HomeMy WebLinkAboutBUILDING PLAN PAGE 1-171 . ALL SANITARY WASTE AND VENT PIP�S AND FITTINGS SHALL BE PVC (SCHED.40 MIN.) OR D.W.V. (ASTM—D-2662). 2. COPPER �TQ. ,ASTM—B-88), USED FOR HOT AND QOLD WATER LINES, USE TYP , L FOR UNDERGROUND AND TYPE "L ABOVE GROUND. PROVIDE DI —ELECTRIC COUPLINGS, AS REQUIRED, FOR CONNECTION TO DIFFERENT MATERIALS, SHUT—OFF VALVES AT FIXTURES, AND EQUIPMENT REQUIRING WATER SUPPLY. 3. ALL PIPES EXPOSED AT FIXTURES AND EQUIPMENT SHALL BE CHROME —PLATED. PROVIDE CHROME —PLATED ESCUTCHEONS AS REQUIRED. 4. ALL PIPING SHALL BE ACOUSTICALLY ISOLATED OR WRAPPED TO PREVENT THE TRANSMISSION OF SOUND INTO THE BUILDING. 5. ALL POTABLE \9ktJFR LINES SHALL BE FLUSHED AND MADE CLEAR OF DEBRIS, SCALE, GREASE, ETC., PRIOR TO CONNECTION WITH EQUIPMECT ' 7. FLASH AND SEAL4LL ROOF PENETRATIONS. 8. CLEAN OUTS 1� ,$A�t�ORDANCE WITH F.P.C. 708.3.2. A 9. TRAP PRIMERS *CCORDANCE WITH "ASSE 1018", PROVIDE UNIONS. FOR NEW, USE T42�":` "K" FOR UNDERGROUND AND TYPE "L" ABOVE GROUND. PROVI tl—ELECTRIC COUPLINGS, AS REQUIRED, FOR CONNECTION TOiCIFFERENT MATERIALS. 11. ALL COPPER PIPING SHALL BE ISOLATED FROM CONTACT WITH OTHER METALS, ACONCRETE OR MASONRY. 12. ENSURE DRAIN AND 2WATER PIPING FROM RE —LOCATED FIXTURES LEAVES NO DFAI-El I,A.S WATER OR WASTE COULD STAGNATE. 'K A,�, 13. PROVIDE SHOC AIR CHAMBERS ON EACH QUICK CLOSING "NJVALVE, INCLUDING M ATER HEATER (IF IN CONTRACT), TO PREVENT "WATER HAMMERIN4. 14. DRINKING FOUNTAIN%SHALL COMPLY w/ 2014 FBC 'i Y* f1i 7; USE EXISTING WATER SUPPLY4;ANI & VENT STACK KEEP ALL VENT PIPES UNDER FLOOR SLAB; INSIDE WALL OR CEILING ASSEMBLIES. ENSURE NO DEAD-END SAN. OR SUPPLY PIPES REMAIN IN FINISHED PLUMBING SYSTEM, (TO AVOID STAGNATION & HEALTH ISSUES). ALL PLUMBING WILL COMPLY WITH 2014 FL P LUMB ING CODE PLUMBING FIXTURES: ALTERNATES TO BELOW ARE ACCEPTABLE & CUT SHEETS OF ALL PLUMBING FIXTURES MUST BE PROVIDED FOR OWNER SIGN —OFF PRIOR TO PURCHASE. 1. ALL W.C.'S TO BE ST THOMAS CREATIONS MARATHON I ADA COMPLIANT 1 �16 GPF ELONGATED 2 PIECE TOILET; 2. ALL LAV'S TO BE WALL MOUNTED SINKS KOHLER MODEL # K-2032-0 INTERNET# 100080811 GREENWICH WALL —MOUNTED BATHROOM SINK IN WHITE'w/ ADA COMPLIANT LEVER TRIM w/ POP UP ASSEMBLY, ONE PIECE CHROME FINISHED BRASS DRAIN & PLUG; 3. URINAL: AMERICAN STANDARD, TRIMBROCKTM 1.0 GPF SIPHON —JET URINAL VITREOUS CHINA; 4. DRINKING FOUNTAIN: ELKAY BI—LEVEL WATER COOLER — EZSTL8LC — VERSATILE 5. SERVICE SINK: FIAT PRODUCTS LAUNDRY TUB KIT, WITH FAUCET, FLOOR, WHITE ITEM # 5NFL8 MFR. MODEL # FL7TG10O LAUNDRY TUB KIT, WITH FAUCET, MATERIAL FIBERGLASS REINFORCED POLYESTER RESIN, MOUNTING TYPE FLOOR; 17"-19" CO co -to CQ ch) E' E� �:) ::) L 0 0 fl� 8"MIN C) DRINKING FOUNTAINS SCALE N.T.S. TO SANITARY LIFT STATION SYTEM SEE CIVIL DRWGS STUDOR OR OTHER AIR EMITTANCE VALVE UNDER SINK OFFICE 11 1 TO LIFT STATION. I z ASEE CIVIL DRAWINGS 1 4" C.O. 40 1— 4. Lu 7ED 1 5" FUTURE CONFERENCE ROOM 1st FLOOR PLUMBING PLAN 311VTR� "6��THROUGH ROOF 121 ASSEMBLY INSIDE LAVI CEILING 2 r 1211 1.5" INSIDE WC 3 go WALL LAV 2 2 CO LAV Rof z 2 2 3 wc 211 CQ WC UR D.F. 211 2 LAV 2 01 1211 2ND FLOOR 21f ASSEMBLY 419CO ol I I I if 2 12" EXTERIOR WALL SCALE: 1/4" = V-10" 1.2511C SUPPLY - - - - - - - - - - - - - - - - - - ----------------- IF F 2nd FLOOR PLUMBING PLAN EXISTING 'N WATER METER SCALE: 1/4" = V-10" INSIDE EXTERIOR WALL LAV 1/211 WALL STING qSIDE :_RIOR WALL 1/211 WC STUDOR OR OTHER AIR FTANCE VALVE DER COUNTER S.S. _211ro NEW #ABOVE SLAB SERVICE SINK. CONNECT 1/2" H&C SUPPLY FROM EXISTING PIPES ON KITCHEN SINK EXISTING HOT WATER TANK TO REMAIN C6 d, VV H L ARCHITECTURE NEW I CONNECTED NEW KITCHEN SINK & 006 &. - TO EXISTING SANI LINE DISHWASHER CONNECTED nnk FOR K.S. UNDER COUNTER TO EXISTING SINK C&H & TIGHT ALONG WALL W.SUPPLY & SAM. DRAIN (772)631-57,og AA26002573 THESE DRAWINGS CONTAIN NEW S.S. TO EXISTING K.S. ARCHITECTURAL SYMBOLS USED FOR GRAPHIC SCALE: 1/4" V-10" PURPOSES ONLY. SIZE AND LOCATION MAY VARY TO MEET MANUFACTURER'S SPECIFICATIONS. DO NOT SCALE DRAWINGS. ANY