HomeMy WebLinkAboutBUILDING PLAN PAGE 1-12I 1 . ALL COMPONENTS SHALL BEAR THE U. L. LABEL FOR FIRE SERVICE USE AND SHALL BE COMPATIBLE FOR USE WITH ALL INTERCONNECTING EQUIPMENT. 2. THE COMPLETE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS, N.E.C., N.F.P.A., A.D.A., ANSI, F.B.C., AND ALL LOCAL CODES. 3. FIRE ALARM DEVICES SPECIFIED HEREIN SHALL BE INSTALLED. NO EXCEPTIONS WILL BE PERMITTED. 4. HORNS AND SPEAKERS SHALL BE OF SUCH CHARACTER AND SO LOCATED, AS TO BE CLEARLY HEARD THROUGHOUT AND ABOVE AMBIENT NOISE LEVELS. 5. MINIMUM CONDUIT SIZE SHALL BE 1/2" FOR ALL RUNS. CONDUIT SHALL LOOP ALL DEVICES AND RETURN TO F.A.T.P. 6. ALL CONDUCTORS SHALL BE COPPER AND SHALL BE SIZED FOR NO MORE THAN 1 dB LOSS. MINIMUM #18 AWG AND #14 AWG FOR HORN AND/OR STROBE CIRCUITS. 7. CONDUCTOR INSULATION FOR CABLES SHALL BE TYPE TFN, IF CABLES PENETRATE INTO OR THROUGH PLENUM AREAS USED FOR TRANSFER OF ENVIRONMENTAL AIR, THEY SHALL BE TYPE FPLP, TEFLON INSULATED TYPE. 8. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT, CONDUIT SYSTEM, CON- DUCTORS, DEVICES, ETC., AND ALL OTHER ACCESSORIES REQUIRED FOR AN ACCEPTABLE AND FULLY FUNCTIONAL SYSTEM. 9. FINAL CONNECTIONS BETWEEN EQUIPMENT AND WIRING SYSTEM SHALL BE MADE UNDER DIRECT SUPERVISION OF A QUALIFIED TECHNICAL REPRESENTATIVE OF THE EQUIPMENT MANU- FACTURER, WHO SHALL TEST THE SYSTEM CONPLETELY AND PROVIDE A CERTIFICATE IN WRITING AS TO THE PROPER INSTALLATION AND OPERATION OF THE FIRE ALARM SYSTEM PRIOR TO FINAL ACCEPTANCE OF THE SYSTEM BY THE OWNER. 10. AS -BUILT DRAWINGS SHOWING POINT BY POINT CONNECTIONS OF ALL DEVICES AND FINAL EQUIPMENT LOCATIONS SHALL BE GIVEN TO THE OWNER UPON ACCEPTANCE OF INSTALLATION BY THE OWNER. 11. MANUAL PULL STATIONS SHALL HAVE Ul. LISTED COVERS. 12. CONTRACTOR SHALL SHALL PROVIDE AND MOUNT A LAMENATED ll"X17" DIAGRAM AT THE FIRE ALARM PANEL SHOWING ALL INITIATING DEVICES. 13. ALL FIRE ALARM STROBES SHALL BE IN COMPLIANCE WITH NFPA 72. 14. ALL SMOKE DETECTORS SHALL BE SPACED PER MANUFACTURER'S RECOMMENDATIONS. PROVIDE ADDITIONAL DEVICES AS NECESSARY TO MEET MANUFACTURER'S REQUIREMENTS. 15. EACH DUCT DETECTOR SHALL HAVE AN LED ON THE CEILING BELOW THE DETECTOR. 16. FIRE ALARM PANEL SHALL BE AN ADDRESSABLE TYPE WITH VOICE EVAC CAPABILITY FIRE ALARM NOTES SCALE NONE I OR 2 HOURS FIRE RATED THROUGH PENETRATION FIRESTOP F13R SINGLE METAL PIPE THROUGH GYPSUM WALLS USING FIRE -SHIELD F-RATING = I & 2 HR. T-RATING = 0 HR, ILL # WL1051 I DR 2 - HOUR FIRE RATED GYPSUM WALLBEIARD/STUD ASSEMBLY (ANGULAR SPACE RANGE, MIN, 1/4' MAX. 5/8') CONDUIT - 4' c1la. (OR SMALLER) EMT OR RIGID STEEL. TREMCD # FIRE -SHIELD- MIN.1/2' THICKNESS OF SEALANT INSTALLED WITHIN OPENING W/ A MIN. OF 1/4' CROWN AROUND GROUND THE PENETRATION ITEM APPLIED FLUSH W/ BOTH SIDE (IF WALL ASSEMBLY. 6 1 FIRE STOPPING DETAILS SCALE: NONE WJ1012 (377) 2 HOURS FIRE RATED THROUGH PENETRATION FIRESTOP FOR SINGLE METAL PIPE THROUGH CONC. FLOOR EIR 13LK. WALLS USING TREMSTOP ACRYLIC. F-RATING = 2 HR, 2 T-RATING = 0 HR. cx� UL # CAJ1205 4 3 1 PRE -RATED CONCRETE FLO13RS OR BLK, WALLS Min. 4/12' THICK, WITH ANNULAR SPACE RANGE OF 0' TO 7/8' 2 CONDUIT - 41 clla, (OR SMALLER) STL. CONDUIT OR EMT. 3 TREMC13 # FIRE -SHIELD- MINJ/2' THICKNESS 13F SEALANT INSTALLED WITHIN OPENING W1 A MIN.OF 1/4' CROWN AROUND GROUND THE ITEM APPLIED FLUSH W/ BOTH SIDE OF WALLS ASSEMBLY, 4 TREMCO # TREMSTOP ACRYLIC - MIn. 1/2' SEALANT APPLIED WITHIN ANNULUS, & A MIn. 1/4' SEALANT APPLIED AT POINT CONTACT AT FLOOR SURFACE FOR FLOORS, OR BOTH SURFACES FOR WALLS. 2 HOURS FIRE RATED THROUGH PENETRATION FIRESTOP FOR MULTIPLE METAL PIPE THROUGH CONCRETE WALLS USING FIRE -SHIELD OR FIRE -SE F-RATING = 1 9. 2 HR. T-RATING = 1/2 HR, (1) WALL ASSEMBLY - 5' THICK GOING. W1 MAX, AREA OF OPENING 35.75 Sq. In. (9) STEEL PIPE = 21 Dia. (OR SMALLER) SCH, 5 OR HEAVIER CONDUIT - 2' dia. (OR SMALLEIR> EMT. MAX. 5 PIPES 13R CONDUITS, 0 A) STEEL SLEEVE - No, 30 MSG ga(v. SHEET FITTED WITHIN OPENING & SECURED TO BOTH SIDES OF WALL. B) PACKING MATERIAL - MINA' THICKNESS CERAMIC FIBER INSULATION (6 PCF) FRICTION FITTED C) MIN, 1/2' THICKNESS FIRE -SHIELD OR FIRE SEAL, WITH 1/4' CR13WN FORMED AROUND PENETRATION ITEMS, STROBE OR HORN/STROE E F 0 0 80" A.F.F. OR R 6" BELOW CEILING JE 0 0 (WHICHEVER IS LOWE 4-11/16- SQUARE, 2-1/8' DEEP BOX. PROVIDE ADEQUATE SUPPORT FOR BOX IN CEILING _1_� FOO 4-11/16- SQUARE III TO 3-0 ADAPTER RIN( I PLUG-IN DETECTOR BASE ?F_ DETECTOR HEAD BOX MOUNTING IN SHEIETROCK OR PLASTER TYP CEILINGS (MUST BE INSTALLED WITH CONDUIT) 31e FIX 4" SQUARE (2-1/8' DEEP) BOX e SQUARE, 2-1/8' DEEP BOX (OR 4-0 8%.R PROVIDE ADEQUATE PULL STkTION SUPPORT F BOX IN CEILING, I CEILING 4' SQUARE BOX TO 3-0 ADAPTER RING 0 (OR NO RING IF 4-0 48" A.F. BOX IS USED) PLUG-114 DETECTOR BASE DETECTOR HEAD BOX MOUNTING IN LIFT OUT OR INTERLOCKING TYPE CEILINGS WITH SYSTEMS INSTALLED IN CONQUI ADA RQMT'S SCALE: NONE 3 DETECTOR MOUNTING SCALE: NONE DUCT HOUSING & BASE. W/ PHOTOELECTRIC DEFECTOR 120 V. CONTROL PROVIDE CONDUIT & WRING CIRCUIT TO PANEL. TO INTERCONNECT DUCT NOTE: DETECTORS, FACP SHALL NOT ELECTRICAL 120/24 V. TRANSFORMER T77 ACTIVATE SHUT -DOWN CONTRACTOR SHALL COORDINATE A/C SHUT LOCATED IN DETECTOR HOUSING DOWN WITH MECHANICAL RATING OF TX SHALL EE BASED CONTRACTOR. ON 125% OF TOTAL CURRENT DRAWN FROM DEVICES 1/2" CONDUIT. (NUMBER 0 REMOTE TEST STATION W/L.E.D. OF WIRES ACCORDING �O MOUNT STATION AT +48' A.F.F. MANUFACTURER) 4 DUCT DETECTO� DETAIL SCALE: NONE SPRINKLER RISER --FTSF7S HAFS SYSTEM k 1 zr Ov CKT. 7 1 FIRE ALARM RISFR SCALE: NONE ITEM DESCRIPTION STANDBY CURRENT PER UNIT (AMPS) QTY TOTAL STANDBY CURRENT (AMPS) ALARM CURRENT PER UNIT (AMPS) QTY TOTAL ALARM CURRENT (AMPS) FACP & DACT 0.150 X 1 0.150 0.49 X 1 0.49 -1 2 NOTIFIER PHOTOELECTRIC SMOKE DETECTOR 0.0003 X 81 0.0243 0.0065 X 81 0.5265 3 NOTIFIER HEAT DETECTOR 0.0003 X 0 0.0000 0.0065 x 0 0.0 4 MONITOR MODULE 0.00075 X 1 0.00075 0.2 x 1 0.2 5 PULL STA11ON 0.0 x 1 3 1 0.0 0.000234 X 3 0.0107 ITOTAL SYSTEM STANDBY CURRENT (AMPS)� 0.1751 - TOTAL SYSTEM ALARM CURRENT (AMPS)l 1.2235 REQUIRED OPERATING TIME OF SECONDARY POWER SOURCE FROM NFPA 72 1-5.2.5: TOTAL CIRCUIT AMP DRAW CIRCUIT #1 CIRCUIT #2 CIRCUIT #1 CIRCUIT #2 DEVICE CD DEVICE COUNT DEVICE AMP DRAW TOTAL DEVICE AMP DRAW MAX AMP 2.5 MAX AMP 2.5 MAX AMP 2.5 MAX AMP 2.5 75 12/0 O�160/0.153 t92 + 0.0 TOTAL: 1,92 75 1/11 0.153/0.160 0.153 + 1.76 TOTAL: 1.913 75 8/0 0.160/0.0 1.28 + 0.0 TOTAL: 1.28 =5 0/12 0,153/0.160 0.0 + 1.92 TOTAL: 1.92 I TEM DESCRIPTION -CIRCUIT STANDBY CURRENT PER UNIT (AMPS) QTY TOTAL STANDBY CURRENT PER ITEM (AMPS) ALARM CURRENT PER UNIT (AMPS) QTY TOTAL ALARM CURRENT (AMPS) 1 #1 0.00 X I 0�00 1.92 X 1 1.92 2 CIRCUIT #2 0.00 X 1 0.00 1.913 X 1 1.913 1 CIRCUIT #1 0.00 X 1 0.00 1,28 X 1 1.28 2 CIRCUIT #2 0.00 x 1 0.00 192 X 1.92 I - � TOTAL SYSTEM STANDBY CURRENT (AMPS)l 0.0000 TOTAL SYSTEM ALARM CURRENT (AMPS)� 7.033 REQUIRED OPERATING TIME OF SECONDARY POWER SOURCE FROM NFPA 72 1-5.2.5: STANDBY: 24 HOURS ALARM: 5 MINUTES X 1/60 0.0833 HOURS REQUIRED TOTAL SYSTEM REQUIRED REQUIRED TOTAL SYSTEM REQUIRED STANDBY STANDBY STANDBY ALARM ALARM ALARM TIME CURRENT CAPACITY TIME CURRENT CAPACITY (HOURS) (AMPS) (AMP -HOURS) (HOURS) (AMPS) (AMP -HOURS) 24 x 0.1751 4.202 0.0833 X 8.257 0.689 REQUIRED REQUIRED REQUIRED DERATING MINIMUM STANDBY ALARM AMPERE HOUR FACTOR @ AMP -HOUR CAPACITY CAPACITY BATTERY 1.2 BATTERY (AMP -HOURS) (AMP -HOURS) REQUIRED 4.202 + 0.689 4.891 X 1.2 5.87 5 1 FIRE ALARM BATTERY CALCS SCALE NONE CEILING 75 75 75 75 75 75 75 75 75 75 75 75 CIRCUIT #4 WID (PWR, GENSET AND BATT. RMS A&B) 75 75 75 75 75 75 75 75 F 7�7 CIRCUIT #3 (EQUIP RMS 1,5,6) WP FCPS 120V CKT- 75 75 75 =1: 75 75 75 75 75 75 75 75 �7 Ell ILI J--[fl-�F �_/7 I E [f j F F F CIRCUIT #2 WP (I.T., MMR's, SECURITY, UPSTAIRS, EQUIP RMS 2,3,4) 75 75 75 75 75 75 75 75 75 75 75 75 CIRCUIT #1 FWID (ADMIN & D.R. OFFICES) FCPS 120V CKT- -p Z2 -p Z2 -P Z2 �2p �2p 2 �P2 �P2 �P2 �P2 �P2 �2 FACP p- P�2 P P 'B') ZP-ZP-ZP-ZP-ZP-ZP-ZP-ZP-ZP-ZP-ZP-ZP-l�p-�p �p �p (POP 120V CKT ij, 1� I i; � :!'