Code Version
2017
FL#
11651.22
Application Type
ALL
Product Manufacturer
ALL
Category
ALL
Subcategory
ALL
Application Status
ALL
Compliance Method
ALL
Quality Assurance Entity
ALL
Quality Assurance Entity Contract Expired
ALL
Product Model, Number or Name
ALL
Product Description
ALL
Approved for use in HVHZ
ALL
Approved for use outside HVHZ
ALL
Impact Resistant
ALL
Design Pressure
ALL
Other
ALL
Search Results - AoDlications
FL#
Tyne
Manufacturer
Validated By
Status
FL11651-R3
Revision
Gulf Coast iSupply & Manufacturing, LLC.
FL#: FL11651.22
Locke Bowden P.E.
(334) 300-1800
Approved
History
Model: 26, Ga. GUIfRib
Description: Min 26 Ga. GulfRib over 15/32" Plywood
Category: Roofing
Subcategory: Metal Roofing
*Approved by DBPR. Approvals by DBPR shall be reviewed and ratified by the POC and/or the Commission if necessary.
I
Contact Us :: 2601 Blair Stone Road, Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida.:: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mail address released In response to a public -records request, do not send electronic
mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. *Pursuant to Section
455.275(1), Florida Statutes, effective October, 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address if they have
one. The emails provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to supply a personal
address, please provide the Department with an email address which can be made available to the public. To determine if you are a licensee under Chapter 455, F.S.,
please click here .
Product Approval Accepts:
i
®� iCf'Rtl
Credit C6rd�
Product Evaluation Report
GULF COAST SUPPLY & MANUFACTURING, LLC
26 Ga. GulfRibTm Roof Panel over 15132" Plywood
RECEIVED
APR `Z.018
ST. Lucie County, Permittifl
FL# 11651.22 R3 • OCTOBER 5, 2017
Florida Product Approval #11651.22 R3
Florida Building Code 2017
Per Rule 61 G20-3
Method: 1 —D
Category: Roofing
Subcategory: Metal Roofing
Compliance Method: 61 G20-3.005(1)(d)
NON HVHZ
: Product Manufacturer:
Gulf Coast Supply & Manufacturing, LLC.
14429 SW 2nd Place, Suite G30 %.%`�4%EL, S��k'�,
Newberry, FL 32669 ; `SOP ��G r;'N,�y •,
Engineer Evaluator:
Dan Kuhn, P.E. #75519
Florida Evaluation ANE ID: 10743
Validator:
Locke Bowden, P.E. #49704
9450 Alysbury Place
Montgomery, AL 36117
Contents:
Evaluation Report Pages 1 — 5
* , No. 7551.9
;4r
STATE OF
'FS►S 0111"R l
O P.G�tJ��.:
�NA �E % 10/05/201 j
Compliance Statement: The product as described in this report has demonstrated compliance with the
Florida Building Code 2017, Sections 1504.3.2.
Product Description: GulfRibTM' 3/a" Rib Roof Panel, Minimum 26 Ga. Steel, 36" Coverage,
through! fastened roof panel over minimum 15/32" Plywood Decking. Non
Structural application.
Panel Material/Standards: Material: Minimum 26 Ga. Steel, ASTM A792 or ASTM A653 G90 conforming to
Florida Building Code 2017 Section 1507.4.3.
Paint Finish Optional
Yield Strength: Min. 80.Oksi
Corrosion Resistance: Panel Material shall comply with Florida Building
Code 2017, Section 1507.4.3.
Panel Dimension(s): Thickness: 0.018" Minimum
Width: 36" Coverage
Rib Height: 3/a" Major Rib at 9" O.C.
Panel Fastener: #9-15x1.5" HWH with sealing washing or approved equal
1/4" minimum penetration through plywood.
Corrosion Resistance: Per Florida Building Code 2017, Section 1506.6, 1507.4.4
Substrate Description: Minimum75/32" thick, APA Rated plywood over supports at maximum 24" O.C.
Design! of plywood and plywood supports are outside the scope of this
evaluation. Must be designed in accordance w/ Florida Building Code 2017.
Design Uplift Pressures:
FL# 11651.22 R3 •OCTOBER 5. 2017
Table"A"
�Maxirrium Total Uphft De ign Pres' q e 69 5 psf� 9 5�psf
Fastener Pattern
9"-9"-9"-9"
6.5"-2.5"-6.5"-
2.5"6.5"-2.5"-6.5 "
FastererPatteni+Spacing
,}WE,
Design Pressure includes a Safety Factor = 2.0.
Aoft Ae I 1r!nWx\Pd 0
Code Compliance: The product described herein has demonstrated compliance with the
Florida' Building Code 2017, Sections 1504.3.2.
Evaluation Report Scope: The product evaluation is limited to compliance with the structural wind load
requirements of the Florida Building Code 2017, as relates to Rule 61 G20-3.
Performance Standards: The product described herein has demonstrated compliance with:
• UL 580-06 - Test for Uplift Resistance of Roof Assemblies
• UL 1897-12 - Uplift Test for Roof Covering Systems.
Reference Data: 1. UL 580-94 / 1897-98 Uplift Test
Force Engineering & Testing, Inc. (FBC Organization # TST-5328)
Report No. 117-0062T-07A, B, Dated 02/19/2007
2. Certificate of Independence
By Dan Kuhn, P.E. (FL# 75519) @ Kuhn Engineering, LLC
(FBC Organization # ANE ID: 10743)
Test Standard Equivalence: 1. The UL 580-94 test standard is equivalent to the UL 580-06 test standard.