QUESTIONS ABOUT D W DIMENSIONS, CONTACT 1/2 go DESIGNER. K.S go 1,0,000 1 i2l; DW 211 1/291 K.S. S.S. 211 PLUMBING IS EXISTING EXCEPT NEW S.S. & DW ADDED AS NEW KITCHEN RISER DIAGRAMS IN EXISTING BLDG 3/411 UR "Vologgli LAV 1/2 1/211 WC RUN H.W. SUPPLY SAME AS WATER TO ALL FIXTURES BUT URINALS, WC'S & D.F. BOTH FLOOR LEVELS 3/411 1/211 3/411 H LAV go (D 3/4 CD rc LAV 1/211 1/211 1.2511 1/211 WC 1219 4 1/211 WC 1/211 H RUN H.W. SUPPLY TO NEW SERVICE SINK NOT TO SCALE 1/211 LAV INSIDE WALL 3/419 1/211 UR D.F. 2ND FLOOR ASSEMBLY 1/209 WC INSIDE WALL 1.25 INSIDE 3/4 1/2 if LAV 411 WC WALL UR /4 3 INSIDE 11 LAV 11 LAV 2 If 3/4 WALL 219 11111111 CO LAV 1/2 UR 1111111111111 R 219 of .0 Ili— 01 if it 1 1/2 219 l0000il! 3 4 WC11 211 f. WC UR INSIDE �.�,IDALL P10100$70 t1h D.F. AR.S'U3,JFCT T0'Afjy cor'496,-C�v, if WALL LAV 1.5 1/2 �QUIRED 0-Y Fl�`LD 111SPECTOPS TH MAY BE NECEnSARY I,% L�jDp 2" 211 LAV _n-,ro LI ALL, �43U; ANGLE STOP FULL OPEW _j, APPL:^ CEDE SHUT-OFF VALVE (EXIST1G) 0 QW) con NO.REVISION/ISSUE DATE & 1ST —REVISION _2Y 2ND—REVISION ZK­�—RD—REVISION CLIENT: A-1 TRUSS COMPANY 4451 ST LUCIE BLVD, FT. PIERCE, FL Rayrfia5d Chladny Licensed Architect #AA-26002573 MAM SANITARY RISER DIAGrxtA WATER SUPPLY DIAGRAM NOT TO SCALE NOT TO SCALE p 1 d Z W 0 W z Lu i6 IT 2 W SURVEY POINTS OF INTEREST G)= 3/4"PIPE DESTROYED - POSITION REESTABLISHED FROM PREVIOUSLY RELATED POINTS & MEASUREMENTS. 4'HIGH HOG WIRE FENCE MEANDERS ALONG R/W LINE - VARIES FROM V S. OF L LINE TO 3'N. OF RM LINE. & CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE GREEN ACRES S/D PLATS. IS)= WOOD LIGHT POLE - CONTROL PANEL ON N. SIDE POLE & UNDERGROUND WIRE$ ON W. SIDE. SOO'09'26W CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED INTHE HARMONY HEIGHTS PLATS, a = GUY WIRE ANCHOR IS 3.7'S. & 3.4'E. OF N.W, CORNER OF PROPERTY. 20.00' FND. 04 CM (NO #) - FND 3' DIAMETER CAR AXLE - 02N. & 0.7' E. - FND. 1" CAR AXLE 02S, & OR E. G = WOOD ELECTRIC POLE (LINE RUNS FROM NO� 9, THEN TO NO. 12) - U/G CABLE ON SW SIDE OF POLE. EX. CONTROL STRUCTURE FND. 4X4 CM (NO #) IS = WOOD ELECTRIC POLE GRATE=19.15 PARCEL ID: 1431-120-0000-000-6 WEIR=16.34 GFND 5/8' IRON ROD & CAP (LB 6674) - FND. 4X4 CM (NO #)1.0 103 = WOOD ELECTRIC POLES ALONG AIRPORT ROAD VARY FROM 0.3'TO 1.0'N. OF THE RIW LINE. ZONING: IL BAFFLE=15.34 ) = - S. & 0.1' W. LAND USE: IND BOTTOM=14.63 S.B.T. FIBER OPTIC UNDERGROUND CABLE MARKER z GUY WIRE ANCHOR 13 5.0'N. & 10.0'E. OF S.W. PROPERTY CORNER. EX. USE: VACANT = WOOD LIGHT POLE WIELECTRIC METER & CONTROL PANEL EX. 8" DDCV & WATER METER M P M X M 0 b3 EX. 8" DDCV & HAIN METER LujsLT BING N EX. 7' C1 WATER I mETA LINK FENCE I .0 EX. TCHAIN 0, LINK FENCE 4 SOO-06'26"W 1214.2 2 -7� x EX. SWALE T_ 77P FT 71'8�7 T7 q- 1 771 EX. DRY DETENTION AREA EX. 8" PVC WATER MAIN & 1 2" PVC WATER SERVICE 95.66' EX. 8" PVC WATER MAIN & j_[7T (per previous site plan) 2" PVC WATER SERVICE lei + Al ��i 10 -I, HO EX. UTILITY POLE (TYP.) x x '0 x EX. 7'CHAIN LINK FENCE TO REMAIN Ilk PROPOSED RELOCATED POSED FENCE EX. 15" CMP 20' PER OWNER INV. EL.=16.57 EX. DITCH fq 1 0 EX. STABILIZED AREA x 246.39' ".1 EX.CONCRETE z EX. TCHAIN LINK FENCE FLUME TO REMAIN 00 WITH BARBED WIRE TO PROPOSED COVERED STORAGE AREA #2 BE RELOCATED x 3,600 SF FFE=21.80' L x 00 EX. SWALE TO REMAIN X, x 'TD 73. 1?ko.o. IN 222.50' z h, . .4 1, . 320.23'- OD i20.O' (o ------- PROPOSED COVERED STORAGE AREA #1 0') 6,250 SF FFE=20.20- CD CT kk 01 x 0 x 0 EX. SWALE TO DRY -Old EX. TCHAIN LINK FENCE WITH MAIL DETENTION AREA BARBED WIRE N _0 EX. COVERED ST . ORAQE I AREA1 EXISTING SWALE TO BE RECONSTRUCTED 0 3,15POSFIFF9=21.901 xv E (TYP.) (3) EX.TRE z Q) C! MIN, S_ EX. ELECTRIC PULL BOX IV 0 K, r- �O '3� x 0) x 0 EX. FIRE HYDRANT TO REMAIN < fh l..Hc)NT I.0 r 7 PROPOSED MITERED END A7 GIVES. EX. COVERED STORAGE ARE , 1 "t /_ SECTION IN REGRADED SWALE 3, 600 &,FFE=?1,.0! x �q� CHRS10 I., . - ;. r '0 PROPOSED WHEEL STOPS (TYP.) 10 ID L ' jr EX. WM REAR 2. EX. TCHAIN LINK FENCE x W LOCATED PROPOSED DRAINAGE MANHOLE WITH GATE BY LOCATE 25' EX. WOOD BRIDGE ZING. EX. BUILPING'A' EX. 6"FiRE LINE COMPANY AND CONCRE INAGE COVERED PRODUCTION AREA 83,200 SF TFC171 (per previous site plan) GE A�RIEA SLAB TO BE NAGE PIP I I x REMOVED I r�.. COVERED STOfi'A '2.03' EX. RISER 3160Q SF FFE=,1,19' FFE=, N .3 PROPOS65' EST IXN=S IL EX. xv x EX. FDC,t\ SHELL EX. BUILDING"D" ---- W ROAD All 0 PROPOSED COVERED EX. 2 STORY C.B.S. BUILDING STORAGE AREA #3 9,080 SF FFE=21.20' EX. ELECTRIC METER EX. BUILDING JRROPOSED EX. LIFT STATION BUILDING EX. 15"CMP CONTROL PANEL ISTORY 2 STOR!