.:: I ��i I lj�) lit! 1p �pp F; 1: !! I I I I I tp-z �pp�p �p �p �p �p �p �p �p �pp�p �p �p �p P.A. 1 �-7 �p �p �p �p �p �,,�p �p �p �p �p �p �,�p SUPERVISORY CIRCUIT EVAC FACP (MONITOR OFC) 120V CKT p �p �p 2 DEDICATED PHONE LINES TO TELEBOARD PROVIDE 7AH BATTERY op PULL STATION, NOTIFIER NOTBG-12LX SMOKE DETECTOR, NOTIFIER NP-100 D �DUCT DETECTOR, NOTIFIER DH1OOAC/DCLP Tp WITH RA40OZ L.E.D. IN CEILING BELOW DETECTOR @R/F ANALOG HEAT DETECTOR, NOTIFIER 5603 FFACP FIRE ALARM PANEL, NOTIFIER NFW2-100 WITH INTERNAL DACT FEVAC VOICE EVAC PANEL, NOTIFIER NFV-25/50 FFCP_s� REMOTE POWER SUPPLY PANEL, NOTIFIER FCPS-24S8 FIRE ALARM ANNUNCIATOR PANEL, NOTIFIER FDU-80 FFAA FP_A_j SUPPRESSION SYSTEM PREACTION PANEL 75 NOTIFIER E70-24MCW-FR SPKR/STROBE 75 CANDELA, WALL MOUNT 75 WHEELOCK RSS-24MCW-FR STROBE 75 CANDELA, WALL OR CEILING MOUNT REMOTE TEST STATION, NOTIFIER RTS51KEY FLOW SWITCH TAMPER SWITCH 181 FIRE ALARM LEGEND SCALE: NONE .GENERAL NOTES: CRAC UNITS SHALL NOT BE CONNECTED TO THE FIRE ALARM PANEL. /74R�k_ T4AE, INC,, ARCHITECTURE & PLANNING AA26001228 & AR92559 (954)839-4258 233 EAST ACRE DR., PLANTATION, FL 33317 *t STRICTURAL AND MECHANICAL ENGINEERING 4 '* A BASE 4 INTERNATIONAL, INC. 9858 GI_ADES ROAD, #237 BASE4CA RATON, FLORIDA 18,0720 72BASE4 .. base-4 com ELECTRICAL ENGINEERING isRIDCE, INC. 5707 S. DIXIE HWY, #8 WEST PALM BEACH, FLORIDA 3W5 PHONE' 5614369198 CERT.OFAUTH. 48800 T4AE, INC., AND ALL PROFESSIONALS OF RECORD, HEREBY RESERVE THEIR INDIVIDUAL AND COLLECTIVE COMMON LAW COPYRIGHT AND ALL OTHER PROPERTY RIGHTS IN THESE DESIGNS, SPECIFICATIONS, PLANS AND IDEAS. THIS DOCUMENT IS NOT TO BE REPRODUCED WITHOUT FIRST OBTAINING THE WRITTEN PERMISSION OF T4AE, INC., AND THE PROFESSIONALS OF RECORD. ANY DISCREPANCY BETWEEN THIS DOCUMENT AND ACTUAL CONDITIONS SHALL BE REPORTED TO T4AE, NC._j P R 0 F E S S 1 0 N A L 0 F R E C 0 R D S E A L 414 pf�4Sj No 75M z ' _0 STATE OF 101VAL DE\ �ETERKIN, PROFESSIONAL ENGINEER NO. 75256 THIS IS A CONFIDENTIAL DOCUMENT THIS DOCUMENT, AND THE INFORMATION DEPICTED HEREIN, PERTAINS TO A SECURE FACILITY DESIGNATED BY THE HOMELAND SECURITY ADMINISTRATION AS "CRITICAL INFRASTRUCTURE" AND MAY NOT BE SHARED WITH ANY PERSONS OR ENTITIES OTHER THAN AUTHORITIES HAVING JURISDICTION WITHOUT WRITTEN CONSENT OF THE OWNER. ANY PERSON OR ENTITY IN POSSESSION OF THIS DOCUMENT SHALL SAFEGUARD IT, AND SHALL DESTROY IT WHEN IT IS NO LONGER IN USE FOR THE PURPOSE FOR WHICH IT WAS PROVIDED. 0 z Z) U) 0 0 z 0 t ry 5c) < UJI u- z z D < V) LLJ 0 < (-)0 z Lu 0 F_ (0 E) ::) 0 < w < _j 0 . w uj F_ -I < F- Z:) < 0 0 U) Cl') 11 R E V 1 3 1 0 N S IREV #1 DATE I REVISIONS MADE DRAWING SCALE T: JOB NUMBER AS NOTED 1 34-84-1501 FIRE ALARM D E T6��ctor COPY SHEET NUMBER INITIAL SUBMITTAL DATE E5.3 4/12/17 a ELECTRICAL SCALE: NONE ,,,�TRANSFORMER WELD > (TYP) 1/2"X4" SQ. VIBRATION ISOLATION PAD i"xi"xi/4" ANGLE 2"X2"Xl/2" ANGLE UNISTRUCT FRAMING NOTE MOUNT TRANSFORMER 8 FT. ABOVE FINSHED FLOOR USE CHANNEL TO BEAM CLAMP, 'KINDORF' E760-2, 3 OR EQUIV. GROUNDING 2-� 75kVA TRANSFORMER MOUNTING E6.1 ) SCALE: NONE 500kCM-1 1/2"C TO A.T.S. AND GROUNDING ELECTRODES - SIDE 'A ) 1/0-1"C TO LIGHTNING PROTECTION SYSTEM �--#3/0-1" C, TYPICAL 0 0 0 1 0 0 is I I 1 9 0 1 1 Tl I I T21 I T3 POWER RM A #3/0 1"C #3/0-1-C GROUND BUS SWBD #3/0-1"C MSBA UPS A 500kCM-1 1/2" C BATTERY RM A DC GROUND BUS 0 0 0 0 0 0 0 0 0 T T T 1 7171 72 1 F3 500kCM-1 1/2"C BATTERY RACKS GROUNDING SYSTEM DIAGRAM SCALE: NONE WALL MOUNTING BRACKET COPPER BUS BAR 0 0 & 0 0 0 0 0 * 0 0 TELECOM. RM. GROUND BUS 'A' 1/4" 4 E6.1 INSULATOR 4 COMPRESSION LUG — BOLT TO BUS BAR TO BLDG. ELECT. GND. TO CABLE TRAY TO EACH EQUIPMENT RACK -�TO EACH PDU GROUNDING CONDUCTOR SIZE AS NOTED MAIN GROUND BAR DETAIL_ SCALE: NONE #2-1 "C CABLE TRAY RACK 1 RACK 2 RACK 3 TELECOM. RM TELECOM. TELECOM. TELECOM RACK 4 TELECOM, 7 /40L T4AE, INC. - ARCHITECTURE & PLANNING AA26001228 & AR92559 (954)839-4258 233 EAST ACRE DR., PLANTATION, FL 33317 STRUCTURAL AND MECHANICAL ENCINEER17 BASE 4 INTERNATIONAL, INC. 9858 GLADES ROAD, 4237 BASE4CA RATON, FLORIDA M�4 18'7'20.72BASE4 ...bas".wm ELECTRICAL ENGINEERING RIDCE, INC. 57078 OlXJE HWY, #8 WEST PALM BEACH, FLORIDA 33406 PHONE: 501436 9198 CERT. OF AUTHLi #aWO T4AE, INC., AND ALL PROFESSIONALS OF RECORD, HEREBY RESERVE THEIR INDIVIDUAL AND COLLECTIVE COMMON LAW COPYRIGHT AND ALL OTHER PROPERTY RIGHTS IN THESE DESIGNS, SPECIFICATIONS, PLANS AND IDEAS. THIS DOCUMENT IS NOT TO BE REPRODUCED WITHOUT FIRST OBTAINING THE WRITTEN PERMISSION OF T4AE, INC., AND THE PROFESSIONALS OF RECORD. ANY DISCREPANCY BETWEEN THIS DOCUMENT AND ACTUAL CONDITIONS SHALL BE REPORTED TO T4AE, INC P R 0 F E S S 1 0 N A F 0 F R F C 0 A D S E A L v� jrEN*4 4^ No. 75M t STATE OF **AX0FtVDFl 0�\ T DEVEREN PETERKIN, PROFESSIONAL ENGINEER NO. 75256 THIS IS A CONFIDENTIAL DOCUMENT THIS DOCUMENT, AND THE INFORMATION DEPICTED HEREIN, PERTAINS TO A SECURE FACILITY DESIGNATED BY THE HOMELAND SECURITY ADMINISTRATION AS "CRITICAL INFRASTRUCTURE" AND MAY NOT BE SHARED WITH ANY PERSONS OR ENTITIES OTHER THAN AUTHORITIES HAVING JURISDICTION WTHOUT WRITTEN CONSENT OF THE OWNER, ANY PERSON OR EN11TY IN POSSESSION OF THIS DOCUMENT SHALL SAFEGUARD IT, AND SHALL DESTROY IT WHEN IT IS NO LONGER IN USE FOR THE PURPOSE FOR WHICH IT WAS PROVIDED. —1 LL 0 0 z Z) F- 0 U) z 0 F- U- -j U) z z Z) < U) uj 0 < (.)0 z LLI 0 F- U) z)- ::) C) < x < _10 < < 0 CN 11 R E V I S 1 0 N S I IREV #1 DATE I REVISIONS MADE 11 DRAWING SCALE JOB NUMBER AS NOTED 64-84-1501 ELECTRICAL 360� N D ING 0 1 1 s zcgf y SHEET NUMBER INITIAL SUBMITTAL DATE E6.1 4/12/17 I ELECTRICAL SCALE: NONE WELD (TYP) ,,-TRANSFORMER 1/2"X4" SQ. VIBRATION ISOLATION PAD 1"Xl"Xl/4" ANGLE 2"X2"Xl/2" ANGLE � \- UNISTRUCT FRAMING NOTE MOUNT TRANSFORMER 8 FT. ABOVE FINSHED FLOOR USE CHANNEL TO BEAM CLAMP, 'KINDORF' E760-2, 3 OR EQUIV. GROUNDING --� 75kVA TRANSFORMER MOUNTING 2 E6.2) SCALE: NONE 500kCM-1 1/2"C TO A.T.S. AND GROUNDING ELECTRODES D E '13' 1/0-1"C TO LIGHTNING PROTECTION SYSTEM b 0 0 e 6 0 o 0 6 6 & e T POWER RM B #3/0-1"C #3/0-1 "C GROUND BUS SWBD #3/0-1 "C MSBB UPS B 500kCM-1 1/2" C BATTERY RM B DC GROUND BUS 0 0 0 0 0 0 0 0 * 500kCM-1 1/2"C BATTERY RACKS #3/0-1" C, TYPICAL Tl I I T21 I T3 GROUNDING SYSTEM DIAGRAM SCALE: NONE WALL MOUNTING BRACKET 0 0 * * 0 0 0 0 * 0 * TELECOM. RM. GROUND BUS 'B' 1/4" 111MMW-111follk COMPRESSION LUG — BOLT TO BUSBAR TO BLDG. ELECT. GND. -TO CABLE TRAY ) TO EACH EQUIPMENT RACK �`TOEACH PDU GROUNDING CONDUCTOR SIZE AS NOTED MAIN GROUND BAR DETAIL_ #2-1 "C CABLE TRAY TELECOM. RM SCALE: NONE RACK 1 RACK 2 RACK 3 RACK 4 TELECOM. TELECOM. TELECOM, TELECOM. T4AE, INC. - ARCHITECTURE & PLANNIN7 AA26001228 & AR92559 (954)839-4258 233 EAST ACRE DR., PLANTA _IEN, F� �l J7 STRUCTURAL AND MECHANICAL ENGINEERING ,Wltg BASE 4 INTERNATIONAL, INC. 9858 GLADES ROAD #237 BOCA RATON, FLORIDA 33434 BASE4 1 720 72BASE4 ..w.base4mm ELECTRICAL ENGINEERING RIDCE, INC. 5707 S. DIXIE HWY, 48 WEST PALM BEACH, FLORIDA 334D5 PHONE 561436 9198 CERT. OF AUTH.: #8800 T4AL, INC., AND ALL PROFESSIONALS OF RECORD, HEREBY RESERVE THEIR INDIVIDUAL AND COLLECTIVE COMMON LAW COPYRIGHT AND ALL OTHER PROPERTY RIGHTS IN THESE DESIGNS, SPECIFICATIONS, PLANS AND IDEAS. THIS DOCUMENT 15 NOT TO BE REPRODUCED WITHOUT FIRST OBTAINING THE WRITTEN PERMISSION OF T4AF, INC., AND THE PROFESSIONALS OF RECORD. ANY DISCREPANCY BETWEEN THIS DOCUMENT AND ACTUAL CONDITIONS SHALL BE REPORTED TO T4AE, INC. P R 0 F E S S 1 0 N A F 0 F R E C 0 R D S E A L _\GEN&, N N, o. 75256 S Sl All TATE OF ............ /I/NALe\\ 1111110\ DEVEREN PETERKIN, PROFESSIONAL ENGINEER NO. 75256 THIS IS A CONFIDENTIAL DOCUMENT THIS DOCUMENT, AND THE INFORMATION DEPICTED HEREIN, PERTAINS TO A SECURE FACILITY DESIGNATED BY THE HOMELAND SECURITY ADMINISTRATION AS "CRITICAL INFRASTRUCTURE" AND MAY NOT BE SHARED WITH ANY PERSONS OR ENTITIES OTHER THAN AUTHORITIES HAVING JURISDICTION WITHOUT WRITTEN CONSENT OF THE OWNER. ANY PERSON OR ENTITY IN POSSESSION OF THIS DOCUMENT SHALL SAFEGUARD IT, AND SHALL DESTROY IT WHEN IT IS NO LONGER IN USE FOR THE PURPOSE FOR WHICH IT WAS PROVIDED. -j u- 0 z F- 0 U) z 0 Lij F- c.) < u- U) z z - Z) 0 < (j) ui < 0 w z F- U) C) < Q� < 0 < U) Z) < 0 II R E V I S 1 0 N S IREV #1 DATE I REVISIONS MADE DRAWNG SCALE T: JOB NUMBER AS NOTED 1 34-84-1501 ELECTRICAL GROUNDING E B' SHEET NUMBE�n 711�AYIIUBMITTTAL DATE _ Fq E6.2 '7 4/12/17 )) A" SIDE CARRIER SERVICE FROM WEST PROPERTY LINE CARRIER DEMARCATION 1) A Il TELECOM RISER SCALE: NONE CROSS CONNECT )) Al )) TO IN IVIDUAL CUSTOMER TO INDIVIDUAL CUSTOMER CABINETS CABINETS III I I I VMRB ROOM MMRA ROOM- F_ F-111-1 ;z CROSS CONNECT 1� A2" V) L __1 L J - 17 1 F _L� - -1 CROSS I CONNECTI )) 132" 1 L - - -1 PQ� B ROM f I I . . . ...... I I L 7 F -1 _L CROSS I CONNECTI I )� Bl L - __1 CARRIER DEMARCATION 1) B L TELECOM RISER DIAGRAM NOTE: RISER DIAGRAM IS SCHEMATIC IN NATURE. ACTUAL LOCATIONS OF ROOMS) EQUIPMENT AND LINES SHALL BE ACCORDING TO PLANS. SOME LINES RUN ABOVE BUILDING ROOF, SOME RUN BELOW RAISED FLOOR AND SOME RUN ABOVE DROPPED CEILING OR IN CABLE TRAYS - COORDINATE ROUTING OF LINES WITH OWNER PRIOR TO CONSTRUCTION. COORDINATE CONTAINMENT AND FIRE -RATING OF CABLE RUNS WITH OWNER PRIOR TO CONSTRUCTION. )) B" SIDE CARRIER SERVICE FROM EAST PROPERTY LINE )Wcm T4AE, INC. - ARCHITECTURE & PLANNING 1AA26001228 & AR92559 (954)830,4258 233 EAST ACRE DR., PLANTATION, FIL 33317 STRUCTURAL AND MECHANICAL ENCINEE ZE 4 INTERNATIONAL, INC. 9858 GLADES ROAD, *237 BASE4CARATON FLORIDA33434 19.0720.72BASE� ..bas".� ELECTRICAL ENGINEERING RDCE, INC. 5707 S DIXJE HWY, 48 WEST PALM BEACH, FLORIDA 33Q5 PHONE 56143091% CERT.OFALrrH. #8800 T4AE, INC., AND ALL PROFESSIONALS OF RECORD, HEREBY RESERVE THEIR INDIVIDUAL AND COLLECTIVE COMMON LAW COPYRIGHT AND ALL OTHER PROPERTY RIGHTS IN THESE DESIGNS, SPECIFICATIONS, PLANS AND IDEAS. THIS DOCUMENT IS NOT TO BE REPRODUCED WITHOUT FIRST OBTAINING THE WRITTEN PERMISSION OF T4AE, INC., AND THE PROFESSIONALS OF RECORD. ANY DISCREPANCY BETWEEN THIS DOCUMENT AND ACTUAL COND111ONS SHALL BE REPORTED TO T4AE, INC. P R 0 F E S S 1 0 N A L 0 F R E C 0 R D S E A L pe;ri ENS, NO. 75m STATE OF Nk. ........... - t�dz, DEVEREN PETERKIN, PROFESSIONAL ENGINEER NO. 75256 THIS IS A CONFIDENTIAL DOCUMENT THIS DOCUMENT, AND THE INFORMATION DEPICTED HEREIN, PERTAINS TO A SECURE FACILITY DESIGNATED BY THE HOMELAND SECURITY ADMINISTRATION AS "CRITICAL INFRASTRUCTURE" AND MAY NOT BE SHARED WITH ANY PERSONS OR ENTITIES OTHER THAN AUTHORITIES HAVING JURISDICTION WITHOUT WRITTEN CONSENT OF THE OWNER. ANY PERSON OR ENTITY IN POSSESSION OF THIS DOCUMENT SHALL SAFEGUARD IT, AND SHALL DESTROY IT WHEN IT IS NO LONGER IN USE FOR THE PURPOSE FOR WHICI _j LL 0 z D F_ 0 z F_ LU 0 F_ 0 < D C) w u- _j < F_ U) z < w z =) r) < V) z (-)0 X ui S� 0 U) D 0 < X < Lu < 0) D < 0 Cl) m (3) 04 rq II R E V I S 1 0 N S I IREV #1 DATE I REVISIONS MADE 11 DRAWING SCALE AS NOTED 64-84-1501 TELECOM RISER Contractor CnPV SHEET NUMBER 1_'RIT IAL SUBMITTAL DATE E 6.3 1 4/12/17 GENERATOR 'A' (D Q FUEL PUMP A2Fl/A2Pl GENERATOR '13' F 15,000 GAL., /—,\ FUEL TANK A \-L/ 15,000 GAL., , cl-� FUEL TANK B 1 GENERAT SCALE: 1"=40'—O" FUEL TANK B2 Lr 250 GAL. DAY TANK (D ON GEN/ "B" 2 HOURS STORAGE LOCATION IN GEN ROOM TBD LEAK DETECTION SEPTIC TANK AND LIFT STN FUEL PUMPS(D B21`1 /B2Pl I F1 R SITE PLAN GENERAL NOTES: CONTROLLER CONDUIT ENTRY CONDUIT 1. GENERATOR SYSTEMS SHALL MEET ISO 8528 AREA ON LEFT LOCATION s (4"sq) 135.9" FUEL STUB STANDARDS. SIDE ONLY WHEN UP AREA 13.2" 2. GENERATOR PERFORMANCE IS BASED ON BREAKERS OR LOAD BUS PRESENT KOLHER MODEL 280OREOZDB OR SIMILAR PRIME RATED UNIT WITH A CONTINUOUS DERATED PRIME CAFACITY OF 707. LOAD AT 99.2 le, F CONDUIT ENTRY L. L 13 DRY BULB TEMPERATURE AND SHALL BE FOR LOAD CENTER - - - . 1 RATED TO MEET A MINIMUM FACILITY LOAD (3"xl 3.8")17� SUGGESTED OF 1.77m�A. BLOCK SUGGESTED 24V 3. AN ALTERNATIVE UNIT MAY BE THE KOHLER HEATER BATTERY MODEL KDlOOO (KD175 WITH KD62Vl2 MOTOR) CONDUIT CHARGER OR SIMILAR UNIT THAT HAS A CONTINUOUS LOCATION CONDUIT NAME PLACARD RATING OR EQUIVALENT FACTORY (3"sq) LOCATION CERTIFICATION TO MEET 100% OF THE LOAD (4"sq) CONTINUOUSLY FOR AN UNLIMITED RUNTIME WITHOUT DERATING FROM THE STATED PRIME OR CONTINUOUS CAPACITY PLACARD AT 12.2' 88.3" 99.2 de DRY BULB TEMPERATURE AND SHALL EV- RATED TO MEET A MINIMUM FACILITY LOAD OF 1.77mVA. CONDUIT ENTRY AREA FOR 143.4" GENERATOR LOAD LEADS (BOTTOM ENTRY) KEY NOTES: (D SEE EQUIPOENT LOCATIONS IN FUEL DIAGRAM EETAIL BELOW. SEE PUMP LOCATIONS IN FUEL DIAGRAM JETAIL BELOW. SLOPES OF BERM AND RELATIVE POSITIONS PF GENERATOR ROOMS AND TANKS AS SHOWN IS DIAGRAM�,ATIC AND NOT REPRESENTATIVE OF EACTU SEE SITE PLAN AND FLOOR PLANS FOR LA'Y UNDERGROUND (D FUELTANKA1 15,000 GALLONS STORAGE GENERATOR FUEL DIAGRAM SCALE: NONE VALVE TPI L VACUUM BF CONTF (BEYO 126.0" Q TRANSFER PUMP TPlAB (CKTS L2A-31,33,35; 1-213-31,33,35) - REVERSIBLE TRANSFER PUMP FOR OWNER CONVENIENCE, MANUALLY OPERATED BY SWITCH, WITH AUTO SHUTF OFF IF PUMP RUNS DRY, NORMAL STATE CLOSED/OFF, (NOT USED FOR NORMAL STATE EQUALIZATION OF TANKS) COVERED PUMP HOUSING ELECTED BY OWNER VALVE TP1 R ABOVE GROUND VENT PIPE WITH CAP . ..... 3/4" MALE JIC MOUNTING HOLES) 264.4" NOTE THAT TRANSFER PUMP AND ALL ASSOCIATED ELEMENTS AND ENCLOSURE ARE TO BE INSTALLED AT OWNER'S DISCRETION. IF PUMP IS ELIMINATED FROM THE PROJECT, THE ASSOCIATED CIRCUITS MAY BECOME SPARES IF NOT OTHER ELECTRICAL ELEMENTS ARE ASSOCIATED WITH THEM (CKT Ll B- 37,39,41) A VACUUM BREAKER A /,/—PUMP B2P1 (CKT Ll B- 37,39,41) \— LEVEL SENSOR FUB1 L:j \—LEVEL SENSOR FLB2 I '�LEAK DET. LDB1 LEAK DET LDB2 FUEL TANK B2 250 GAL, DAY TANK UNDERGROUND (D ON GEN/ "B" FUEL TANK Bl 2 HOURS STORAGE 15,000 GALLONS STORAGE LOCATION IN GEN ROOM TBD GENERATOR ROOM B` 151.0" 130.0" 2.0" 0 — REMOVABLEFILL NECK & CA, 0 A ni A YnD 114.3" 126.0" GENERAL NOTES: 1. INFORMATION SHOWN IS DIAGRAMMATIC IN NATURE. FUEL TANK VENDOR TO PROVIDE FULL SHOP DRAWINGS AND CUTSHEETS FOR ALL EQUIPMENT AND VALVES, AND CONFIRM TANK AND PUMP SIZES AND TYPES, AND VALVING AND LINE CONFIGURATIONS WITH OWNER PRIOR TO SUBMITTING FOR TRADE PERMIT. 2. VENDOR SHALL CONFIRM ALL OWNER REQUIREMENTS PRIOR TO PREPARATION OF SHOP DRAWINGS, INCLUDING GENERATOR SIZE AND TYPE, TANK SIZES AND TYPES, ACCESSORIES SUCH AS VERMIN SCREENS, VENTED CAPS, LOCKING MECHANISMS, VALVE DETECTOR/PUMP AND SENSOR TYPES. OWNER REQUIREMENTS EXCEED CODE REQUIRMENTS. 3. DAY TANKS MAY BE BELLY TANKS INTEGRAL TO GENERATOR, OR STAND ALONE TANKS IN GENERATOR ROOM — TO BE DETERMINED ALL EQUIPMENT AND VALVES AND CONFIRM BY SUPPLIER. LEAK DETECT16N SENSOR FOR DAY TANKS TO BE PLACED ACCORDINGLY. T4AE, INC. - ARCHITECTURE & PLANNIM AA26001228 & AR92559 (954)839-425� 233 EAST ACRE DR., PLANTATION, FL 333 7 STRUCTURAL AND MECHANICAL ENGINEER BASE 4 INTERNATIONAL, INC. MS GLADES ROAD, #237 BASE4BOCA RATON, FLORIDA 33434 1120.728ASIE4 w�.bas".� RIDCE, INC. 5707 S. DIME HWY, #8 WEST PALM BEACH, FLORIDA 33405 PHONE: 561 430 91M CERIE OF AUTH.i #BWD T4AE, INC,, AND ALL PROFESSIONALS OF RECORD, HEREBY RESERVE THEIR INDIVIDUAL AND COLLECTIVE COMMON LAW COPYRIGHT AND ALL OTHER PROPERT' RIGHTS IN THESE DESIGNS, SPECIFICATIONS, PLANS Al' IDEAS. THIS DOCUMENT IS NOT TO BE REPRODUCE1 WITHOUT FIRST OBTAINING THE WRITTEN PERMISSION ( T4AE, INC., AND THE PROFESSIONALS OF RECORD, 4 DISCREPANCY BETWEEN THIS DOCUMENT AND ACTUA CONDITIONS SHALL BE REPORTED TO T4AE, INC. P R 0 F E S S 1 0 N A L 0 F R E C 0 R D S E A L �%xiiIIIIIIIII, / ps EN No. STATE OF 1111111110 ETERIKIN, PROFESSIONAL ENGINEER NO. 752! THIS IS A CONFIDENTIAL DOCUMENT THIS DOCUMENT, AND THE INFORMATION DEPICTED HEREIN, PERTAINS TO A SECURE FACILITY DESIGNATED BY THE HOMELAND SECURITY ADMINISTRATION AS "CRITICAL INFRASTRUCTURE" AND MAY NOT BE SHARED WITH ANY PERSONS OR ENT171ES OTHER THAN AUTHORITIES HAVING JURISDICTION MATHOUT WRITTEN CONSENT OF THE OWNER. ANY PERSON OR ENTITY IN POSSESSION OF THIS DOCUMENT SHALL SAFEGUARD IT, AND SHALL DESTROY IT WHEN IT IS NO LONGER IN USE FO THE PURPOSE FOR WHICH IT WAS PROVIDED, 0 F- U) z 0 w 0 z < w V) z 0 U) F- < Lu H- F- Q DRAWING SCALE T7 JOB NUMBER AS NOTED 1 34-84-1501 GENERATOR DETAILS Co tmctor SHEET NUMBER SUBMITTAL DATE E6.4 4/12/17 NONCRITICAL POWER I - ___� Q CRITICAL POWER (D(D@ 2500A INSULATED BUS DUCT 3000A INSULATED 277/48OV, 30, 4W BUS DUCT 277/480V 30, 4W <EXTERIOR) (FPL VAULT 'A') <GENERATOR RM 'A') (POWER RM 'A') 3000A INSULATED SECTION I SECTION 2 SECTION 3 SECTION 4 BUS DUCT OOOA 2500A 2000A IOTA 277/48OV, 30, 4W @ NOMA 3R /a NON- CTION 2500A UPS PNL 3 200 SPARE 4#3, NON -UPS PNL 'NHA' I I(S R #815 UPS 'A' W/PUL 'S 1 I/4'C UPS 'A' MAINT. BYPASS MNIG NCOMIN MAIN LUGS 3 400 FPL TRANSFORMER 'A' L-0 400 UPS 'A' 2500kVA-277/48OV-30 48OV, 30,3W IN NON -UPS XFMR 'TIA' 480V, 30,3W OUT PNL 'GA' 200kAIC 120/208V, 3 2500 3 2000 2500A 3PHIAW A.T.S. 