HomeMy WebLinkAboutALTERATION DRAWINGSSTRUCTURAL DESIGN CRITERIA:
THE DESIGN CO PLIES
ITH THE REQUIREMEWTS OF THE 2017 FLORIDA BUILDING CODE; 6TH EDITION
MEAN ROOF HEIGHT
35,
WIND LOAD
FBC 2017 & CHAPTERS 1, 2, 26, & 28 OF ASCE 7-10
WIND VELOCITY
160 MPH; ULTIMATE WIND SPEED; 124 MPH NOMINAL SPEED
Qz
56 PSF WIND PRESSURE
EXPOSURE
"C"; ENCLOSED DESIGN
Kz
1.01
ALPHA HEIGHT & EXPOSURE FACTOR 1.45
LOAD COMBINATIONS
ASCE 7-10 CHAPTER 2A DL+LL; DL+0.6WL; 0.6DL+0.6WL
INTERNAL PRESSURE COEFFICIENT +/-0.18 PER TABLE 26.11-1
RISK CATEGORY II
MAIN FRAME:
MAX. HORIZONTAL LOAD +49 PSF
MAX. VERTICAL LOAD —42 PSF
EXISTING POOL
SCOPE OF WORK:
1. MOBILIZE AND INSTALL TEMPORARY SHORING FOR TIMBER FLOOR SYSTEM PER PLANS.
2. INSTALL NEW STEEL CHANNEL PER PLANS.
3. DEMO TWO EXISTING CONCRETE COLUMNS AS LOCATED PER PLANS.
4. REMOVE PORTION OF CONCRETE AT TWO ARCH BEAM LOCATIONS PER PLANS.
5. REMOVE TEMPORARY SHORING.
6. RE -STUCCO ANY DAMAGED AREAS TO MATCH EXISTING.
7. CLEAN-UP AND DEMOBIUZE
EXISTING FAMILY ROOM
REMOVE TWO CONCRETE
COLUMNS PER PLANS
T.,
PROJECT,
EXISTING KITCHEN
EXISTING DINING ROOM
EXISTING POOL ROOM
EXISTING FOYER
AREA OF WORK. REMOVE TWO CONCRETE COLUMNS
PER SCOPE OF WORK ON S-1.
EXISTINP TRUSSES
TO REMAIN SHORE
EXISTING
PLANS
EXISTING MORNING ROOM
EXISTING PLAN WITH DEMO
SCALE = 1/4" TO 1'-0"
EXISTING MAIN RESIDENCE
44 POST SHORE -TYP.
PER PLANS
EXISTING 12"x3O" _�
CONCRETE BEAM W/ (2)
#5 BARS TOP, MID., & BOT.
CONTRACTOR TO VERIFY
EXISTING LIVING ROOM
EXISTING
SHORING PLAN
SHORING TO REMAIN IN PLACE
UNTIL NEW STEEL PLATE HAS
BEEN COMPLETELY INSTALLED
SHORING BEAM = 4x6 WITH MAX. SPAN OF 4'-0"
SHORING POST 4x4 WITH MAXIMUM' HEIGHT OF 12'-0"
OR STEEL SCREW JACK
UPPER DECK
EXISTING 2x12'S C 16" O.C.'.
i IMBER BM S.Y.P. GD. 2
= 1250 PSI MIN.
CONSTRUCTION PLAN';
SHEET DESCRIPTION
S1 COVER SHEET AND NOTES
S2 ALTERATION PLAN AND SECTION
TOTAL NUMBER OF SHEETS = 2
GENERAL NOTES:
DESIGN LOADS:
ROOF LIVE LOAD = 20 PSF
ROOF DEAD LOAD = 30 PSF
FLOOR LIVE LOAD = 40 PSF LIVING/ 60 PSF BALCONY
FLOOR DEAD LOAD = 25 PSF LIVING/ 5 PSF BALCONY
CODES AND STANDARDS
1 THE PROJECT WAS DESIGNED IN ACCORDANCE WITH THE FOLLOWING CODES:
A FLORIDA BUILDING CODE 2017; 6TH EDITION, EXISTING FBC 2017, AISC, ASD, & ASCE 7-10.
8 LEVEL TWO ALTERATION
DIMENSIONS:
1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS ON JOB SITE WITH THE DIMENSION SHOWN ON
DRAWINGS. ANY DISCREPANCIES IN NOTES OR DIMENSIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER BEFORE COMMENCING WORK. DO NOT ASSUME OR GUESS
ANY DIMENSIONS, ELEMENTS, CONNECTIONS, OR ELEVATIONS.