� x EX. DITCH EX. 8" PCV EX. FPL TRANSFORMER PAD OFFICE ,�'ftbFFICE X, A BUILDING BUILDING WATER MAIN PROPOSED STRIPING I rill AND WHEEL STOPS 11 5,250 SF 09,920 SF'0L 339.45' 1, FFE=21.93' FFE=21.93, L X.. NCRETEx EX. 1"WATER 7 ........ FLUME TO BE SERVICE 7 REPLACED x x F o PER FDOT I 0 EX. EDGE 0 PAVEMENT v0INDEX#21 10 x XIV L EX. SIGJ*� EX TYPE'D'CURB '.0 x x 40.15' X, EX. LIFT STATIOU 4 Is'- EX- CONCRETE SLAB IW- .1" V - ----------- _X� -- - ---- -ul 18.10' -7 x 1� X'A vl�__ 01 7EX. BUILDING'C' EX. UTILITY POLE I STORY CB.S. BUILDING EX. 1 1/2" 1 �X. SWAI F S00010'08"W 1214.06' 15.46' TO REMAIN UTILI OLE EX. AT&T T BE RISER 900 SF FFE=21.16' EX. LIFT STATION FORCE MAIN EX. CONCRETE EX. CONCRETE POLE BE EX. 2" FORCE MA114 RELOCATED ---- TOP=16.85 TO EX 1 EX. CONCRETE FLUME .1 STORY EX ' ISTORY FND 6/8" IRON ROD & CAP EX. FIRE RELOCATED BY OTHERS EX, UTILITY POLE TO BE BUILDIN I FLUME G EX. 16" CMP BUILDING (LB6674) - FND 5/8" IRON ROD PARCEL ID: 1431-114-0 HYDRANT (TYP.) PARCEL ID: 1431-111-0020_0 RELOCATED BY OTHERS & CAP (LB4223), 0.6' EAST ZONING: IL ZONING: IL LAND USE: IND 10'LANDSCAPE LAND USE: IND PROPOSED MITERED LEGAL DESCRIPTION EX.USE: VACANT BUFFER EX. USE: WAREHOUSES END SECTION IN ) SWALE THE WEST 1/2 OF THE NORTHEAST 1/4 OF THE NORTHEAST 1/4 OF SECTION 31, TOWNSHIP 34 SOUTH, RANGE 40 EAST, LESS AND EXCEPTING THEREFROM THE PREVIOUSLY APPROVED IN 2000 RES. 00-136 PROPOSED ADDITIONS RIGHT-OF-WAY OF ST. LUCIE BOULEVARD AND LESS AND EXCEPTING THEREFROM THE RIGHT-OF-WAY OF FT. PIERCE FARMS DRAINAGE DISTRICT. Total Site Area = 822,848 SF = 18.89 Acre 100 % Total Site Area = 809,799 SF = 18.59 Acre 100 % ALSO LESS THE NORTH 20.00 FEET OF THE ABOVE DESCRIBED PARCEL OF LAND. PRE-201 ROW DEDICATION TO ST. LUCIE BLVD. POST-202 ROW DEDICATION TO ST. LUCIE BLVD. SUBJECTTO: IMPERVIOUS AREA ALL RESTRICTIONS, EASEMENTS RIGHT-OF-WAY RESTRICTIONS OF RECORDS. IMPERVIOUS AREA STRUCTURES 174,400 S.F. CONTAINING 18.590 ACRES, MORE OR LESS. PAVEMENT 246,976 S.F. PROPOSED BUILDING 28,850 S.F. 0.662 AG. 3.56% PROJECT NAME: A-1 ROOF TRUSSES STORAGE 100,998 S.F. PROPOSED PAVEMENT 24,178 S.F. 0.555 AC. 2.99% 4451 ST. LUCIE BLVD. EX. PAVEMENT REMOVED 10,011 S.F. 0.230 AC. 1.24% FORT PIERCE, FL. 34946 IMPERVIOUS/PERVIOUS PARCEL 10 M 1431-112-0001-000-8 TOTAL IMPERVIOUS 522,374 S.F. 63.50% IMPERVIOUS/PERVIOUS FUTURE LAND USE: IND ZONING: IL PERVIOUS AREA 300,474 S.F. 36.50% TOTAL IMPERVIOUS ADDED 43,017 S.F. 0.987 AC. 5.31% OWNERIDEVELOPER: BETKOR PROPERTIES LLC. 4451 SAINT LUCIE BLVD, TOTAL FLOOR AREA = 151,900 SF FORT PIERCE, FL 34946 BUILDING AREA PARCEL ID #: 1431-140-0000-000-8 Phase One 94,900 S.F. Proposed Office 9,920 S.F. 0.228 AC. 1.23% FUTURE LAND USE: IND Office 5,000 S.F. ZONING: Ix Proposed Manufacturing 18,930 S.F. 0.435 AC. 2.33% OWNER: BETKOR P PERTIES LLC Phase Two 52,000 S.F. 4451 SAINT LUCIE BLVD. FORT Pf ERCE, FL 34946 TOTAL BUILDING AREA 28,850 S.F. 0.662 AC. 3.56% INV. EL.=17.31 EX. 2 - BACKFLOW PREVENTERS AND 1" METERS EX. 15" CMP 1 800*1 1 0*08"W EX. 12" PVC WATER MAIN 80' 1 81 EX. WOODEN POWER POLE a > z 1�� 0 so IN FEET ) I Inch - 60 ft. LEGEND EXISTING SPOT ELEVATION PROPOSED FLOW ARROW PARKING STALL COUNT EXISTING CONCRETE PROPOSED CONCRETE PROPOSED ASPHALT EXISTING ASPHALT 0 EXISTING UTILITY POLE N.T. 1-5 NEW TREE IN PROPOSED PARKING LOT DATUM: ALL ELEVATIONS ARE BASED ON NORTH AMERICAN VERTICAL DATUM OF 1988a to .1 *LANDSCAPE NOTE: C ALL PROPOSED LANDSCAPING SMALL �0 M COMPLY TO ST. LUCIE COUNTY CODE 7.09.00 W 1 0 0 z PROPERTY LINE z I-T x x EX. OAK TREE TO REMAIN 1 1 �2 *PROPOSED 368' SLC APPROVED CONTINUOUS HEDGE TO.C. (38872' O.C. = 194 SHRUBS) Z 0 *PROPOSED SLC APPROVED TREES EVERY 1O'ALO11 RIGHT OF WAY (APPROX. 