HomeMy WebLinkAboutBUILDING PLANGRAND ISLE CONDOMINIUM 3702 NORTH All A, N HUTCHINSON ISLAND, FL 34949 REPLACEMENT OF EXISTING FIRE ALARM SYSTEM FIRE ALARM SYSTEM GENERAL NOTES 1. ALL WALL -MOUNTED VISUAL SIGNALING APPLIANCES SHALL BE MOUNTED SUCH THAT THE ENTIRE LENS IS NOT LESS THAN 80IN. (2.03m) AND NOT GREATER THAN 96 IN. ABOVE THE FINISHED FLOOR (A.F.F.) PER NFPA 72 2013 CH. 18.5.4 ALL WALL MOUNTED AUDIBLE DEVICES SHALL BE A MINIMUM OF 90" A.F.F. TO THE TOP OF DEVICE PER NFPA 72 2013 (SECTION 18.4.8.1). AREAS HAVING MORE THAN 2 STROBES IN THE FIELD OF VIEW SHALL BE SYNCHRONIZED PER NFPA 72, SECTION 18.5.4.3.2. 2. SMOKE DETECTORS AND HEAT DETECTOR LOCATIONS ARE BASED ON SMOOTH CEILING WITH MAXIMUM HEIGHT OF 10 FEET UNLESS OTHERWISE NOTED. 3. STROBE LOCATION IS BASED ON 10 FOOT CEILING HEIGHT AND ARE INSTALLED ACCORDING TO NFPA 72 REQUIREMENTS UNLESS OTHERWISE NOTED. ANY DEVICES ON CEILINGS OVER 10 WILL BE DERATED PER NFPA 72. 4. CENTER OF MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" ABOVE FLOOR LEVEL. 5. ALL EQUIPMENT SHALL BE U.L. LISTED. 6. ALL WIRING SHALL BE IN ACCORDANCE WITH N.E.C. AND AUTHORITIES HAVING JURISDICTION. 7. ALL JUNCTION BOXES SHALL BE SIZED IN ACCORDANCE WITH THE N.E.C. 8. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT REQUIRE SERVICING, TROUBLE SHOOTING, ETC. 9. DO NOT DEVIATE FROM CONDUIT RUNS AS SHOWN ON FLOOR PLANS WITHOUT PRIOR APPROVAL FROM SYSTEM SUPPLIER. FACTORS SUCH AS EXCESSIVE VOLTAGE DROP, ADDITIONAL PARTS, ENGINEERING, ETC. THAT ARE A RESULT OF CONDUIT RUN DEVIATIONS SHALL BE THE SOLE RESPONSIBILITY OF ELECTRICAL CONTRACTOR. 10. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR -FLOW, NOR CLOSER THAN 3 FEET (900mm) FROM AN AIR SUPPLY DIFFUSER. 11. ALL DUCT SMOKE DETECTORS SHALL BE MOUNTED BY THE MECHANICAL OR ELECTRICAL CONTRACTOR. DUCT DETECTORS EXPOSED TO THE WEATHER SHALL BE WEATHER PROTECTED BY THE MECHANICAL CONTRACTOR. ALL AIR VELOCITY TESTING SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR. 12. ALL 120 VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHALL BE FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. 13. ALL FIRE ALARM DEVICE BACK BOXES, FIRE ALARM TERMINAL CABINETS, GUTTERS, JUNCTION BOXES AND ASSOCIATED SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. REFER TO FIRE ALARM SYMBOL LIST AND/OR MOUNTING DETAILS FOR ADDITIONAL INFORMATION. SYSTEM SUPPLIER PROVIDED BACK BOXES SHALL BE INSTALLED BY ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED. 14. SMOKE DETECTOR TESTING SHALL BE ACCOMPLISHED WITH SMOKE OR LISTED AEROSOL APPROVED BY THE MANUFACTURER PER NAFP 72, AS ACCEPTABLE BY THE A.H.J. 15. ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION. THE FIRE ALARM CONTROL PANEL TO SUPERVISE THE ANNUNCIATOR PANEL, ALL INITIATING AND INDICATING DEVICE CIRCUITS. 16. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE LOOPED THROUGH DEVICES. 17. POINT AND COMMON ANNUNCIATION AND T-TAPPING ARE PROHIBITED. (r-TAPPING IS ALLOWABLE ON ADDRESSABLE STYLE 4 SLC LOOPS). 18. PROVIDE 3/4" CONDUIT WITH (2) DEDICATED TELEPHONE LINES WITH RJ-31X PHONE JACKS FROM TELEPHONE BACKBOARD FOR OWNER PROVIDED CENTRAL STATION MONITORING LOCATED ADJACENT TO FIRE ALARM CONTROL PANEL. 19. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15clB ABOVE AMBIENT NOISE LEVELS, BUT NOT LESS THAN 75clB THROUGHOUT AREA OF ALARM. TESTING SHALL BE ACCOMPLISHED WITH A dB METER. WHERE APPLICABLE, AUDIBLE TONE WILL BE TEMPORAL PATTERN. 20. FIRE ALARM SIGNAL SHALL MEET ANSI S3A1. AUDIBILITY EMERGENCY EVACUATION SIGNAL (TEMPORAL PATTERN) 21. ALL CONDUITS ARE 3/4" UNLESS OTHERWISE NOTED. 22. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED PER MANUFACTURERS SPECIFICATIONS. 23. SYSTEM SHALL BE FURNISHED AND INSTALLED BY AN AUTHORIZED DISTRIBUTOR. 24. TAMPER PROOF SCREWS OR OTHER APPROVED MECHANICAL MEANS SHALL BE USED ON ALL COVERS OF EXTERIOR ELECTRICAL JUNCTION BOXES IN LIEU OF ELECTRICAL SUPERVISION OF THE COVERS. PER THE 2013 NFPA 72 23.8.5.11.1. 25. ELECTRICAL POWER SERVICE SHALL BE ON A DEDICATED BRANCH CIRCUIT(S) AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED (CIRCUIT BREAKERS SHALL BE LOCKED IN THE ON POSITION WITH AN APPROVED MECHANICAL CLIP). CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT." THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.(NFPA 72, 10.5.5.21 26. UPON COMPLETION OF ALL INSTALLATION AND TESTING, THE CONTRACTOR SHALL PROVIDE TO THE AUTHORITY HAVING JURISDICTION AND THE BUILDING OWNER A COMPLETED AND SIGNED NFPA 72 CERTIFICATE OF COMPLETION. 27. SECTION 17.7.1.11.3 OF THE 2013 EDITION OF NFPA 72 STATES THAT "WHERE DETECTION IS NOT REQUIRED DURING CONSTRUCTION, DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER ALL OTHER CONSTRUCTION TRADES HAVE COMPLETED CLEANUP." 28. IN -BUILDING PUBLIC SAFETY RADIO SYSTEM ENHANCEMENT, IF REQUIRED, SHALL BE FURNISHED AND INSTALLED BY OTHERS. PROJECT SCOPE OF WORK 1. DIRECT REPLACEMENT OF EXISTING FA SYSTEM INSTALLATION OF NEW FIRE ALARM CONTROL PANEL & REMOTE ANNUNCIATOR & BOOSTER PANELS. 2. INSTALLATION OF NEW FIRE ALARM SYSTEM INITIATION DEVICES, (SMOKE DET., HEAT DET., DUCT DET., PULL STATIONS, INTERFACE MODULES) 3. INSTALLATION OF NEW FIRE ALARM SYSTEM AUDIBLE/VISUALS, & VISUAL DEVICES. 4. MONITOR MODULES FOR CONNECTIONS TO SMOKE FIRE DAMPERS, WATERFLOW SW., TAMPER SW., TO BE PROVIDED. CONNECTIONS BY OTHER. 5. ALL EXISTING CONDUITS AND WIRINGS TO BE RE -USED. 6. 120VAC POWER CONNECTION TO BE PROVIDED BY DEDICATED CIRCUIT. 7. CELLULAR COMMUNICATOR TO BE PROVIDED FOR CENTRAL STATION MONITORING. 8. HVAC SHUTDOWN CONNECTION TO BE PROVIDED BY MECHANICAL CONTRACTOR 9, PROGRAMMING OF FIRE ALARM SYSTEM TO OPERATE AS SHOWN IN SEQUENCE OF OPERATIONS. APPLICABLE CODES / STANDARDS PARTIAL LIST OF APPLICABLE NFPA STANDARDS NFPA 72-National Fire Alarm Codes (2013 Edition) NFPA 101-Life Safety Code (2015 Edition) Florida Fire Prevention Code 6th Edition PROJECT G RAN D ISLE CON DOMIN IU M `_ Ist Fire &Security,.,,. k!1-'r4 /' *oasi Ro Stnare ADDRESS 3702NORTHAIA CITY,ST,ZIP N HUTCHINSON ISLAND, FL 34949 ITEM PART QUANTITY STANDBY CURRENTPER UNIT(AMPS) TOTALSTANDBY CURRENT PER UNIT(AMPS) ALARM CURRENT PER UNIT(AMPS) TOTAL ALARM PER UNIT (AMPS) FACP EST-3 EST-3 1 0.000000 0.000000 0.000000 0.000000 CENTRAL PROCESSOR SIGNATURE DRIVER 95WATTZONE AUDIOAMP RS4850PTION MODEM COMM LCD DISPLAY MODULE AUDIOSOURCEUNIT 12 SWITCH LED DISPLAY CELL DIALER REMOrrEANNUNgIATOR PHOTOELECTRIC SUPER DUCT DETECTOR HEATDETECTOR CONTROL RELAY UNIT CONTROLLER DUAL D NICATOR MODULE OKE DET j 3-CPU3 3-SDDC1 3-ZA95 3-RE485 3-MODCOM 3-LCD 3-ASU 3-12SG SLE-LTEV-FIRE 3-LCDANN SIGA-OSD SIGA-SD SIGA-HRD SIGA-CR 1 2 1 1 1 1 1 2 1 1 26 2 3 151 0.155000 0.155000 0.52800• 0.064000 0.0980 0.060000 0.043000 0,080000 0.040000 0,200000 0.184000 0.000832 0-000090 0.001530 0.001125 0.165000 0.336000 5.540000 0.098000 0.095000 0.043000 0.080000 0.020000 0.200000 0.186000 0.000045 0.000045 0.000068 0.000075 0.165000 0.672000 5.5400xJ 0.098000 0,095000 0.043000 0.080000 0.040000 0.200000 0.186000 0.001170 0.000090 0.002040 0.001125 0.264000 0.064000' 0.098000 0.060000 0.043000 0.080000 0.020000 0.200000 0.184000 0.000032 0.000045 0,000051 0.000075 TATION DOUBLE ACTION SIGA-278 OUTPUT MODULE %L MODULE SIGA-CCiS SIGA-MCC1 r MODULE SING LE SIGA-CT1 r MODULE DOUBLE SIGA-CT2 TOTAL STANDBY CURRENT Q TOTALALARM CURRENT REQUIRED TOTAL SYSTEM STANDBY REQUIRES TOTAL SYSTEM REQUIRED ISTANDBYTIME(HOURS) STANDBY CURRENT CAPACITY ALARMTIME ALARMCURRENT REQUIRED ALARM CAPACITY (AMPHOURS) (AMPS) (AMP (MINUTES) (AMPS) HOURS 24.00 0.693000 16.39 15.00 1 7.163945 1 1.79 REQUIRED STAN'DBYCAPACITY (AMP HOURS) REQUIRED ALARM CAPACITY(AMP TOTAL REQUIRED SAFETY FACTOR REQUIRED BATTERY 2X12VOLTBATTERIESINSTAILED HOUR) CAPACITY (AMP CAPACITY(AMP HOURS) AMP/HRRATING PART 26.00 IZV26A 16.39 1 1,79 18.18 1 20% 1 21.82 FACP BATTERY CALCULATIONS PROJECT GRAND ISLE CONDOMINIUM I - 1st Fire & Security„ Lile&iftayNw,edFr, Sn,wrr ADDRESS 3702 NORTH A1A CITY,ST,ZIP AN HUTCHINSON ISLAND, FL34949 (STANDBY ITSTANDBY ALARM ITOPSM IT(T(T ITEM PART IQUANTITY I UNIT(AMPS) UNI(AMPS)UNITfAM EMOTE POWER SUPPLY ENESIS SPEAKER STROBE,110CD ENESIS SPEAKER STROBE, 75CD EN ESIS SPEAKER STROBE, 1SCD ENESIS SPEAKER/STFROBE W P 97cd ENESIS SPEAKER ST6E, 3DCD BPS-10A 1 G4HFRF-S7VMC-110 7 G4HFRF-57VMC-7S 3 G4HFRF-S7VMC-15 6 WG4RF-SVMC/87 18 G4HFRF-S7VMC-30 2 0.070000 0.070000 0.070000 0.203000 0.159000 0.065000 0.31900D 0.086000 TOTAL ALARM CURRENT 0. 1. 0. 0. 5. 0. 