Conditions of
Standard
SSTD 11
Reference
P39740.02.12
P39740.11.13-R1
ESR-1709
17-0322.03
ECM-001-02-01
PFI-006-02-01
PFI-006-02-02
PFI-007-02-01
PFI-008-02-04
PFI-009-02-03
TG RI-001-02-03
TG RI-001-02-03
PFPI-010-02-01
PFPI-011-02-01
PFPI-012-02-01
PFPI-013-02-01
PFPI-014-02-01
ECM-003-02-01
ECM-004-02-01
ECM-005-02-01
ECM-006-02-01
ECM-007-02-01
ECM-008-02-01
Service Confirmation
Year
1997
Date
02/20/2012
01/02/2015
12/01/2016
04/27/2017
09/21/2001
05/09/2005
05/09/2005
10/11/2005
02/21/2006
02/21/2006
10/30/2006
10/30/2006
12/07/2006
12/07/2006
12/07/2006
12/07/2006
12/07/2006
06/13/2008
06/13/2008
06/13/2008
06/13/2008
06/13/2008
06/13/2008
Exp. 06/05/2018
4.1 ICP Adhesives Polyset® AH-160 is a two -component expanding polyurethane roof tile adhesive that is mixed
and dispensed from a dispensing system provided by ICP Adhesives and Sealants, Inc. The components are
available in refillable tanks or disposable cylinders (ICP Adhesives ProPack® 30 & 100).
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity ERD nor Robert Nieminen, P.E. are, in anyway, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for
permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
Exterior Research and Design, I.I.C. I Evaluation Report 02768.03.06-R8
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset® AH-160; (888) 774-1419 Revision 8:10/12/2017
j Page 2 of 9
-"1
\I TRINITYIERD
5.3 Fire classification is not part of this evaluation. Refer to a current Roofing Materials Directory for fire ratings
of this product and FBC 1505.2.
5.4 ICP Adhesives Polyset® AH-160 can be used with flat, low and high profile tiles or any rigid, discontinuous roof
assembly having a current Florida Statewide Product Approval or approved on a local -level by the Authority
Having Jurisdiction.
5.5 Minimum underlayment shall be per FRSA/TRI April 2012 (04-12) or having a current Florida Statewide
Product Approval or approved on a local -level by the Authority Having Jurisdiction for use with ICP Adhesives
Polyset® AH-160.
5.6 Field tiles, meeting the limitations of FBC 1609.5.3, using ICP Adhesives Polyset® AH-160 are limited to
projects having an Aerodynamic Uplift Moment (Ma), determined in accordance with FBC 1609.5.3 or Tables
2A and 26 of FRSA TRI April 2012 (04-12 ), not greater than the following Allowable Overturning Moment
values. Refer to Section 10 and ICP Adhesives and Sealants, Inc. published installation instructions for
Adhesive Paddy Placement details.
TABLE 1:: FIELD TILESIIN ICP ADHESIVES POLYSET® AH-160
ALLOWABLE,OVERTURNING MOMENT:PERFORMANCE DATA
2 To JNFARGINOFSAFETYALREADYAPPLIED FOR INDEPENDENT (SINGLE OR CONTINUOLIS PADDY) PLACEMENT -
_ 4TOIMARGINOFSAFETYALREADYAPPLIEDFORINTERDEPENDENT(TWOPADDY)PLACEMENF - •
Tile (FBC 1609.5.3)
'Adhesive Paddy Placement
Allowable
Overturning
Type
Profile
Moment (ft-lbf)
Independent; Single Paddy, Medium (2x7-inch, -80 gram)
60
Clay or
Flat
Independent; Single Paddy;, Large (2x10-inch, -45 gram)
112
Concrete
Interdependent; Two Paddy (4x4-inch on underlayment, 2x4-inch at tile overlap)
54
Independent; Single Paddy, Medium (20-inch, -30 gram)
39
Clay or
Low/
Independent; Single Paddy;, Large (2x10-inch, -54 gram)
67
Concrete
Medium
Interdependent; Two Paddy (4x4-inch on underlayment, 2x4-inch at tile overlap)
58
Clay
High
Independent; Single Paddy, Large (2x10-1nch, -45 gram)
134
Independent; Single Paddy, Medium (2x7-inch, -30 gram)
65
Concrete Clay
High
Independent; Single Paddy, Large (2x10-inch, -63 gram)
109
Interdependent; Two Paddy (4x4-inch on underlayment, 2x4-inch at tile overlap)
40
Clay
Barrel
2x10-inch x -35 gram for pans; 2 @ 1x10-inch x -17 gram for cap
147
Concrete
Barrel
2x10-inch x -35 gram for pans; 2 @ 1x10-inch x -17 gram for cap
107
Clay
Cap atop 2x
Independent: Continuous Paddy (-34 gram/ft)
135
stringer
Concrete
Cap atop 2x
Independent: Continuous Paddy (- 34 gram/ft)
116
stringer
Clay
Cap atop 2x
Interdependent:
105
stringer
Head: One (1) #10 x 2Y:' screw; Overlap: 1 x 6 inch (-10.5 gram)
Concrete
Cap atop 2x
Interdependent:
76
stringer
Head: One (1) #10 x 2Y=' screw; Overlap: 1 x 6 inch (-10.5 gram)
5.6.1 Data in Table 1 relates to installation over a '30/90' underlayment system, as detailed in the FRSA/TRI April
2012 (04-12). Alternate underlayment systems include those having a current Florida Statewide Product
Approval and/or approved on a local -level by the Authority Having Jurisdiction specifically for use with ICP
Adhesives Polyset® AH-160. 1
5.6.2 Tile roof systems using tile types or profiles other than those listed above acquiring acceptance for use with
ICP Adhesives Polyset® AH-160 shall be tested in accordance with SSTD 11 or Testing Application Standard
TAS 101. For the interdependent two -paddy method, an additional 2-to-1 margin above that specified in
SSTD 11 or Testing Application Standard TAS 101 shall be applied in determining the 'allowable overturning
moment'.