9 TREES) F-1105 EX 6" PVC FOF.CE MAIN Tree Mi iz;. Lu�u M Z PROPOSED NEW TREES Al �a (N.T.) �.j E Item 15'LANDSCAPE BUFFER Oaks Removed PROPOSED STOP SIGN AND STOP BAR (TYP.) Oaks Preserved z . 01 C2 EX. 10" DDCV & BACKFLOW PREVENTOR, EX. TREES TO BE REMAIN EX. FORCE MAIN VALVE EX. SWALE TO BE RECONSTRUCTED EX. SIGN TO REMAIN PROPOSED MITERED END SECTION IN REGRADED SWALE EX. TOB OF FT. PIERCE FARMS WATER CONTROL DISTRICT t CANAL NO. 26 Developer proposes removal of three (3) oaks totaling 40 inches DBH and preserving the remaining oaks in the area of development being 244 inches DBH. The developer also proposes installing new oaks in the new parking islands as required by St. Lucie Code. SET5/8"IRONROD&CAP (LB6674) Parkinq Information INV. EL.=17.48 20.00' I Proposed Development: Manufacturing Area (1112,930 SF @ 1 spaces per 1000 SF) I=> 113 Stalls TOTAL AT BUILDOUT Office Area (15,170 SF @ 1 spaces per 200 SF) => 76 Stalls Total Site Area = 809,799 SF = 18.59 Acre 100 % Total Parking Required => 189 Stalls Total Parking Provided => 184 Stalls 1POST-20'ROW DEDICATION TO ST. LUCIE BLVD. Required Handicapped => 6 Stalls Provided Handicapped => 6 Stalls IMPERVIOUS AREA BUILDING 129,000 S.F. 2.961 AC. 15.93% Proposed Parking for Phase I (See Sheet 2) => 77 Stalls Handicap Parking => 6 Stalls PAVEMENT 278,868 S.F. 6.402 AC. 34.44% IMPERVIOUS/PERVIOUS TOTAL IMPERVIOUS 407,868 S.F. 9.363 AC. 50.37% PERVIOUS AREA 401,931 S.F. 9.227 AC. 49.63% EX. 12" PVC WATER MAIN BUILDING AREA CA Manufacturing Building 112,930 S.F. 2.592 AC. 13.94% Office Building 15,170 S.F. 0.348 AC. 1.88% TOTAL BUILDING AREA 129,000 S.F. 2.961 AC. 15.93% Ar,'Z "U10JUTTO ANY CONIX711CNO AtGUIRED SY RUD INSPECTORS VAT LIU 9111 NVISSAXY IN 0AW �0 C2.L',TLVWi7"', ALLVFU�MU CODES, Building Height: Two Story (Height of 35 FT.) BUILDING SETBACKS J!LL FRONT: 25 FT. SIDE: 10 FT. SIDE CORNER: 20 FT. REAR: 20 FT. PROVIDER QF UTILITIES: WATER & WASTEWATER: FORT PIEROE UTILITIES AUTHORITY Z U 0 z LO LU z (n 0) a: . 0 1.- C:) W M LO K 2 0) Lo 0 =) .t Lo z Z z 0 cy) 'Wt W z C� 40 U') r- 04 t z < ILL to N -01, 00 W 'T C� 22 (.5 04 CD z z I 1L 0 04 L� LL LU r, 00 1129 0 W z co < 0 m < F-: 0 M .4- 0 LU ca �01 ILL. CL 420 F= Ix Uj 0 (a) z 2 z z 0 F_ 0 z _j W LjL 2 z 113 < co Z j Uj a. LLJ F_ z < .J W 0 z M CL 0 0 UJI F- < Lu U) ME 0 z z R IMM a I W e, 2 S) 6 IW i D R. 'NNE #5621 1934 T FT. PIE phone: 77 15-251 I OF2 figation Table Total Inches (D13H) 40 244 New Oaks 15 Mill d W 0 W Z Z I P 5; � �O Z Z cc 0 0 C Z M PI CD P P. 0 00 W 0 m X P P EX. TCHAIN t8 Pi LINK FENCE �SO0009'26"W 1214.20' EX. DRY DETENTION AREA PROPOSED PHASE 3 EX. DITCH: EX. STABILIZED AREA PROPOSED COVERED STORAGE AREA #2 3,600 SF FFE=21.80' EX. SHELL ROAD FTP 25 EX. UTILITY POLE d EX. 16" CMP EX. DITCH r I � = 1 PROPOSED COVERED STORAGE AREA #3 . ..... 9',0'8'0 SF FFE=21.20' PARCEL ID: 1431-120-0000-000-6 ZONING: IL LAND USE: IND EX.USE: VACANT �'.�6.6: � — - , ' " ' , '4 ------------ — I ____ - EX. COVERED STOkAQE�AkEA 3,6PO SIP FFI�=21,9Q' PROPOSED PHASE1 17",Ex7c,�ERED STORAGE AR _71 3,606,S0yFE=?,,.93', L EX. BUILDING'A' COVERED PRODUCTION AREA 83,200 SF COVERED STORAGE A' REA FFE=22.03' 3,60Q SF FFE,=�1.89' L _J _JL. ft. EX. BUILDING "D" EX. FDC EX.2STORYC. &BUILDING 6— PROPOSED PHASE 2A & 2B. EX. BUILDING �PROPOSED, 2A-FIRST 2 BAYS 'B' G 'E', 2[3-REMAINING 4 BAYS 1STORY RY BICE OFF111 E OU FILFD I N G SUILDING 5 250 SF 9,920 SF L FFE=21.93- 7 EX. 1"WATER FFE=21.93' SERVIC7E 11 1 Et Eli! E),. EDGE OF 1-711 PAVEMENT 7&U, J 4 EX. LIFTIT I ---------------- ­�7 EX. BUILDING ' C. J 10'LANDSCAPE S00*1 708"W 1214.06' F_ 1 STORY C.B.S. BUILDING BUFFER 900 SF FFE=21.16' Install Handicap I 7PARCE L ID: 1431-114-0001-000-4 Sign Per FDOT PARCEL ID:1431-111- Fo�� Index No. 17355 ZONING' IL Install Striping Per FDOT Index No. 17346 NOTES: 1. TOP PORTION OF FTP 25 & 26 SHALL HAVE A REFLECTIVE BLUE BACKGROUND WITH WHITE REFLECTIVE SYMBOL AND BORDER. 