0.00000C 0.000D00 0.0000 0.000000 0.00000C 0.000000 0.0 0.000OW 0.00000C TOTALSTANDBY CURRENT 0.000000 REQUIRED REQUI RED STAND BY TI ME (HOURS) TOTAL SYSTEM STANDBYCURRENT STANDBY CAPACITY REQUIRES ALARMTiME TOTAL SYSTEM ALARMCURRENT REQUIRED ALARM CAPACITY (AMPHOURS) (AMPS) (AMP (MINUTES) (AMPS) HOURS) 2..4.00 0.070000 1.68 15.00 8.272000 2.07 REQUIRED STANDBY uCAPACITY ! (AMP HOURS) REQUIREDALARM CAPACITY (AMP TOTAL REQUIRED SAFETY FACTOR REQUIRED BATTERY 2 X 12 VOLT BATTERIES INSTALLED HOUR) CAPACITY CAPACITY(AMP AMP/HRRATING PART# AMP HOURS •68 2.07 3.75 20% 4.50 7.00 12V7A BPS-1 BATTERY CALCULATIONS 1st Fire & SectintyNC. Life Safety Powered BY Service VOLTAGE DROP CALCULATIONS PROJECT NAME GRAND ISLE CONDOMINIUM PANEL BPS101A BPSA NAC Circuit 1 Wire AWG & Type 14ga Solid 14ga Solid 14ga Sdid 14ga Solid Ohms Per 1000 Ft.' 3.19 Length(ft) One -Way 496 Starting Voltage 24.0 Actual Ohms'" 3.16 I Volts @ EOL 17.04 q,"Dro p 29.01 Total current (A 2.2 2 3.19 455 24.0 2.90 18.44 23.15 1.914 3 3.19 510 24.0 3.25 17.36 27.71 2044 4 3.19 520 24.0 3.32 17.22 28.25 1 2.044 ' taken from NEC Chapter 9 Table 8 " calculated for resistance over 2 conductors Maximum Current per NAC Circuit = 2. AUX-1 G4HFRFS7VMC-15 G4HFRFSNMC30 G4HFRFS7VMC-75 GENESIS SPEAKERSTR08El15cd GENESIS SPEAKERSTROBE130cd GENESIS SPEAKERSTROBE175cd GENESIS SPEAKERSTROBE110cd 2 2 3 7 65 mA mA mAG4HFRPS7VMC-110 mA 130 41ammA mA 6u 172 mA 159 mA 203 1421 Current Subtotals- mA 22 _ AUX-2 WG4RF-SVMC-87 GENESIS OUTDOOR SPEAKERSTROBEIREM87cd 61 .Alarm: mA 1 319 iniA i 9 -41 Current Subtotals: mA 1914 NAC-3 G4tiFRFS7VMC-15 GENESIS SPEAKERSTROBB15cd GENESIS OUTDOOR SPEAKERSTROBEIRED187cd 2 Alarm: mA 65 mA 130 WG4RFSVPdC-87 1 61 Alarm: mA 3-,91 1 mA 191q G4HFRFS7VMCA5 IGENESIS SPEAKERSTROBE115cd 2 Alann: mA 651 Current Subtotajs I mA 1 mA 1 2044 130 W G4RFSVMC-87 IGENESIS OUTDOOR SPEAKERSTROBMRED187cd 61 Alarm mA 1 3191 mA 1914 Current totals: Sub m.A - BPS-1 VOLTAGE DROP CALCULATIONS CONTROL UNIT ANNUNCIATION SYSTEM INPUTS A BI C I D I E F G HvI I I J I K-1 M N 0 1. MANUAL FIRE ALARM BOXES • • • • • 2. SMOKE DETECTOR • • • • • • 3. SMOKE DETECTOR - 1ST FL ELEV. LOBBY. • • • • • • 4. IN -DUCT SMOKE DETECTOR. • • • • 5. HEAT DETECTOR • • • • • • 6. WATERFLOW • • • • • • 7. SPRINKLER CONTROL VALVE TAMPER SWITCH • • • • 8. FIRE PUMP RUNNING • • • • 9. 1 FIRE PUMP POWER FAILURE/PHASE REVERSAL 16111111 61 101 10. FIRE ALARM AC POWER FAILURE • •1 1 1• 11. FIRE ALARM SYSTEM LOW BATTERY 1 1 IAN 12. OPEN CIRCUIT • • • 13. GROUND FAULT • • • 14. NOTIFICATION APPLIANCE CIRCUIT SHORT • • • SEQUENCE OF OPERATION NOTIFICATION )_(co S - 6 63 ` REVIEWED FOR 'ODE COMPLIANCE ST. LUCIE COUNTY BOCC- 6/)(f2ez'p FILE COPY E COUNTY FIRE DI T CT ST. LUCI REVIEWED FOR COMP CTION SUBJECT TO FIELD INS SHEET SEE ATTACHED (tEVIS REVIEWED AV, J Q 0 z H N a o 0 o c=i z 0 w v� Z^Ai UW _jw o Zw1,�u.M 0 UU5U tcw� 4 wLwl CZ) 7W_J25in 9 SCANNE® z Ify Z StCucie'oIty w - v T Life Safety & Communications _CZ G O z rn O � UCY'3 V L. L.L. LU t� J z C/) J Uj 0 Q O � = rn Q oZ U o �in� a (D o = c~•b Z w LU w Cj) Z � w Wo � U FA-0 1 OF 21 s PROJECTGRAN CONDOMINIUM Ist Fire&Security. Snfeq- Po eerrd 73y. sirr•ia ADDRESS 3702NORTH AlA CITY,ST,ZIP N HUTCHINSON ISLAND, FL 34949 STANDBY TOTALSTANDBY ALARM TOTALALARM CURRENTPER CURRENTPER CURRENTPER PER UNIT ITEM PART QUANTITY UNIT(AMPS) UNIT(AMPS) UNIT(AMPS) (AMPS) REMOTE POWER SUPPLY BPS-10A 1 0.070000 0.070000 0.070000 0.070000 GENESIS SPEAKERISTROBE WP 87cd WG4RF-SVMC/87 18 0.000000 0.000000 0.319000 5.742000 0.000000 0.000000 GENESIS SPEAKERSTROBE, 15CD G4HFRF-S7VMC-15 4 0.065000 0.260000 TOTALSTANDBY TOTALALARM CURRENT CURRENT (AMPS) 0.070000 (AMPS) 6.0720001 REQUIRED TOTALSYSTEM STANDBY REQUIRES TOTALSYSTEM REQUIRED ALARM CAPACITY (AMP REQUIRED STANDBY TIME (HOURS) STANDBY CURRENT CAPACITY ALARMTIME ALARMCURRENT HOURS) (AMPS) (AMP (MINUTES) (AMPS) HOURS) 24.00 0.070000 1 1.68 1 15.00 1 6.072000 1 1.52 REQUIREDALARM TOTAL REQUIRED REQUIRED BATTERY 2X 12VOLT BATTERIES INSTALLED REQUIRED STANDBY CAPACITY (AMP HOURS) CAPACITY (AMP SAFETY FACTOR CAPACITY CAPACITY (AMP AMP/HR RATING PART # HOUR) AMP HOURS 7.00 12V7A 1.68 1.52 3.20 20% 3.84 BPS-2 BATTERY CALCULATIONS PROJECT GRAND ISLE CONDOMINIUM //► 1st Fire & Security. Life Safety Powered BY .Bernice 1 ADDRESS 3702 NORTH A1A CITY,ST,ZIP N HUTCHINSON ISLAND, FL 34949 STANDBY TOTALSTANDBY ALARM TOTALALARM CURRENTPER CURRENTPER CURRENTPER PER UNIT ITEM PART QUANTITY UNIT(AMPS) UNIT(AMPS) UNIT(AMPS) (AMPS) REMOTE POWER SUPPLY BPS-1DA 1 0,070000 0.0700D0 0.070000 0.070000 GENESIS LED G4STROBE, WALL, IS-30-75-110CID G4VRF 2 O.OD0000 0.000000 0.0280DO 0.056000 GENESIS LED G4HORN STROBE, WALL, 75,110CD G4AVRF/75-110 7 0.OD0000 0.0000D0 0.050000 0.350000 0.000000 0.000000 GENESIS LOW FREQUENCY HORN G41_FWF-H 5 0.112000 0.560000 TOTALSTANDBY TOTALALARM CURRENT CURRENT (AMPS) 0.070j(AMPS) L036000 REQUIRED TOTALSYSTEM STANDBY REQUIRES TOTALSYSTEM REQUIRED ALARM CAPACITY (AMP REQUIRED STANDBYTIME(HOURS) STANDBYCURRENT CAPACITY ALARMTIME ALARMCURRENT HOURS) (AMPS) (AMP (MINUTES) (AMPS) HOURS) 24.00 0.0700DO 1.68 15.00 1.036000 0.26 REQUIREDALARM TOTAL REQUIRED REQUIRED BATTERY 2 X 12 VOLT BATTERIES INSTALLED REQUIRED STANDBY CAPACITY (AMP HOURS) CAPACITY (AMP SAFETY FACTOR CAPACITY CAPACITY (AMP AMP/HRRATING PART# HOUR) (AMP HOURS) 7.00 12V7A 1.68 1 0.26 1 1.94 20% 2.33 BPS-3 BATTERY CALCULATIONS AMOW a 1st Fire & Security.... Life Safety Powered By Service VOLTAGE DROP CALCULATIONS PROJECTNAME GRAND ISLE CONDOMINIUM PANEL BPSIOIA BPS-1 NAC Circuit Wire AWG & Type Ohms Per 1000 Ft ' Length(fl) One_ ay Starting Voltage Actual Ohms`" Volts @ ryoDrop EOL Total current (A 1 14ga Solid 3.19 496 24.0 3.16 17.04 29.01 2.2 '.. 2 14ga Solid 3.19 455 24.0 2.90 18.44 23.15 1.914 3 14ga Solid 3.19 510 24.0 3.25 17.35 27.71 2.044 4 14ga Solid 3.19 520 24.0 3.32 17.22 28.25 2.044 taken from NEC Chapter 9 Table 8 " ealculatpd for resistance over 2 conductors Maximum Current per NAC Circuit = AUX-1 G4HFRF-S7VMC-15 G4HFRF-S7VMC-30 G4HFRF-$7VMC-75 G4HFRF-37VMC-110 GENESIS SPEAKER-STROBE15cd GENESIS SPEAKERSTROBE30cd GENESIS SPEAKERSTROBE75cd GENESIS SPEAKERSTROBE1110cd 2 21 3 7 Alarm: mA 65 mP. mA mA mA. 130 Alarm: mA 172 477 Alarm: mA A2O Alarm: mA 1421 Q.InertSub'.ota!e.: mA 200 AUX-2 WG4RF-SVMC-87 IGENESIS OUTDOOR SPEAKERSTROBE'REDI87cd 1 61 1 mA. 1 1914 Current Subtotals: I mA 191A NAC-3 G4HFRF.S7VMC-15 GENESIS SPEAKER-STROBE15cd GENESIS OUTDOOR SPEAKER-3TROBEREM87cd 2 Alarm. mA 65 mA 130 WG4RF-SVMC-87 6 Alarm: it 1 319 mA 1914 G4HFRF-37VMC-15 IGENESIS SPEAKER-STROBE15cd 21 Alarm. mAj Current Subtotals: mA mA 130 WG4RF-SVMC-87 GENESIS OUTDOOR SPEAKERSTROBBREO187cd 6 Alarm, mA 319 mA 7514 - Current Subtotzs: mA 2044 BPS-2 VOLTAGE DROP CALCULATIONS 1st Fire & Security.N i Life Safety Powered By Service VOLTAGE DROP CALCULATIONS PROJECT NAME GRAND ISLE CONDOMINIUM PANEL BPS1OIA BP" NAC Circuit Wire AWG & Type Ohms Per 100D Ft. ' Length(Hj One -Way Starting Voltage Actual Ohms"current Total (A 1 14ga Solid 3.19 303 24.0 1.93 0: 2 14ga Solid 3.19 146 24.0 0.93 MOOO.00 ,,°10.§'11 3 14ga Solid 3.19 0 24.0 0.00 -t:^'r.:-. p,;,,,. 4 14ga Solid 3.19 0 24.0 0.00 .`,1. +•.1,. " taken from NEC iihapter 9 Table 8 calculated for resistance over 2 conductors Maximum Current per NAG Circuit = AUX-1 G4AVRF-75-110 Gi GENESIS LED G4 HORN STROBEt751110 CD GENESIS LED G4 STROBE 15f301751110 CD I 6 2 Alarm: mA 50 mA mA 300 Alamr mA. 28 5e CLneni Subtomfls I mA 30 AUX-2 GIAVRF-75-110 G4LFWF-H GENESIS LED G4 HORNSTROBE175I110 CD GENESIS LOW FREQUENCY HORN 1 5 1 A?