2. The UL 1897-98 test standard is equivalent to the UL 1897-12 test
standard.
Quality Assurance Entity: The'manufacturer has established compliance of roof panel products in
accordance with the Florida Building Code and Rule 61 G20-3.005(3) for
manufacturing under a quality assurance program audited by an approved quality
assurance entity.
Minimum Slope Range: Minimum Slope shall comply with Florida Building Code 2017, including
Section 1507.4.2 and in accordance with Manufacturers recommendations. For
slopes less than 3:12, lap sealant must be used in the panel side laps.
Installation: Install per Manufacturer's recommended details.
Underlayment: Shall comply with Florida Building Code 2017 section 1507.1.1.
FL# 11651.22 R3 • OCTOBER 5, 2017
lr/wl` e o
i
Roof Panel Fire Classification: Fire classification is not part of this acceptance.
Shear Diaphragm: Shear Diaphragm values are outside the scope of this report.
i
Design Procedure: For roofs within the parameters listed on the load table, fastening pattern must
at a minimum meet those listed for the applicable wind zone. For all roofs outside
the parameters listed on the load table, design wind loads shall be determined
for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10
using allowable stress design. The maximum fastener spacing listed herein shall
not be exceeded. This evaluation report is not applicable in High Velocity
Hurricane Zone. Refer to current NOA or HVHZ evaluation report for use of this
product in High Velocity Hurricane Zone.
FL# 11651.22 R3 • OCTOBER 5, 2017
i_,N-�N --
ENGINEER LOAD TABLE: 26 Ga. GulfRibT'" Panel over 15132" Plywood
Buildings having a Roof�Mean;Heigk 5:Z0' O';;Roof Slope: 2"/12` 12 /12'�Gable or Hlp,Roof, Wind Speeds 120
1'80mph;posure:C,, Risk Category'11; EncloseU Building, based on,>Ffonda.Buiiding Code 20>17
;.
120
130
140
150
160
170
180
WIIND
FASTENER
SUBSTRATE
SPEED
(MIN. 1/4"
penetration)
(MIN. 15/32")
ON CENTER
ON CENTER
ON CENTER
ON CENTER
ON CENTER
ON CENTER
ON CENTER
SPACING
SPACING
SPACING
SPACING
SPACING
SPACING
SPACING
ZONE.1
#9 15x1 5' ,
Plywood
TYPE 1
24" TYPE 1'
24 TyPE51
24 TYPE 1
f
24"> TYPE 1 r
i Y
24 TYPE 1/
24 TYPE 1 `
}24
,
ZONE 2
#9-15x1.5"
Plywood
24", TYPE I1
24", TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 2
ZONES
#9-15x1 5"
Plywood
',24TYPE�1
i
4. TYPE 1^
24 TYPE 1
kQ. e
' 12 TYPE 2
y 's
12 1TYPE 2. `
i s�
12 TYPE 2
i.
12 TYPE 2-
.
1.) PANEL DESCRIPTION: GULFRIBTM, MIN. 26 GA., GRADE 80, 36"COVERAGE, 3/4" TALL:
2.) PANEL FASTENER: #9-15X1.5" HWH WITH SEALING WASHER OR APPROVED EQUAL
3.) MAXIMUM ALLOWABLE PANEL UPLIFT PRESSURE: 69.25 PSF @ 24" O.C. FASTENER SPACING TYPE I FASTENER PATTERN, 159.25
PSF @ 12" O,C. FASTENER SPACING TYPE 2 FASTENER PATTERN BASED ON TAS 125, UL 580/UL 1897 TESTING.
4.) PLYWOOD DECKING: MIN. 75/a2" THICK PLYWOOD MUST BE DESIGNED IN ACCORDANCE WITH FLORIDA BUILDING CODE 2017.
5.) ROOF SLOPE: ON ROOF SLOPES LESS THAN 3:12, ILAP SEALANT MUST BE USED IN PANEL SIDE LAPS.
6.) LOAD TABLE BASED ON WIND PRESSURES CALCULATED PER ASCE 7-10 (KD = 0.85) MULTIPLIED BY 0.6 PER FLORIDA BUILDING
CODE 2017.
wo MAC
tulle z ZONE 3)
J----------------
nIt RIDGE
i•-- ------
ZONE1 \\\\\ l
------------------�
Note: Dimension (a) is defined as 10% of the minimum width of the building or
1 40% of the mean height of the roof, whichever is smaller, however, (a) cannot be
:=Ia i less than either 4% of the minimum width of the building or 3 feet.
TYPE 1 FASTENER PATTERN
ZONE 2
GABLE ROOF TaT
-----------------
t �
I
—a
I
RIDGE I
�-
----- --
—— — — — — — — — — —
—
a
+-----------------------
a
I
�
ZONE
I \
I
"ZONE3 HEAVE
FL# 11651.22 R3 • OCTOBER 5, 2017
At Panel
Cont. Tape Seal for use on Slopes less than 3:1
#9-15 x 1-1/2' w/Sealer Washer @ 24' O.C. Max.
TYPE 2 FASTENER PATTERN
Cant. Tape Seal for use on Slopes less than
#945 x 1.1/2° w/Sealer Washer @ 12' O.C. Max.