2. BOTTOM PORTION SHALL HAVE A REFLECTIVE WHITE BACKGROUND WITH BLACK OPAQUE LEGEND AND BORDER 3. FTP 25 & 26 MAY BE FABRICATED ON ONE PANEL OR TWO. 4. FTP 25 IS FOR USE IN AREAS WHERE SPACE IS LIMITED. 5. REFER TO FDOT INDEX NO. 17355 FOR HANDICAP SIGN STANDARDS. HANDICAP SPACE DETAIL WHITE HANDICAP SIGN BLUE WHITE F11MIA BLUE (A 111110� CA (:�3 5711h) EX. 1 STORY BUILDING 2663.W PROPERTY LINE 0 50 IN FEET I inch — 60 ft. LEGEND ��s EXISTING SPOT ELEVATION 1)91� PROPOSED FLOW ARROW PARKING STALL COUNT EXISTING CONCRETE PROPOSED CONCRETE PROPOSED ASPHALT EXISTING ASPHALT 0 EXISTING UTILITY POLE C� Z Varies Provide 1111" to 1/4" contraction joints at 10'centers (max). -M rn 0 7 0 Z 0 W Compact Subgrade to 98% of the Maximum Density as u) NOTES: Determined by AASHTO T-99 1. Use 3,000 P.S.I. Concrete At 28 Days for sidewalk construction. D' 14V I I 'E: W Z Z . rJ m X 0 W m 0 4" THICK SIDEWALK DETAIL a, Z 2" ASPHALT PAVEMENT FOOT TYPE SP 9.5 FOOT P *E S P 9 '1 8" LIMEROCK OR COQUINA BASE 98% Modified Proctor tea max. dry density. EX. SIGN LBIR min of at least 100 12" min. STABILIZED SUB -BASE COURSE /. 9 M I �mAx E 8% Modified Proctor test max. dry Idensit Stabilized to an LBR of at least 40 TYPICAL PAVEMENT SECTION L —1 THESIS PUNIS A,*JD ALL REQUIRED BY RUD IM"11"ECTOPS THAT My EE. NFOff"JuxY I.N mr)�S_rj TO C 11 ILI 11-1 LY YJ I ' 1 114 X L APPL:0A3Lj1' cCi)ES. EX. 12" PVC WATER MAIN I ;i_2 M. lu lu 1wiLt 1JY Construct Concrete 1­_ -I- I..., 111� 5tall striping per )OT Index No. 17346 PARKING AREA DETAILS (TYPICAL) Z (j Z Z W) 0) LLI 0 F_ 0 W Ld M 0 5 LO N W U-) Lr) Z 2 a :3 WZ Z Z 0 LO Z U_ N (0 0 UJ UJ LLF 't UJ Z Z (.5 CN,4 0 5- < 0 L� U- 00 Z 0 LLI 06 ILL CL 420 TqP11M Z 74 0 0 Z 0 0 0 Z _J Z Co Z Z J IV) < W CL .J LL, M CL W Z U) U) < W < J Z x a. 0 5 CL LLJ 0 0 LLJ U) 0 Z Z CO) FAII (DATE) ir 1104. KUMMY, 15-251 2 OF 2 CONSTRU KEY WEST �%.. alp j '0060 TION PLANS AND SPECIFICATIONS 1100m Aml TRUSS SECTIONS 28, 29) & 33, TOWNSHIP 34S, RANGE 40E ST, LUCIE COUNTY, FLORIDA Proiect Location INDEX OF SHEETS I COVER 2 OVERALL KEY SHEET a -CT 3 DEMOL"47ON PLAN 4 DEMOLITION PLAN 5 HORIZONTAL CONTROL AND STRIPING PLAN L 1-7 A 6 HORIZONTAL CONTROL AND STRIPING PLAN 7 PAVING, GRADING, & DRAINAGE PLAN J 8 PAVING, GRADING, & DRAINAGE PLAN 9 STORAGE BUILDING #3 CONSTRUCTION PLAN ST LUCIE BLVD COU TY ROAD 608 EAST E 10 PAVING, GRADING AND DRAINAGE DETAILS 11 STORMWATER POLLUTION PREVENTION PLAN 12 SPECIFICATIONS �RqEl i� I Lbli AND ALL PROP OS.1-1) RizLWIRELI By HUD MpE IN E 0 f-l" cr -DURS THAT 8� RY I'N ORD M � C -"'�4'1"Ly K'1171LI 'Ll L APPU a4XE CCDE& VICINITY MAP E ENGINEERING DESIGN & CONSTRUCTION, INC. 1934 TUCKER COURT FT. PIERCE, FIL 34950 DATUM NOTE: t4o Cft phone: 772-462-2455 ALL VERTICAL ELEVATIONS SHOWN ON THESE PLANS REFERENCE THE It. RENN 10. 51, fax: 772-462-2454 NORTH AMERICAN VERTICAL DATUM 1988 (NAVD), A TYPICAL ACCEPTED 0a+lUCSKEW'�6IJIRTl I BOARD OF PROFESSIONAL ENGINEERS CONVERSION FROM NAVD TO NGVD IS NAVD = NGVD - 1.475' F!A� ft& CERTIFICATE OF AUTHORIZATION NUMBER 9935 qr� Lf) C4 1 L0 qr� ii� to ll�— z U.J z w 0 d z w m 0 w b 9 Ls 6; I 0 0 p EX. DITCH EX. STABILIZED AREA 0 EXDRYDE TORAF— Imw PARCEL ID: 1431-120-0000-000�6 ZONING: IL LAND USE: IND EX,USE: VACANT 2 0 EX. 7' -'8 INO LWTALT..___] CHAIN 157 LINK 79 =ENCE T's'mp I -T- -T I-T 1 1 7 -17 1 1 F-T 1 --7 1 -F-1 T F71 71 r�d 7 FT� _FT FFI T T F F-1 T F 1-1-1— — — — t9 41678 PROPOSED COVERED STORAGE AREA#2 3,600 SF FFE=21.50' -4, EX. SWALE TO DRY DETENTION AREA N T 0 > z L A z X z 0 m i 0 6 E�. BUILDING'A' COVERED PRODUCTION AREA 37577 I — Elf,-- 83,200 SF ----------------------- 0 0 PROPOSED COVERED STORAGE AREA #1 6,250 SF MIN FFE=21,50' 15'LANDSCAPE BUFFER PROPOSED PARKING LOT EX, UTILITY v EX. FDC EX. I POLE SHELL I ------------ ROAD Hill 9 EX. 15" -T.F—FICE CMP EX. 1 99�llN� " — - : FFE-o— E-11 . — :;,: .