>rm. mA 50 mA mA 5G Alarm: mA 112 560 3 Current Subtotals: mA 610 NAC-3 NIA N?A. 1 01 Alarm mAj 01 A 0 Curs t � f l >I5 r1?A 0 NAC-4 NIA N!A I0 Alarm: mA 0 mA G Current Subtotals: mA 0 BPS-3 VOLTAGE DROP CALCULATIONS AUDIO CIRCUIT WATT LOAD CALCULATIONS -AMP 1 PROJECT GRAND ISLE CONDOMINIUM PANEL EST-3 NODE/AMP 3-ZA95 BUILDING/LOCATION CIRCUIT# TOTALDEVICES DEVICE DETAILS CIRCUITLOAD TAP TAP TAP TAP 1/4W 1/2W 1W 2W GRAND ISLE CONDOMINIUM 1 5 5 1.25 2 5 5 1.25 3 12 12 3.00 4 21 21 5.25 5 21 21 5.25 6 21 21 5.25 7 21 21 5.25 8 21 21 1 5.25 9 21 21 5.25 10 21 21 5.2S 11 21 21 5.25 12 21 21 5.25 13 21 21 5.25 141 21 21 5.25 151 21 21 5.25 TOTAL AUDIO LOAD IN WATTS 68.50 TOTAL WATTS OF AUDIO POWER AVAILABLE 95.00 TOTAL WATTS OF AUDIO POWER IN RESERVE 26,50 FIRE ALARM SYMBOL LEGEND SYMBOL DESCRIPTION MODEL # TOTAL BACKBOX MOUNTING (I� HEIGHT FACP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAP FIRE ALARM ANNUNCIATOR PANEL 3-1_CDANN 1 PROVIDED 66" A.F.F. OB-P-S-1 REMOTE BOOSTER POWER SUPPLY BPSIOA 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- OSD OPITCAL SMOKE DETECTOR WITH BASE SIGA-OSD/SIGA S84 26 4" SQUARE 1-1/2" DEEP CEILING SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE 1-1/2" DEEP VERIFY IN FIELD HD HEAT DETECTOR SIGA-HRD 30 4" SQUARE 1-1/2" DEEP VERIFY IN FIELD F HD WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING ❑p DOUBLE ACTION PULLSTATION SIGA-278 11 1 GANG 1-1/2" DEEP 48" A.F.F. ❑� WEATHERPROOF, DOUBLE ACTION PULLSTA7TON BG-12LOB 26 PROVIDED 48" A.F.F. HS HORN STROBE G4AVRF 7 1 GANG STANDARD 80" A.F.F. S STROBE - RED G4VRF 2 1 GANG STANDARD 80" A.F.F. SS SPEAKER STROBE G4HFRF-S7VMC 22 4" SQUARE 2-1/8" DEEP 80 A.F.F. O SSAI!lA WEATHERPROOF SPEAKER STROBE WG4RF-SVMC 36 OUTDOOR RA 80" A.F.F. PROVIDED 0 EXISTING SPEAKER - CEILING MOUNTED F.B.O 216 ----- CEILING CONTROL RELAY MODULE SIGA-CR 15 1 GANG VERIFY IN FIELD STANDARD CT1 SINGLE INPUT MODULE SIGA-CT1 62 1 GANG VERIFY IN FIELD STANDARD CTZ DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD CONTROL INPUT MODULE SIGA-MCC1 15 UIO MOUNT VERIFY IN FIELD ® CONTROL SYNC MODULE SIGA-CC1S 3 2 GANG STANDARD VERIFY IN FIELD OTAMPER SWITCH Ti 18 ----- -___- O WATERFLOW SNATCH F.B.O 13 ----- ----- VOLTAGE SURGE PROTECTOR ASCO 237 4 ----- ----- M I EXISTING MINI -HORN F.B.O 5 ----- FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # Bt-1 S1 170 CD 4--CANDELIA RATING DEVICE SYMBOL SD DEVICE ADDRESS 1-004 EX "EX" DENOTES AN EXISTING DEVICE TO SD REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG YRRE USE A (NAC) 14-2 FPL B (9.0 DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT) 16-2 TWSTED SHIELDED FPLR ALL EASTING CONDUITS AND VARINGS TO BE RE -USED REVIEWED FOR CODE COMPLIANCE ST. LUCIEl+COUNTY BOCC FILE Cope W 6 z F NUJ Q Q U W w U O a o o W 0 O W w a� Z;:C Ciw JLLa zwFwry;.o 0 7 W N cv �ULUVl cQv w JW2Mcc O =in¢Qg a naw� W C1a s W�F a �10 a. w w z 0 z W I f78 T Life Safety & Communications G CZ G 0 0 z rn rn UJ v Ll LIJ o J Z � V J Cf) _ ¢z 0Qo W < z�z = C� z Q 2 0 Wi LJ_ cN ::D O CL fIn'� V CD = Z Drawing Number FA=02 2OF21 w � IY z W w F- y DO AUDIO CIRCUIT WATT LOAD CALCULATIONS p1 i t 1A1E A,1B,1E A1B,1E EXACT LOCATION T.H.D EXACT LOCATION BACKFLOIP I PREVENTER I r - - - - T,H_D PHASE 1 Eon'I TS I POWER IPUMP RUN FAIL REVERSAL I I I I I k I I CT1 CT1 CT1 CT1 - 337 I I -1 8 -13 -140 — — SPENELER MOIMOMG A1E CR 1E ❑ I I I 18 iH D 1 ❑ \ DETAIL "A" \ / 110 \ / 15K0 0.25W E.M:: SS 1A,1 SS 15 / 75CD \ -1A B,1E 0.25W lAlPlr\ A1B,1E 1A,1B,1E 75 SS SD SD 1 1A,1B,1E p d Ir 1 1A,1B,1E CT1 TS [1�1 1 - SS • -1 1B 1 SD 15CD FA •RISE SD -o1z 1 B 0.25W p SD FATC k 1B c 1D I��� wl SPKR. CKT. 1 TO FOURTH LEVEL SPKR. STROBE GARAGE 3A,1 B,13E A CR 1 F'I \ DETAIL "B ' / \ 1A1B,1E /1A16' 1A,1B,1E 1=19 WI CR i 1D A1E T1A1B,1E M M OUTSUIE GAS I SHUTOFF SPKR. CKT. 2 TO FOURTH LEVEL SPKR. STROBE E VEL — DEVICE LAYOUT N s SCALE: 1/8" = 1'-0" w G,W-1D �. 1A1E a FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX QTY HEIGHT FACP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAp FIRE ALARM ANNUNCIATOR PANEL 3-LCDANN 1 PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS10A 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- SD OPITCAL SMOKE DETECTOR WITH BASE SIGA-OSDD/SIGA 26 141/2Q"UDEEP CEILING SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE 1-1/2" DEEP VERIFY IN FIELD HD O HEAT DETECTOR SIGA-HRD 30 4" SQUARE 1-1/2' DEEP VERIFY IN FIELD HD� WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING ❑ElDOUBLE ACTION PULLSTA11ON SIGA-278 11 1 GANG 1-1/2' DEEP 48" A.F.F. ❑ WP p WEATHERPROOF, DOUBLE ACTION PULLSTATION BG-12LOB 26 PROVIDED 48" A.F.F. Hs HORN STROBE G4AVRF 7 1 GANG STANDARD 80" A.F.F. S STROBE - RED G4VRF 2 1 GANG STANDARD 80" A.F.F. SS SPEAKER STROBE G4HFRF-S7VMC 22 4" SQUARE 2-1/8° DEEP 80" A.F.F. 449BOX WEATHERPROOF SPEAKER STROBE WG4-RF-SVMC 36 OUTDOOR RATED 80" A.F.F. SS PROVIDED ® EXISTING SPEAKER - CEILING MOUNTED F.B.O 216 ----- CEILING CR CONTROL RELAY MODULE SIGA-CR 15 1 GANG VERIFY IN FIELD STANDARD CT1 SINGLE INPUT MODULE SIGA-CT1 62 1 GANG STANDARD VERIFY IN FIELD CT2 DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD MCCt CONTROL INPUT MODULE SIGA-MCC1 15 UIO MOUNT VERIFY IN FIELD C1 CONTROL SYNC MODULE SIGA-CC1S 3 2 GANG STANDARD VERIFY IN FIELD TS TAMPER SWITCH F.B.O 18 ----- ----- OWATERFLOW SWITCH F.B.O 13 ----- ----- 7 VOLTAGE SURGE PROTECTOR ASCO 237 4 ----- ----_ I M I EXISTING MINI -HORN F.B.O 5 ----- ----- FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F FffFF:::: CKT # DEVICE # AB1-1-1 S 110 CD-CANDELLA RATING — DEVICE SYMBOL �— SD DEVICE ADDRESS 1-004 Ex �--"EX" DENOTES AN EXISTING DEVICE TO SD REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 TWISTED SHIELDED FPLR ALL EXISTING CONDUITS AND WIRINGS TO BE RE -USED REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC FILE COPY d w R z LLJ Uj z S2 �T0) ULn WJu Z J F- LL n_•� _o UUWLUWUd o W�0 a U v4i a �---� 7"- W Q Uj _.. a ^cr O W W z t7 z W r8T Lite Safety &Communications G Z 0 Z N O 6' -,1- 0 U e _1 L.L LU o J w U J Q w C/) cl) o Q Q O LLT w = cn Z� z w z Q00 w CD 0 N Z I— LL N W f1n'� a V M Z W C Drawing Number FA=03 3OF21 NOTES: EXISTING 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) C u EX SD v EX MASTER m SD 1 NAM BED A4- 0.25W EX EX SD UNIT A 1E UNIT B I I I 1 E BATH BATH uBATH UTTLTTY EX 1E LAUNDRY SID 0.25W BATH 1/2 EX �� SD 1E A - -1 SP EX Q25W 0.2. W EX EX Sp gp SD OFFICE/DEN BID BID adilu 1_ i 1A,1B,1E BATH [,IT -,;I, EX SD A E iL MASTRR BED A4- 75 0.25W BATH BATH LIT LAUNDUTIRYY 1 E BSD ®� m7irmbmm all, _ STAIR _wd ; al iL 7ti4i 1/2 BATH LAUNDRY E BED SPKR. CKT. 1 TO SPKR. CKT. 2 TO FOURTH LEVEL SPKR. STROBE FOURTH LEVEL SPKR. STROBE E SECOND LEVEL - DEVICE LAYOUT N S SCALE: 1/8" = 1'—O" w 1E 1E EX SD UNIT B OFFICE/DEN EX SP 4-1 D.25W EN FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX QTY HEIGHT FACP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAP FIRE ALARM ANNUNCIATOR PANEL 3-LCDANN 1 PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY SPS10A 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- SD OPITCAL SMOKE DETECTOR WITH BASE SIGA-OSD/SIGA 26 4" SQUARE CEILING sB4 1-1/2" DEEP 3* SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE VERIFY IN FIELD 1-1/2' DEEP HD HEAT DETECTOR SIGA-HRD 30 4" SQUARE VERIFY IN FIELD 1-1/2' DEEP r� HD WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING ❑p DOUBLE ACTION PULLSTATION SIGA-278 11 1 GANG 48" A.F.F. 1-1/2" DEEP ❑� p WEATHERPROOF, DOUBLE ACTION PULLSTATION BG-12LOB 26 PROVIDED 48" A.F.F. HS HORN STROBE G4AVRF 7 1 GANG STANDARD 80" A.F.F. S STROBE - RED G4VRF 2 1 GANG 80" A.F.F. STANDARD SPEAKER STROBE G4HFRF-S7VMC 22 4" SQUARE g0" A.F.F. SS 2-1/8" DEEP vR 449BOX SS WEATHERPROOF SPEAKER STROBE WG4RF-SVMC 36 OUTDOOR RATED 80" A.F.F. PROVIDED ® EXISTING SPEAKER - CEILING MOUNTED F.B.O 216 ----- CEILING CR CONTROL RELAY MODULE SIGA-CR 15 1 GANG VERIFY IN FIELD STANDARD CT1 SINGLE INPUT MODULE SIGA-CT1 62 1 GANG VERIFY IN FIELD STANDARD CT2 DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD MCC1 CONTROL INPUT MODULE SIGA-MCC1 15 UIO MOUNT VERIFY IN FIELD ® CONTROL SYNC MODULE SIGA-CC1S 3 2 GANG STANDARD VERIFY IN FIELD TS TAMPER SWITCH F.B.0 18 ----- ----- OWATERFLOW SWITCH F.B.O 13 ----- ----- u® VOLTAGE SURGE PROTECTOR ASCO 237 4 ----- ----- I AA I EXISTING MINI -HORN F.B.O 5 ----- ----- FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F FffF,-= CKT # DEVICE # ASSS 110 CD—CANDELLA RATING DEVICE SYMBOL SD DEVICE ADDRESS 1-DD4 Ex .3 "EX" DENOTES AN EXISTING DEVICE TO Sp REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 TWISTED SHIELDED FPLR ALL EXISTING CONDUITS AND WIRINGS TO BE RE -USED REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCK° J 4 d z U i co ro O d w co z 0 w w a� z- UW*�JW Z r f. u, rim c" UUWWvO `� Uw.