'A' 2500 2000 DIESEL GENSET 'A' 3000A IOOA 277/48OV, 3 110 277/48OV, BKR MCD 3-POUE SWITCHBOARD 200 3-POLE 200kAIC SOLID NEU. NSBA' SOLID NEU. lOkAIC 3000A 277/48OV, 30,4Wj 4ON-UPS XFMR 'T2A' 3.175mVA 200kAIC 2 SERVICE 3000A SUPPLY ENTRANCE RATED 3 110 WITH GND FAULT PROTECTION #3/0 CU GEC TYPICkL TELECOM GND BUS BLD'3 STEEIC FPL PRIMARY CABLE -9, WP " @ 2-3/4" X 10' Cwv�� LT�G PROT. SYSTEM ROD 6 FT APART CONIC. ENCASED. ELECTRODE GROUNDING ELECTRODES PER NEC 250.52 7 3#2, 3#2, T 14 FEEDERS TO 14 FEEDERS TO #813 #8G 12 FEEDERS TO EQUIP RM 1 EQUIP RMS 2 - 6 1 - 1/4'C 1 - 1/4'C & PWR RM A XFMJR 74A, 3 2� J & MMRA g 200 j 10 FEEDERS TO 3 6 100 CRACS & CU'S 100 3 loo XFMR 'T2A, 3 200 J EQUIP RN I EQUIP RM2 2 6 CRACS & CU'S 3 loo XFMR 'TlA' 200 100 200 4BOV-120/208V, 48OV-120/208V, 4BOV-120/208V, 3PHAW 65kAIC 3PHAW lOkAIC 3PHAW (POWER RM 'A') fr ir F_ 65kAIC 25kVA lOkAl 75kVA 4#3/0, 65kAIC 75kVA IOkAIC Z=2% Z=2% #66 Z=2y. @ I - ec II 4#3, - 4#3/01 1 #813 #615 4#3, 3#3, @ I 1/4-C I - 2'C #8G #813 3#8,- 1 1 1/4'C 1 1/4'1 #106 PNL 'L4A' 3#3, 3#3, -J #8G #815 PNL 'SCA' 11C 120/208V, I 1/4'C I 1/4'C 120/208V, 3PHAW 3PH,4W PDUI 'A' PNL 'LIA' PDU2 'A' PNL 12A' PNL 13A' PNL 'HI PNL 'H2A' 43OkVA 120/208V, 430kVA 120/208V, 120/208V, 277/480 IDOA 200A 48OV, 30,3W IN 3PHAW 48OV, 30,3W IN 3PH,4W 3PH,4W 3PH,4W MUO 277/48OV, MUD 120/208V, 30,4W OUT 120/208V, 30,4W OUT 3PH,4W IOOkAIC 1200A 1200A -HE 100A 500A IOkAIC 500A IOkAIC 1200A MOB lOOkAIC 1200A MCB MLO MCB MCB 65kAIC 65kAIC 651RAIC 65kAIC 65kAIC Tin TPI 4#3, #813 1 - 1/4'C 3NL 'DRA' PNL 'ADA' PNL 'SC2A' 20/208v, 120/208V, 120/208V, 3PHAW 3PH,4W 3PH,4W 200A 100A 200A MLO MILO MLO IOkAIC lOkAIC IOkAIC .R. AREA) (ADMIN AREA) (PDP-A AREA) SER - 'A' SIDE (MAINT. BLDG) PNL 'NH' PNL 'NL' 277/48OV, 120/208v, 3PH,4W 3PHAW 400A 200A MCB MOB 3#31 l4kAIC #8G IOkAIC 4#3/0 #66 1 - 2'C @ I #6CU G CWPA____� 3/4' X 10' CW ROD Z=2% PNL 'NLA' 120/208V, IPH,3W 30A MCD lOkAIC 3#8, #813 I - 11C FENCE 4�' 3/4" X 10' CW ROD I #6CU G 74k�_ T4AE, INC. - ARCHITECTURE & PLANNING AA26001228 & AR92559 (954)839-4258 ,233 EAST ACRE DR., PLANTATION, FL 33317 STRUCTURAL ANN MECHANICAL ENGINEERING I oil$ BASE 4 W4 INTERNATIONAL, INC. 98W GLADES ROADT 0237 CA RATON, FLORIDA 33434 BASE4 I ..,base4.mm ELECTRICAL ENGINEERING RDCE, INC. 5707 S. DIXIE HVVY, #8 WEST PALM BEACH FLORIDA 33405 PHONE Wl 436 9198 CERT. OF ALI #8800 T4AE, INC., AND ALL PROFESSIONALS OF RECORD, HEREBY RESERVE THEIR INDIVIDUAL AND COLLECTIVE COMMON LAW COPYRIGHT AND ALL OTHER PROPERTY RIGHTS IN THESE DESIGNS, SPECIFICATIONS, PLANS AND IDEAS. THIS DOCUMENT IS NOT TO BE REPRODUCED WITHOUT FIRST OBTAINING THE WRITTEN PERMISSION OF T4AE, INC,, AND THE PROFESSIONALS OF RECORD. ANY DISCREPANCY BETWEEN THIS DOCUMENT AND ACTUAL CONDITIONS SHALL BE REPORTED TO T4AE, INC. P R 0 F E S SI 0 A A L 0 F R E C 0 R D S E A L III . I111,F pe loc No. 75m STATE OF .411 # ORMN ........ *** IONAL NN:� IIIIIII11%0% I DEVEREN PETERKIN, PROFESSIONAL ENGINEER NO, 75256 THIS IS A CONFIDENTIAL DOCUMENT THIS DOCUMENT, AND THE INFORMATION DEPICTED HEREIN, PERTAINS TO A SECURE FACILITY DESIGNATED BY THE HOMELAND SECURITY ADMINISTRATION AS "CRITICAL INFRASTRUCTURE" AND MAY NOT BE SHARED WITH ANY PERSONS OR ENTITIES OTHER THAN AUTHORITIES HAVING JURISDICTION WITHOUT WRITTEN CONSENT OF THE OWNER. ANY PERSON OR ENTITY IN POSSESSION OF THIS DOCUMENT SHALL SAFEGUARD IT, AND SHALL DESTROY IT WHEN IT IS NO LON ER IN USE FOR THE PURPOSE FOR WHICH IT WAS PROVIDED. LL 0 z F_ 0 z 0 < D w U- _j < 0 z < w z =) 0 < U) z 00 LLI F_ U) 0 M < O� < _10 . w Lu F_ F- 1: co I.- 0 cn a) 0) CNI CN E V I S 1 0 IN 5 :: I IRLV #I DATE I REVISIONS MADE DRAWING SCALE JOB NUMBER AS NOTED 34-84-1501 ELECTRICAL Ft�l S E R 'A' SHEET NUMBER 'TJVIAL SUBMITTAL DATE E6.5 1 4/12/17 NONCRITI'AL POWER CRITTCAL POWER 2500A INSULATED BUS DUCT 3000A INSULATED 277/48OV, 30, 4W BUS DUCT 277/48OV, 30, 4W (EXTERIOR) (FPL VAULT 'B') (GENERATOR RM IBI) (POWER RM 'B' 3000A INSULATED SECTION I SECTION 2 SECTION 3 SECTION 4 BUS DUCT @ 3000A 2500A 2000A IOTA 277/48OV, 30, 4W NEMA 3R NON- --- UPS PINE 3 - 200 SPARE NON -UPS PNL 'NHB' 4#3, UPS IBI 1 1/2' RGS #815 I I/4'C UPS 'B' MAINT. BYPASS 400 W/PULLSTRING NCOMING MAIN LU(S 3 400 AER 'B FPL TRANSFORMER 'B' -0 NON -UPS XFMR 'TlB' 2500kVA-277/48OV-30 8 OV_ 156 1 T.U.V. PNL 'GB' /0--- li 2500 2000 120/208V, _46 3 3 3PH,4W A.T.S. 7 2500 M000 110 MTR DIESEL GENSET 7 3000A IOOA 277/48OV, 3 -FO-0- 277/48OV, BKR NICE 3-POLE SWITCHBOARD El 3-POLE 2OOkAIC SOLID NEU. IMSBBI 4ON-UPS XFMR 'T2B' SOLID NEU. IOkAIC 3000A 277/48OV, 30,4W, 3.175mVA 200kAIC 2OOkAIC SERVICE 3000A SUPPLY 110 ENTRANCE RATED 3 WITH GND FAULT 200 PROTEC ION E� #3/0 CU GEC TYPICAL TELEC M GIND BUS BLDG STEE FPL PRIMARY CABLE CWP !TNG 2-3/4' X 1 , CW PROT SYSTEM ROD 6 FT A RT CONIC. ENCASED. ELECTRODI[ GROUNDING ELECTRODES PER NEC 250.52 Qs___ TO TO 'MSBA' ' SBB' @ D.P.D.T. MANUAL XlER 3 NF J SWITCH 400 4P,4W 400A 65kAIC T (MEZZANINE OFC) 12 FEEDERS TO EQUIP RM I PDU1 'B' PNL 'LlB' 430kVA 120/208V, 48OV, 30,3W IN 3PH,4W 120/208V, 30,4W OUT 1200A IOOkAIC 1200A MCD 65kAIC (POWER RM 'B') 4#3, #813 1 - I/4'C PINE 'DRB' PNI_ 'ADB' 120/208V, 120/208V, 3PH,4W 3PH,4W 200A lOOA MLO NED lOkAIC lOkAIC (D.R AREA) (ADMIN AREA) ELECTRICAL RISER 'B' SIDE SCALE: NONE lam QD S,- 14 FEEDERS TO EQUIP RM I 10 FEEDERS TO & PWR RM B EQUIP RM2 2 6 CRACS & CU'S Pr 3#3, #8G 1 1/4'C PDU2 'B' j[PNL 12B: PNl_ 'L3B' PNL 'HlB' 43OkVA 20/208V 120/208V, 277/48OV, 48OV, 30,3W IN 3pH,4W 3PH,4W 31 120/208V, 30AW OUT 1200A lom 500A IOOkAIC MI MLO NICE 1200A 65kAIC 65kAIC 65kAIC 14 FEEDERS TO EQUIP RMS 2 - 6 3 �LO j 60 XFMR 'T4B, 3 90 J 100 & MMRB CRACS & CU'S 48OV-120/208V, 65kAIC 3PH,4W lOkAI 25kVA Z=2% 4#3, A#8G @ I I/4'C 3#8, __j #1013 PNL 1413' I'D 120/208v, 3PHAW PNL 'H2B' IOOA 277/48OV, MLO 3PH,4W IOkAIC 500A MCB 65kAIC 3 too too F_ 7 I F- UPS 1131 480V, 30,3W IN 48OV, 30,3W OUT 200kAIC 2500A - 3#21 3#21 #8G #815 I - I/4'C - I - 1/4'C XFMR 'Till, 3200 J 200 3 1 too XFMR 'T2B, 3 ZU 200 480V-120/208V, 4BOV-120/208V, 3PH,4W lOkAIC 65 1 3PH,4V IOkAlI 75kVA 4#3/0, 75kVA Z=2% r #6G Z=2% T I - 2'C 3#3,-J #813 I I/4'C (MAINT. BLDG) PNL 'SC23' PNL 'NH' PNL 'NL' 120/208V, 277/48OV, 120/208V, 3PH,4W 3PH,4W 3PH,4W 200A 400A 200A MLO MCB MCB 3#3, lOkAIC l4kAIC #8G IOkAIC I I/4'C (POP-B AREA) XFMR T3' 480V-120/208V, 4#3/0 3PH,4W #615 75kVA I - 2'C Z=2% @ I #6CU IS cwpj4�'N 3/4" X 10' CW ROD m I 1/4'C PNL 'NLA' 120/208VI IPH,3W 30A MCB lOkAIC 3#81 #813 I - I'D FENCE .14 3/4" X 10' CW ROD 101 #613 4#3, 1 - BID #813 t I I/4'C PNL 'SCB' 120/208V, 3PH,4W 200A MILO IOkAIC #6CU G T4AE, INC. -ARCHITECTURE & PLANNING AA26001228 & AR92559 (954)83T4258 233 EAST ACRE DR., PLANTATION, F 333171 STRUCTURAL AND MECHANICAL ENGINFERIN3 4 *,Cg BASE 4 INTERNATIONAL, INC. 91351 GLAIDES ROAD, 11237 BASE4BOCA RATON, FLORIDA 33434 1.720 72BASE4 W�base4wm ELECTRICAL ENGINEERING RDCE, INC. 6707 S. DIXIE HWY, #8 WEST PALM BEACH, FLORIDA 33�5 PHONE: W 438 9198 DEFT. OF ALI 4WW T4AE, INC., AND ALL PROFESSIONALS OF RECORD, HERESY RESERVE THEIR INDIVIDUAL AND COLLECTIVE COMMON LAW COPYRIGHT AND ALL OTHER PROPERTY RIGHTS IN THESE LESIONS, SPECIFICAflONS, PLANS AND IDEAS. THIS DOCUMENT IS NOT TO BE REPRODUCED WITHOUT FIRST OBTAINING THE WRITTEN PERMISSION OF T4AE, INC., AND THE PROFESSIONALS OF RECORD. ANY DISCREPANCY BETIENB THIS DOCUMENT AND ACTUAL CONDTIONS SH E REPORTED TO T4AE, INC. P R 0 F E S S 1 0 N A L 0 F R E C 0 R D S E A L pje No. 75M STATS OF A401110� ONAl. DEVEREN PETERKIN, PROFESSIONAL ENGINEER NO. 75256 THIS IS A CONFIDENTIAL DOCUMENT THIS DOCUMENT, AND THE INFORMATION DEPICTED HEREIN, PERTAINS TO A SECURE FACILITY DESIGNATED BY THE HOMELAND SECURITY ADMINISTRATION AS "CRITICAL INFRASTRUCTURE" AND MAY NOT BE SHARED WITH ANY PERSONS OR ENTITIES OTHER THAN AUTHORITIES HAVING JURISDICT10N WITHOUT WRITTEN CONSENT OF THE OWNER. ANY PERSON OR ENTITY IN POSSESSION OF THI S DOCUMENT SHALL SAFEGUARD IT, AND BHA LL DESTROY IT WHEN IT IS NO LONGER IN USE FOR THE PURPOSE FOR WHICH IT WAS PROVIDED. -1 LL 0 z