Loading...
HomeMy WebLinkAboutHVAC LOADSChvac Full Commercial HVAC Loads Calculation Fort Pierce Engmeennq`_ Program' Elite Software Development Inc Harvest,Table Restaurant. _ ` rdL• 3 Building Summa Loads Building peaks in August at 3pm. Bldg Load' Area Sen %Tot Lat Sen Net[%oNet i .. Descn `tions .:. uan :Loss ' , .L,f . r mf Loss ��.. ; . �G'aln � Gam `u _ - yss,1i'.` k�+ ai'�•tti'.. Gain ain Roof 2,650 3,604 5.11 0 4,697 4,697 2.79 Wall 1,580 5,103 7.24 0 2,190 2,190 1.30 Glass 480 13,553 19.23 0 15,944 15,944 9.48 Floor Slab 198 4,174 5.92 0 0 0 0.00 Skin Loads 26,433 37.51 0 22,831 22,831 13.58 Lighting 5,300 0 0.00 0 18,084 18,084 10.75 Equipment 9,020 0 0.00 0 30,778 30,778 18.30 Pool Latent 0 0 0.00 0 0 0 0.00 People 70 0 0.00 8,800 17,200 26,000 15.46 Partition 0 0 0.00 0 0 0 0.00 Cool. Pret. 0 0 0.00 0 0 0 0.00 Heat. Pret. 0 0 0.00 0 0 0 0.00 Cool. Vent. 1,200 0 0.00 43,127 26,386 69,513 41.34 Heat. Vent. 1,200 44,040 62.49 0 0 0 0.00 Cool.lnfil. 0 0 0.00 0 0 0 0.00 Heat.lnfil. 0 0 0.00 0 0 0 0.00 Draw-Thru Fan 0 0 0.00 0 949 949 0.56 Blow-Thru Fan 0 0 0.00 0 0 0 0.00 Reserve Cap. 0 0 0.00 0 0 0 0.00 Reheat Cap. 0 0 0.00 0 0 0 0.00 Supply Duct 0 0 0.00 0 0 0 0.00 Return Duct 0 0 0.00 0 0 0 0.00 Misc. Supply 0 0 0.00 0 0 0 0.00 Misc. Return 0 0 0.00 0 0 0 0.00 Building Totals 70,473 100.00 51,927 116,228 168,155 100.00 Builtling Sen %Tots Lat 2 , Sen , Net %Net Surrimary s ' Loss.'' r Galn _ ,� �GalriGain. �, GainVentilation 44,040 62.49 43,127' 26,386 69,513 41.34 Infiltration 0 0.00 0 0 0 0.00 Pretreated Air 0 0.00 0 0 0 0.00 Room Loads 26,433 37.51 8,800 88,893 97,693 58.10 Plenum Loads 0 0.00 0 0 0 0.00 Fan/Duct/Misc Loads 0 0.00 0 949 949 0.56 Building Totals 70,473 100.00 51,927 116,228 168,155 100.00 Check. i ores Total Building Supply Air (based on a 21 ° TD): 3,964 CFM Total Building Vent. Air (30.27% of Supply): 1,200 CFM Total Conditioned Air Space: 2,650 Sq.ft ` Supply Air Per Unit Area: 1.4960 CFM/Sq.ft Area Per Cooling Capacity: 189.1 Sq.ft/Ton Cooling Capacity Per Area: 0.0053 Tons/Sq.ft Heating Capacity Per Area: 26.59 Btuh/Sq.ft Total Heating Required With Outside Air: 70,473 Btuh Total Cooling Required With Outside Air: 14.01 Tons Z:\ ...\Harvest Table Heat Load.CH8 Thursday, September 15, 2016, 06:23 PM Chvac Full Commercial HVAC Loads Calculat!on Program Elite Software Development Inc: Fort Fierce Ergineennq N _ „ f Harvest ble Restaurant_ TaP' it950 e Air Handler #1- AHU 1 - Total Load Summa Air Handler Description: AHU 1 Constant Volume - Proportion Supply Air Fan: Draw-Thru with program estimated horsepower of 0.14 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.94 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 3pm in August. Outdoor Conditions: Clg: 95° DB, 780 WB, 117.56 grains, Htg: 41 ° DB Indoor Conditions: Cig: 75' DB, 50% RH, Htg: 75° DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: 4,107 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 14,680 Btuh 400 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 18,787 Btuh Heating Supply Air: 4,107 / (.999 X 1.08 X 10) = 400 CFM Winter Vent Outside Air (100.0% of supply) = 400 CFM Room space sensible gain: 33,319 