Exterior Research and Design, I.I.C. Evaluation Report 02768.03.06-118
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset® AH-160; (888) 774-1419 Revision 8:10/12/2017
Page 3 of 9
I
•
UT--RINITYIERD
5.7 Hip and ridge tiles using ICP Adhesives Polyset® AH-160 are limited to projects having hip/ridge design pressure
requirements, determined in accordance with Table 1A of FRSA/TRI April 2012 (04-12), not greater than the
following values. Refer to ICP Adhesives and Sealants, Inc. published installation instructions for Adhesive
Paddy Placement details.
TABLE 2: HIP& RIDGE TILES IN ICP ADHESIVESPOLYSET® AH-160
ALLOWABLE'UPLIFT RESISTANCE PERFORMANCE DATA
2 To I MARGIN OF SAFETYALREADYAPPLIED FOR INDEPENDENT (CONTINUOUS PADDY) PLACEMENT
4 TO I MARGIN OF SAFETYALREADY.APPLIED FOR INTERDEPENDENT PLACEMENT
Allowable
Tile
Substrate
Attachment Method
Design Pressure
(Psf)
Clay
2x PT ridge board
Independent: Continuous Paddy (-34 gram/ft)
116
Concrete
2x PT ridge board
Independent: Continuous Paddy (- 34 gram/ft)
107
Interdependent: Head: One (1) #10 x 2'/2" screw;
90
Clay
2x PT ridge board
I
Overlap: 1 x 6 inch (-10.5 gram)
Interdependent: Head: One (1) #10 x 2'/2" screw;
56
Concrete
2x PT ridge board
Overlap: 1 x 6 inch (-10.5 gram)
Clay or
Hip & Ridge Channel Metal (FL5374):
Independent: Continuous Paddy (-34 gram/ft)
169
Concrete
galvanized only
Clay or
Trim Lock'" (FL5374): aluminum,
Independent: Continuous Paddy (-34 gram/ft)
173
Concrete
galvanized, Galvalume or stainless steel
Clay or
Trim Lock'" Plus (FL537® ): aluminum, i
Independent: Continuous Paddy (^ 34 gram/ft)
178
Concrete
galvanized, Galvalume or stainless steel
Clay
Top Notch (FL8095)
Independent: Continuous Paddy (^ 32 gram/ft)
125
Concrete
Top Notch (FL8095)
Independent: Continuous Paddy 32 gram/ft)
146
6. INSTALLATION:
6.1 ICP Adhesives Polyset® AH-160 and the tile roof assembly shall be installed in accordance with FRSA/TRI
April 2012 (04-12) and ICP Adhesives and Sealants, Inc. published installation instructions, subject to the
limitations outlined in Section 5.
6.2 Hip and ridge boards or hip/ridge metal shall .be installed in accordance with the FRSA/TRI April 2012 (04-12).
Proprietary hip and ridge metal shall be installed in accordance with the manufacturer's Florida Product
Approval.
6.3 Installation shall be performed by applicators who hold a valid Qualified Applicator Card presented by ICP
Adhesives and Sealants, Inc.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the
installation of this product.
8. MANUFACTURING PLANTS:
Tomball, TX
9. QUALITY ASSURANCE ENTITY:
UL, LLC.-QUA9625; (847) 664-3623; LeAnna.Gradecki@ul.com
Exterior Research and Design, I.I.C. Evaluation Report 02768.03.06-118
Certificate ofAuthori2ation #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-R8
ICP Adhesives Polyset® !AH-160; (888) 774-1419 Revision 8:10/12/2017
Page 4 of 9
I
TRINITY I ERD
10. PADDY PLACEMENT DETAILS (FROM ICP ADHESIVES AND SEALANTS, INC. PUBLISHED LITERATURE):
10.1 Independent, Medium Paddy:
Nail through plastic cement Paddy (Beneath Tile)
(when required)
Underlayment
o
— �4I
Eave
Eave
7in. '►i.12in. \\
s optional f J0
o
%0
10in. ��.
