HomeMy WebLinkAboutELECTRICALLOCATION: MAINTENANCE BLDG SPEC: SQUARE
171 EXISTING M NEW PANEL "NH" SCHEDULE M COPPER BUS
V OR EQUAL
::]ALUMINUM BUS
CKT.
LOAD DESCRIPTION Z<'
WIRE
GIRD.
COND,
_P_O�LE/
TRIP
A PHASE
B PHASE
___F
_KVA
C PHASE
PO-LE/
I TRIP
COND.
GRD.
WIRE
LOAD DESCRIRTION
CKT.
1
SITE LTG
#8
#10
1-
30
30
ill
#10
#8
1 SITE LIGHTING
2
3
SITE LTG
#8
#10
1"
30
-
475T-45
30
1.
#10
#8
1 SITE LIGHTING
4
5
SITE LTG
#8
#10
ill
30
-
4_5_76_.O
3-0
_1"
#10
#8
1 SITE LIGHTIN
6
7
SITE LTG
#8
#10
-1"
-To--
0
4 - 5
-
-
30
1.
#10
#8
1 SITE LIGHTING
8
9
SITE LTG
#8
#10
30
So
-
-
3.0 1 4.5
-
30
1"
#10
#8
1 SITE LIGHTING
10
11
SI TE LTG
#8
#10
lv_�F_30_
4,5 0.5
30
1-
#10
48
1 SITE LIGHTING CONTROL
12
13
j3
R-2.2
-
30
ill
#10
#8
DRIVE LIGHTS . / CCNTROL
14
15
2.6 2.0
30
ill
#10
#8
LANDSCAPE /CONTROL
/BLDG SIGN
16
17
SPACE
18
19
20
21
22
23
25
.0
��25.0
100
1 1/4"
#8
1
#3
'T3'(75kVA XFMR)
__24
26
-28
30
27
29
125.0
ALL FEEDER CALCULATIONS ARE BASED ON:THHN/THWN CU.
NOT MORE THAN 4 CONDUCTORS IN A RACEWAY
SUBTOTAL
42.2
1 43.5
1 40.0
__
CIRCUIT TYPE
SHUNT TRIP 0 GROUND FAULT @ DEDICATED ID
ISOLATED GRD.
TOTAL 125.7 KVA
TOTAL 151.3 AMPS
TOTAL CONNECTED LOAD= 151.3 AMPS
ESTIMATED DEMAND LOAD= 159.6 AMPS
POLE
TRIP
TYPE
RATED VOLTAGE= 277/480 VOLTS 3 PHASE 4 WIRE M EQPT. GRD. ID ISOL. GIRD.
MAINS: 0M.L.C. M BREAKER
3
I 400
FEEDER SIZE IS: MCABLE = SEE RISER EIBUSWAY =
BRANCH POLES: 301:
BRANCH BREAKERS=
14 KAIC
MOUNTING: N SURFACE 11 FLUSH 13 FREE STANDING 0 KEYED DOOR:
BUS RATINGI 400A
BRACING =
14 KAIC
NEUTRAL BUS IS: C__I HALF SIZE M FULL SIZE Ill KRATED (1.5) 13 KRATED (2.0)
GROUND BAR: M EQUIPMENT ED ISOLATED ED
OTH
ENCLOSUR M NEMA 1 E-I NEMA 3R [::] NEMA 0 CLASS ? DIV ?
FEED LOCATION : 0 TOP M BOTTOM ED
ED THRU
PANEL TYPE DFUSED 0 CB PLUG IN El CB BOLT IN
BRANCH E:INORMAL 0 EMERGENCY 0
NINTERRUPTABLE
S = SAME AS ITEM OR DEVICE AS ABOVE I
CALCS: -LTG 0 125% (50.7 X 1.25) = 63.4kVA, EQUIP 0 100% (69.2 X 1.0) = 69.2kVA => TOTAL = 1,32.6k4A
= 159.6A
LOCATION: MAINTENANCE BLDG
EXISTING M NEW
PANEL "NL" SCHEDULE
SPEC: SQUARE 1'
M COPPER BUS I:]
OR EQUAL
ALUMINUM BUS
CKT.
LOAD DESCRIPTION
WIRE
GRID.
COND.
POLE/
TRIP
KVA
A PHASE
KVA
B PHASE
KVA
C PHASE
POLE/
TRIP
COND.
GRID.
WIRE
��/ LOAD DESCRIPTION
CKT.