•-i W~OZ ==M<< - nUv�au- w wWi- mlo co co w w z z w r8T 1_ife Safety &Communications G Z 75 O Z O U M J LL LLl c J z Cn J co — ¢ Z Q Q O w Z�z = cn z < 0= w Z Z a V o M Z u w Z � O w W � C/D Draw ng Number FA=04 4OF21 NOTES: EXISTING 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) u UNff B OFFICE/DEN BATH LII: E�/ EX MAISM DID MASTER BED SD SD U.25W EX� 1E 1E BATH BATH BATH EX SD 1E UTILm LAUNDRY 25WVDIATR C 1E EX SP Q25J EX SD LAUNDRY BED Fl UTum 1® 0.25W re J SS CT1 yp� wp �pc25W 88D 5"1'AIR 1 UNrr A 1E 1MRIE --03311A, SPKR. CKT. 1 TO FOURTH LEVEL SPKR. STROBE A 1E BATH I BATH EX SD RED I DED I 41 1E BATH BATH UTHHY 1E LAUNDRY MASTER BED EX 1E 1/2 RATH BATH BED SPKR. CKT. 2 TO FOURTH LEVEL SPKR. STROBE E RD LEVEL — DEVICE LAYOUT N 8 SCALE: iIf = 1'-0" W 1E 1E EX SD EX SD UNIT B o1fiCRARN EX SP o.25w 1E BATH FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX OTY HEIGHT FACP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAP FIRE ALARM ANNUNCIATOR PANEL 3-LCDANN 1 PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS10A 3 PROVIDED 66" A.F.F. _A7SD EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- SD OPITCAL SMOKE DETECTOR WITH BASE SIGA-OSD/SIGA SB4 26 4" SQUARE 1-1/2" DEEP CEILING SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE 1-1/2" DEEP VERIFY IN FIELD OHD HEAT DETECTOR SIGA-HRD 30 4" SQUARE 1-1/2" DEEP VERIFY IN FIELD HD WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING ❑p DOUBLE ACTION PULLSTATION SIGA-278 11 1 GANG 1-1/2" DEEP 48" A.F.F. p ❑ * WEATHERPROOF, DOUBLE ACTION PULLSTAl10N BG-12LOB 26 PROVIDED 48" A.F.F. HS HORN STROBE G4AVRF 7 1 GANG STANDARD 80" A.F.F. S STROBE - RED G4VRF 2 STANDARD I GANG 80" A.F.F. SS SPEAKER STROBE G4HFRF-S7VMC 22 4" SQUARE 2-1/8" DEEP 80" A.F.F. rr 449BOX WEATHERPROOF SPEAKER STROBE WG4RF-SVMC 36 OUTDOOR RATED 80" A.F.F. SS PROVIDED ® EXISTING SPEAKER - CEILING MOUNTED F.B.O 216 ----- CEILING CR CONTROL RELAY MODULE SIGA-CR 15 1 GANG VERIFY IN FIELD STANDARD CT1 SINGLE INPUT MODULE SIGA-CT1 62 1 GANG VERIFY IN FIELD STANDARD CT2 DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD NCC1 CONTROL INPUT MODULE SIGA-MCC1 15 UIO MOUNT VERIFY IN FIELD ® CONTROL SYNC MODULE SIGA-CCiS 3 2 GANG STANDARD VERIFY IN FIELD TS TAMPER SWITCH F.B.O 18 ----- _---_ O WATERFLOW SWITCH F.B.O 13 ----- ----- VOLTAGE SURGE PROTECTOR ASCO 237 4 ----- M I EXISTING MINI -HORN F.B.O 5 ----_ FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # SS 11101CD m—CANDELLA RATING V DEVICE SYMBOL .—DEVICE ADDRESS SD 1-004 EX a 'EX" DENOTES AN EXISTING DEVICE TO SD REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 TtWSTED SHIELDED FPLR ALL EXISTING CONDUITS AND WIRINGS TO BE RE -USED REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC FILE COPY 6 Q z ~ J 4 i1 W yqQ w Y Q¢ z 0 S2 a, 00 Uw�kLL Z.� F w o-m w � q Lcur U U O ui 314J o a JW J Z J 62m`ta - r dUvWaw wcoF- �0)cc a w w z z w E Life Safety & Communications G Z 0 0 z rn 0 U J Lu L L o J z cf) Z Q QO Lu Z ~ Z_ _ z W O Z ~ O a I. 04 O = _ !!nn V ciZ Lu U w 0 J Lu W J z C) w Drawing Number FA=05 5OF21 NOTES: EXISTING 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) EX SD UNIT B OFFICE/DEN EX SP o2sW 1E 1E RAM BED 0.25W I 1/2 BATH LAUNDRY I J 11A,1B,1E BATH BATH LMM 1E LAUNDRY a -A� A1B,1E EX SD 1E UNIT A 1E 1 d� SPKR. CKT. 1 TO SEVENTH LEVEL SPKR. STROBE FOU UNIT A BATH I BATH 1A,1B,1E EX SD [ LEVEL DEVICE SCALE: 1/8" = 1'-0" 1E BATH MASTER BED EX EX SD SD 0.25W 1E BATH dTY 1E LAUNDUTIIRY 1/2 BATH LAUNDRY 15KD w RR BED STAIR 2 1E 1E SPKR. CKT. 2 TO SEVENTH LEVEL SPKR. STROBE UNIT B C. EX SP 2 U.25W BATH FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX QTY HEIGHT FACP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAP FIRE ALARM ANNUNCIATOR PANEL 3-LCDANN 1 PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS10A 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- OSD OPITCAL SMOKE DETECTOR WITH BASE SIGA-OSD/SIGA SB4 28 4" SQUARE 1-1/2" DEEP CEILING SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE VERIFY IN FIELD 1-1/2" DEEP HD O HEAT DETECTOR SIGA-HRD 30 4" SQUARE 1-1/2" DEEP VERIFY IN FIELD �a HD WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING ❑p DOUBLE ACTION PULLSTATION SIGA-278 11 1 GANG 1-1/2" DEEP 48" A.F.F. ❑ WEATHERPROOF, DOUBLE ACTION PULLSTATION BG-12LOB 26 PROVIDED 48" A.F.F. HS HORN STROBE G4AVRF 7 1 GANG STANDARD 80" A.F.F. S STROBE - RED G4VRF 2 1 GANG STANDARD 80" A.F.F. SS SPEAKER STROBE G4HFRF-S7VMC 22 4" SQUARE 2-1/8" DEEP 80" A.F.F. 449BOX WEATHERPROOF SPEAKER STROBE WG4RF-SVMC 36 OUTDOOR RATED 80" A.F.F. SS PROVIDED ® EXISTING SPEAKER - CEILING MOUNTED F.B.O 216 ----- CEILING CR CONTROL RELAY MODULE SIGA-CR 15 i GANG VERIFY IN FIELD STANDARD CT1 SINGLE INPUT MODULE SIGA-CT1 62 1 GANG VERIFY IN FIELD STANDARD CT2 DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD MCC1 CONTROL INPUT MODULE SIGA-MCC1 15 UIO MOUNT VERIFY IN FIELD CONTROL SYNC MODULE SIGA-CC1S 3 2 GANG STANDARD VERIFY IN FIELD TS TAMPER SWITCH F.B.O 18 ----- ----- WF WATERFLOW SWITCH F.B.O 13 ----- ----- u�x VOLTAGE SURGE PROTECTOR ASCO 237 4 ----- ----- ne I EXISTING MINI -HORN F.B.O 5 FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # AsBt-1-1 110 CD—CANDELLA RATING DEVICE SYMBOL � SD DEVICE ADDRESS 1-004 EX "EX" DENOTES AN EXISTING DEVICE TO SD REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 TWISTED SHIELDED FPLR ALL EXISTING CONDUITS AND WRINGS TO BE RE -USED REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY ROCC Me cup w J 4 d z ~ U W N eR j d i Q N O N 2 Zvi S U - z 0 v� z_jl-u a•� N_ UULwUUO ~ W~Oz)wz 3J �3 o I JZ =W<0. Y ILL)g a 210 a (L w w z 0 z w Life Safety& Communications G Z z � Ov U M J LLI Ll c z —¢z 0 Q O Z ~ Z _ z O C)LLI O� ��1'► Z 04 0 2 , J W W J z = w � Co LL Drawing Number FA=06 6OF21 NOTES: EXISTING 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) EX BBD EX SD SD 1E 1E BATH 1/2 BATH MASTIR BED 0.25W �. 4 '\ EX BATH (_ Lo UTMM LAUNDRY EX SD UNIT A 1E BATH �— SDEX SDi IA�RY 0.25W OFFICE/DIN BID 1 1E BlAmpi � ® SPKR. CKT. 1 TO SEVENTH LEVEL SPKR. STROBE BATH FIFTH LEVEL — D BED EX SD UNIT A T 1E 1A,1B,1E CT1 MAM BID ME BATH MASTER BID EX v SD EX 777171 SD 0.25W 1E BATH UTM 1E LAUNDRY 1/2 BATH LAUNDRY AI ®OE 0:25W BID 7 1E 1E SPKR. CKT. 2 TO SEVENTH LEVEL SPKR. STROBE E CE LAYOUT N s SCALE: 118" = 1'-0" W UNIT B OFHCE/DEN' Ex �P A - 0.25W BATH FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX QTY HEIGHT FACP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAP FIRE ALARM ANNUNCIATOR PANEL 3-LCDANN 1 PROVIDED 66" A.F.F. OB-P-S-1 REMOTE BOOSTER POWER SUPPLY BPS10A 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- SD OPITCAL SMOKE DETECTOR WITH BASE SIGH-OSD/SIGH S84 26 4" SQUARE 1-1/2" DEEP CEILING SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE 1-1/2" DEEP VERIFY IN FIELD HD O HEAT DETECTOR SIGA-HRD 30 4" SQUARE 1-1/2 DEEP VERIFY IN FIELD HD� WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING ❑ DOUBLE ACTION PULLSTATION SIGA-278 11 1 GANG 1-1/2" DEEP 48 A.F.F. ❑ WEATHERPROOF, DOUBLE ACTION PULLSTATION BG-12LOB 26 PROVIDED 48" A.F.F. HS HORN STROBE G4AVRF 7 STANDARD 1 GANG 80" A.F.F. S STROBE - RED G4VRF 2 1 GANG STANDARD 80" A.F.F. SS SPEAKER STROBE G4HFRF—S7VMC 22 4" SQUARE 2-1/8" DEEP 80" A.F.F. 44980X WEATHERPROOF SPEAKER STROBE WG4RF-SVMC 36 OUTDOOR RATED 80" A.F.F. SS PROVIDED ® EXISTING SPEAKER - CEILING MOUNTED F.B.O 216 ----- CEILING CR CONTROL RELAY MODULE SIGA-CR 15 1 GANG STANDARD VERIFY IN FIELD CT1 SINGLE INPUT MODULE SIGA-CT1 62 1 GANG STANDARD VERIFY IN FIELD CT2 DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD Fmc-cMCC1 li CONTROL INPUT MODULE SIGA-MCC1 15 UIO MOUNT VERIFY IN FIELD ® CONTROL SYNC MODULE SIGA-CC1S 3 2 GANG STANDARD VERIFY IN FIELD OTAMPER SWITCH F.B.O 18 ----- ----- OWATERFLOW SWITCH F.B.O 13 ----- ----- uzn VOLTAGE SURGE PROTECTOR ASCO 237 4 AA I EXISTING MINI -HORN F.B.O 5 FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # SS 1101CD--CANDELLA RATING �-DEVICE SYMBOL � DEVICE ADDRESS SD 1-004 EX �`EX" DENOTES AN EXISTING DEVICE TO SD REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 THSTED SHIELDED FPLR ALL EXISTING CONDUITS AND WRINGS TO BE RE -USED D FOR CODE COMPLIANCE ; T" LUCIE COUNTY BOCC FILE COPY v�rn Z"g 'toCiw o _jui'r 1-LL 6.p7j o =�10 W=N N .pg ou:lUgZ 3J��3W o IL U .