D F_ U) 0 0 z 0 W F_ 5c) < ::) Lij u- _j < r F� 0 z z =) < z w 0 < ()0 0 F_ U) 9 < _j 0 . w LL] F_ < Z) < 0 W 0) 04 04 EDRTR SHEEL-TEER, II R E V I S 1 0 N S IREV #1 DATE I REVISIONS MADE DRAWING SCALE JOB NUMBER AS NOTED 34-84-1501 ELECTRICAL RISER '[3' 0,6� R AM SHEET NUMBER CfL,,jNJ7A?WAITTAL DATE E6.6 7 4/12/17 3 2.27MVA, 48OV,30,4W DIESEL GENERATOR 3000A, 65kAIC OUTPUT BREAKER 2 2500A 2000A 3P UP 4) <4 FPL XFMR VAULT 'A' SERVICE ENTRANCE RATED ATS, 3000A, 48OV,30,4W WITH BYPASS ISOLATION GROUND FAULT PROTECTIVE RELAY STATIC SWITCH 2500A 3P OUTPUT FUSE L __o 11 v RECTIFIER INVERTER INPUT FILTER UPS A (1.6MVA) BATTERY CABINET PDUlA PDU2A 480V: 480V: 208Y/120 208Y/120 43OkVA 43OkVA K=13 K-13 4J Y6, Y6 1200A 1200A 3P 3P 7 7 F_ PANELI ITVSS H PANEL PANEL LlA I _2A _3A ELECTRICAL ONE LINE 'A' SIDE SCALE: NONE 3000A 3P 480V- 480V 30,3W 5 05C 03F PANEL HlA BOND TEM NFUT[SYS� �Al_ IND G OUND CONDUCTOR TOG�THER AT ATS MAIN BREAKER. JER MONITORING C D Eo E P D I ITAL METER) MAINTENANCE BYPASS CABINET �20 0 c 3P 200OA3 N.O. )3P 480v- N.C. 480V 30,3W 1 j KIRK KEY INTER -LOCK I L, ,, — — — 2000A 3P N. C. 5 5c 0 3F PANEL 112A 3/60- 40RK5/1 18 3/100- 9ORK5/1 18 PANEL L4A Illily-il 208YV120 25kVA 3/100- 10ORK5 3/200- 20ORK5/1 MAIN SWITCHBOARD MSBA 3000A, 480Y/277V,30,4W, 65kAIC 12 5 110A 3P IN Tl A 48OV: 208Y/120 75kVA Lol 3/100- 100RK5/1 10 �l 1 3/200- 20ORK5/1 110A 3P T2A 480V: 208Y/120 75kVA PANEL oic DRA PANEL 0 3F SCA PANEL PANEL ADA PANEL SC2A GENERAL NOTE: 1. ALL OVER CURRENT DEVICES TO BE SIZED PER EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. 2. ALL SWITCHBOARDS AND PANELS SHALL BE FULLY RATED EQUIPMENT, NOT SERIES RATED AND SHALL BE MANUFACTURED BY SIEMENS OR SQUARE V. 7 8 400A 200A 3P 3P SPARE 14 400A NON -FUSED 4P, 4W, MANUAL XFR SWITCH (SWITCHED NEUTRAL) PANEL INH (015 03F PANEL NL 03C 02F PANEL NLA T3 48OV: 208Y/120 75kVA I fem 1-bi -.rl FEEDER SCHEDULE FEEDER SIZE MARK PARALLEL SET No OF WIRES IN EACH RUN AWG 13ROUND WIRE CONDUIT SIZE (INCH) CONDUIT T P TYPE 1 BUS DUCT 3000A NEMA13R 2 BUS DUCT 3000A I NEMAl 3 BUS DUCT 3000A 2500A NEMA 1 NEMA 1 4 BUS DUCT 5 BUS DUCT - 2500A - - NEMA 1 6 4 5 350kCM 3/0 3 EMT 7 4 5 350kCM 3/0 3 EMT 8 1 4 3 8 1 1/4 EMT 9 1 3 2 8 1 1/4 EMT 10 1 — 3 3 8 1 1/4 EMT 11 1 4 3/0 6 2 EMT 12 1 4 3/0 6 2 EMT 13 1 4 3 8 1 1/4 EMT 14 1 4 500kCM 3 3 RGS 15 1 3 4 8 1 EMT 16 1 4 1/0 6 2 EMT 17 -1 1 3 8 8 1 EMT 18 1 4 1 3 8 1 1/4 EMT T4AE, INC,, ARCHITECTURE& PLANNING AA26001228 & AR92559 (954)839-4258 233 EAST ACRE DR., PLANTATION, FL 33317 STRUCTURAL AND MECHANICAL ENGINEERING W4oft BASE4 INTERNATIONAL, INC. 9858 GLADES ROAD, #237 BASE4CA RATON, FLORIDA 3W4 100720.72131 ELECTRICAL ENGINEERING f&RDCE, INC. 5707 S, DIYdE HWY, #8 WEST PALM BEACH, FLORIDA 3M5 PHONE: 661436 9198 ,i� CFRT. OF AUTH.: #8800 T4AE, INC., AND ALL PROFESSIONALS OF RECORD, HEREBY RESERVE THEIR INDIVIDUAL AND COLLECTIVE COVIVON LAW COPYRIGHT AND ALL OTHER PROPERTY RIGHTS IN THESE DESIGNS, SPECIFICATIONS, PLANS AND IDEAS THIS DOCUMENT IS NOT TO BE REPRODUCED WITHOUT FIRST OBTAINING THE WRITTEN PERMISSION OF T4AE, INC., AND THE PROFESSIONALS OF RECORD. ANY CONNUONS SHALL BE REPORTED TO T4AE, INC. DISCREPANCY BETWEEN THIS DOCUMENT AND ACTUAL P R 0 F F. S S 1 0 N A L 0 F R E C 0 R D S E A L ....... Nwo. VMTEOF "ZORI X .......... AL 1111100 DEVE 'ETERKIN, PROFESSIONAL ENGINEER THIS IS A CONFIDENTIAL DOCUMENT THIS DOCUMENT, AND THE INFORMATION DEPICTED HEREIN, PERTAINS TO A SECURE FACILITY DESIGNATED BY THE HOMELAND SECURITY ADMINISTRATION AS "CRITICAL INFRASTRUCTURE" AND MAY NOT BE SHARED WITH ANY PERSONS OR ENTITIES OTHER THAN AUTHORITIES HAVING JURISDICTION WITHOUT WRITTEN CONSENT OF THE OWNER. ANY PERSON OR ENTITY IN POSSESSION OF THIS DOCUMENT SHALL SAFEGUARD IT, AND SHALL DESTROY IT WHEN IT IS NO LONGER IN USE FOR THE PURPOSE FOR WHICH IT WAS PROVIDED, LL 0 0 z D F_ >_ 0 U) z I-_ 0 ::i LU F_ 5o < Z) ES 0 ui ILL _j < z z D 0 < U) ui 0 < (.)0 w z w 0 F U) �Iif 0 < w < 0 w F_ < F- 0 U) 0') 04 ORTIR SHEEUTEER R E V I S 1 0 IN S REV # DATE REVISIONS MADE — DRAWING SCALE JOB NUMBER — AS NOTED 34-84-1501 ELECTRICAL ONE LINE 'A' (��_G R A M SHEET NUKR"rft&1TlAL SUBMITTAL DATE "1'* 0 E 6.7 �q� -wr 4/12/17 FPL XFMR VAULT 'B' SERVICE ENTRANCE RATED ATS, 3000A, 480V,30,4W BOND SYSTEM WITH BYPASS NEUTRAL AND GROUND ISOLATION CONDUCTOR TOG THER AT ATS MAIN BREAKER. 3000A 3P 0, 2.27MVA, 480V,30,4W DIESEL GENERATOR 3000A, 65kAIC OUTPUT BREAKER 3 2 GROUND FAULT PROTECTIVE RELAY Po ER MONITORING DEI 110E (D TAL METER) MAIN SWITCHBOARD MSBB 3000A, 480Y/277V,30,4W, 65kAIC GENERAL NOTE: 1. ALL OVER CURRENT DEVICES TO BE SIZED PER EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. 2. ALL SWITCHBOARDS AND PANELS SHALL BE FULLY RATED EQUIPMENT, NOT SERIES RATED AND SHALL BE MANUFACTURED BY SIEMENS OR SQUARE V. 1 2 5 6 7 8 T 2500A 3P 2000A 3P 110A 3P T 110A 3P 400A 3p 200A 3P ARE INPUT FILTER 4 2500A 3P 5 PDUlB 480V: 208Y/120 430lkVA K=13 �__T (6) 4 UPS 8 (1.6MVA) �1200A 03P 7 PANEL 1_11B STATIC SWITCH OUTPUT FUSE I z I __J _X L _lz_:_JFT Zff RECTIFIER INVERTER 2 OOA I 5 ? 3p BATTERY CABINET PDU2B 480V: 208Y/120 430kVA K=13 5 (6) �1200A 03P 7 PANEL r-�"8 PANEL L3B ELECTRICAL ONE LINE 'A' SIDE. SCALE: NONE F_ MAINTENANCE BYPASS CABINET 200 3P 2000A, F___�I"N.O. )3P 480V- N.C. 480V 30,3W KIRK KEY INTER -LOCK 480V- K 480V T 30,3W __o 2000A 3P N. C. 5) (5 (050 A (o 5C 03P 03F PANEL PANEL HlB H2B 3/60- 40RK5/1 3/100- 9ORK5/1 PANEL L4B T4B 480V 208Y 120 3/100- 10ORK5 Tl B 48OV: 208Y/120 75kVA 3/200- 20ORK5/1 3/100- 3/200- 20ORK5/1 PANEL DRB ETVSjS PSACN E L SCB 13 PANEL� ADB PANEL � SC2B 400A NON -FUSED 4P, 4W, MANUAL XFR SWITCH (SWITCHED NEUTRAL) 14 14 PANEL NH T2B 48OV: 208Y/120 75kVA 0' A (015 0 30P 03F PANEL PANEL NIL (03C 02F PANEL NLA 14 T3 480V: 208Y/120 75kVA 1116102VARl"j-11 FEEDER SCHEDULE FEEDER SIZE MARK PARALLEL SET No OF WIRES IN EACH RUN AWG GROUND WIRE CONDUIT SIZE (INCH) CONDUIT TYPE 1 BUS DUCT 3000A NEMA 3R 2 BUS DUCT-- 3000A NEMA 1 3 BUS DUCT 3000A NEMA 1 4 BUS DUCT 2500A NEMA 1 5 BUS DUCT - 2500A - - NEMA 1 6 4 5 350kCM 3/0 3 EMT 7 4 5 350kCM 3/0 3 EMT 8 1 4 3 8 1 1/4 EMT 9 1 3 2 8 1 1/4 EMT 10 1 3 3 8 1 1/4 EMT 11 1 4 3/0 6 2 EMT 12 1 4 3/0 6 2 EMT 13 1 4 3 8 1 1/4 EMT 14 1 - 4 500kCM 3 3 RGS 15 1 3 4 8 1 EMT 16 1 4 1/0 6 2 EMT 17 1 3 8 8 1 EMT 18 1 4 3 8 1 1/4 EMT T4AE, INC. - ARCHITECTURE & PLANNING AA26001228 & AR92559 (954)839-4258 233 EAST ACRE DR., PLANTATION, FL 33317 STRUCTURAL AND MECHANICAL ENGINEER17 BASE4 INTERNATIONAL, INC. 9M GLADES ROP0, #237 BOCA RATON, FLORIDA 33434 BASE4 1.720-72BASE4 ELECTRICAL ENGINEERING RDCE, INC. 6707 S, DIYJE HWY, #8 WEST PPL.M BEACH, FLORIDA 33405 PHONE: 551436 9198 CERT� OF AUTH.: #8800 T4AE, INC., AND ALL PROFESSIONALS OF RECORD, HEREBY RESERVE THEIR INDIVIDUAL AND COLLECTIVE COMMON LAW COPYRIGHT AND ALL OTHER PROPERTY RIGHTS IN THESE DESIGNS, SPECIFICATIONS, PLANS AND IDEAS. THIS DOCUMENT IS NOT TO BE REPRODUCED WITHOUT FIRST OBTAINING THE WRITTEN PERMISSION OF T4AE, INC., AND THE PROFESSIONALS OF RECORD. ANY DISCREPANCY BETWEEN THIS DOCUMENT AND ACTUAL CONDITIONS SHALL BE REPORTED TO T4AE, INC. P R 0 F E S S 1 0 IN A L 0 F R E C 0 R D S E A L , III,,/ ` p ..... EN .%r- ao STATE OF Aw ..AX0FI ........ cp DEVEREN PETERKN, PROFESSIONAL ENGINEER NO. 75256 THIS IS A CONFIDENTIAL DOCUMENT THIS DOCUMENT, AND THE INFORMATION DEPICTED HEREIN, PERTAINS TO A SECURE FACILITY DESIGNATED BY THE HOMELAND SECURITY ADMINISTRATION AS "CRITICAL INFRASTRUCTURE" AND MAY NOT BE SHARED WITH ANY PERSONS OR ENTITIES OTHER THAN AUTHORITIES HAVING JURISDICTION WITHOUT WRITTEN CONSENT OF THE OWNER. ANY PERSON OR ENTITY IN POSSESSION OF THIS DOCUMENT SHALL SAFEGUARD IT, AND SHALL DESTROY IT WHEN IT IS NO LONGER IN USE FOR THE PURPOSE FOR WHICH IT WAS PROVIDED. 