�i! ij�::�i EX. DITCH WATER r�#O, i7,l SERVICE EX. EDGE OF PROPOSED COVERED STORAGE 0 AREA#3 PAVEMENT 9,080 SIF FFE=21. EX. SIGN 50' EX. LIFT STATION ------------- ------ ----- ----- -------- -- E X.. ILDING 'C'7/ 10'LANDSCAPE 1 STORY C.B. BUILDING BUFFER 900 SF FFE=21.16' PARCEL ID 1431-114-0,001-000-4 PARCEL ID: 1431-111-0020-0004 ZONING: IL ZONING: IL L AND USE IND LAND USE: IND EX USE VACANT EX. USE: WAREHOUSES PROPOSED OFFICE BUILDING 'E" 9,920 SF FFE 21.93 NAVD L —1 I C 0 0 40' 40' 1 120 EX. SIG IN 91, W lol 1 74T EX. 12" PVC WATER MAIN PROPERTY LINE 0 60 IN FEET I inch = 60 ft. LEGEND EXISTING SPOT ELEVATION PROPOSED FLOW ARROW PARKING STALL COUNT EXISTING CONCRETE PROPOSED CONCRETE PROPOSED ASPHALT F-1 EXISTING ASPHALT 0 EXISTING UTILITY POLE 1 12, Z Z 7, K) cf) Z LLI 0) 0 C:) Lo z 2 0.) Lo r3m --t U,) zz z 0 CY) Ld z � 0 C14 < I U,) Z LL C*4 'q- 0 r-4 (.0 N 0) Fp LLI �--m w - t I (n 5 cf) w I CNI E 04 (o o M Lu C.) I,- z Z X r-, Z) CN 0 W b5 r, 00 C: z Co 0 < 0 0) F-: m 0 LLI Ca LL CL 4CU- F- Lu 0 (m) w w x L z 2 :E z 0 x 4 z w 9 w 0 U) U) J��o I-- Lu w oc U) Lu LLI 0 #59+11 193* CKERIAT j FT.. L 3419( p hon m hon -Ak- 15-251 2 OF 12 0 0 z 0 0 —j LL G z 0 C.) Lu -j 16- z R (1) (5 Z w 0 6 z z 0 z ILI m 0 z 0 w z E SURVEY POINTS OF INTEREST (D= 3/4"PIPE DESTROYED - POSITION REESTABLISHED FROM PREVIOUSLY RELATED POINTS & MEASUREMENTS, CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE GREEN ACRES SID PLATS. CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE HARMONY HEIGHTS PLATS. FND, 4X4 CM (NO #) - FND 3" DIAMETER CAR AXLE - 0.2'N. & 0.7'E. � FND. I'CAR AXLE 0.2- S. & offE. FIND. 4X4 CM (NO #) G) = FIND 5/8" IRON ROD & CAP (LB 6674) - FIND. 4X4 CM (NO #)1.0'S. & 0.11 W. 0 = S.B.T. FIBER OPTIC UNDERGROUND CABLE MARKER 4- IT I GH HOG WI RE FENCE M EAN DERS ALON G R/W I -I N E - VARI ES FROM VS. OF RfW LINE TO 3'N. OF RIW U NE. WOOD LIGHT POLE - CONTROL PANEL ON N. SIDE POLE & UNDERGROUND WIRES ON W. SIDE. GUY WIRE ANCHOR 15 3.7'S. & 34E. OF N.W. CORNER OF PROPERTY. S= WOOL) ELECTRIC POLE (LINE RUNS FROM NO. 9, THEN TO NO, 12) - U/G CABLE ON SW SIDE OF POLE. G) = WOOD ELECTRIC POLE (B = WOOD ELECTRIC POLES ALONG AIRPORT ROAD VARY FROM 03TO 1.0'N. OF THE RIW LINE. S= GUY WIRE ANCHOR IS 5.0'N. & 10.0'E. OF S.W. PROPERTY CORNER. 8 = WOOD LIGHT POLE W/ELECTRIC METER & CONTROL PANEL I MATCHLINE STA: 22+50.00 LEGEND ,,C� EXISTING SPOT ELEVATION PROPOSED FLOW ARROW PARKING STALL COUNT EXISTING CONCRETE PROPOSED CONCRETE q;fg, 11 �i PROPOSED ASPHALT w EXISTING ASPHALT 0 EXISTING UTILITY POLE N.T. 1-5 NEW TREE IN PROPOSED PARKING LOT DEMOLITION Z 0 20 z L0 Z' uj U) 0) w w IN YEET 0 C:) w w I inch = 20 ft. JIL: Lf) IL 0) Lo %T LO zw z IL 0 cy) -t z IL z 04 -1 0 DATUM: 1E LL 04 't Z2 r<4 (0 04 in Fr ALL ELEVATIONS ARE BASED Lu LLJ Lj -t - (n 0 ON NORTH AMERICAN IE UJ �e ( 1 C-4 tu _) 04 (D 0 z z VERTICAL DATUM 6F 1988. 1E W IE 0 00 IE C) 0 C.) it IE z cy) 0 < 0 m uj 06 LL CIL 4- w 0 EX. COVERED STORAGE AREA 0 PROPERTY LINE 3,600 SF FFE=21.93' 0 50. SAW CUT AND REMOVE EX. ASPHALT Y 0 x X�lx� + x X�00 X,95� 0 RELOCATE LIGHT POLE EX. BUILDING'A' tq COVERED PRODUCTION AREA I 0 83,200 SF 4N� b, EX. COVERED STORAGE AREA FFE=22.03'NAVD 3,600 SF FFE=21.89' REMOVE EX, FENCE REMOVE EX. BOARDWALK L 0 RE OVE EX. CONCRETE SLAB FL FL FL FL p. 0 XNI CONCRETE EX. BUILDING "D" EX. FENCE TO REMAIN SLAB CONCRETE S B EX. 2 STORY C.B.S. BUILDING ws 0 ;C��ATr x 50.00' Ol .,logo ws z ws ws-�J-A 00 El OD 9.9 Xl RELOCATE EX. TREES + + 5.95' X2 x gN SAW CUT AND X7.090 REMOVE EX. ASPHALT x 0 F9 x7o 46 5- 0 EX. BUILDING'B' WM TOP )F I STORY OFFICE El El BA IK BUILDING 5,250 SF m FFE=21.93'NAVD wM VMOLND lwM— \NM 5.95' x 0 PHALT REMOVE EX. SIDEWALK AND AS REMOVE EX. FLUME N,36 xAq N90 1� I Xqgs xs� ",g,50.00' x .51 RELOCATE POWER I— .78 EX. SIGN 10 REMAIN POWER POLE AND AND ELECTRIC BOX ELECTRIC BOX TO REMAIN Zs 7 0 I z 2 z .5 'w z 0 E cn j a. cn m z 0 Q M TOM 4 0 m 9?0� — 7.0 X7.019 '701, .