�• N CL �. ¢ gym¢ EL �n w z w E Life Safety &Communications v 1� co N M L4 N n ti y C�q' L4 o QEU N , +, *r t-4 N �J z c G z � O U v J "' LL w o J g -aZ pa0 z Z_ z � T O U ui I� Z C'4 ap ffnn V O= M Z 0 J Lu Lu > Lu J Z = w I w U- y LL Drawing Number FA=07 7OF21 NOTES: EXISTING 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) N UNIT B OFFICE/DEN EX SD EX MASTER RED MASTER BED MASTER BED MASTER BED EI SD 0.25W 0.25W 0.25W 0 25W EX SP 1 SP EX EX EX EX EX EX SP 1E SP EX SD SD SD SD 1E 1E 1/2 us LAUNDRY J BATH BATH UTR" 1E LAUNDRY 01 P EOL. 1E SPKR. CKT. 1 TO SEVENTH LEVEL SPKR. STROBE UNIT A I I UNIT A 1E I I 1E ;1 ilA E ■ 1A,1B,1E SIXTH LEVEL - DEVICE L, SCALE: 1/8" = 1'-O" T BATH BATH DTI 1E LAUNDRY STAIR BATH 1/2 BATH LAUNDRY BED SPKR. CKT. 2 TO SEVENTH LEVEL SPKR. STROBE E YOUTN w 1E UNIT B OFFICE/DEN EX Sf 1 0.25W BATH O FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX QTY HEIGHT FACT FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAP FIRE ALARM ANNUNCIATOR PANEL 3-LCDANN 1 PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS1OA 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- SD O OPITCAL SMOKE DETECTOR WITH BASE SIGA-OSD/SIGA 26 4" SQUARE CEILING SB4 1-1/2" DEEP SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE VERIFY IN FIELD 1-1/2" DEEP HD HEAT DETECTOR SIGA-HRD 30 4" SQUARE VERIFY IN FIELD 1-1/2" DEEP rR HD WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING RP DOUBLE ACTION PULLSTATION SIGA-278 11 1 GANG 48" A.F.F. 1-1/2" DEEP EDla WEATHERPROOF, DOUBLE ACTION PULLSTATION BG-12LOB 26 PROVIDED 48" A.F.F. HS HORN STROBE G4AVRF 7 1 GANG STANDARD 80" A.F.F. S STROBE - RED G4VRF 2 1 GANG STANDARD 80" A.F.F. SPEAKER STROBE G4HFRF-S7VMC 22 4" SQUARE g0" A.F.F. SS 2-1/8" DEEP AV 449BOX SS WEATHERPROOF SPEAKER STROBE WG4RF-SVMC 36 OUTDOOR RATED 80" A.F.F. PROVIDED ® EXISTING SPEAKER - CEILING MOUNTED F.B.O 216 ----- CEILING CR CONTROL RELAY MODULE SIGA-CR 15 1 GANG VERIFY IN FIELD STANDARD CT1 SINGLE INPUT MODULE SIGA-CT1 62 1 GANG VERIFY IN FIELD STANDARD CT2 DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD MCC( CONTROL INPUT MODULE SIGA-MCC1 15 UIO MOUNT VERIFY IN FIELD CONTROL SYNC MODULE SIGA-CC1S 3 2 GANG STANDARD VERIFY IN FIELD OTAMPER SWITCH F.B.O 18 ----- -____ OWATERFLOW SWITCH F.B.O 13 ----- _____ u�n VOLTAGE SURGE PROTECTOR ASCO 237 4 I AA 1 EXISTING MINI -HORN F.B.O 5 FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # A81-1-1 SS 110 CD ®—CANDELLA RATING DEVICE SYMBOL . SD DEVICE ADDRESS 1-004 EX .e "EX" DENOTES AN EXISTING DEVICE TO SD REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 TWISTED SHIELDED FPLR ALL EASTING CONDUITS AND WIRINGS TO BE RE -USED REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC FILE COPY d z m ffi O a Q r R 0 w U - U) z O w A WS J I...w W d'0 _ VULLIWUO F_�3Wma�gm 1a0< cc 21O � a a co m w w z z z w l;;:pMf'k Life Safety &Communications ti 1� O C% C d �n 1p v N v�Nv � o � G ZD Z 2E O 0 Z Orn U"' v J LL LU 0 � z J C/) v i cl) ¢z DQo w M Z = cn z _Z 0 2 O ULU Z IL V CD S cl Z I— ZD 0 w U_ 0 W �2u LLI Q J z = w w _ a) C/) Drawing Number FA=08 8OF21 NOTES: EXISTING 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) OMCE/DEN m EX NASTBR BED MASM BED MASTER BED MASTER BID EX EX SID SD SD SD EX 0.25W 0. SSW 0.251W 0.251W EX EX EX EX sp 1 SP EX EX EX EX SID 1E SP SD SD SD SD OMT A UNIT A 1E 1E 1E 1E 1 IE BATH 1/2 BATH 1I: fl all"4�1 BATH UTHdT1f 1 E umff BED J [ 1A,1B,1E i STAIR 1 1E SPKR. CKT. 1 TO TENTH LEVEL SPKR. STROBE BATH BED 11 1A,1B,1E BATH BATH BATH �;�'N_r�lopllvld::11 BATH i if2 BATH 1E LAUNDRY Umxff UNIT B OFFICE/DEN EX IE 9-I0.25W Ell � IQIcI� ,, iII�GI] F BED SEVENTH LEVEL ® DEVICE SCALE: 118" = 1'-0" STAIR 2 SPKR. CKT. 2 TO TENTH LEVEL SPKR. STROBE E YOUT N W C FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX QTY HEIGHT FRCP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAP FIRE ALARM ANNUNCIATOR PANEL 3-LCDANN 1 PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS1CA 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- SD O OPITCAL SMOKE DETECTOR WITH BASE SIGA-OSD/SIGA 26 4" SQUARE CEILING SB4 1-1/2" DEEP SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE VERIFY IN FIELD 1-1/2" DEEP HD HEAT DETECTOR SIGA-HRD 30 4" SQUARE 1-1/2" DEEP VERIFY IN FIELD VIPHD WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING EDOUBLE ACTION PULLSTATION SIGA-278 11 1GN1_1/2A G 48" A.F.F. p WEATHERPROOF, DOUBLE ACTION PULLSTATION BG-12L06 26 PROVIDED 48" A.F.F. HS HORN STROBE G4AVRF 7 1 GANG STANDARD 80" A.F.F. S STROBE - RED G4VRF 2 1 GANG STANDARD 80" A.F.F. SPEAKER STROBE G4HFRF-S7VMC 22 4" SQUARE 80" A.F.F. SS 2-1/8" DEEP 449BOX SS WEATHERPROOF SPEAKER STROBE WG4RF-SVMC 36 OUTDOOR RATED 80" A.F.F. PROVIDED ® EXISTING SPEAKER - CEILING MOUNTED F.B.O 216 ----- CEILING El CONTROL RELAY MODULE SIGA-CR 15 1 GANG VERIFY IN FIELD STANDARD CT1 SINGLE INPUT MODULE SIGA-CT1 62 1 GANG VERIFY IN FIELD STANDARD El DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD MCC, CONTROL INPUT MODULE SIGA-MCC1 15 UIO MOUNT VERIFY IN FIELD CONTROL SYNC MODULE SIGA-CC1S 3 2 GANG STANDARD VERIFY IN FIELD OTAMPER SWITCH F.B.O 18 ----- ----- OWATERFLOW SWITCH F.B.O 13 ----- ----- uI VOLTAGE SURGE PROTECTOR ASCO 237 4 I AA I EXISTING MINI -HORN F.B.O 5 FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # Bi-1-1 SS1 110 CD e CANDELLA RATING DEVICE SYMBOL SD � DEVICE ADDRESS 1-004 Ex EX" DENOTES AN EXISTING DEVICE TO SD REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 TWISTED SHIELDED FPLR ALL EASTING CONDUITS AND WIRINGS TO BE RE -USED REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC lom 0 z CJ w g Uj r. y W N yi CJ Z O tv U C7 z 0 �n T VWOk Wv Lz=i f- W a'a o o UUwWZ \ N grL5JU \l 3J~UjW ~ �W JZ�CcC� O aW W o]F-a�-�a g a m iY w w z z w r8T Life Safety & Commemications 75 G Z 0 z Odam. U "' J 11 LLI o J z U) cn —¢z QQo w M z = v7 2 O ULLJ Z 0 a fno= r 1 c1-m z Ala 1 gQ H z Z LU > w LU co U) Drawing Number FA=09 9OF21 NOTES: EXISTING 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) UNIT B OFECE/DEN SPEx 005W q�1E BATH I / EXSD SD EX MAST R BED A 0.25W 1E 1E 1E VASTER BED 1- 0.25W EX BATH BATH BATH UTILITY 1E LAUNDRY 1/2 BATH LAUNDRY IJI EX 1 SD BED CTi P I SfA1R 1 EX SD 1E UNIT A 1E 1A,1B,1E- -190 CTi 113,1E � :Ifi ■ n :I:� ■ 1A,1B,1E UNIT A 1E EX SD U14 W 1A,1B,1E CT1 R�m 1E MAMR BED VASTER BED EX Ex SD SD AIU-1 U- 0.25W 0.25W Ex SP 1E SP Ex BATH BATH BATH 7M '1E .2 Ron STAIR TAUNDBY BED SPKR. CKT. 1 TO SPKR. CKT, 2 TO TENTH LEVEL SPKR. STROBE TENTH LEVEL SPKR. STROBE E EIGHTH LEVEL - DEVICE LAYOUT N SCALE: 1 f 8" = 1'-0" W 1E 1E OFFICE/DEN EIE 225W$ BED BATH FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX QTY HEIGHT FACP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAP FIRE ALARM ANNUNCIATOR PANEL 3-LCDANN i PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS1CA 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- SD OPITCAL SMOKE DETECTOR WITH BASE SIGA-OSD/SIGA 26 4" SQUARE CEILING SB4 1-1/2" DEEP SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE VERIFY IN FIELD 1-1/2" DEEP HD HEAT DETECTOR SIGA-HRD 30 4" SQUARE 1 -1/2" DEEP VERIFY IN FIELD HD vp WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING ❑p DOUBLE ACTION PULLSTATION SIGA-278 11 1 GANG 48" A.F.F. 1-1/2" DEEP p ❑ wp WEATHERPROOF, DOUBLE ACTION PULLSTATION BG-12LOB 26 PROVIDED 48" A.F.F. Ut HS HORN STROBE G4AVRF 7 1 GANG STANDARD 80" A.F.F. S STROBE - RED G4VRF 2 1 GANG STANDARD 80" A.F.F. SPEAKER STROBE G4HFRF-S7VMC 22 4" SQUARE g0" A.F.F. SS 2-1/8" DEEP 449E X SS WEATHERPROOF SPEAKER STROBE WG4RF-SVMC 36 OUTDOOR RATED 80" A.F.F. PROVIDED ® EXISTING SPEAKER -CEILING MOUNTED F.B.O 216 ----- CEILING CONTROL RELAY MODULE SIGA-CR 15 1 GANG VERIFY IN FIELD STANDARD CT1 SINGLE INPUT MODULE SIGA-CT1 62 1 GANG VERIFY IN FIELD STANDARD C12 DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD MCCI CONTROL INPUT MODULE SIGA-MCC1 15 UIO MOUNT VERIFY IN FIELD RE,CONTROL SYNC MODULE SIGA-CCIS 3 2 GANG STANDARD VERIFY IN FIELD TS TAMPER SWITCH F.B.O 18 ----- ----_ OWATERFLOW SWITCH F.B.O 13 ----- ----- VOLTAGE SURGE PROTECTOR ASCO 237 4 _____ EXISTING MINI -HORN F.B.O 5 FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # Bt-1-1 SS 11D CD o--CANDELLA RATING DEVICE SYMBOL SD DEVICE ADDRESS 1-004 Ex a "EX" DENOTES AN EXISTING DEVICE TO SD REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 TWISTED SHIELDED FPLR ALL EXISTING CONDUITS AND WIRINGS TO BE RE -USED REVIEWED FOR CODE COMPLIANCE ST" LUCIE COUNTY ROCC FILE COPS' 4 O F 0 W �S Y fq C 1 1- N a w U .: z O C2 > w - y Ta Vw -W o 2w�LLi�, N UUwwUCi UOwwCry � w_ J m Q Q Q= d0a.lnwg �0)O CO a cn cy w w z z w r9T Life Sai�ty &Communications G Z O 0 Z0-1 Orn v J Lu o J z J c/) v i c/) Z Q QO n Z z z _ h U IJ w Z c,4 ::D O d �n V O= M Z w -� z F- w _ = 0 rn W Drawing Number FA=10 10 OF 21 NOTES: EXISTING 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) Ex EX MASTER BED x4m w SD SD Ai- Al--0, 0.25W C.25W ExSP 1 SP r_x 1E 1E EX SD UNIT A 1E BATH BATH I I / BATH 1/2 BATH UM" 1E LAUNDRY OFFICE/DEN LAUNDRY B� Iil IamismabrINWIMME1. e E $D BED 1E BATH I BATH BED I "t BED 1A,1B,1E ... 