0 z F_ U) 0 z 0 Zi �Lj w 6c) < cl Lij U- < II-_ to z _j z =) < U) ui 0 < (J 0 z uj 0 P: a 0 < w < __Io w < 0 < 0 0 w CD m 04 C14 s f R E V I S 1 0 N S REV # DATE - REV SIONS MADE DRAWING SCALE T JOB NUMBER AS NOTED 1 84-84-1501 ELECTRICAL ONE LINE '[3' S6�; RAM SHEET RUMP IAL SUBMITTAL DATE E6.8 4/12/17 LOCATION: POWER ROOM 'A' 0 EXISTING 0 NEW PANEL 11A" SCHEDULE SPEC: SQUARE V OR EQUAL M COPPER BUS 0 ALUMINUM BUS CKT. LOAD DESCRIPTION -vllzil�l WIRE GIRD. --P COND. TORLIEV� A PKHASE -IVA B PHASE -KVA C PHASE POLE/ TRIP COND. GIRD. WIRE LOAD DESCRIPTION CKT. 1 3 5 POD 111 #1/0 #6 2- 150 13.31 150 2" #6 #1/0 POD 112 - 2 -4 6 13�A3 -13.3 13.3 13.3 7 9 11 POD 121 #4 #8 2- 80 8.0 1 8.0 - -- 80 2" #8 #4 POD 122 3 10 12 8-0 � 8-0 - - 8,01 -8.0 13 15 -T7- PODS 131/141 #1/0 #6 2" 150 - 150 2" #6 #4 POD 132/142 1�4 1 1-8 -14-71-14-7 - - -- 1 19 21 ff PODS 151/152 #2 #6 2- 110 10.7110.7 - --- 110 2- #6 #2 POD 161/162 2�0 2 24 - 1:0 - 7=1 0 - 7 - - - -10-.7--71-0.7- j25 27 - 20 PODS 171/172 #2 #6 2" 110 110 2- #6 #2 POD 181/182 2�6 2 J1 0. 7 0 30 31 33 35 PODS 191/192 #2 #6 2" 110 125 2" #6 #2 MMRA/MMR8 32 34 36 =0-7 =11-4 - - 37 39 4-1 GEN. FUEL PUMPS A2F1/A2P1 #10 #10 ill 30 2.0 � 38 - 0- 40 42 - --T. - ALL FEEDER CALCULATIONS ARE BASED ON: THHN/THWN CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY - SLI 138.9 138.9 1 138.9 SHUNT CIRCUIT TYPE TRIP 0 GROUND FAULT @ DEDICATED @ ISOLATED GIRD. TOTAL 41 b, KVA TOTAL 1154. AMPS TOTAL CONNECTED LOAD= 1154.3 AMPS ESTIMATED DEMAND LOAD= 1154.3 AMPS I POLE I E RATED VOLTAGE= 120/208 VOLTS 3 PHASE 4 WIRE M EQPT. GIRD. ED ISOL. GRID. MAINS: 171 M. L. 0. M BREAKER 1 3 1 1200 1 FEEDER SIZE IS: [:]CABLE -- M BUSWAY = BRANCH POLES: 42 BRANCH BREAKERS= 65 KAIC MOUNTING: 0 SURFACE ED FLUSH M FREE STANDING E--I KEYED DOOR: BUS RATING: 1200A BRACING = 65 KAIC NEUTRAL BUS IS: 0 HALF SIZE L] FULL SIZE 0 KRATED (1.5) M KRATED (2.0) GROUND BAR: ED EQUIPMENT [::] ISOLATED M BOTH ENCLOSURE MNEMA 1 El NEMA 3R 0 NEMA 4X CLASS DIV ? FEED LOCATION ; M TOP E3 BOTTOM [--]FEED THRU PANEL TYPE E:IFUSED ED CB PLUG IN M CB BOLT IN BRANCH EjNORMAL M EMERGENCY 171 UNINTERRUPTABLE S = SAME AS ITEM OR DEVICE AS ABOVE I SPECIAL NOTES: LOCATION: POWER ROOM 'A' EDEXISTING M NEW PANEL 12A" SCHEDULE - SPEC: SQUARE V OR EQUAL M COPPER BUS [::]ALUMINUM BUS CKT. LOAD DESCRIPTION - WIRE GIRD. COND. F OLE/ TRIP KVA A PHASE B PHASE KVA C PHASE POLE/ TRIP COND.TGRD. [WIRE LOAD DESCRIPTION CKT. 1 POD 211 #2 #6 2" 110 10.7 � 10.7 - 150 2" #6 #1 /0 POD 221 2 4 6 3 7 �10. 7 5 7 POD 311 - #1 /0 #6 2" 150 150 2- #6 #1 /0 POD 321 -10 12 9 -fi 13.3 13.3 - 1-33713-3 3 PODS 411/421 #1 /0 #6 2" 150 14.7 14.7 - 150 2- #6 #1 /0 POD 412/422 14 16 18 15 �7 - 14.7 11 M13.31 14.7 19 PODS 511 #1 /0 #6 2" 1 E50 113.3 � 13-.3 150 2" #6 #1 /0 POD 521 20 22 21 I - 3.3 13.3 F1 3.3 24 25 PODS 611 #1 /0 #6 2" 150 13.3113.3 - 150 0 2" #6 #1 /0 POD 621 2�6 2 30 27 - - 13 3=3 3 2-9 31 XFER PUMP TP1AB #10 #10 ill 30 80 1" #8 #4 PANEL L3A 32 33 707.5 =8-25 3-4 36 M- - -0-.5-79-.16- 37 38 40 39 41 ALL FEEDER CALCULATIONS ARE BASED ON:THHN/THWN CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUBTOTAL 140.95 3935 140.3� SHUNT CIRCUIT TYPE TRIP 0 GROUND FAULT @ DEDICATED ISOLATED GIRD. O.� TOTA 4 7KVA F TOTAL 1165.2 AMPS TOTAL CONNECTED LOAD= 1165.2 AMPS I ESTIMATED DEMAND LOAD= 1165.2 AMPS POLE TRWP�E RATED VOLTAGE= 120/208 VOLTS 3 PHASE 4 WIRE 0 EQPT. GIRD. 73 ISOL. GIRD. MAINS; E::] M1.0. M BREAKER -3 1200 1 FEEDER SIZE IS: ED CABLE = WBUSWAY = BRANCH POLES: 42 BRANCH BREAKERS= 65 KAIC MOUNTING� 0 SURFACE 0 FLUSH N FREE STANDING 0 KEYED DOOR: BUS 1 65 KAIC NEUTRAL BUS IS: OHALF SIZE 1:1 FULL SIZE E3 KRATED (1.5) M KRATED (2.0) GROUND BAR: ED EQUIPMENT E:I ISOLATED 0 BOTH ENCLOSURE NNEMA 1 NEMA 3R NEMA 4X CLASS 7 DIV ? FEED LOCATION TOP 0 BOTTOM ED FEED THRU PANEL TYPE [:]FUSED E] CB PLUG IN N CB BOLT IN BRANCH ONORMAL 0EMERGENCY 0 UNINTERRUPTABLE S = SAME AS ITEM OR DEVICE AS ABOVE SPECIAL NOTES: - LOCATION: POWER ROOM 'A' E] EXISTING M NEW PANEL '13A" SCHEDULE SPEC: SQUARE V OR EQUAL 0 COPPER BUS F-3 ALUMINUM BUS CKT. LOAD DESCRIPTION WIRE GRID. COND. POLE/ TRIP KVA A PHASE KVA 8 PHASE KVA C PHASE POLE/ TRIP COND. GIRD. WIRE LOAD DESCRIPTION CKT. -3 5 7 9 11 13 FC MMRA #12 #12 1/2" 20 60 1" #10 #6 CU MPA 2 -4 -.07 T4.8 - FC POP A #12 #12 1/2" 20 - '18 6 20 3/4" #12 #12 FC BRA 8 10 FC POP B #12 #12 1/2- 20 18_1 1.2 - .18 2.4 -- 3/4" #10 #8 CU BRA 12 14 BMS A #12 #12 1/2" 20 15 17 BVA-1,2/AEF-Al,A2/HS-A/INERGEN PNL� 1_ #12 #12 1/2" 20 1=0 30 3/4" #10 #10 CONV. RCPTS (NON-COINC.) 16 1 CONV. RCPTS (NON-COINC.) #12 #12 1/2" 20 0.2 1.0 19 CONV. RCPTS (NON-COINC.) #12 #12 1/2" 20 - - - - - SPACE 20 21 SPACE - - - - SPACE -22 23 SPACE - - S PACE 24 25 BATT. RM INERGEN SYSTEM #12 #12 1/2" 20 20 -- 1/�2' - 12 1 i:2 � DOOR ACCESS SYSTEM 26 27 POWER RM INERGEN SYSTEM #12 #1 1'2" 20 0.5 -- 20 1/2" #12 1 #12 1 IDOOR ACCESS SYSTEM 28 29 POP RM INERGEN SYSTEM #12 �2 #1 1 1/2" 20 -0.5 - 0.5 1 1 - I ISPACE 36 ALL FEEDER CALCULATIONS ARE BASED ON: THHN/THWN CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUBTOTALI 9.45 8,25 1 9.16 @ SHUNT TRIP CIRCUIT TYPE GROUND FAULT (@ DEDICATED (9 ISOLATED GIRD. - TOTAL 27.36 KVA TOTAL 75.6 AMPS TOTAL CONNECTED LOAD= 75.6 AMPS ESTIMATED DEMAND LOAD= 75.6 AMPS I POLE TRIP TYPE RATED VOLTAGE= 120/208 VOLTS 3 PHASE 4 WIRE 0 EQPT. GRID. 17-1 [SOL. GIRD. MAINS: OM.L.O. E] BREAKER ; I - - FEEDER SIZE IS: M CABLE = S3 E: a: FR I �S E:: FR [--I BUSWAY BRANCH POLES: 0 37 BRANCH BREAKERS= 65 KAIC MOUNTING: M SURFACE 0 FLUSH El FREE STANDING 0 KEYED D IOOA] BRACING 65 KAIC NEUTRAL BUS IS: EDHALF SIZE 0 FULL SIZE 0 KRATED (1.5) 0 KRATED (2.0) GROUND BAR: M EQUIPMENT = ISOLATED BOTH ENCLOSURE NNEMA 1 [=] NEMA 3R E] NEMA 4X CLASS ? DIV ? FEED LOCATION W TOP 0 BOTTOM =1 FEED THIRD PANEL TYPE OFUSED 0 CB PLUG IN E3 CB BOLT IN BRANCH =NORMAL 0 EMERGENCY = UNINTERRUPTABLE S = SAME AS ITEM OR DEVICE AS ABOVE I SPECIAL NOTES: ELECTRICAL SCALE: NONE PANELS - 'A' &DE J. AREA LOAD r, LTG 0 125% (0.0 x 1,2 HVAC 0 100% (0.0 x 1 EQUIP 0 100% (416,7 : RCPTS: 1ST 1OkVA 0 1 BALANCE 0 50% (0,0 : LOAD C, LTG 0 125% (0.0 x 1.2 HVAC 0 100% (0.0 x 1 EQUIP C 100% (420.62 RCPTS: 1ST 1OkVA 0 1 BALANCE @ 50% (0.0 � LOAD Q LTG @ 125% (0.0 x 1.25) HVAC 0 100% (0.0 x 1 EQUIP 0 100% (27�36 RCPTS: 1ST 1OkVA 0 1 BALANCE 0 50% (0.0 : = O�OkVA I' OR EQUAL :]ALUMINUM BUS TION CKT. 2 4 6 8 1-0 12 14 16 is 20 22 24 26 28 30 312 34 36 38 40 42 -A' 44 46 ISOLATED GIRD. 65 KAIC K IC IOTH EED THRU NINTERRUPTABLE T4AE, INC., ARCHITECTURE & PLANNING AA26001228 & AR92559 (954)839-4258 233 EAST ACRE DR., PLANTATION, FL 33317 STRUCTURAL AND MECHANICAL ENGINEERIN� A BASE 4 INTERNATIONAL, INC. 9858 GLADES ROAD, #237 BASE4BOCA RATON. FLORIDA 33434 1,720 72BASE4 W.la"4�wm ELECTRICAL ENGINEERING RDCE, INC. 5707 S. DIXIE HWY, 48 WEST PALM BEACH, FLORiDA33405 PHONE 561436 9198 CERT. OF ALI 48800 T4AE, INC., AND ALL PROFESSIONALS OF RECORD, HEREBY RESERVE THEIR INDIVIDUAL AND COLLECTIVE COMMON LAW COPYRIGHT AND ALL OTHER PROPERTY RIGHTS IN THESE DESIGNS, SPECIFICATIONS, PLANS AND IDEAS. THIS DOCUMENT IS NOT TO BE REPRODUCED WITHOUT FIRST OBTAINING THE WRITTEN PERMISSION OF T4AE, I C, AND THE PROFESSIONALS OF RECORD. ANY DISCREPANCY BETWEEN THIS DOCUMENT AND ACTUAL T4AE, INC. P R 0 F E S S 1 0 N A L 0 F R E C 0 R D E A L .�CIEN Z No. 75256 0 STATE OF ZOI ..-* C "17;, ZONAL 111111111%0�\\ DEVERLN PETERKIN, PROFESSIONAL LNGINEER NO. 75256 THIS IS A CONFIDENTIAL DOCUMENT THIS DOCUMENT, AND THE INFORMATION DEPICTED HEREIN, PERTAINS TO A SECURE FACILITY DESIGNATED BY THE HOMELAND SECURITY ADMINISTRATION AS "CRITICAL INFRASTRUCTURE" AND MAY NOT BE SHARED WITH ANY PERSONS OR ENTITIES OTHER THAN AUTHORITIES HAVING JURISDICTION WITHOUT WRITTEN CONSEN OF THE OWNER. ANY PERSON OR ENTITY IN POSSESSION OF THIS DOCUMENT SHALL SAFEGUARD IT, AND SHALL DESTROY IT WHEN IT IS NO LONGER IN USE FOR THE PURPOSE FOR WHICH IT WAS PROVIDED, LL 0 z F- U) 0 z 0 LLI LL < ill- � 0 z j z ::) < U) LLJ 0 < (.)0 z ILLI 0 F- U) < w < _j 0 . w uj F- -j F- < F- (1) < 0 CNI CN R E V I S 1 0 N S REV # DATE REVISIONS MADE DRAWING SCALE -F JOB NUMBER AS NOTED 1 34-84-1501 ELECTRICAL PANEL SCHEDULES SHE^j1MBER INITIAL SUBMITTAL DATE ET fts tol. 4/12/17 . r I LOCATION: POWER ROOM 'B' OEXISTING 0 NEW - L )) PANE L113 SCHEDULE SPEC: SQUARE 'D' OR EOUAL 0 COPPER BUS 0 ALUM NUM BUS CKT. LOAD DESCRIPTION WIRE ORD. COND. POLE/ TRIP KVA A PHASE KVA B PHASE KVA C PHASE POLE/ TRIP COND. ORD. WIRE ��/ LOAD DESCRIPTION CKT. 1 3 5 POD 111 #1 /0 #6 2' 150 T3�3 ] 13.3 - - 150 2- #6 #1 /0 POD 112 2 4 6 - 13.3113.3 7 9 11 POD 121 #4 #8 2" 80 31o: 18 mo - - 80 2" #8 #4 POD 122 8 8.0 8.0 - 10 12 - - F__ 8.0 80 13 15 17 PODS 131/141 #1 /0 #6 2" - 