�Og, A REMOVE LANDSCAPE ISLAND. R.J. PRESERVE AND RELOCATE MAILBOX. #56i, — 1111, — — — — — UAI&T UAT&T — — — — — — UAT&T UATJ, 0 0b BID: 20+00.00 ..... . j IJATIT� -m----------WAT&T- UAT&T UAT&T 19347 4+00 — —WM— WM 2+00 1+00 —UP FT. PIE 5U — — — — — — Wm— phone: Wm— — — — — — WM wm wm ------ xq0 — — — — — — =M x FM FM FM — — — — — — 1 0 0 _fM - — ----- qi5l X�99.& 10'. k, X,q.gl 5 xoo� —==±- rtj.o� "l 5 1096 18-60' T&T �,q.v A X�93P IRON Xl� 51 20.90' 0— 0— 0— 0 O—s�� 0 EX. TOP OF BANK PROPERTY LINE S00*1 0'08"W 1214.06 N 89'48'19.1 W / c EX� FENCE 35.35' r7 Till a ,NV'%'2 J K "/Z No -4 , RNEDY,,P. 0 m&_0,quIlf , 11 - 7 — amn- - 15-251 3 OF 12 z 0 u z 0 0 —j U. L7 z 0 0 w z d d z z 0 w Q z w 0 z 0 w SURVEY POINTS OF INTEREST 3/4" PIPE DESTROYED - POSITION REESTABLISHED FROM PREVIOUSLY RELATED POIN rS & MEASUREMENTS CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE GREEN ACRES SID PLATS. CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE HARMONY HEIGHTS PLATS. FND. 4X4 CM (NO #) FND 3- DIAMETER CAR AXLE - 02N. & 07E. - FND. V CAR AXLE 0,2'S. & 0.6- E. FND. 4X4 CM (NO#) G) m FND 518" IRON ROD CAP (LB 6674) - FND. 4X4 CM (NO #)1.0'S. & 0,1'W, 0 = S.B.T. FIBER OPTIC UNDERGROUND CABLE MARKER 4'HIGH HOG WIRE FENCE MEANDERS ALONG R/W LINE - VARIES FROM VS. 6F R/W LINE TO 3'N. OF RIW LINE. WOOD LIGHT POLE - CONTROL PANEL ON N. SIDE POLE & UNDERGROUND WIRES ON W. SIDE. GUY WIRE ANCHOR IS 37S. & 3AE. OF N.W. CORNER OF PROPERTY. G= WOOD ELECTRIC POLE (LINE RUNS FROM NO. 9, THEN TO NO. 12) - U/G CABLE ON SW SIDE OF POLE. = WOOD ELECTRIC POLE = WOOD ELECTRIC POLES ALONG AIRPORT ROAD VARY FROM O.TTO 1.0'N. OF THE RIW LINE. GUY WIRE ANCHOR WOOD LIGHT POLE -�00 x x4T SAW CUT AND REMOVE E). ASPHALT 0 AND CONCR TE FLUME 4.�A — — — — 777 7-77-71 .,4�11 0 29 0 EX, FENCE TO BE REMOVED SAW CUT AND 01 REMOVE EX. ASPHALT �,S.,62 -.3D50— — -- — — — — X�0� X,04 EX. FENCE TO BE REMOVED r 0 )i� 0 0 1 XI:\l 0 IEX. LIGHT POLE TO BE RELOCATED 0 . �3t MOVE EX. ASPHALT Be`1 D xj \qj55 14 0 MATCHLINE STA: 22+50.00 x,gip �,00 LEGEND EXISTING SPOT ELEVATION PROPOSED FLOW ARROW PARKING STALL COUNT EXISTING CONCRETE PROPOSED CONCRETE PROPOSED ASPHALT lilm -m! H. 11 EXISTING ASPHALT 0 EXISTING UTILITY POLE N.T. 1-5 NEW TREE IN PROPOSED PARKING LOT 0 20 IN FEET I inch = 20 ft. DATUM: ALL ELEVATIONS ARE BASED ON NORTH AMERICAN VERTICAL DATUM OF 1988. Z Z L0 U) 2F 0) Lu 0 0) w 0: 0 C) LLI LLI w m L0 z 2 0) Lo C5 =1 L0 z Z w z 0 co "'t -,t -, z c� z Lo < F,- LL IN 0 <N (0 N V-) rr LLJ ui qct 1 00 LLj 1 04 Efl LLI cn 04 Q0 0 z z r-- "t x r, I (L N u- 0 w 00 -,Zj- z co 0 ICU 0 Lu ad u- CL F= Lu 0 (m) 0 E 0 -Ml E M C� V IL z 1: /011 V r 0 IE z 1E > 0 IE IE IE r IE IE ]I -- A - 4—v, 0 IE U. 1E 1E z IE 1- JE cl) cl) [L z IE 0 IE 1E F- IE .1 z IE M 1E 0 0 IE IE 17- z R %'6 wc 4,0 , R.J.Ji !NEDY #56 rm-, 1934 )%W FT. P1 �0��?L4A50 72 .�4 phone: 15-251 4 OF 12 W SURVEY POINTS OF INTEREST 3/4"PIPE DESTROYED - POSITION REESTABLISHED FROM PREVIOUSLY RELATED POINTS & MEASUREMENTS. CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE GREEN ACRES SO PLATS. CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE HARMONY HEIGHTS PLATS. FND. 4X4 CM (NO #) FND 3" DIAMETER CAR AXLE - 0.2'N. & OXE. - FND. V CAR AXLE 0.2- S. & 0.6- E. FND. 4X4 CM (NO #) FIND 5/8" IRON ROD CAP (LB 6674) - FND. 4X4 CM (NO #)1,0' S. & 0.1- W. S.B.T. FIBER OPTIC UNDERGROUND CABLE MARKER EX. BUILDING'A' COVERED PRODUCTION AREA 83,200 SF FFE=22.03'NAVD EX. BUILDING "D" EX. 2 STORY C.B.S. BUILDING 4'HIGH HOG WIRE FENCE MEANDERS ALONG RfW LINE - VARIES FROM VS. OF R(W LINE TO VN OF R/W LINE. WOOD LIGHT POLE - CONTROL PANEL ON N. SIDE POLE & UNDERGROUND WIRES ON W. SIDE. GUY WIRE ANCHOR IS 3.7'S. & 3.4'E. OF N.W. CORNER OF PROPERTY. WOOD ELECTRIC POLE (LINE RUNS FROM NO. 9, THEN TO NO. 12) - U/G CABLE ON SW SIDE OF POLE. WOOD ELECTRIC POLE WOOL) ELECTRIC POLES ALONG AIRPORT ROAD VARY FROM OZTO 1.0'N. OF THE RfW LINE. S= GUY WIRE ANCHOR IS 5.0'N. & 10.0'E. OF S.W. PROPERTY CORNEI. (3 = WOOD LIGHT POLE WIELECTRIC METER & CONTROL PANEL MATCHLINE STA: 22+50.00 TIT EX. COVERED STORAGE AREA 3,600 SF FFE=21.93' STA:21+86.81 OFF:9.13' EX. COVERED STORAGE AREA l I 'Il? R �u -0- ER il 3,600 SF FFE=21.89' :21+79.80 "Tillill OFF:39.12' ulli I'N STA:21+79.75 llill."