R. V. 1
#6
#8
2"
50
5.0 5.0
50
2-
#8
#6
R.V. 4
2
4
3
5
R.V. 2
#6
#8
2"
50
2-
#8
#6
R.V. 5
6
8
7
9
_11
R.V. 3
#6
#8
2"
50
50
2-
#8
#6
R.V. 6
lo
12
13
SPACE
-
-
-
-
-
-
-
-
SPACE
__T14
15
SPACE
10
20
1 1 L2"
#12
#12
LIGHTING - MAINT.
SHED
16
17
SPACE __dA_TE__
1.0
20
1/2"
#12
#12
LIGHTING - MAINT.
SHED
18
19
SOUTH
#8
#10
_1"
20 -_
1.5 1.5
20
1.
#10
#8
NORTH GATE
20
21
GATE SIGN
fl 0
1"
fO
30
ill
#10
#10
WELL WATER PUMP
22
24
-26
23
SPACE
-
-
-
25
RECPTS - MAINT. SHED
#12
#12
1 2
27
RECPTS - MAINT. SHED
#12
12
Ri*
1 2"
20
-
30
ill
#8
#8
PANEL 'NLA'
28
30
29
RECPTS - MAINT. SHED
1/2"
20
-
1 0 0.6
ALL FEEDER CALCULA11ONS ARE BASED ON:THHN/THWN CU.
NOT MORE THAN 4 CONDUCTORS IN A RACEWAY
SUBTOTALI
25.0
24.2
24.0
CIRCUIT TYPE
SHUNT TRIP 0 GROUND FAULT (@ DEDICATED
@ ISOLATED GIRD.
TOTAL 74.2 KVA
TOTTAL 199.0 AM PS
TOTAL CONNECTED LOAD= 199.0 AMPS
ESTIMATED
DEMAND
LOAD= 199.0 AMPS
I POLI
RATED VOLTAGE= 120/208 VOLTS
3 PHASE
4 WIRE 0 EQPT. GRD. ED ISOL. GIRD.
MAINS:
MM.L.O.
0 BREAKER
FEEDER SIZE IS: WCABLE = SEE
RISER
E] BUSWAY
BRANCH POLES: 30
BRANCH BREAKERS=
10 KAIC
MOUNTING: M SURFACE
0 FLUSH
El FREE STANDING
E] KEYED DOOR:
BUS RATING:
200A
BRACING =
10 KAIC
NEUTRAL BUS IS: E] HALF SIZE
M FULL SIZE
0 KRATED (1.5) EJ KRATED (2.0)
GROUND BAR:
0 EQUIPMENT 0 ISOLATED I-1] BOTH
ENCLOSURE WNEMA 1
EI NEMA 3R
0 NEMA 4X
CLASS ? DIV ?
FEED LOCATION : E] TOP
W BOTTOM [--]FEED
THRU
PANEL TYPE 0FUSED
M CB PLUG IN
[71 CB BOLT IN
BRANCH
EDNORMAL
0 EMERGENCY ED LNINTERRUPTABLE
I
S = SAME AS ITEM OR DEVICE AS ABOVE
I
SPECIAL NOTES: -
I
LOCATION: FENCE GATE 1) 11 SPEC: SQUARE V
E__IEX1STING M NEW PANEL NLA SCHEDULE M COPPER BUS [::]ALUMINUM
OR EQUAL
BUS
CKTJ
LOAD DESCRIPTION \Z<�
WIRE
GRD.
COND.
POLE/
TRIP
KVA
A PHASE
KVA
B PHASE
POLE/
TRIP
COND.
GIRD.
WIRE
1��/ LOAD DESCRip
riON
CKT.
1
SEC GATE 1
12
12
1 2"
20
20
1/2"
#12
#12
ADDRESS SIGN
2
3
SEC GATE 2
#12
#1
1/2-
20
0.57-0.1
4
5
SPARE
-
- .
1/2-
20
20
1 2"'
12
#12
PHOTOCELL
6
7
8
9
10
11
12
ALL FEEDER CALCULATIONS ARE BASED ON:THHN/THWN CU.
NOT MORE THAN 4 CONDUCTORS IN A RACEWAY
___S_UBT0TAL
0.8
0.6
CIRCUIT TYPE
SHUNT TRIP (D GROUND FAULT @ DEDICATED 43)
ISOLATED GIRD.