2. DETAILS AND CONDITIONS NOT SPECIFICALLY SHOWN SHALL BE CONSTRUCTED IN ACCORDANCE
WITH DETAILS SHOWN FOR SIMILAR CONDITIONS AND MATERIAL,
FOUNDATION:
1 ALL FOOTINGS AND FOUNDATION ARE EXISTING TO REMAIN. FOOTINGS HAVE BEEN VERIFIED TO
ACCEPT NEW POINT LOADS. CONTRACTOR TO VERIFY MIN. SIZES HAVE BEEN PROVIDED AS SHOWN IN
THESE PLANS.
BUILDING EXISTING NDTES:
1. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND BE AWARE OF ALL EXISTING CONDITIONS AND
INTERFERENCES.
2. THE CONTRACTOR SHALL CHECK CONDITION FOR EXISTING WIRING INSULATION AND NOTIFY THE OWNER,
ARCHITECT, OR ENGINEER OF ANY DANGEROUS CONDITIONS.
3. THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR HAVING VISITED THE SITE AND HAVING FAMILIARIZED
HIMSELF WITH ALL EXISTING CONDITIONS. ANY QUESTIONS OR DISCREPANCIES FOUND WITH REGARD TO
THE DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE BUILDING ENGINEER BEFORE SUBMITTING
A PROPOSAL. FIELD MEASURE EXISTING CONDITIONS PRIOR TO FABRICATION OF ALL MATERIALS.
4. ALL DIMENSIONS AND ELEVATIONS SHOWN ON THE DRAWINGS SHALL BE FIELD
VERIFIED BY THE CONTRACTOR.
5. IF MATERIALS, QUANTITIES, STRENGTHS OR SIZES INDICATED BY THE DRAWINGS OR
SPECIFICATIONS ARE NOT IN AGREEMENT WITH THESE NOTES, THE BETTER
QUALITY AND/OR GREATER QUANTITY, STRENGTH OR SIZE INDICATED, SPECIFIED
OR NOTED SHALL BE PROVIDED AND APPROVED BY FOR PRIOR TO INSTALLATION.
2"x4'! HORIZONTAL BRACE ATTACH W/ (2)
16-d'NAILS EACH POST, BRACE NOT
RQES. FOR STEEL SCREW JACK POST
18"x16" DBL 3/4" CDX
Pl.400D MUD SILLS
FIELD VERIFY ALL DIMENSIONS AND CONDITIONS.
THE FLOOR SYSTEM SHALL BE TEMPORARILY SHORED IN ACCORDANCE WITH
OSHA AND ANSI. THE DESIGN OF THE SHORING SHALL BE IN ACCORDANCE
WITH THE LOCAL BUILDING CODE PROVISIONS AND SHALL BE PLACED TO
PROVIDE A LEVEL AND CONTINUOUS SURFACE FOR THE FLOOR SYSTEM TO
REST ON. THE SHORING SHALL BE LEFT IN PLACE UNTIL ALL CONNECTIONS
HAVE BEEN COMPLETED.
EXISTING MASTER SUITE
0
APR S 6 2018
ST. LucCounty, Permitting
PROJECT:
HARDING RESIDENCE
ALTERATION PLANS
HARBOUR RIDGE LOT11
FLORIDA
c:sm
EN I N E E R I N G
CIVIL • STRUCTURAL MARINE
CSM ENGINEERING' LLC
2❑EI1 SE OCEAN BOULEVARD SUITE I
STUART� FL13RIDA 34996
o: 772-220-4601
w: www.CSM—E.net
CERTIFICATE OF AUTHORIY11ON: 29057
THE ENGINEER HEREBY EXPRESSLY RESERVES HIS/HER COMMON LAW COPYRIGHT
AND OTHER PROPERTY RIGHTS. THESE PLANS AND DRAWINGS ARE NOT TO BE
REPRODUCED, CHANGED, COPIED, OR ASSIGNED TO ANY THIRD PARTY IN ANY
FORM OR MANNER WHATSOEVER WITHOUT FIRST OBTAINING THE EXPRESS WRITTEN
PERMISSION AND CONSENT OF CSM ENGINEERING, LLC.
