Loading...
HomeMy WebLinkAboutPROJECT INFORMATION-- wrightsoft, Project Summa Entire House QUICK CALCS, IN . 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax For: THE GRAND C WYNNE DEVE Notes: \�-A J Weather: Winter Design Conditions Outside db 42 OF Inside db 70 OF Design TD 28 OF Heating Summary Structure 17848 Ducts 5654 Central vent (0 cfm) 0 (none) Humidification 0 Piping 0 Equipment load 23503 Infiltration Method Construction quality Fireplaces He 1'g Coc Area ft Volume (ft3) 12511 1 Air changes/hour 0.45 Equiv. AVF (cfm) 94 Heating. Equipment Summary Make Carrier Trade CARRIER AIR CONDITIONING Model 25HBC536A*030 AHRI ref 7914585 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat Capacity balance point = 32 OF Backup: SCANN Job: � Date: Li By: Email: QUICKCALCS@AQL.COM. FT. PIERCE, FL : `at Fort Pierce, FL, US 48 8.5 HSP 34600 Btuh @ 47°F 27.OF 1160 cfm 0.049 cfm/Btuh 0.50 in H2O Input = 7 kW, Output = 23009 Btuh, 100 AFU Summer Design Conditions Outside db 90 OF Inside db 75 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 gr/Ib Sensible Cooling Equipment Load Sizing Structure 17520 Btuh Ducts Central vent (0 cfm) 8536 0 Btuh Btuh (none) Blower 0 Btuh Use manufacturer's data Rate/swing multiplier n 0.95 Equipment sensible load 24753 Btuh Latent Cooling Equipment Load Sizing Structure 3203 Btuh Ducts 2318 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 5521 Btuh Equipment total load 30274 Btuh Req. total capacity at 0.70 SHR 2.9 ton Cooling Equipment Summary Make Carrier Trade CARRIER AIR CONDITIONING Cond 25HBC536A*030 Coil FX4DN(B,F)037 AHRI ref 7914585 Efficiency 12.0 EER, 15 SEER Sensible cooling 24360 Btuh Latent cooling 10440 Btuh Total cooling 34800 Btuh Actual air flow 1160 cfm Air flow factor 0.045 cfm/Btuh Static pressure 0.50 in H2O Load sensible heat ratio 0.83 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. ACC. wrightsoftQ Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-11 09:Page age I ...uick CaIcslDocuments\THE GRAND CARLTON-1446.rup Calc,= MJB Front Door faces: N -1- wrightsoft Right-JO Worksheet Job: Entire House °ate` By. QUICK CALCS, INC. . 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House BEDROOM 2 Exposed wall 156.2 ft 49.0 ft 3 Room height 8.7 ft d 8.0 ft heat/cool 4 5 Room dimensions Room area 1445.5 ft2 1.0 x 297.0 ft 297.0 ft2 Ty Construction U-value Or HTA� Area (ft2) Load Area (ft2) Load number (Btuh/ft'L°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) . Heat 600l Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs• . • 0143 c n 4:00 2.55 503 465 1862 1184 .- 72 72. 288 ' 183 .4A5-26m ' 13A-4ocs 0:770 0.143 : n" a 21.66 4.00 19.:M 2.55 38 128 ' 0. 83 815 333 730 212 0 0 0 0 :0 0 6 0 11 1Ao1om 11DO 1.270 0.390 a a 35.56 10.92 87.29 11.31 24 21 2 21 848 229 2082 238 0 0 0 0 0 0 0 0 W t-G 13A-4ocs 13A4ocs 0:143 0.143 se s 4.00 4.00 2.55 2.55 34 360 34 353 136 1414 86 899 0 216 0 216 0 865 0 550 1A-clom 1.270 s 35.56 34.77 7 7 247 241 0 0 0 0 13A4ocs 1Ao1om 0.143 1.270 . w w 4.00 35.56 • 2.55 55.21 310 32 237 2 949 1140 603 1770 104 32 •72 2 288 1140 183 - 1770 '4A5r2om . 0.770 w 21:56 19.31 _ 41 . 41 860 788 0 - - 0 . D _ .. 