150 14. �71 4.7 150 2' #6 #4 POD 132/142 14 16 18 - 19 21 23 PODS 151/152 #2 -:1:0:7 110 �10.7 #6 #2 POD 161/162 20 22 24 25 27 29 PODS 171/172 #2 - 110 E00:7 Ll 0-7 110 2- #6 #2 POD 181/182 26 10.7 110.7 ___F__ 28 10.7 10.7 30 31 33 35 PODS 191/192 #2 #6 2" -:1-00 110 �11.4 125 2' #6 #2 MMRA/MMR8 32 34 36 37 39 41 GEN, FUEL PUMPS B2Fl/B2Pl #10 #10 1" 30 230�_ 38 40 _42 2.0 - 2.0 ALL FEEDER CALCULATIONS ARE BASED ON:THHN /THWN CUE NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUBTOTAL­f38.9 138.9 138.9- SHUNT TRIP CIRCUIT TYPE GROUND FAULT (@ DEDICATED @ ISOLATED ORD. TOTAL 41b./ KVA TOTAL 1154.3 AMPS TOTAL CONNECTED LOAD= 1154.3 AMPS ESTIMATED DEMAND LOAD= 1154.3 AMPS POLE TRI I I TYPE RATED VOLTAGE= 120/208 VOLTS 3 PHASE 4 WIRE M EQPT. ORD. ED ISOL. ORD. MAINS: C] M. L. 0. M BREAKER a 1200' FEEDER SIZE IS: EDCABLE = WBUSWAY = BRANCH POLES: 42 BRANCH BREAKERS= 65 KAIC MOUNTING: EDSURFACE 1::1 FLUSH M FREE STANDING ED KEYED DOOR: BUS RATING: 1200A 13RACING = 65 KAIC NEUTRAL BUS IS: OHALF SIZE 0 FULL SIZE 1:1 KRATED (1.5) 0 KRATED (2.0) GROUND BAR: ED EQUIPMENT ED ISOLATED 0 BOTH , ENCLOSURE WNEIMA 1 ED NEMA 3R El NEMA 4X CLASS ? DIV ? FEED LOCATION M TOP [--]BOTTOM ED FEED TH RU PANEL TYPE [::]FUSED E:ICB PLUG IN 0 CB BOLT IN BRANCH EDNORMAL M EMERGENCY 0 U N I N TE R f � U:P T:A B J:LE S = SAME AS ITEM OR DEMCE AS ABOVE SPECIAL NOTES: LOCATION; POWER ROOM 'B' 0 EXISTING M NEW PANEL 1213" SCHEDULE SPEC: SQUARE V OR EOUAL M COPPER BUS 0 ALUM NUM BUS CKT. LOAD DESCRIPTION WIRE ORD. COND. POLE/ TRIP KVA A PHASE KVA B PHASE KVA C PHASE POLE/ TRIP COND. ORD, WIRE LOAD DESCRIPTION CKT. POD 211 #2 #6 2- 110 107 7[ 10.7 150 2 #6 #1 /0 POD 221 2 4 3 - 5 7 POD 311 #1 /0 #6 2" 150 13.3 � 13.3 150 2" #6 #1 /0 POD 321 8 9 - 13.3 1_3_3 - 10 12 11 - 13.3 F13.3 13 PODS 411/421 #1 /0 #6 2" 150 14:E 14 7 - - 150 2' #6 #1 /0 POD 412/422 *4 18 18 15 17 - _14-7-T-14-.7 19 PODS 511 #1 /0 #6 2" 150 - 150 2" #6 #1 /0 POD 521 20 22 24 21 �213] 13. 3 _3j13, 25 PODS 611 #1 /0 150 11. 3 1113. 3 - 150 2" #6 #1 /0 POD 621 26 28 30 27 13.3113.3 29 13.3 03.3 31 XFER PUMP TP1AB #10 #10 t#62�" ill 30 CW5 9.85 80 ill #8 #4 PANEL _313 32 34 ��6 33 0.5 8..25 35 37 1 1 1 38 40 42 39 41 ALL FEEDER CALCULATIONS ARE BASED ON:THHN/THWN CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUBTOTAL 1 1.40.95 1 139.35 � 140.32 SHUNT TRIP CIRCUIT TYPE 0 GROUND FAULT (@ DEDICATED @ ISOLATED ORD. TOTAL 420.67KVA TOTAL 1165.2 AMPS TOTAL CONNECTED LOAD= 1165.2 AMPS 4D LOAD= 1165.2 AMPS POLE TRIP TYPE RATED VOLTAGE= 120/208 VOLTS 3 PHASE 4 WIRE M EQPT. ORD. ED ISOL. ORD. MAINS: 1:1 M. L. 0. M BREAKER 3 120D FEEDER SIZE IS: E]CABLE = M BUSWAY = BRANCH POLES: :42= BRANCH BREAKERS= 65 KAIC MOUNTING: EISURFACE E] FLUSH M FREE STANDING [__I KEYED DOOR: BUS RATING: 1200A I BRACING = 65 KAIC NEUTRAL BUS IS: E:I HALF SIZE 1:1 FULL SIZE [I KRATED (1.5) M KRATED QUO) GROUND BAR: E3 EQUIPMENT ED ISOLATED ED BOTH ENCLOSURE MNEMA 1 E-1 NEMA 3R [::] NEMA 4X CLASS ? DIV ? FEED LOCATION : E:] TOP [:] BOTTOM E] FEED PANEL TYPE [3FUSED EJ CB PLUG IN M C13 BOLT IN BRANCH CINORMAL 0 EMERGENCY ED UNINTERRUPTABLE S = SAME AS ITEM OR DEVICE AS ABOVE I SPECIAL NOTES: LOCATION: POWER ROOM 'B' =1 EXISTING M NEW PANEL 1313" SCHEDULE SPEC: SQUARE 'D' OR EQUAL M COPPER BUS = ALUMINUM BUS CKT. LOAD DESCRIPTION \11�el WIRE ORD. CON D. POLE/ TRIP KVA A PHASE KVA B PHASE KVA C PHASE POLE/ TRIP COND. ORD. WIRE LOAD DESCRIPTION CKT. 1 FC MMRA #12 #12 1/2" 20 =0 =74. 8 60 ill #10 #6 C U MPA 2 3 - -4 6 5 FC POP A #12 #12 1/2" 20 .1 7874-.8 7 .18 .2 20 3/4" #12 #12 FC BRA 8 10 9 FC POP B #12 #12 1/2" 20 - 11 35 3/4" #10 #8 CU BRA 12 14 13 BIVIS 8 #12 #12 1/2" f0____0.1_F2_.4 - - 15 BVA-1,2/AEF-91,82/HS-BANERGEN PNLS #12 #12 1/2" 20 0.3 1 1'0 - 30 3/4" #10 #10 CONV. RCPTS (NON-COINC 16 17 CONV, RCPTS (NON -CO #12 #12 1/2" 26- - 0.2 1.0 18 19 (NON_CO�N CONV. RCPTS Nfl #12 #12 1/2" SPACE 20 21 SPACE - - - SPACE 22 23 SPACE - - - SPACE 24 25 BATT. RM INERGEN SYSTEM #12 #12 1/2" 20 0, �50, 5 20 /2' 12 '12 CESS SYSTEM 26 27 POWER RM INERGEN SYSTEM #12 #12 1/2" 2-0- 0. 20 1 2-' #12 1 #12 1 1 DOOR A CCESS SYSTEM 28 29 POP RM INERGEN SYSTEM #12 #12 1/2" 20 - - - j - I ISPACE 30 ALL FEEDER CALCULATIONS ARE BASED ON:THHN/THWN CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUBTOTAL 8.25 1 9,16 (b SHUNT TRIP CIRCUIT TYPE 0 GROUND FAULT @ DEDICATED @ ISOLA TE TED ORD. TOTAL 27.36 KVA - TOTAL 75.6 AMPS TOTAL CONNECTED LOAD= 75.6 AMPS ESTIMATED DEMAND LOAD= 75.6 AMPS POLE TRIP TYPE RATED VOLTAGE= 120/208 VOLTS 3 PHASE 4 WIRE M EQPT. ORD. ED ISOL. ORD. MAINS: 1111111111M.L.O. ED BREAKER : I - T FEEDER SIZE IS: 0 CABLE = S3 E: E: FR I E3 E: FR EDBUSWAY = POLES: 30 BRANCH BREAKERS= 63 KAIC MOUNTING: 0 SURFACE E3 FLUSH 0 FREE STANDING ED KEYED DOOR: -BRAINCH BUS RATING: 100A BRACING = 65 KAIC NEUTRAL BUS IS: OHALF SIZE I=] FULL SIZE 0 KRATED (1.5) ED KRATED (2.0) GROUND BAR: 0 EQUIPMENT =1 ISOLATED 0 BOTH ENCLOSURE ONEMA 1 ED NEM A 3R 0 NEMA 4X CLASS ? DIV ? FEED LOCATION : W TOP 0 BOTTOM ID FEED THRU PANEL TYPE [:]FUSED M CB PLUG IN 0 CB BOLT IN BRANCH EDNORMAL M EMERGENCY E] UNINTERRUPTABLE S = SAME ASITEM OR DEVICE AS ABOVE SPECIAL NOTES: - ommommomm ELECTRI SCALE: NONE CAL PANELS - ) B' SIDE T. AREA LOAD C) LTG 0 125% (0.0 x 1,2 HVAC 0 l00% (o.o x 1 EQUIP 0 100% (416.7 ) RCPTS: IST 1OkVA 0 1 BALANCE 0 50% (0.0 ) LOAD Ci LTG 0 125% (0.0 x 1.2 HVAC 0 100% (QUO x 1 EQUIP 0 100% (420.62 RCPTS: 1ST 1OkVA 0 1 BALANCE 0 50% (0.0 ; LOAD CAL ,r \ Ll� � 145% kO.O x 1.2 HVAC 0 100% (0.0 x 1 EQUIP 0 100% (27.36 RCPTS: 1ST 1OkVA 0 1 BALANCE 0 50% (0.0 ) LOCATION: POWER El EXISTING ROOM 'B' M NEW PANEL "H213" SCHEDULE SPEC: SQUARE 'D' OR EQUAL 0 COPPER BUS EJ ALUMINUM BUS CKT. LOAD DESCIRIPTION WIRE ORD. COND. POLE/ TRIP KVA A PHASE KVA B PHASE KVA C PHASE POLE/ TRIP COND. ORD. WIRE ��/ LOAD DESCRIPTION CKT. 1 3 5 CRA 02 #4 #8 1 80 15 3/4" #12 #12 CRA CU 02 2 - _F873 Fl-.75 - -4 - 18.311. 6 7 9 11 CRA 03 #4 #8 1 80 18.3 1.75 - 15 3/4- #12 #12 CRA CU 03 8 10 12 - 18.3 1.75 13 15 17 CRA 04 #4 #8 1 80 18.3 1.75 - 15 3/4" #12 #12 CRA CU 04 14 16 18 - 18.3 Fl-.75 - - - 18. 19 21 CRA 05 #4 #8 1 80 :18�75 - 15 3/4" #12 #12 CRA CU 05 20 22 - 18.3 1.75 - 25 27 29 CRA 10 #4 #8 1 80 18.3 � 1.75 15 3/4" #12 #12 CRA CU 10 26 28 30 - 31 33 _35- CRA 13 #8 #10 1" 50 11.8 1.0 - 15 3/4" #12 #12 CRA CU13 32 34 36 - - - 11.8T-to 37 39 41 CRA 14 #10 #10 1/2- 30 11.81 1.0 - 15 #12 CRA CU 14 38 - 11.8 1.0 - - - 42 43 45 4�7 6.3 - 40 #8 'T4B' (25kVA) '1_4B' 44 -7.9 - 46 I - 1 5.2 -4-8 ALL FEEDER CALCULATIONS ARE BASED ON: THHN/THWN CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUBTOTAL 132.15 133.75 1 131.05 CIRCUIT TYPE SHUNT TRIP GROUND FAULT (@ DEDICATED @ ISOLATED ORD. TOTAL 396.95KVA TOTAL 477.7 AMPS TOTAL CONNECTED LOAD= 477.7 AMPS ESTIMATED DEMAND LOAD= 483.6 AMPS I POLE IP TYPE RATED VOLTAGE= 277/480 VOLTS 3 PHASE 4 WIRE M EQPT. GRID. ED ISOL. ORD. MAINS: OM.L.O. EI BREAKER : I - - FEEDER SIZE IS: 0 CABLE = !S E: E: F=R I �S E: F:R 13BUSWAY = BRANCH POLES� 48 BRANCH BREAKERS= 65 KAIC MOUNTING: EDSURFACE ED FLUSH M FREE STANDING ED KEYED DOOR: BUS RATING: 600A BRACING - 65 KAIC NEUTRAL BUS IS: WHALF SIZE L] FULL SIZE ED KRATED (1.5) 1:1 KRATED (2.0) GROUNDBAR: 0 EQUIPMENT 17-1 ISOLATED 173 BOTH ENCLOSURE NNEMA 1 E-I NEMA 3R E:] NEMA 4X CLASS ? DIV FEED LOCATION W TOP ED BOTTOM Ill FEED THRU E-IFUSED M CB PLUG IN ED CO BOLT IN BRANCH E:1NORMAL N EMERGENCY E3 UNINTERRUPTABLE S = SAME AS ITEM OR DEVICE AS ABOVE I SPECIAL NOTES: - T -/4km T4A I .,ARCHITECTURE ll PLANNING AA26001228 & AR92559 (954)839-4258 233 EAST ACRE DR., PLANTATION, FL 33317 STRUCTURAL AND MECHANICAL ENGINEERINE 01 BASE 4 4wd 'lip INTERNATIONAL, INC. 9858 GLADES ROAD, #237 BASE4 BOCA RATON, FLORIDA 33� .... as" com ELECTRICAL ENGINEERING fa�RDCE, INC. 5707 S, DIME HWY #8 WEST PALM BEACH, FLORIDA 334D5 PHONE: 561 �6 9198 CERT.OFAUTH 488M T4AE, INC., AND ALL PROFESSIONALS OF RECORD, HEREBY RESERVE THEIR INDIVIDUAL AND COLLECTIVE COMMON LAW COPYRIGHT AND ALL OTHER PROPERTY RIGHTS IN THESE DESIGNS, SPECIFICATIONS, PLANS AND IDEAS. THIS DOCUMENT IS NOT TO BE REPRODUCED WITHOUT FIRST OBTAINING THE WRITTEN PERMISSION OF T4AE, INC., AND THE PROFESSIONALS OF RECORD, ANY DISCREPANCY BETWEEN THIS