0M®R STAIR 1 I I I1A,1B, SPKR. CKT. 1 TO TENTH LEVEL SPKR. STROBE 1A,1B,1E UNIT A 1E EX SD IQ1�: 1E UTUM LAUNDRY NINTH LEVEL - DEVICE LAYOUT SCALE: 1/8" = 1'-0" MASTER BED Ex 1E 1E RATH 1/2 BATH LAUNDRY 1::11 $15K0 SS EOL. CT1 P R I I-LU Q25W BED STAIR I SPKR. CKT. 2 TO TENTH LEVEL SPKR. STROBE 1E 1E EX SD UNIT B OFFICE/DEN �.EX RATH u FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX QTY HEIGHT FACP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAP FIRE ALARM ANNUNCIATOR PANEL 3-LCDANN 1 PROVIDED 66" A.F.F. BPS I REMOTE BOOSTER POWER SUPPLY BPS1OA 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- SD OPITCAL SMOKE DETECTOR WITH BASE SIGA-OSD/SIGA 26 4" SQUARE CEILING SB4 1-1/2" DEEP SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE VERIFY IN FIELD 1-1/2" DEEP HD HEAT DETECTOR SIGA-HRD 30 4" SQUARE 1 -1/2" DEEP VERIFY IN FIELD wHD WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING ❑p DOUBLE ACTION PULLSTATION SIGA-278 11 1 GANG 48" A.F.F. 1-1/2" DEEP ❑VP p WEATHERPROOF, DOUBLE ACTION PULLSTATION BG-12L0B 26 PROVIDED 48" A.F.F. HS HORN STROBE G4AVRF 7 I GANG STANDARD 80" A.F.F. S STROBE - RED G4VRF 2 I GANG STANDARD 80" A.F.F. SPEAKER STROBE G4HFRF-S7VMC 22 4" SQUARE 80" A.F.F. SS 2-1/8" DEEP SS WEATHERPROOF SPEAKER STROBE WG4RF-SVMC 36 OUTDOOR RATED 80" A.F.F. PROVIDED ® EXISTING SPEAKER - CEILING MOUNTED F.B.O 216 ----- CEILING CR CONTROL RELAY MODULE SIGA-CR 15 1 GANG VERIFY IN FIELD STANDARD CT1 SINGLE INPUT MODULE SIGA-CT1 62 1 GANG VERIFY IN FIELD STANDARD El DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD MCC1 CONTROL INPUT MODULE SIGA-MCCI 15 UIO MOUNT VERIFY IN FIELD El CONTROL SYNC MODULE SIGA-CC1S 3 2 GANG STANDARD VERIFY IN FIELD OTAMPER SWITCH F.B.O 18 ----- _-___ OWATERFLOW SWITCH F•B•0 13 ----- ----- u® VOLTAGE SURGE PROTECTOR ASCO 237 4 ----- AA I EXISTING MINI -HORN F.B.O 5 _____ FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # B1-1- S 1110 CD ®—CANDELLA RATING 1r DEVICE SYMBOL + DEVICE ADDRESS SD 1-004 Ex ®"EX" DENOTES AN EXISTING DEVICE TO $D REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 TWISTED SHIELDED FPLR ALL EXISTING CONDUITS AND WIRINGS TO BE RE -USED REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC FILE COPY u,. R d IZ- £� o Q I I U W ul Y 0 U (7 fn z 0 Of v� T N Vwfwoymu .=>w LL12N N _1 y�wg-��c7 o a2maa a nL.1vNo.g w w co - Mop g a. a w w z z z w E T [.ife Safety � Communications C Z 75 Z Ocn U`" LLJ LIJ 0 Z J C/) v i U) — Q Z ®Q O Q z=z z Q 0 0 O U LU �O Z = a !0:�n �! o ccn Z 0 LLI _U LLI 0 w J z = w Z_ co Z Drawing Number FA=11 11 OF 21 NOTES: EXISTING 12CV SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) L v EX MASTER BED MASTER BED MASTER BED MASTER BED EX v EX SD SD SID SD EX 0.?SW D?5W 5WI 0.25W EX EX SP 1 SP EX EX r6XEX1ESD SD SD UNIT A UNIT A 11E E UNIT B 1E 1E UNIT B F BATH n I I n BATH K[TCHEN KITCHEN %' BATHrE[ \ 4L�WNDRUY BATH urum Jn BATH BATH BATH EX UEx EX BATH V SD S 1E 1E _OX 0.25W U 0 25W EX 0.25W EX SPESP SD EX SDLAUNDRY EXSPLAUNDRY OFFICE EN 1 BED Do OFFICE EN �1 EX SP EX -1 SP 0.25W 0.25W -UTUMT UTIIITY 1E 1E 7cD _ _ 1E 0.25W 87 Ail-21 15KO r ;1E EX xa J 1A,1B;1E 0.25W $15K0 �wCT EOL.P EX S� BATH �D CTl P 147KD f4nKO 1F BATH WZA ill I s _f. - _ I'M 000AMER I AP g9 ® m -- 7SID Sp FX Al -19 WIN ::yl 1B,1E STAIR 1 SPKR. CKT. 1 TO THIRTEENTH LEVEL SPKR. STROBE 1A,1B,1E TENTH LEVEL - DEVICE LAY SCALE: 118" = 1'-0" STAR 2 SPKR. CKT, 2 TO THIRTEENTH LEVEL SPKR. STROBE E N g w P FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX QTY HEIGHT FACP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAP FIRE ALARM ANNUNCIATOR PANEL 3-LCDANN 1 PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS10A 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- OSD OPITCAL SMOKE DETECTOR WITH BASE SIGA-OSD/SIGA S84 26 4" SQUARE 1-1/2" DEEP CEILING SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE VERIFY IN FIELD 1-1/2' DEEP HD HEAT DETECTOR SIGA-HRD 30 4" SQUARE 1-1/2' DEEP VERIFY IN FIELD HDVP WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING ❑ DOUBLE ACTION PULLSTATION SIGA-278 11 1 GANG 4.8" A.F.F. 1-1/2" DEEP ❑� WEATHERPROOF, DOUBLE ACTION PULLSTATION BG-12LOB 26 PROVIDED 48" A.F.F. HS HORN STROBE G4AVRF 7 1 GANG STANDARD 80" A.F.F. S STROBE - RED G4VRF 2 1 GANG STANDARD 80" A.F.F. SPEAKER STROBE G4HFRF-S7VMC 22 4" SQUARE 80" A.F.F. SS 2-1/8" DEEP 449BOX SS WEATHERPROOF SPEAKER STROBE WG4RF-SVMC 36 OUTDOOR RATED 80" A.F.F. PROVIDED ® EXISTING SPEAKER - CEILING MOUNTED F.B.O 216 ----- CEILING CR CONTROL RELAY MODULE SIGA-CR 15 1 GANG VERIFY IN FIELD STANDARD CTt SINGLE INPUT MODULE SIGA-CT1 62 1 GANG VERIFY IN FIELD STANDARD CT2 DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD MCCi CONTROL INPUT MODULE SIGA-MCCI 15 UIO MOUNT VERIFY IN FIELD C1 CONTROL SYNC MODULE SIGA-CC1S 3 2 GANG STANDARD VERIFY IN FIELD OTAMPER SWITCH F.B.O 18 ----- __--- OWATERFLOW SWITCH F.B.O 13 ----- ----- a® VOLTAGE SURGE PROTECTOR ASCO 237 4 ----- ----- fnI EXISTING MINI -HORN F.B.O 5 ----- FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # AB1-1-1 SS 110 CD-CANDELLA RATING DEVICE SYMBOL SD DEVICE ADDRESS 1-DD4 EX ® "EX" DENOTES AN EXISTING DEVICE TO $p REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 TWSTED SHIELDED FPLR ALL EXISTING CONDUITS AND WIRINGS TO BE RE -USED REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC FILE COPY 0 z U w `� w Q QQ K U 2 a i 0 tQi O . U z Z 0 w rr z� d ik Jujv ¢UJZ 7 uj JW ca =wJz�[C ay.eU) LUMM 210 a. a w z 0 z w f7ST Life Safety& Communications 2i ZD Z M Z Orn v J ILL Lij I] � z J n r v J (n Z Q 0 LLIQ Z F- z 4 Z < 0 0 0 LU N Z F O n fn V O = cco u J Z = r- 1- W Z Drawing Number FA=12 12 OF 21 NOTES: EXISTING 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) E v EX MASTBR BED NASTRB BCD SD SD 0.25W 0.25W `X/ 1 EX 1E i[ 1;iyiii7 OFFICE/DEN 1E EX SD UNff A 1E 1/2 BATH LAUNDRY BED IJI BATH BATH UTUM 1 E11 IA STATE 1 C�fil a B'r' 1E SPKR. CKT. 1 TO THIRTEENTH LEVEL SPKR. STROBE BATH I I BATH 1A,1B,1E UNff A 1E 1A,1B,1E CT1 1E BATH BATH UTUHY 1E LAUNDRY 15K0 Woo STAIR NAM BED EX EX SD SD. T 1/2 BATH LAUNDRY E T.,-2D 0.25W BED SPKR. CKT. 2 TO THIRTEENTH LEVEL SPKR. STROBE E ELEVENTH LEVEL - DEVICE LAYOUT N $ SCALE: 1/8" = 1'-O" w 1E 1E UNff B OFFICE/DEN EX SF A J—i D. 5W 1E C MI BATH FIRE ALARM SYMBOL LEGEND TOTAL MOUNTING SYMBOL DESCRIPTION MODEL # BACKBOX QTY HEIGHT FRCP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAP FIRE ALARM ANNUNCIATOR PANEL 3—LCDANN 1 PROVIDED 66" A.F.F. B-P-S-1 REMOTE BOOSTER POWER SUPPLY BPS10A 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- SD OPITCAL SMOKE DETECTOR WITH BASE SIGA—OSD/SIGA 26 4" SQUARE CEILING SB4 1-1/2" DEEP �I SUPER DUCT DETECTOR SIGA—SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD—TRK 2 4" SQUARE VERIFY IN FIELD 1-1/2' DEEP HD HEAT DETECTOR SIGA—HRD 30 4" SQUARE VERIFY IN FIELD 1-1/2" DEEP vP HD WEATHERPROOF, HEAT DETECTOR 302—AW-135 24 PROVIDED CEILING ❑p DOUBLE ACTION PULLSTATION SIGA-278 11 1 GANG 48" A.F.F. 1-1/2" DEEP ❑�' WEATHERPROOF, DOUBLE ACTION PULLSTATION BG-12LOB 26 PROVIDED 48" A.F.F. HS HORN STROBE G4AVRF 7 1 GANG STANDARD 80" A.F.F. S STROBE — RED G4VRF 2 1 GANG STANDARD 80" A.F.F. SPEAKER STROBE G4HFRF—S7VMC 22 4" SQUARE g0" A.F.F. SS 2-1/8" DEEP vp 449BOX SS WEATHERPROOF SPEAKER STROBE WG4RF—SVMC 36 OUTDOOR RATED 80" A.F.F. PROVIDED ® EXISTING SPEAKER — CEILING MOUNTED F.B.O 216 ----- CEILING El CONTROL RELAY MODULE SIGA—CR 15 1 GANG VERIFY IN FIELD STANDARD Full SINGLE INPUT MODULE SIGA—CT1 62 1 GANG VERIFY IN FIELD STANDARD CT2 Eg DUAL INPUT MODULE SIGA—CT2 14 1 GANG VERIFY IN FIELD STANDARD CC1 CONTROL INPUT MODULE SIGA—MCC1 15 UIO MOUNT VERIFY IN FIELD H CONTROL SYNC MODULE SIGA—CCiS 3 2 GANG VERIFY IN FIELD STANDARD OTAMPER SWITCH F.B.O 18 ----- ----- OWATERFLOW SWITCH F.B.O 13 ----- ----- VOLTAGE SURGE PROTECTOR ASCO 237 4 AA I EXISTING MINI —HORN F.B.O 5 FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT # DEVICE # B1-1-1 SS 110 CD s3—CANDELLA RATING DEVICE SYMBOL SD DEVICE ADDRESS 1-004 EX "EX" DENOTES AN EXISTING DEVICE TO $D REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 TWISTED SHIELDED FPLR ALL EXISTING CONDUITS AND WIRINGS TO BE RE —USED REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC or F e' W Y ca N w Z 0 w UW4k_jwI o LLp61 cis xq � WUO UUw\ "O Z cJ J W LU mWm< :s ZZ w LLUamra-u_ w icio�1O IL `n rn W z w E Life S.afery g Communications G Z 0 Z 0 U"' J Ll LU c _J Z a C/) co ¢Z 0 Q O Q Z�Z =W z 0 _ O U O N IJ� Z 04 r�O= P m = 0 W 0 w 0 W w J _ Z z W w LU w J ca W Drawing Number FA=13 13 OF 21 NOTES: EXISTING 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) O UNIT B OFFICE/DEN E � EX MASTSR HED MAM BED SD SD 0.25W EX 1E EX SD BATH BATH BATH [t=1AUNDIRY 1E C.25J rI/2 CS I 1E EX 4-1 SP 0.?5'W EX IA��, SD 1E ?jj ssP 2 EOL° STAIR I 1E Nrlson WE, Y� SPKR. CKT. 1 TO THIRTEENTH LEVEL SPKR. STROBE 5vv 1 P� BED 1A,1B,1E BATH i[ I�IYII1 1E EX E [lfRiol1Xll BATR BATH UTILITY LAUNDRY iL 'AI i15KO 3 EOL. STAIR MASTER BED A14- 0:25W BATH 1/2 BATH LAUNDRY BED SPKR. CKT. 2 TO THIRTEENTH LEVEL SPKR. STROBE E TWELVTH LEVEL - DEVICE LAYOUT N S SCALE: 118" = 1'-O" W 1E 1E EX SD Lh OFFICE/DEN 1E BED O FIRE ALARM SYMBOL LEGEND