0 P 12C-0sw 0.091 - 2.55 1.28 192 192 489 246 0 0 0 0 C:., -16A-30m_d 0.032 - -OM 2.3.2 1446. .1446 1295.:. 3354 297. 297: 266 :689 ]12 F , w. 22A tpl 0.989 - 27.69 0.00 1446 156 4325 0 297 49 1357 0 c)AED excursion 918 627 Envelope loss/gain 14961 13349 4204 4003 a) Infiltration 2887 791 848 232 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 6 1380 3 690 Appliances/other 2000 0 Subtotal lines 6 to 13 ( ) ; 17848 17520 5053 4925 Less external load 0 0 0 0 14 15 Less transfer Redistribution Subtotal Ducfloads 32% 49% 0 0 17848 5654 0 0 17520 8536 32% 49% 0 0 5053 1601 0 0 4925 2400 Total roam load Air required (cfm) 23503 1160 26056 1160 6653 328 7325 326 J 8th Ag& -Fp- wrightsoft- Right -Suite® Universal 2017 17.0.14 RSU08101 ...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces: N 2017-Apr-11 09:29:38 Page 1 - - wrightsoft* Right-M Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax (72-466-6796 Email: QUICKCALCS a(AOL.COM 1 Room name WIC KrrCHEN 2 3 E)posed wall Room height O ft 8.0 ft heat/cool O ft 8.0 ft heat/cool 4 5 Room dimensions Room area 6.0 x 9.0 ft 54.0 ft2 1.0 x 172.0 ft 1720 f12 Ty Construction number U-value (Btuh/ft2--°F) Or HTM (Btu2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat (Cool Gross WP/S Heat Cool Gross WP/S Heat Cool 6 ' T{/-G 13A�ocs' :4A5.2orn 13A-4ocs 0143 0.770 0.143 •0: n a 4;00 ; 21:56 4.00 2.55 19;31 2.55 0 0 0 0 0 0 0 0 0 :0 0 0 0 0 0 0 0 0. .p 0 0 ;'.. p 0 11 � IA-clom 11DO 13AAocs 13A-0ocs 1Aclom 13A-4ocs 1A-clom -. 4A5-2om 12C-0sw •16A 30md 22A tpI 1.270 0.390 0.143. 0.143 1.270 0.143 1.270 0.770 0.091 0:032 0.9n a a se , s s w w w - - - - 35.56 10.92 4.00 4.00 35.56 4.00 35.56 21.56 2.55 0:90 27.69 87.29 11.31 2.55 2.55 34.77 2.55 55.21 19.31 1.28 2.32 0.00 0 0 0 0 0 0 0 0 0 .54 54 0 0 0 0 0 0 0 0 0 54 0 0 0 0. 0 0 0 0 0 0 48 0 0 0 0 0 0 0 0 0 0 125 0 0 0 0 0 0 0 0 0 64 172 172 0 0 0 0 0 0- 0 0. 64 172 0 0 0 0 0 0 0 0 0 163 154 0 0 0 0 0 0 0 0 0 82 399 0 __D W V!J T-G P G ..:: F 6 c)AED excursion 9 -170 Envelope loss/gain 48 117 317 311 12 a) Infiltration b) Room ventilation 0 0 0 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 p 0 0 2000 Subtotal (lines 6 to 13) I 48 117 317 2311 14 15 Less extemal load Less transfer Redistribution Subtotal Duct loads 32% 49% 0 0 0 48 15 0 0 0 117 57 32% 49% 0 0 0 317 100 0 0 0 2311 1126 Total room load Air required (cfm) 64 31 174 81 418 21 3437 153 to meet all requirements of Manual J_8th �A '- wrightsOft" Right -Suite® Universal 2017 17.0.14 RSU08101 ...uick Caics\Documents\THE GRAND CARLTON-1446.rup I Calc = 10J8 Front Door faces: N 2017-Apr-11 09:29:38 Page 2 wriohtsoft° Right-M Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@,AOL,COM 1 Room name BATH BEDROOM 2 2 Exposed wall 5.0 ft 34.2 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 5 Room dimensions Room area 9.0 x 5.0 ft 45.0 ft2 1.0 x 203.5 ft 203.5 ft2 Ty Construction U-value Or HTIu Area (ft2) Load Area (ft2) Load number (Btuh/W-°F) (Btu 2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cocl Gross N/P/S Heat Cool Gross N/P/S Heat Cool 5 13A4ogs 0143 .•m -4:00. 2.55 40 40" - 160 '102 128 .-•:128 513. 326 •. 4A5 loin . 