Flat/Low Profile Tile
Nail through plastic ce ent
(when required)
Underlayment
21n.
Battens optional
y Eave Course
10in. 2in. �
Nail through plastic cement
(when required)
Paddy (Beneath Tile)
Underlayment a `
e
71n
21n.
Battens optional
w
loll. ``t, 21n.
Gave Closure
Eave Course Fascia
High Profile Tile
I
Medium Profile Tile
Paddy (Beneath Tile)
Weephole
Eave closure
Drip edge
Exterior Research and Design, I.I.C. I Evaluation Report 02768.03.06-R8
CertiJkate of Authoriratlon u9503 6T" EDITION (2017) FBC NON-HVH2 EVALUATION FL6332-R8
ICP Adhesives Polyset° AH-160; (888) 774-1419 Revision 8:10/12/2017
Page 5 of 9
10.2 Independent, Laree Paddy:
Flat/Low Profile Tile
Nall through plasticce
(when required)
Underlayment o
Exterior Research and Design, LLC.
Certificate of Authorization #9503
_� 10in.x '
2in. wide
Battens o
optional Ski
Eave Course
10 in. 2 in.
.11
I
i
QOTRINITYIERD
Nall through plastic cement
(when required)
-------Paddy (Beneath Tile)
Underlayment
I a
r.
10in.x
2in.wide
Battens optional
L
10 in. ` 2 in.
Eave Closure
Eave Course Fascia
i Profile Tile
Medium Profile Tile
Paddy (Beneath Tile)
Weephole
Eave closure
Drip edge
6'" EDITION (2017) FBC NON-HVHZ EVALUATION
ICP Adhesives Polyset! AH-160; (888) 774-1419
I
Evaluation Report 02768.03.06-118
FL6332-R8
Revision 8:10/12/2017
Page 6 of 9
11J.3 I1-ILCrut!Pt:F1Ut:11L. .YVU rd UUY:
Nail through plastic cement Paddy (between tiles)
(when required)
Battens optional °
° Padd�-�/ / y (under tile)
single paddy
on top of tale <!
L
x4in.
on underlayment 2 x 4 in.
0
hfi
10 m.
�2 i
Flat/Low Profile Tile
Exterior Research and Design, I.I.C.
Certificate of Authorization #9503
Eave Closure
(-)o
,-,I TRINITY I ERD
Nail through plastic cement Single paddy under tile
(when required)
Paddy (between tiles)
Battens /Paddy (under tile)
optional
W �3
Single paddy
of tile
V4x4in. x4m
Single paddy on
underlayment
10 in. 2 in.
Eave Closure
Eave Course Fascia
Medium ProfileTile
Nail through plastic cep Single paddy under tile
(when required)
\ I
Paddy (between tiles)
Battens optional °
l
Paddy (under tile)
W Singlepaddy
on underlayment tf
4 x 4 in.
Single 2x4in.
r
paddy on
top of the A
Eave Course —_ `'
Fascia
F
Weephole
10in.2in.
Eaveclosure
Drip edge
High ProfileTile
I
I
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
ICP Adhesives Polyset® A1-1-160; (888) 774-1419
Evaluation Report 02768.03.06-118
FL6332-RB
Revision 8:10/12/2017
Page 7 of 9
TRINITY I ERA
10.4 Two Piece Barrel (Cap & Pan) Tile:
1) Place enough adhesive to achlave 6S to 70 sq.in. Steep pitch applications
In contact with the pan tile. A (when required)
2) Turn Covers upside down: Place adhosiva
112 In. to 1 Inch In from outside edge of cover tile.'
Install Cover tile.
Ensure 20 to 2b sq. contact area ofi
each slde'of cover Ola. ���o
(motor shown)
Weephole Fascia Board
Remove top portion of the ea4e course cover tile.Abut to second course of
pan t11es.Ensure eave end of pan and covertilesare flush at eave line.
Two Piece Barel - High Profile Tile
10.5 Hip and Ridge (independent placement):
A bead of ICP Polysel!ZAH-160 my be applied above Ole hild To attach hiplddgc iks, a bead of ICP-Polysogffil.160 may
the surface on both sides of the hipIrWga board or galvinimr! be applied dourn the center of the h4*Wge board or galviaized
nrttal frame to provide n eatheiblockirrg. frame.
i
Exterior Research and Design, LLC. Evaluation Report 02768.03.06-RS
Certificate oJAuthorizatfon #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL6332-118
ICP Adhesives Polyset® AH-160; (888) 774-1419 Revision 8: 10/12/2017
Page 8 of 9
10.6
Exterior Research and Design,LLC.
Certificate of Authorization #9503
- END OF EVALUATION REPORT -