SYMBOL DESCRIPTION MODEL # TOTAL BACKBOX MOUNTING QTY HEIGHT FACP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. AAP FIRE ALARM ANNUNCIATOR PANEL 3-LCDANN 1 PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS10A 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- SD OPITCAL SMOKE DETECTOR WITH BASE SIGH-OSD/SIGA SB4 26 4" SQUARE 1-1/2" DEEP CEILING SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE VERIFY IN FIELD 1-1/2" DEEP HD HEAT DETECTOR SIGA-HRD 30 4" SQUARE VERIFY IN FIELD 1-1/2" DEEP xa HD WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING �P DOUBLE ACTION PULLSTATION SIGA-278 11 1 GANG 48" A.F.F. 1-1/2" DEEP ❑ WEATHERPROOF, DOUBLE ACTION PULLSTATION BG-12LOB 26 PROVIDED 48" A.F.F. HS HORN STROBE 04AVRF 7 1 GANG STANDARD g0" A.F.F. S STROBE - RED G4VRF 2 1 GANG STANDARD 80" A.F.F. SPEAKER STROBE G4HFRF-S7VMC 22 4" SQUARE g0" A.F.F. SS 2-1/8" DEEP ve 44 BOX SS WEATHERPROOF SPEAKER STROBE WG4RF-SVMC 36 OUTDOOR RATED 80" A.F.F. PROVIDED ® EXISTING SPEAKER - CEILING MOUNTED F.B.O 216 ----- CEILING CONTROL RELAY MODULE SIGA-CR 15 1 GANG VERIFY IN FIELD STANDARD El INPUT MODULE SIGA-CT1 62 1 GANG VERIFY IN FIELD STANDARD CT2 DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD MCCi CONTROL INPUT MODULE SIGA-MCC1 15 UIO MOUNT VERIFY IN FIELD ® CONTROL SYNC MODULE SIGA-CC1S 3 2 GANGS TANDARD VERIFY IN FIELD O TAMPER SWITCH F.B.O 18 ----- ----- OWATERFLOW SWITCH F.B.O 13 ----- ----- ElVOLTAGE VOLTAGE SURGE PROTECTOR ASCO 237 4 ----- ----- AA I EXISTING MINI -HORN F.B.O 5 ----- ----- FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP=F CKT# DEVICE # B1-1-1 S 110 CD oCANDELLA RATING -DEVICE SYMBOL SD �DEVICE ADDRESS i-004 EX e"EX" DENOTES AN EXISTING DEVICE TO SD REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNCIATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 TWISTED SHIELDED FPLR ALL EXISTING CONDUITS AND WIRINGS TO BE RE -USED RE ED FOR CODE COMPLIANCE ST" LU IF_ COUNTY FILE COPY J Q Q = 0 z ~ Lu �y 1 X Y I aL�uj z 0 S2 cr 14. a o09 0 Jti(aaix G il.1Fj,'(aydx_ L co < wq m a w z z w leg T iJle Safeh� � Conununicalri�ns _Z 0 Z � O v J LL w c z J 1 Cn — ¢ Z QQO Z = C0 I"- = z r Q O Z FU-- (L c� o= c z O LLI U > LI.I 0 LU Wg J z Zs 1 w W c Drawing Number FA=14 14 OF 21 NOTES: EXISTING 120V SINGLE STATION SMOKE DETECTOR (SUPPLIED & INSTALLED BY OTHERS) E SD SD EX MASTER RED WAITER DIM MASTER BED MASTER RED EX Sp EX r SD -0.25W 0.25W CO.25VY EX EX EX 0.25W EX SP 1 SIP EX EX EX SP 1E SP EX SD SD SD SD uxrr a uxrr e 1E 1E UNIT B 1E 1E- BATH I\ i n BATH INdwo ., ETTCAEN ETTCBBci —' BATH BATH HATH BATH fTTIIM pggjjg'T SPE 1E LAUNDRY LAUNDRY 1E l -5 SPEx A RATH BATH 0.25W I/2 1/2 BATH SD Ex 1 -1 ExSD BATH 1E 1E 0.25w U 025w X EX SD L LAUNDRY 0.25W SDEX SDEX SP SP EXSD EXSD SP 0.25W OFFICE/DEN 1 LAUNDRY EX BED BED RED BSD OFFICE/DEN SP Ex JP 0.25W UTI M 1E - - 1E 0.25W _ UTlI1TY 1E 0.25W 87CD sK( 1E EX ,� R25w O VOL.0 EX BATHWp SD J 1A,1B,1E SSA 7W SS VSD CT1 P EOLL.. CT1 P f47Kn BATH t Eol. 1E X SSE 1A,16,1E rlA,18JE2 TS WF ss X SD 1E 1E SD E X SP E SD SP 15 D tSKn CTi HD HD CT1 - CT2 L Sp SD SP t \� L. FA- p_ yy 0.25W 01 5W ,16,1E _ _ 1B 1 D 0.25W 0,25W 7CD - 0.25W BRD 1E RED FATC ELEC. �Sf o.25w1 T� — BED qlE BED HD HD A,1B,1E - 1A,1 - STAIR 1 1A,1 B,1 E STAIR 2 SPKR. CKT. 1 FROM TWELVTH LEVEL SPKR. STROBE THIRTEENTH - DEVICE L. SCALE: 1/8" = 1'-0" SPKR. CKT. 2 FROM TWELVTH LEVEL SPKR. STROBE E "OUT N W El FIRE ALARM SYMBOL LEGEND SYMBOL DESCRIPTION MODEL # TOTAL BACKBOX MOUNTING OTY HEIGHT FACP FIRE ALARM CONTROL PANEL EST-3 1 PROVIDED 66" A.F.F. FAAP FIRE ALARM ANNUNCIATOR PANEL 3-LCDANN 1 PROVIDED 66" A.F.F. BPS REMOTE BOOSTER POWER SUPPLY BPS1CA 3 PROVIDED 66" A.F.F. FATC EXISTING FIRE ALARM TERMINAL CABINET F.B.O 16 ----- ----- SD OPITCAL SMOKE DETECTOR WITH BASE SIGA-OSD/SIGA 26 4" SQUARE CEILING SB4 1-1/2" DEEP SUPER DUCT DETECTOR SIGA-SD 2 N/A VERIFY IN FIELD RTS REMOTE TEST STATION, KEYED SD-TRK 2 4" SQUARE VERIFY IN FIELD 1-1/2" DEEP HD HEAT DETECTOR SIGA-HRD 30 4' SQUARE VERIFY IN FIELD 1-1/2" DEEP HD VP WEATHERPROOF, HEAT DETECTOR 302-AW-135 24 PROVIDED CEILING �p DOUBLE ACTION PULLSTATION SIGA-278 11 1 GANG 48" A.F.F. 1-1/2" DEEP �P rr WEATHERPROOF, DOUBLE ACTION PULLSTATION BG-12LOB 26 PROVIDED 48" A.F.F. HS HORN STROBE G4AVRF 7 1 GANG gp" A.F.F. STANDARD S STROBE - RED G4VRF 2 1 GANG 80" A.F.F. STANDARD SS SPEAKER STROBE G4HFRF—S7VMC 22 2-14" SQUARE " 80" A.F.F. /8DEEP �+ 449BOX SS WEATHERPROOF SPEAKER STROBE WG4RF-SVMC 36 OUTDOOR RATED 80" A.F.F. PROVIDED ® EXISTING SPEAKER - CEILING MOUNTED F.B.O 216 ----- CEILING CR CONTROL RELAY MODULE SIG 15 1 GANG VERIFY IN FIELD STANDARD CT1 SINGLE INPUT MODULE SIGA-CT1 62 1 GANG VERIFY IN FIELD STANDARD Ci2 DUAL INPUT MODULE SIGA-CT2 14 1 GANG VERIFY IN FIELD STANDARD 61cC1 CONTROL INPUT MODULE SIGA-MCC1 15 UIO MOUNT VERIFY IN FIELD C1 CONTROL SYNC MODULE SIGA-CC1S 3 2 GANG VERIFY IN FIELD STANDARD OTAMPER SWITCH F.B.O 18 ----- ---_- OWATERFLOW SWITCH F.B.O 13 ----- ----_ u® VOLTAGE SURGE PROTECTOR ASCO 237 4 NA I EXISTING MINI -HORN F.B.O 5 FIRE ALARM PLAN SYMBOL ID LEGEND DEVICE SYMBOL BPS PANEL=B, FACP-F CKT # DEVICE # B1-1-1 SS 110 CD ®—CANDELLA RATING ®-- DEVICE SYMBOL SD 1-004 DEVICE ADDRESS Ex 'EX" DENOTES AN EXISTING DEVICE TO $D REMAIN. FIRE ALARM WIRE LEGEND WIRE TAG WIRE USE A (NAC) 14-2 FPL B (SLC DATA LOOP) 18-2 FPL C (REMOTE TEST STATION) 22-4 FPL D (ANNUNOATOR CONNECTION) 18-4 FPL E (SPEAKER CKT.) 16-2 TWSTED SHIELDED FPLR ALL EXISTING CONDUITS AND WIRINGS TO BE RE -USED WED FOR Ft C®pE COMPLIANCE gT. LlI AE ANT S FILE COPS' J J o z V Lu W 6LL' 6 o z 0 w '> w It — T Vwgp WLO N z_j.:u.Ja,9 N x�OuixN uaVo ad o Z Gw w Qxmaa ac>vNdg a war y 0 iL w w E .. Life Safety � Cern�nunic:�� 1 ZD Z 0 Z O U "' J Ll W o J z U <0 p LLI_C/) Z�z <00 v w 'o H = a (J o cc ) 0 W z W r �w w � Drawing Number FA=15 15 OF 21 NOT IN SCOPE OF WORK. NOTES: 1E(SPKRCKT, 11) 1Eo) P 1. FIRE ALARM CONTROL PANEL SHALL BE ANALOG ADDRESSABLE TYPE. TO JUNCTION LEVEL 1 A w "� 1 2. INITIATING DEVICE CIRCUIT SHALL BE CLASS "B". JDNCTION Box BPS-2 SS ,m SS m SSe� �" I / 3. NOTIFICATION APPLIANCE CIRCUIT SHALL BE CLASS "B'. (SEE FA-20) / / I - —L_L_/_� �1_1_1_ _L_L_�� 1 1 1_ 1 L_L_L�1 11 1_L_L�� �1 1 1 _L_L/ _ a2sw D.2sw _o.z5W 1 2B,3A,6E HD EOL P EOL HD �E4pL P 3 7K 47KO 47KO 1113 EOL. TS WF EOL. HD CT1 CT1 HD CT1 CT1 CT2 -04Fo -1 7 F-04-0 ®9 -199 ®0 1- 01 J. BOX 9TH LEVEL 9TH LEVEL 2B,4A,7E 1A �w - I �/ / / / 1Ej3PKRCKT.10) EOL. BPS-2 ss m SS 7m ss �m / / L_ L_ 1_ L/ 1_ 1_ zo.2sw®__L_/_� 1_ _L_L_ /_ 1 _1 L_ L_ /__/_ 1_ L_ L_L_�_ /—z- 47KD P $47KO HDEOL.P �476) HD 47K0 47KOl EOL, fS EOL. EOL EOL. 1113 Ea TS W EOL HD CTi CTi HD CTi CTi CT2 -190 170 ® -192 -193 -194 oa ggF-1951 OUNO `�� � J. BOX 1) # 12THHN 8TH LEVEL = (GREEN) 8TH LEVEL 1 E(SPKR CKT. 2) 1E(SPKR CKT. 1) _ NOT IN SCOPE OF WORK. — — — — — — — — — 1E(SPKRCKT.9) -- �,. �— T— — /— — — —T— T— -- —7— �T— —T— T�-- 213,8E /J/J�/ T/ /� BPS-1 SS ss EOL I / SS elm 7m sm SS ism SS 87CD 87CD 15CD 15CD as _oi nr Al-o3 a a5=?i 1_ 1_ 1_ 1_ L_1_ 1_ _ L_L _�� 1_ 1_ _ L_ L_L _� 1_ 11_ —L_ _/_ _ �1_ 1_ 1_ _ L_ L _-i 0.7'�W 0,25W 0.25W 0.L5W 0.25W� wp KL HD EOL. HD EOL. EOLK 14EL TS 1B EO HD CT1 CT1 HD CT1 CT1 CT2 041 -184 -ta5 -04 - 886 -1 7 1--188 -189 — — J. Box 7TH LEVEL 7TH LEVEL ---------------------------------------------.._.----..._NOT_IN_SC9PEOFWORK.---------------------- 1E(SPKRCKT. 8) P— T— — -- �— — r 1--- —7-7— — — — — -- —— % —T— — T— -- — �— — T— /—/� — — — /T / /� /T %i BPS-1 w SS SS 7m sS �m / / 2B,1A,9E 87CD 87CD 87CD L1_11 �L_ _/_� �1_1_1_ _L_L_�� 1_1_1_.- L_L_L�1_11_�L_1 1 _L_L_/ o.z�w o.z:w oz�wv 47M 47Mp 1471 P 141Kf1 47K0 47KO HD EOL P EOL, HD EOL. ; EOL 7K TS WF EOL. 1B HD CT1 CTi HD CT1 CT1 CT2 ®3 -1 8 -1 9 -04 -1 01 i-181 -182 J. BOX 6TH LEVEL 6TH LEVEL - - - -- - --- - -- - --- - -- - - - - --- - - - - - - - - -- - - - - -- - -----,-5KO/�------T--T-- - --/- -T---NOT-INSCOPE-OF-WORK.------%- T- --T --- �I 1E(SPKR CKT. 7) / EO - - / 7/ _ �_ EOL. BPS-11A 2B,1A,10E SSmm SSam SS I/ 7CD 87C 7® I // / / / / % I -.i a. - �1_11_1_L_ _/_� �1_1 1 _L_L_�� 1 1 _1 L_L_L__� 1 11_ L L_ _/_� �1_1_1- _L_L_/ 0.2.5W 0.2 0.25W HD EOIL. P EpL 47KHD EOL P 147 EOL 47KO 47M 1 e EOL TS EOL REVIEWED FOR HD CT1 CT1 HD CT1 CT1 CT2 CODE COMPLIANCE ®0 -172 -173 -03 -174 -1 5 -17 0 ST. LUCIE COUNTY -17 BOCK 5TH LEVEL 2B,2A,11 E 2B,2A,12E J. Box J. BOX 5TH LEVEL - I1E(SPKRCKT. 