DOCUMENT AND ACTUAL CONDITIONS SHALL BE REPORTED TO T4AE, INC. P R 0 F E S S 1 0 N A L 0 F R E C 0 R D S E A L -%k No. 75256 STATE OF a ?0NAL 111111111%0 DEVEREN PETERKIN, PROFESSIONAL ENGINEER NO. 75256 THIS IS A CONFIDENTIAL DOCUMENT THIS DOCUMENT, AND THE INFORMATION DEPICTED HEREIN, PERTAINS TO A SECURE FACILITY DESIGNATED BY THE HOMELAND SECURITY ADMINISTRATION AS CRITICAL INFRASTRUCTURE AND MAY NOT BE SHARED WITH ANY PERSONS OR ENTITIES OTHER THAN AUTHORITIES HAVING JURISDICTION WITHOUT WRITTEN CONSENT OF THE OWNER. ANY PERSON OR ENTITY IN POSSESSION OF THIS DOCUMENT SHALL SAFEGUARD IT, AND SHALL DESTROY IT WHEN IT IS NO LONGER IN USE FOR THE PURPOSE FOR WHICH IT WAS PROVIDED 0 z 0 0 z 0 < c) Lu LL _j < 0 z z :) < (1) Lij 0 < (.)0 z Lu 0 I-_ < 12� < 0 Lu F_ _j F_ F- 0 04 04 S H E=- UTEE R N S REV # DATE REVISIONS MADE DRAWING SCALE JOB NUMBER AS NOTED B4-84-1501 ELECTRICAL PANEL &�HEDULES (jI SHEET NUM5Q SUBMITTAL DATE E7,2 P 4/12/17 or iF= (U,) Om Z'T V) z -, 0) z z Q� -Z ZA 0 Q Dimco F- m z n P: z z X It z z < XH a LLJ Hi =W < R LLj AM§< F, <'O '0 LJJ ;2 LU 0'6�.O 0 Oz <ww z .0 cq o (3 N I < z - ZO Li F= M z z m Lj m M z A 0 All: 6 .......... WN e z 4 Am < z It% N't w w Ow"000 04 '4 (O�Oc)�O N N N K) w m ca (WD Li 0 < < = = CY M 0 — 0 W W W ui < z z 0 CA 0 M 0 CL 0 0 0 of =1 < CE 0 V) �; LO F� 0 (1) (1) w m Lw' ') LL LLI uj z L'i �3 CY cn 0 a CE Fn L) U.1 z CL CL co Z m 0 < 0 w m 0 0 LLI 0 w �F- 0� �-u m Q m m 0 0 (n 0 m CL (n 222- V� U) n- 0 z o < aw CL a� < z Lu cr 0 CL 0 m 0 00 C4 a N lk ;-k CL Fr LLI < z 0 '04 0 z m 1 z 0 0 z Z) C) Of Z 0 M: m z z < (A 0 z < IL LLI 000 0 a X D 0� x m CL LLJ LLI 0 rl) 4't U > YO- U) n - x > (J� 0 LO < cn 0 0 > 0 0 U.1 0 PO to y (1) 11 N J (n m Ot " )9- LLI LLI 0 0 z Q- LO Lr) CD w �4 LO = m -i U� 0 141 —W 0 0 K) LO rl) U) < < L6 o- U) > X: �4 CL 0 C 0 < 0 M CY LLI 0 LLJ < '� �L n K , U� < M z < 0 RE c:l X z - uj Q� 0 0 0 0 0 <1 -'Q� 0 F- Cq N N N ID 0 H LU 0 'n CL 1-- m < m Oz 'N 'c'! 04 'C4 cm = U m C) 0 0 0 11 0 CS CA C14 N C-4 0 cn w Cw ri ri ff H L(LOJ w to V) m U < w — — — — — — — — — — n (n 0 m LO ED < z 0 OD C) W < M W w 0 0 LL 0 m < x < (n Z) U- L) X z = �-- < < x < 0 M L) U) y M 2 �2 L'i 0 LLI Z) C) - 0 a_ z p LLJ m 0 0 < ui co �U- CUDJ < 00 < < z N < z z m ui z 6 z m 0 p LU Gi < 0 ui Z < i:= D I.-: �- 0 < cn x L) < w UJ 0 m =� z z < CL �C4 0 [] V) U) -�M� 04 Ka, I I V) Y- N 't U) 10010�04 04 014 C-4 m CL Z CY 0 0 X M M z S z LJ 0 m :ZD (n Of 0 ww (n �2 0 11 11 El =5 m CY m L) z Ei 0 u CL C5 Ld x uj Lj L) EL (n m 0 0 z 0 m ui cn (n LL U- CL Z< 0< < M M w < z w 0-- 0- cr CY 0 0 z V) C4 CL n z Z N 0- < m < - -ij 0 z = Z C ) 0 M: (n Z z Ln 0 uj Z < ui 0 N 3 0 to D m m 0 Lu = M CL ui < < 'n 1� L') 't a. I LO I '0— Oi 6� > - - - Ln' --< co CL a 0 fm > '* 0 - - - - - - - - LJ 0 --: to L6 �� Z �2 < < * - -- 'D 't >- < ui LO (0 Lu z LO m < 0 0 C/) Lu 0 LLI (1) < LO C� CIL (n �e 0- to 0 C14 C3 < 0 CL CY La LJ =-i < < < z < LLJ IL 0 0 0 0 0 < �O C-4 04 N C-4 (0 F-- 000 w 0 m w m 'C4 Z M 0 Z N ��N N 0 0 0 0 0 — - - - - - - - - - - 0 N N C14 04 z w (r) LU - - - - - - L'j C-4 C4 C4 04 < m M �4k CL U. Z Q — - - - - - - - - - - - - w - - - - - - - - - - - - w V) 0 m < u U-) 00 < z 0 0 0 0 o- m N wz > af w z < < 0 < 0 0 E 1 0 w wx fL U.1 LLJ:D Om (L z 0 00 0 LLI U) X Fn < Li 0 IL < 0 < < 0 C, Ff LZLI i� LLJ W LLJ < 0 z z CL 0 m LLI M < < 0 0 N U) z D w 0 P- L) L'i -j �- < CL 0 af F- U) 0 < P= Ln <><----T Of lw� H 0 I - CL < LLI 0 z :D UJ w w L'i 0 z I.� - - 14) - Ln - � 0 0 m C-4 C14 C4 16 < z < Oz '0 Z'� < z < V, 0 m z Z-Z D :< < lJ'AiNnOO 31oni'JS'OVO�l AOMJ HinOS 66ZZ ,killlOV=J,klNn003iom'is 01 -1 '�J 3 1-13 H S ViVG 01 SNOlil(](]V (INV SNOliV`83ilV '- cq y N 't (D 'D 00 - 14LN 0 Cl -* rD N loolc'� N C4 tO w do w m 0 L L) m 0 0 w 0 0 < z z 0 0 Ln F 0 El P= m U.1 C-4 uj 0 (=n, V) U z -0 Z (n L uj z < o- m LLJ Q- n LO W CL < < 0 C3 LO LO W of CO Ld C) 0 -j -i au, w UJ w x U.1 0 m S xw m :r mu z 0 M 7 W :r < W < j u z cl- 0 UZ:C U< :9 � cn 3: LO 0 U- a- z 0 C141 04 a) 0 CL CL m w 0 < z z 0 < 0 a- Z P M z = C-) < x 0 z S (M) Li W =) 0 0 LLJ x 1� CL 0 _j LLI 0 V) 00 04 Cq 0 V 00 0 C'4 0 w G D 3 x m D 0 LLi LLI LO LO Z: C� 0 CL 0 Lq to - > C� W m V) CL 0 0 5 7 < 2 0 0 C! N w to to U') W < C� N C� -: LO PO 0 't 't >- uj )U-j 0 m > Z: ya- - 0 - U) � - V) I rl� I � - (D L6 Cq 6 Ln n' (0 to* ko Ln < z 6 06 —1 - - =1 x 0 (n -j < 0 Fl LLI Ul) U) 0 Ld U) < < C� U� IL _j >=— x CL 0 — a LO (0 0 < 0 IL 0 Ld LLJ < z 25 Z Lq z < LU 0 0 0 0 0 0 0 0 1 LO 0 < < C 4 C 4 N CA N (N C,4 LLJ < m cc) N CA N D V) wz z < W w z x ui V) W LLI C'4 C-4 V) m ce IL z C-) CL V) < w w 0 n V) m < < > Il LLJ Q w W z < 00 0 < < 0— cq M C14 m < C:� =) < 2 M 0 0 U W !ZW-M m X= < 0 V) z z 03 C) () 0 w N- OW < V) LL L� Of CL o 0 Ld 0 0 U.1 �j IL WWLI 00 �= w 00copom L) (D 0 (n (n V) 10 < < w z Z i!S w N 0 Le) M LJJ w LLJ L) LL ri 0 pqpq-w� m ui 2 X zmn) F= cn L'i LLI LLJ uj 0 < 0 W Z x w - - - - 0 LLI D L) — - - rl) LO w 0 LLJ z 0 in r10) c"! It (D 00 0 C14 w 00 'D cco, '0' L) 0 m 7 < 0 0 < z D LU El 0 P= Q) W a_ m LLI N LLI c E01 0 < W LLI �O ca uj L) z CL FL LLI Lj 0 0 LLj L) uj LLI m m Ci C) EL U) LLI 1-- < C) a- 0 z L) 0 0 < 2 V) C a: 0 < x < 0� M M z LLI o m z M S < Or W F- 0 z CR 0 1 0 a 0 z z 6�1 04 C4 c"I z F= m < 0 - 0 L) z < 0 z 0 = a Li Z 7': z < =1 0 0 Z CL LU � fr 0 '0 (N ID x M 0 LLJ LLI Zn 0 > m � � 15 1 1 �2 y 0- 0' LO LO - > 6 c"I <0- (n Ln EL —j 0 0 , Z5 cn >m �e < 2 < 0 V) 0 cli V) uj LO LO to "� C-4 '6 LO El ) 0 -1 0 0 < LO 1 �O I'l � I LO C-4 Oi LO I-i (0 ID :X- V) U�j z d . - < L'i LO tr) 0 0 LLA < C� C'4 U� 0- W m 0- LO 0' < 13- LLJ < < < z < z LLI Q- 0 0 ul 0 Cq C4 C-4 N N N N 0 w �2 P �- 0 LLI w m �N 204 � 2N �C'4 C-4 m D 0 w z M 0 0 < 0 0 0 L) Cq N Cq C-4 Cq N 0 Ln z 4k w V ) w x .1 < LLJ (14 C4 N N 04 N < m W m z a- n 4� m < w w 0 to M m (0 11 ui 0 t! z co 0 (n �ti < cl < wo N M I cwn LL Z L11 M 0 0 0 0 Z z 06 u 0 0 cl� 0 N < (n Ld U- 0 LL 0 - - W Et CL 0 L) :� W -j CL 0 H 11 LLJ C� M O� cl L� 0 0 F- 0 0 0 L) LLI < 0 I En I (f) I I L) 0 < LLI z Z F- W (n =) m w < F- CL I- CL m CL Of Li m LL; LL' 0 > z x z z 0 o L) UJ < F- < U) < LU LLI LLJ w a < U- EL LF<UM, LU z 0 w cn < x 0 C) LLJ 0 uj z _j z LIJ z < �-10 LO :(-3) C01'4 Q�(n -01 z :2 0 0 z 0 > Ld W W < V) W M a 3 PO — — - — - — - — - — - — - — - — - — - — w w— 0 m 0 I L0 OD LO 0 < V) LLI z C) > 0 3t P zzzm 0 0 0 11 lc� m <0 x a I wz 0 0 (.) w Z 9= L) LL C.) P 0- P Q- P EL ir OP A < 0 N- 0 1 0 _j < 0 U) 0 W (.) LLI 0 W (-) z 6 Ld (f) (n LLJ L'i LLI 0 F5 C, z x X U H m q uj 0 < L 'j 0< ui M U, FV- 0- Q 0 z 5 w 0 U LU < D CL LLI LU UJ LU P z 0 < .1 co x w x Q� < Z) U z < x 0 UJ n 1--: ro Ln 0 c cn C-4 0 N'* N C4 00 ro 0 uj 0 LU Ln 0 z 0 000 0 m 0 0000 L) CO CL m ul LL: LL: L': L.� Z LU D U.1 Z zzzm 0000 < L) 0 L) z a. 0 L) 0 < 0 U<j H :m 0 w 0 _0 0 �2 �2 K) r ui 0 11 uj 0 LLJ < a_ (L IL a. 0 L, L CL LLJ U W 0 LLJ 0 LU Q L'i L) U Z< z - 0< El() U.1 m LU LLJ Ui Lij reo m < t: M M < z uj LLJ C.4 4 N C4 N CII 0 d a. m 0 m Or 0 0 ui z z a- LU 0 < 0 0 z IL z < 0 0 L) z D < 0 ?, V) z < En 0 U, z < _j LAj 0 0 LO 0000 x Z:) m w w � E 0 � N N C4 N C4 04 N m m 0 M CL - — — — — - - - L-Li UJ LO r YO IL 0 > Cn 04 0 W CL CL — w - - - - - - - - LO > - M < 2 V) - I] - En (n �z - IU3 13 rl) - - El a LL' o 00 00 C5 LJ z U) Ln y 0 c; D m (n 0 -i < of 0 0 LLJ W 0 Ln C) U.1 0- < Lq 'w V) _j > X: Y 0- LO 0" < LJ-J < - - - - - - - Z I - z z - - < L�'j ot (D 'D m 0 C'4 N C-4 10 N C4 N L'i 0 -C n 0 w m C4 'ClJ 'N � C4 �Cl`l (n w z m C-) z 0 0 0 0 0 0 PO - - - - m U) 0 C-4 C-4 C-4 N Cq N C4 r4h Fit Tk �b FA LLI V) w N C14 N < m MC14NN r* F* I Tb Z-* F* 5 (1) (L E E� 2 z u m n 0 1 0 1 — - - — — - - - - - - - - - - - - - - - - - - w w - - 7: W 0 LO m 0 < N M LA > z 0 0 zzz m m w 0 m L, m < M Ln w 0 0 P 90 L� coo 0 < 5 < m z 2 5. () L'i Z CL P= CL F= EL P= a- < 0 0 0 0 0 0 _j L) U) LLI LLJ LLJ z V) LLJ 12� 0 () w C-) LLI () LLI z 0 0 8 0 0 z D) cl < 0 0 V) V) (n Ln WZ z F<- Wr 14 < 0 0� LLJ 1-- EL UJ LLJ L) �- CL F- a. F- (L CL z 0 P= - CL 0 L) ui < Q- I p < CL 0 LLI C-) LLJ C) LLJ 0 Lli 05 :2 L) U=)) m < En w Q� W 0 W - X - = - [if - W - - < x 0 w z m rl) LO rl 0) �N 0 Pf) LO rl 0) - - - Z� CU-4) fN [014) :3 � �l i U� < LLJ Lij =)a u < LLJ __j LLJ (.n L-L LLJ U� --- i LL1 LO rr- -'7- 0 z < 0 V) i j� lw