TOTAL 1.4 KVA
TOTAL 6.7 AMPS
TOTAL CONNECTED LOAD= 6.7 AMPS
ESTIMATED DEMAND LOAD= 5�7 AMPS
POLE
TRIP
TYPE
RATED VOLTAGE= 120/208 VOLTS I PHASE 3 WIRE M EQPT. GRID, ED ISOL. GRID.
MAINS: 13M.L.O. M BREAKER
2
3 0
FEEDER SIZE & [--]CABLE = SEE RISER I--] BUSWAY =
BRANCH POLES: 12
BRANCH BREAKERS=
10 KAIC
MOUNTING: 0SURFACE 0 FLUSH M FREE STANDING E:I KEYED DOOR:
BUS RATING: 100A
BRACING =
10 KAIC
S IS: E3HALF SIZE M FULL SIZE 13 KRATED (1.5) El KRATED (2.0)
GROUND BAR: M EQUIPMENT 0 ISOLATED I--] EOTH
ENCLOSURE CJ NEMA 1 0 NEMA 3R 0 NEMA 4X CLASS ? DIV ?
FEED LOCATION E:] TOP N BOTTOM ED REED
THRU
PANEL TYPE =FUSED 0 CB PLUG IN = CB BOLT IN
:]NORMAL M EMERGENCY = LNINTERRUPTABLE
S = SAME AS ITEM OR DEVICE AS ABOVE-
SPECIAL NOTES:
ELECTRICAL DETAILS
SCALE: NONE
T4AE, INC. - ARCHITECTURE & PLANNING
1AA26001228 & AR92559 (954)839-4258
233 EAST ACRE DR., PLANTATION, FL 33317
STRUCTURAL AND MECHANICAL ENGINEER7G
BASE 4
INTERNATIONAL, INC.
9858 GLADES ROAD, �37
BASE4CA RATON, FLORIDA 33434
'1'.0720.72BASE4
ELECTRICAL 7NGINEERIN�G
WEST M BEACH, FLORIDA 33406
PHONE 551 436 9198
CERT OFAUTH.: #8800
T4AE, INC., AND ALL PROFESSIONALS OF RECORD,
HEREBY RESERVE THEIR INDIVIDUAL AND COLLECTIVE
COMMON LAW COPYRIGHT AND ALL OTHER PROPERTY
RIGHTS IN THESE DESIGNS, SPECIFICATIONS, PLANS AND
IDEAS. THIS DOCUMENT IS NOT TO BE REPRODUCED
WITHOUT FIRST OBTAINING THE WRITTEN PERMISSION OF
T4AE, INC., AND THE PROFESSIONALS OF RECORD. ANY
DISCREPANCY BETWEEN THIS DOCUMENT AND ACTUAL
CONDITIONS SHALL BE REPORTED TO T4AE, INC.
0 F E S 5 1 0 N A L 0 F R E C 0 R D
S E A L
��jj I I I I III,
...... ......
No. 75256
STATE OF
DEVEREN PETERKIN, PROFESSIONAL ENGINEER NO. 75256
If THIS IS A CONFIDENTIAL DOCUMENT 11
THIS DOCUMENT, AND THE INFORMATION
DEPICTED HEREIN, PERTAINS TO A SECURE
FACILITY DESIGNATED BY THE HOMELAND
SECURITY ADMINISTRATION AS CRITICAL
INFRASTRUCTURE" AND MAY NOT BE SHARED
WITH ANY PERSONS OR ENTITIES OTHER THAN
AUTHORITIES HAVING JURISDICTION WITHOUT
WRITTEN CONSENT OF THE OWNER. ANY
PERSON OR ENTITY IN POSSESSION OF THIS
DOCUMENT SHALL SAFEGUARD IT, AND SHALL
ESTROY IT WHEN IT IS NO LONGER IN USE FOR
-I
ILL
0
z
D
F_
0
z
0
Lij
U-
F_
U)
z
z
::)
<
(1)
LLj
0 <
(.)0
z
Lij
!2
F_
U)
z)-
0
<
_j 0
.
Lu
F_
F-
F-
(1)
0
U)
R E V I S [ 0 N S
IIREV #1 DATE I REVISIONS MADE 11
DRAWING SCALE
T JOB NUMBER
AS NOTED
I B4-84-1501
MAINT. SHED
PANEL
SCH -
^ r%nt6�ia S
SHEET NUMBCIII!f_
hRIWUBMITTAL DATE I
E5.1
4/12/17