2) NOT IN SCOPE OF WORK. FILE C r1E(SPKR CKT. 1) �1E(SPKR CKT. 6) � 1 tEe�n P — — — — — 7-7 — — — — — — /— -� 7 — — � — — — /— — — — — — — — — — — — — — — — � — BPS-1FQl 1A SS 7m SS 7m SS ism SS ism SS 7m 87187CD 15CD 15CD 822 In f - I / / n �,-� aim F:-i7 L1_11 �L_L_/_� �1_1_1_ _L_L_�� 1 1 _ L_L_L_�1 L_ 0.25W 025NJ 0.25W �D2sw W47KO � � � HD IEOL P EOL HD EOL P J K 4 EOL. TS WF 1 7KO 1B --a—CT1 CTi HD CT1 CTi CT2 ®3 -166 -1® ®D -16 a © -1 0 W W U 0 0 z W i N g LU U O Z N Q w w 0 co a� 2-c o W j wN U?\ 1-11 ¢NwUO U�Z ) O wpO�w 3w� ¢ w Z �=roaQ w �10 a a it w w z E T !_ife ..Safety &Communications q Z Z 0 v UJ-i Ll_ W 0 ''J Z VJ QZ 0 ¢O w M Z = Cn z _Z 2 O LU IJ� Z CV ::D fn c) = a V ri Z CV � 0 z elf w L1J w C7 �5 CL' FROM 3RRD LEVEL Drawing Number JUNCTION BOX FA l9 4TH LEVEL ------------(SEE FA-18)4TH LEVEL -------------------------- --_ ..----------------------- - _-------_ _ RISER DIAGRAM-2 19 OF 21 w 2B,1A,3E NOTES: 1. FIRE ALARM CONTROL PANEL SHALL BE ANALOG ADDESSABLE TYPE. 2. INITIATING DEVICE CIRCUIT SHALL BE CLAS5)) "B". 3. NOTIFICATION APPLIANCE CIRCUIT SHALL BE CLASS "B'. I .1 J. BOX In: W P aTS EOL. EOLrrcu CT7 CTi SD HD -22 -22 -05 � z QC Lu Y �n O N �� W C u ------------------- HUNT PRH(ARY ALTERNATE FIRERAT SHUNT TRIP S STATUS i P EOL. TS IEOL iP ALTERNATE FIREHAT SHUNT TRIP SHSTATUS UNT TRTPI I I I I I CR CR CR CR CT1 CT1 CT1 CR CR CR CR CT1 -12-6 -127 E1251 2 129 F2 I -131 -13 I -133 -134 2-135 12273661 2- 7 I L- - - - - - - - --- - - - - - - - - L--------------------� ELEVATOR CONTROL ELEVATOR CONTROL ROOF LEVEL ----LEVEL—— --- — — -- —— — — — — — — — — — — — — OF LEVEL - 13TH LEVEL CKT. 1E(SPKR CKT. 1) � v SS w op SSum 15KC) EOL. .,w. SS lktl L SS Ik 1E(SPKR CKT. 15) BPS-21A 7® I 87CD I 15CD I 15C n ;!'J 11>DUhl I'R25W 0.'+5W HD 47K(1 EOL. P 147KMO 1B 3 EOL. HD CT1 CT1 HD � 1- 1 -O5 J. BOX NOT IN SCOPE OF WORK. P—J J — — — /--- —7— — 7— —7— -- — j-- — w YEOL. I s7cD I / z L_.L_ _L_L_�� 1_1_ _1 L_L / / z _L_-� 1 11_1_L_L_/_� �1_L_L_� W m CT1 CT1 EOL. -- — — — — — — — — — ————————————--———————————————————————————————————--—————— -_---— - --—---- — — —— - ------ — 13TH LEVEL NOT IN SCOPE OF WORK 1E(SPKR CKT. 14) 1 A ^", I4I✓P�� ! j /_ T /� _ _ _ _ / j _ _ _ _ 7 r _ _ _ JT /— EOL.' 1BPS-2 SS SS EOL. 87CD r 87CD n a7cD I 7 �1 1_L_ _/_ �1_1_1_ _L_L_�� J 1 _1 L_L_/---- 1_1 L_/ l xv 47Kn xr xrf XP HD EOL. P EOL. HD H D f EOL P S47KS] EO ps TS WF EOL 3 EOL j 1B HD CT1 CT7 HD CT1 CT1 CT2 1-Os1 -214 F--2-151 F-T51 -216 -217 -2 8 J. BOX - 19 12TH LEVEL 12TH LEVEL 1 /� T ? NOT IN SCOPE OF WORK. 1E(SPKRCKT. 13) T --- �— — � — -- — — — —— — —�— �—T— T— EOL. II" / BPS-21A � w« �' I 2B 2A 4E SS B,m SS , SS e,m I/ / � / / / /i 7 � ®c I " �� o�, 13�?I ors-2 I_1 11_�L_ _/_� �1 1__Z _L_L_�� 1_1_1_1 1_L_,C_ 1_11 / ) ,�_`;!aJ lu�_W, lo.2ha_v� _1_L_L_/_� �1 �1 _L_L_/ J 47XO wp xf4 47KO 16 HD EOL P j L HD IEOL. P lEOL. Eon rs WF 7KO REVIEWED FOR CODE COMPLIANCE HD CT1 CT7 HD CT1 CT1 CT2 - ST. LUCIE COUNTY 4 -20 � 105 -210 1- 11 - 12 BOCC - 13 J. BOX of i-9 wrui4 _J F- LL o >Nryj=N env U w� U J Z 7 yLF�y?W C u�z �o ? E6 c.ife Safety & CommunicationS 11TH LEVEL 11TH LEVEL 1E SPKR CKT. 2 _z 1E(SPKR CKT. 1) NOT IN SCOPE OF WORK. FILE COP 15KP 1E(SPKR CKT. 12) EOL 2B,2A,5E BPS-21A iSKf / /; ' ` d' SS SS SS SS SS EOL I 87,d O � arm arm ika rxa 87CD 87CD 15CD 15CD 87CD I U <') J� J HIVE�1_11_ L_ _/_� �1_ L= _L_C—_� 1_1_ L_ /___1 1_11_ L_ /_� �1 1 1 _L_L_/ L` 0.25W 0.2 W 0.25W 0.25W 0.25W W Q 47K0 f wp Z HD EOL. P 1 EOL7KC) HD EOL P 7K 47KO 47K� 1 B EOL. TS WF I EOL co Q U) cv HD 0 CT1 HD CT1 CT1 CT2 Q Q zp -04 -20 F-703 -04 -20-20 F-2-061 _ � 20 z Z 2-7 -= w Q J. BOX c~j � O � a Lu z 2B,3A,6E a 0 ti z X FROM 9TH LEVEL cr JUNCTION BOX Drawing Number 10TH LEVEL (SEE FA-Ie) 10TH LEVEL FA=20 RISER DIAGRAM-3 20 of 21 T- 1110 VAC (NON-LIMITED)1 O 10 POWER LIMITED ONLY G G DO NOT USE HOLES FIRE ALARM DEVICE MOUNTING GUIDE CEILING MOUNTED SMOKE/NEAT ^-3' (MIN) DEFECTOR II 4' oio�CEILING MN 24• MIN HANDICAP BEDROOM STROBE A/C SUPPLY DIFFUSER ACCEPTABLE HEREJAREA 4• AUDIOVISUAL DO N 12" (MAX) VISUAL -ONLY INEVICES ® CEILING MOUNTEp NOTIFICATION DEVICE. WALL MOUSEE PLAN FOR LOCATION. SMOEK/HEAT D ABOVEFIMAX(NFPA, AEA) TO THE BOTTOM. ABOVE FINISHED F TO TOP OF LENS MORE THAN TWO APPLIANCES MAX FROMM IXR DOOR IN THE SAME ROOM OR ADJACENT SPACE WITHIN THE FIELD OF VIEW SHALL FLASH IN SYNCHRONIZATION. MANUAL PULL �DDpC -I FIRE STATION HOLDER REMOTE PHONE ® JACK 5 ANNUNCA 0 DUCT DETECTOR DOOR 80' MIN (NFPA, AD)4 REMOTE TEST LESS 3" ABOVE FINISHED FLOOR TO BOTTOM OF LENS c ® 4 a x 48" MAX (NFPA. A)A) �a 42• MIN (NF'A) o MEASUREMENTS SHOWN ARE ¢ .N TO THE TOP OF PULL HANDLE FINISHED FLOOR FIRE DEVICE MOUNTING DETAILffMB'-lEcT�r=-"MD IMPORTANT NOTE NOTE NOT ALL DEVICES SHOWN ON THIS DETAIL APPLY TO THIS UFACTURES INSTALLATION SHEET PROJECT. SEE THE PLAN NEW LAYOUT OF THE FIRE ALARM SYSTEM Tn VERIFY WHICH DEVICES APPLY, AND wicN W NOT. N.T.S. ROUGH -IN HEIGHTS, UD TION OF WIRING REQUIREMENTS._--_ STROIINE OR W ART. OR � e• BELDYI GEErG A E O (wxICHEvm 6 LDLWR) FXRL srATpN O ,e AF.F. O ADA HEIGHT REQUIREMENTS NO SCALE WIRE STRIPPING GUIDE STRIP 1/4" FROM THE ENDS OF ALL WIRES THAT CONNECT TO THE TERMINAL BLOCKS OF THE MODULE. 1 /4"1 DO NOT EXPOSE MORE THAN 1/4" MOUNT EST SIQA SERIES NODULES. -.--..- SGA�.Tf/CR, 5161-CR, SIO4-NM1 sMJ.-WIN. ro STANNAD SINGLE GeNG 1/1 IN45-R• DEEP E3ECIRIOAI BOx. mE iERN LL MCEPf i14AWG WIBE OE, WMOE FROM FACP OR DEVICEPREVIOUS SIGA-CT1 MOUNTING DETAIL N.T.S. SINGLE INPUT MODULE WIRING DIAGRAM N.T.S. 11Px,2 IPIAme Oft. Fn ESN oIr IBA P e TIB3 SIGA-CCl o 0 IxN.. 1B1 e r a s a 3 v+ TIBt �F�II DSIg1 FROM FACP FROM FRCP OR 0 NEM FE DEVICE SINGLE INPUT RISER MODULE WIRING DIAGRAM N.T.S. m oir TO NI DEVICE COVER REL&SE BOXF�;3EVSW �CRE /COMPATIBLE ElEMIAL X I! 1BR f/ ev SIGA-270 O N BAaL PLATE ® O ® Iew,a ,Ap�[T TBi , 3 R 1 ',I; SNITCH '' FROM FkCP- t`"1 _ xSL l._- OR I TO NEXT B - l ww wN-) DEVICE GLASS;�.^---R RELEASE LEER MANUAL PULL STATION SINGLE MODEL — SIGA-270 STAGE WIRING DIAGRAM N.T.S. INSTALL EST SIGA SERIFS 2T0 Te MANUAL PULL STATION U G STARDMID 1-1/2•(3Bmm) DEEP CONCRETE SLAB BACK BOX o: 1 3/4" EMT CONDUIT J \\ DETECTOR TYPICAL HEAT DETECTOR/SMOKE DETECTOR MOUNTED ON CONCRETE OR GYPSUM CEILING - NOT TO SCALE - 3/- EMT CONDUI4T BACK BOX MOUNT ES/TT SKA SEGEB MODULES SIGA-�WM. ib MIS SINGLE GANG 1 1-2• �ID ELECiRIGL BOX, THE TONAINALS ACCEPT ;i1AWG WIRE. /COMPATIBLE ELECRICAL BOX SIGA—CT2 MOUNTING DETAIL N.T.S. M. p TrP,110 o1 ] Iu1u�� INPUW T 1 Wr R 4W 4W a3X T% oNM aw SIGA•CT2 OPTIONAL SEU,-ADNEsrvE °. .,°... FRENCH LABEL (SUPPLIED) T61 WA1L PLATE. WHITE (1 OIAG) FROM FACP.."-A OR PREVIOUS DEVICE EVCE Tmlrx tuFwwrc CNr. < < < ew4W T94 te'e T83 SIGA-CC1 a a tlNM. T81 B T e 4] 4+ 1B1 ) �L'DU PESIBTM FROM FACP FROM FRCP W�l L OR TO NE1D PREMDUB - �, DEVICE DencE - SINGLE INPUT RISER MODULE WIRING DIAGRAM N.T.S. AM-07-06-052197-00 / NAC1' NAC2 i NAC3 i NAC44 24VDC IN SENSE 1 CON out IN SENSE 2 COIN OUT TROUBLE CNOAOF cwr, arq I TD EX ewu wN-1 DEVICE j DUAL INPUT MODULE WIRING DIAGRAM N.T.S. LIOUNT EST BGA 9ERE5 YOWL6 sIDA-Cf1/CT2, SIGA-OR, SIM-Nut s%Y.-DUTY 1D STANDARD sINGLE TYING 91ACCEPT O V"%. THE TERYMMS ND ORE, _0010M N CLOSET, Y_ COMPATIBLE RECDM.LL BDx f/ tsz • Y SIGH-CR DPlaxu. ® SELF-AWEBEL TBt (ENIED) WALL PLATE, WHITE (1 GINO) 0 a FROM ORFACP �. TO NEM PSIS em ex-) '•. _I, Wx+, WA(-) DEVICE SIGA-CR MOUNTING DETAIL N.T.S. Nv� —xFe Rucr \ maloq mXTM oLlmlgl O I TIM W >r mowur,�c `61gW `` DUCT DETECTOR HOUSING DIAGRAM N.T.S. TION REMOTE POWER SUPPLY _�� I�--� I NOIIFICAxIN MPILW�C�E ORIWR 1 NMGATIDN APPLMNCE ORCUB 2 NOTIFIATION APPUMTCE CIRORT 3 NOTIFICATION APPLACE OROUT 4 OAiF JUe(t - - -- - TO NCR DATA DUN-) DEVICE REMOTE BOOSTER POWER SUPPLIES MOUNTING DETAIL (BPS10A) N.T.S. NEW VISUAL ALARM DEVICE DRYWALL TYPICAL VISUAL DEVICE INSTALLATION ON GYPSUM WALL - NOT TO SCALE - FAWALL-F FROM FACP OR wrA_) PREVIOUS DEVICE CONTROL RELAY MODULE WIRING DIAGRAM N.T.S. DETECTOR MWNT BASE TO 4• SQUARE STAMOARD aMMICN. WX 1-1/2• DEEP. TAMPER -RESIST LEVER ARM O -BRHA( OFF TO DIS,RLE- (LOCATED ON MISS) TAMPP ACCESS MECSLOT �IMIISM O �aD® SD / HD SIGA—PS/HRS MOUNTING DETAIL N.T.S. Fx CONTACTS RELAY 6 H —FW—N ES.T. SIGA-CR I POKER NOTE ALSO USED FOR ELEVATOR SHUNT TRIP, RECALL. AND FAN SHUTDOWN ,Rnw TBI wAaP «} FROM FRCP ••• •� - - OR PREVIOUS I. OW-) DEVICE DENE CONTROL RELAY MODULE WIRING DIAGRAM DETAIL j5 REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC FILE COPY O Z W ¢ 1— UU h Y0 uvi oz w H U w CD v co z O y w tl p�j 2 VW Juice N Z_J( u-C:q) s�v S-zfnu;=T1cc r{ U(?W-UO 0 K-OpwZ W O 3J2-13w a. jWJZ-ACC -C� Q avaUca.U- WOOF- �^O g D. w z 0 W 14 ;: Safe. �:aaxnunrcaUc� Z O 0 z O UJ L.L LLI 0 z �J V i J 0 Q QO LU a z�Z = CIJ z 0 2 U G~J N Il H CN O a f �► 4J CZ)= ciZ w � LU F > w w LLJ Do Drawing Number FA=21 21 OF 21