THIS DOCUMENT, THE IDEAS, AND DESIGNS INCORPORATED HEREIN, AS AN
INSTRUMENT OF PROFESSIONAL SERVICE, IS PROPERTY OF CSM ENGINEERING, LLC
AND IS NOT TO BE USED, IN WHOLE OR IN PART FOR ANY OTHER PROJECT
WITHOUT THE WRITTEN AUTHORIZATION OF CSM ENGINEERING, LLC,
CSM ENGINEERING, LLC COPYRIGHT C2018
ST. LIiCTF COUNTY RTSI .]TTN ION
REVIEWED FOR COAL C 1
REVIEWED 1#Y
DATE GG P� I l
PLANS AND PERMIT MUST 9E KEPT ON 701D
OR NO INSPECTION WILL BE DIADE.
THESE PLANS AND ALL PROPOSED WORK
ARE SUBJECT TO ANY CORRECTIONS
REQUIRED BY FIELD INSPECTORS THAT
MAY BE NECESSARY IN ORDER TO '
COMPLY WITH ALL APPLICABLE CODEB�
6GANNW
By
p
r•r,�_,.— _.___ __. , , ._......_,ryya
Ha,i J.,S.LII IhV , dlL11� vi1' i i if„IL.�7I Y
ARE THE RESPONSIBILITY OF THE
CONtRACTOflOFRECORD
PERMIT SET
4-1 -18
FILE COPY
NOTES & COMMENTS
ALL DIMENSIONS SHALL BE VERIFIED IN THE FIELD BY THE CONTRACTOR. THE
CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF ALL DIMENSIONS.
ALL SCALES INDICATED PERTAIN TO 24'X36' PLOTS
3
4
5
DESIGNED BY: CAD
DRAWN BY: CAD
CHECKED BY: CAD
PLOT DATE 16—Apr-2018
X:\MASTER PLAN — HARDING
SCALE AS SHOWN
PROJECT J:
rj1tl I1rrt 7
..........
-}fin.
1
HARLES A DARDEN JR
DATE
FLORIDA REGISTERED PROFESSIONAL ENGINEER
N0. 76910
SHEET NAME:
COVER AND NOTES
a..,.,.,..,^.....,.�...,�,w.®®..^.,,..^.,.
SHEEP
S-1
! ::
Am,
(2) 5/8"Ox8" EPDXY OR
WEDGE ANCHORS MIN. CONCRETE
EMBEDMENT 6"-T�P-1'-O' MAX.-"
.I_ 5'-,i'
AT EACH END -TYP.
-I
3/4"0
-TYP.
SCALE = 1/4" TO I1'-O"
5/8"Ox8" EPDXY OR WEDGE
ANCHOR INTO CONCRETE PER PLANS
3/15"
C4x7.2 CHANNEL ELEVATION
SCALE:1 =1 -0
CONTRACTOR TO VERIFY
EXISTING FOOTINGS PER
NOTES
C4x7.25 CHANNEL, SEE SECTION
AND ELEVATION DETAILS.
CONTRACTOR TO VERIFY TWO
CELLS FILLED AT END -TYP.
CONTRACTOR TO VERIFY
EXISTING FOOTINGS PER
NOTES
2.5"Tx8"Wx3/8"
THICK STL
MENDING PLATE lz�
Fv=50 KSI
CONTRACTOR TO VERIFY
FOOTING MEETS OR EXCEEDS
ONE OF THE FOLLOWING
CONDITIONS:
1. SQUARE FOOTING:
30N30N12" DEEP W/ (3) #5
BOTTOM BARS EACH WAY
2. STRIP FOOTING:
16" WIDE x 8" DEEP W/ (2) #5
CONT. BOTTOM BARS
3. IF FOOTING IS MONOLITHIC
WITH SLAB, CONTRACTOR
MUST NOTIFY EOR, THIS
FOOTING TYPE WILL NO
WORK.
4. THE ABOVE DESIGNS ARE
BASED ON 2,500 PSF SOIL
BEARING PRESSURE AN
3,000 PSI CONCRETE
STRENGTH.
A
(2) 5/8"Ox8" EPDXY OR
WEDGE ANCHORS MIN. CONCRETE
EMBEDMENT 6" -TYP.
5"
TOP OF BOND BEAM = 12'-6"
CONTRACTOR TO VERIFY
EXISTING 12%30"
CONCRETE BEAM W/ (2)
#5 BARS TOP, MID., & BOT.
CONTRACTOR TO VERIFY
•e
EXISTING 2x12'S
AT 16" O.C. MAX.