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 367 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 33,686 Btuh Cooling Supply Air: 33,686 / (.999 X 1.1 X 20) = 1,532 CFM Summer Vent Outside Air (26.1 % of supply) = 400 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 8,795 Btuh 400 CFM Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 8,795 Btuh Total sensible gain on air handling system: 42,481 Btuh Room space latent gain: 2,000 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 14,376 Btuh Total latent gain on air handling system: 16,376 Btuh Total system sensible and latent gain: 58,857 'Btuh Check F'i ores Total Air Handler Supply Air (based on a 20' TD): 1,532 CFM Total Air Handler Vent. Air (26.11 % of Supply): 400 CFM Total Conditioned Air Space: 630 Sq.ft Supply Air Per Unit Area: 2.4317 CFM/Sq.ft Area Per Cooling Capacity: 128.4 Sq.ft/Ton Cooling Capacity Per Area: 0.0078 Tons/Sq.ft Heating Capacity Per Area: 29.82 Btuh/Sq.ft Total Heating Required With Outside Air: 18,787 Btuh Total Cooling Required With Outside Air: 4.90 Tons Z:\ ...\Harvest Table Heat Load.CH8 Thursday, September 15', 2016, 06:23 PM Chvac Full Commercial HUAC Loads Calculation Program ( Elite Software Development Inc` Fort Pierce Engmeennq n Ha°west Table Restaurant` - -- _ Air Handler #2 - AHU 2 & 3 - Total Load Summa Air Handler Description: AHU 2 & 3 Constant Volume - Proportion Supply Air Fan: Draw-Thru with program estimated horsepower of 0.23 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.89 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 3pm in August. ' Outdoor Conditions: Clg: 95° DB, 78' WB, 117.56 grains, Htg: 410 DB Indoor Conditions: Clg: 75' DB, 50% RH, Htg: 75° DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: 22,326 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 29,360 Btuh 800 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 51,686 Btuh Heating Supply Air: 22,326 / (.999 X 1.08 X 20) = 1,034 CFM Winter Vent Outside Air (77.4% of supply) = 800 CFM Room space sensible gain: 55,574 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 582 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 56,156 Btuh Cooling Supply Air: 56,156 / (.999 X 1.1 X 21) = 2,432 CFM Summer Vent Outside Air (32.9% of supply) = 800 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 17,590 Btuh 800 CFM Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 17,590 Btuh Total sensible gain on air handling system: 73,747 Btuh Room space latent gain: 6,800 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 28,751 Btuh Total latent gain on air handling system: 35,551 Btuh Total system sensible and latent gain: 109,298 Btuh ., Check FI "lres f. Total Air Handler Supply Air (based on a 21 ° TD): 2,432 CFM Total Air Handler Vent. Air (32.89% of Supply): 800 CFM Total Conditioned Air Space: 2,020 Sq.ft Supply Air Per Unit Area: 1.2041 CFM/Sq.ft Area Per Cooling Capacity: 221.8 Sq.ft/Ton Cooling Capacity Per Area: 0.0045 Tons/Sq.ft Heating Capacity Per Area: 25.59 Btuh/Sq.ft Total Heating Required With Outside Air: 51,686 Btuh Total Cooling Required With Outside Air: 9.11 Tons Z:\ ...\Harvest Table Heat Load.CH8 Thursday, September 15, 2016, 06:23 PM