0.770 ri 21 56 19:31 0 0 0 0 0` 0 0 0 13A-4ocs 0,143 a 4.00 2.55 0 0 0 0 80 56 225 143 11 -G L-D IA-clom 11DO 1.270 0.390 a a 35.56 10.92 87.29 11.31 0 0 0 0 0 0 0 0 24 0 2 0 848 0 2082 0 W V}/ t-G 13A4ocs 13A4ocs 1A-clom 0:143 0.143 1.270 se s s .4.00 4.00 35.56 2.55 2.55 34.77 0 0 0 0 0 0 0 0 0 0 0 0 34 32 0 .34 32 0 136 128 0 86 81 0 13A-4ocs 1A-clom 0 143 1.216 w -. w 4.00 35.56 , 2.55 55.21 0 0 0 0. 0 0. 0 0 0 0 0. 0 0 0-. '0 0 4A5?2om- 12C-Osw 0.770 0.091 w - 29:56 . 2.55 1931 1.28 - 0. 0 0 0 0 0 0 0 0 0 . 0 0 0: 0 0 0 P %AwMrn& - 0.032 .. _ -. 0.90 2,3.2 .. 45 . 45 40 104 .204 .. - 204- 182 ; - 472 IF22A-tpl 0.989 - 27.69 0.00 45 5 138 . 0 . 204 . 34 946 0 l 6 c)AED excursion -16 -85 Envelope loss/gain 339 190 2978 3106 12 a) Infiltration 87 24 593 162 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13) 425 214 3571 3498 14 15 Less extemal load Less transfer Redistribution Subtotal Duct loads 32% 49% 0 0 0 425 135 0 0 0 214 104 32% 49% 0 0 0 3571 1131 0 0 0 3498 1704 Total room load Air required (cfm) 560 28 318 141 1 4702 232 5203 232 all �� wrightsOft' Right -Suite® Universal2017 17L0.14 RSU08101 ...uick Calcs%DocumentS\THE GRAND CARLTON-1446.rup C; lc = MJ8 Front Door faces: N 2017-Apr-11 09:29:38 Page 3 -�- wrightsoft- Right-M Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM 1 Room name LAUNDRY GREAT/DINING 2 Exposed wall 6.0 ft 47.0 ft 3 Room height 8.0 ft heat/cool 9.8 ft heat/cool 4 5 Room dimensions Room area 7.0 x 6.0 ft 42.0 ft2 1.0 x 526.0 ft 526.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft-) Load number (Stuh/ft2--°F) (13tuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat "Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs: _ 0143 - n 4:00 : Z55 0 0 . 0 0 255 217 869 :552 1-G.''4A5-2om' 0.770 0.143 -n'. a 21:56: 4.00 1931 2.55 ' 0 0 0 0 :0 0 0 0 38 0 0. 0 -815 0 730. 0 'L�13A4ocs 11 BD 1Aclom 11DO 1.270 0.390 a a 35.56 10.92 87.29 11.31 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W. VIl L--C .13A4ocs 13A4ocs 0.143 0.143 se s 4.00 4.00 2.55 2.55 0 48 0 48 0 192 0 122 0 0 0 0 0 0 0 0 1A-clom 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0 13A46cs 1Ac1om 0.143 1.270 - w w 4.00 35.56 2.55 55.21 0 0 0 0 0 0 0 0 206 0 165 0 661 0 420 0 4A5-26m 0.770 w 21.56 19.31 0 0 z 0 .0 41 41 880 788 P 12C-0sw 0.091 - 2.55 1.28 56 56 143 72 0 0 0 0 . C . 16A 30r nd. 0.032 - 0.90 2.32 42 42 38.. 97 .526 526, 471. ; : : 1220 F 22A tpI 0.989 - 27.69 0.06 42 6 166 0 526 47 1302 0 6 c)AED excursion -22 �8 Envelope loss/gain 539 270 4997 4379 12 a) Infiltration 104 28 997 273 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 2 460 Appliances/other 0 0 Subtotal (lines 6 to 13) 643 298 5994 5112 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 32% 49% 0 0 0 643 204 0 0 0 298 145 32% 49% 0 0 0 5994 1899 0 0 0 5112 2490 Total room load Air required (cfm) 846 42 443 20 7892 390 7602 338 Calculations Of wrightsoft' i 2017-Apr-11 09:29:38 Right -Suite® Universal 2017 17.0.14 RSU08101 Page 4 ...uick CalcskDocuments\THE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces: N -�+ wrightsoft, Right- J® Wor sheet Job: Entire House Date: ' QUICK CALCS, INC. By: 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@,AOL.COM 1 Room name FOYER M. BATH 2 Exposed wall 7.0 ft 8.