•! �'' `� TO REMAIN
• a, jjjfLL..... 6. .� ,
S.. ��jC4x7,2 CHANNEL; Fy=50 KSI
5/8"0 A325 ALL THREADS
EPDXY OR WEDGE ANCHOR
INTO CONCRETE PER PLANS
C4x7.2 CHANNEL SECTION TO CONCRETE BEAM
SCALE:1"-1'-O"
STRUCTURAL AND _ MISCELLANEOUS STEEL:
1. GRADES:
A. ALL STRUCTURAL SHAPES..................Fy = 50 ksi.
2. ALL STRUCTURAL STEEL TO BE DOMESTIC ASTM A992 GD. 50 (Fy=50 ksi)
AND DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH THE LATEST EDITION OF THE
AISC "SPECIFICATION FOR THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL STEEL
FOR BUILDINGS" AND THE AISC CODE OF STANDARD PRACTICE.
3. HIGH STRENGTH BOLTS (ASTM A325-N) TO BE THE TYPE SPECIFIED ON THE PLANS
PROVIDE MATCHING H.S. NUTS AND WASHERS.
4. ALL WELDING TO BE IN ACCORDANCE WITH AWS LATEST "STRUCTURAL WELDING CODE - STEEL"
(ANSI/AWS D1.1-2010). RUSTPROOF ALL WELDS AND PLATES WITH HEAVY DUTY RUSTPROOFING PAINT.
5. ALL MEMBERS TO BE WELDED SHALL USE E70-XX ELECTRODES (MIN.).
6. SHOP COAT ALL STRUCTURAL STEEL WITH RUSTOLEUM "RED PRIMER OR APPROVED
EQUAL (U.O.N.). FIELD PATCH PAINT AFTER ERECTION. SEE STRUCTURAL E.O.R. PLANS
7. THESE PLANS SHALL BE WORKED WITH THE ARCH. PLANS FROM SUN OCEAN DESIGN DATED-8-26-88
8. ADHESIVE SHALL BE SIMPSON EPDXY TIE ET22 OR HILTI RE-500.
PROJECT:
HARDING RESIDENCE
ALTERATION PLANS
HARBOUR RIDGE LOT11
FLORIDA
ENGINEERING
CIVIL a STRUCTURAL MARI1
CSM ENGINEERINGI LLC
2081 SE OCEAN BOULEVARD SUITE I A
STUART9 FLORIDA 34996
o: 772-220-4601
w: www.CSM—E.net
CERTIFICATE OF AUTHORIZA110N: 29057
THE ENGINEER HEREBY EXPRESSLY RESERVES HIS/HER COMMON LAW COPYRI(
AND OTHER PROPERTY RIGHTS. THESE PLANS AND DRAWINGS ARE NOT TO B
REPRODUCED, CHANGED, COPIED, OR ASSIGNED TO ANY THIRD PARTY IN ANY
FORM OR MANNER WHATSOEVER WITHOUT FIRST OBTAINING THE EXPRESS WRIT
PERMISSION AND CONSENT OF CSM ENGINEERING, U.C.
THIS DOCUMENT, THE IDEAS, AND DESIGNS INCORPORATED HEREIN, AS AN
INSTRUMENT OF PROFESSIONAL SERVICE, IS PROPERTY OF CSM ENGINEERING,
AND IS NOT TO BE USED, IN WHOLE OR IN PART FOR ANY OTHER PROJECT
WITHOUT THE WRITTEN AUTHORIZATION OF CSM ENGINEERING, U.C.
CSM ENGINEERING, LLC COPYRIGHT C2018
NOTES & COMMENTS
ALL DIMENSIONS SHALL BE VERIFIED IN THE FIELD BY THE CONTRACTOR. THE
CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF ALL DIMENSIONS.
ALL SCALES INDICATED PERTAIN TO 24X36' PLOTS
1
CHANGES PER ST. LUCIE COUNTY 5-3-18
5-8-11
3
4
5
DESIGNED BY: CAD
DRAWN BY: CAD -
CHECXED BY: CAD
PLOT DATE: 08-May-2018
X:\MASTER PLAN - HARDING
SCALE: AS SHOWN
PROJECT
H 1 H P 7 tY�
``119
oef NA
}off �' •'����
i
P F
V,
1
CHAR LES A ARDEN JR DA
FLORIDA REGISTERED PROFESSIONAL ENGINEER NO. 76
SHEET NAME:
ALTERATION PLAN & DETAILS
SHEEP �: � �......Wm..M......
S-2
s