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 50.0 ft 7.0 x 8.0 ft 5 Room area 50.0 f12 56.0 ftz Ty Construction U-value Or HTM Area (ft2)Load (ft') Load number (Btuh/ft2 °F) (Btuh/ft2) or perimeter� (ft) (Btuh) orpedmeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P(S Heat Cool 6 13A-4ocs 0143 :: n. 4.00 ' 2 55 $ : - 8 32 ..20 0 b 0 '' 0 4A5=2om . - Ano • n 21.56 - 19.31 .- . o 0 0 0 .. 0 • . 0. 0. 0. 13A-4ocs 0.143 a 4.00 2.55 48 27 108 69 0 0 0 0 -G IA-clom 1.270 a 35.56 87.29 0 0 0 0 0 0 0 0 11 i- -D 11130 0.390 a 10.92 11.31 21 21 229 238 0 0 0 0 W .13A4ocs 0.143 se. 4.00 2.55 0 0 0 0 0 0 0 0 t-C 13A-4ocs 0.143 s 4.00 2.55 0 0 0 0 64 57 228 145 1A-clom 1.270 s 35.56 34.77 0 0 0 0 7 7 247 241 V613A-1ocs 0.143 w 4.00. 2.55 0 0 0 0 0 0 .0 0. 1Ac1om 1.276 w 35.56: 55.21 0 0 0 0- 01 0 0 4A5-2om .0.770 w 21.56 19.31 0 0 0 0. 0 0 0 0 P 12C-0sw 0.091 - 2.55 1.28 72 72 183 92 0 0 0 0 C ::...: ,16A-30md 0.032 -- - .0.90 2;32 50 50 45 - 116 - 56 56 . 50 130 F 22A-tpl 0.90 - 27.69 0.00 50 7 194 0 55 8 222 0 6 c)AED excursion -39 -38 Envelope loss/gain 792 496 747 478 12 a) Infiltration 121 33 138 38 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 p p 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 913 529 885 516 Less extemal load 0 0 0 0 Less transfer 0 0 Redistribution 0 0 0 0 14 Subtotal 913 529 885 516 15 Duct loads 32% 49% 289 258 32% 49% 280 2551 Total room load 1202 787 1166 768 Air required (cfm) 59 35 58 Of AM 'V- wright5oft- Right -Suite® Universal 2017 17I0.14 RSU08101 ...uick CalcslDocumentslTHE GRAND CARLTON-1446.rup Calc = MJ8 Front Door faces: N 2017-Apr-11 09:29:38 Page 5 �1 -1- wrightsoft� Duct System Summary Date: Entire House By: QUICK CALCS,'INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone:.772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM For: THE GRAND CARLTON WYNNE DEVELOPMENT, FT. PIERCE, FL External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.50 in H2O 0 in H2O .0.50 in H2O 0.250 / 0.250 in H2O 0.285 in/100ft 1160 cfm Cooling 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.285 in/100ft 1160 cfm 176 ft Name Design (Btuh) Htg (cfm) C1g (Cf�) i Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h 560 28 14 0.364 4.0 Ox0 VIFx 22.4 115.0 st1 BEDROOM h 4702 232 232 0.360 7.0 Ox0 VIFx 23.9 115.0 st1 BEDROOM -A h 3327 164 163 0.300 6.0 OxO VIFx 31.8 135.0 st2 BEDROOM-B h 3327 164 163 0.285 6.0 OxO VIFx 40.6 135.0 st2 FOYER h 1202 59 35 0.505 4.0 Ox0 VIFx 4.0 95.0 GREAT/DINING h 3946 195 169 0.300 7.0 Ox0 VIFx 31.8 135.0 st2 GREAT/DINING-A h 3946 195 (69 0.300 7.0 Ox0 VIFx 31.8 135.0 st2 KITCHEN c 3437 21 153 0.379 6.0 Ox0 VIFx 17.0 115.0 st1 LAUNDRY h 846 42 20 0.361 4.0 Ox 0 VIFx 23.3 115.0 st1 M. BATH -A h 768 58 34 0 0 Ox0 VIFx 0 0 wlc c 174 3 8 0.309 4.0 Ox 0 VIFx 27.0 135.0 st2 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 Peak AVF 721 672 0.285 918 12.0 0 x 0 VInIFIX st1 St1 Peak AVF 1043 1091 0.285 1020 14.0 0 x 0 VinlFlx - - wrightsoft° Right -Suite® Universal 201i7 17.0.14 RSU08101 ...uick CalcMDocuments\THE GRAND CARLTON-1446.rup Cale = MJ8 Front Door faces: N 2017-Apr-11 09:29:38 Page 1 Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) . (in) Opening (in) Matl Trunk rb1 Ox0 1160 1160 0� 0 0 0 Ox 0 VIFx