!1611fill, i I ii; i 9 lgi OFF:52,49' STA:21+61.7 IN �4,lqiglg OFF:52.43' mg FL FL FL FL STA:21+28.76 IMMM, OFF:-28.98' lim STA:21+15.26 OFF:24,T �i.11p ii; l OFF:-29.02' STA:21+20.25 STA:21+18,90 OFF:-24.00' STA:21+15.30 OFF:-42.02" Ws OFF:52,23' OFF:-59.18' STA:21+06,75 0 TE ..... 50.00' 10.1 1-1111"Nill 1 IQ 0 897 STA:21 +1 18 PROPOSED STORAGE AREA #1 6,250 SF FFE=20.20'NAVD STA:21+86.81 OFF:59.13' STA:2+30.91 OFF:191.13' INSTALL WHEEL STOP (TYP,) N.T. 3 -1 LEGEND EXISTING SPOT ELEVATION PROPOSED FLOW ARROW PARKING STALL COUNT EXISTING CONCRETE PROPOSED CONCRETE lip liffl 11H PROPOSED ASPHALT EXISTING ASPHALT 0 EXISTING UTILITY POLE N.T. 1-5 NEWTREE INSTALL HEDGE PER SLC LANDSCAPE CODE 7.09.00 0 20 IN FEET I inch = 20 ft. DATUM: ALL ELEVATIONS ARE BASED ON NORTH AMERICAN VERTICAL DATUM OF 1988. PROPERTY LINE Z U CD Z Lf) w 0) 0: 0: Ld Ld 0 c) ui m 0) Lo 't LO z Z z 0 cr) qt IRt Ld z CN � 0 i LO '< F- z < 0 N Q0 N On y LLJ w I (n 0 W CN E� Lu (J) Y L) (0 0 z z L) X I CL 0 w C4 L� U- P, 00 0- z 0 < 0 5� 0 co uj 06 LL 'CL 4- M r- Lu a u 7 z �5 z IL z 117 G IL ROW DEDICATION z 1E STA:1+04.79 0 OFF:164.46' 1 IE z STA:0+89.78 4 IL OFF:165.13' 16LANDSCAPE IL 0 STA:0+63.78 1E INSTALL TREES PER SLC BUFFER LANDSCAPE CODE 7.09.00 INSTALL STRIPING OFF:165.04' N.T. 1 IL STA:11+84,79 1E ---�OFF:164.65' STA:0+45.80 N.T. 2 STA:0+58.97 w r, N, i F, i! ff, I N 0 FF: 110.03' Pit Hill 0. Hill STA:0+45.97 OFF:109.98' ME Hl U nl NAM z ws W X 0 F F: - 12 11-1. 1�8�1 1, 11, % Im ep1g, DO STA:21+26.71 T :2 +06.80 �c CIO Nil OFF:39.23' 01 N.T. 5 OFF:26.92' S 0 g"I lighoglify m, TA:21+01.82 Fill 8 14' I ITT NO " Tl 11-111,111"i . .. . . ...... 5' STA:20+94.83 -..,.-+29..79 glmlilI! OFF:101.69' LK Toll %illmil", SSIDEWA V IT Egli STA:2+29.82 I H 1 0 5, 4..74' . . . . . . . . . M u ®r T, EX. BUILDINGH PROPOSED BUILDING'E' % 1; - 11 ! , i. --jr glillilp"I'l (D luilil IIIIIIlIIMIMMI OFF-47.76- I STORY OFFI 2 STORY OFFICE IM '20+ 8.61 STA 8 'j, CD P CE BUILDING TOP )F L] BUILDING 5,250 SF STA:20+84.80 BA IK� �*,,* Iiiijjijilj!�lillid! 9,920 SF al l-i FFE=21.93'NAVD OFF:44.16" STA:20+84.78 'Ilig TIM 0 :20+68.81 STA ln MOL ND OFF:60.16" 2 OFF:4T81' ! N lu ll�i ;ll4iMMIill!l!4 17, All, FFE=21.93'NAVD T1 339.45' 03, �jg limi. i T j il! Ual i llil!!l i 19 0 Mlii�,il iwgl-, ST Till lici T tiq iN lo'! STA:5+71.54 STA:5+01.5 STA:20+36.30 STA:20+57.841---� . I ill , ill, I ? iiiiii , ; ij� l) m R F RIN! OFF:-42.23' It OFF:29.48' 9 UW STA:0+46.1 91 f:42.25' OFFA2.06 '010 MHT 9 STA:20+38.90 STA:20+56.40-z� IV -'s Pill gm, l!,. I ill., 1 Ill. OFF:44.64' STA:20+38.97 R-59.28' OFF:33.97' 0 F STA:2 OFF:-121.28' 5'SIDEWAL STA:20+36.26 OFF: 0 STA:20+58.76 /-OFF:-29,23- OFF:61.16' 5 STA:20+30.56 STA:4+16.25 STA:20+31.25 OFF:33.8, '//-OFF: 10, OFF:31 �50 -24.25' 18' �j 50.00' lilj!li�� l I MR, 30.91 t8.25 OFF:49.56' jillii'll'i il 81.54 STA: 1 +51 54 -- S :4+16 8 ijI%,,illl filgillifl 32' STA:3+24.25 STA:1+91.54 STA.1+31.54i STA:0+54 23 0 F:1 . i-, . All i Tj 1 lill l I TA:1+81.54 STA:1+61.54 STA:0+64.211 111, R I j OFF:2825' STA:2+2 OFF:40.66' OF --40 64- in 9q, OFF:40.'57'- OFFA0 21 Z4 OFF:39.71' OFF:29.67' liM, illilli + OFF:30.16' Ill OFFAO.50' 0.21 INSTALL STRIPING AND 0 . . . . . . . . . . OFF:39,75' -7 1, � C) WHEEL STOPS FOR 7 SPOTS STAA+21.28 STA:3+43 22 STA:3+37.88 40.15' OFF:13.42' OFF:18.32' OFF:13.29' OFF:13.35' UAT&T UAT&T UAT&T - - - - - - UAT&T UATJ, 2�1.61' BP: 20+00.00 -T UATIT UAT&T a M- 5+00 4+00 WM - _c,&+.w W 2+00 1+00 O� )0 -wM - - - - - - wM - WM - - - - - - UAT& c wm Wm wm 0 FM FM FM FM FM - 73.17' 11,1Z 18.6 0' 15 5 uAT&T 20.90' 0- 0-0-0-0-0- o-6 PROPERTY LINE 1 0'08"W 1214.06' I =q� W F- s00* N 89*48'19" 35.35' 15.46' F- �,a �Ibmi WTI 1934T FT. PIE phone: a n Pas In It 0 z -j U. 0 z z a. 00 L) z a. z 0 z u 0 w N 0 z R co P.E. I 15-251 5 OF 12 uk z 11 SURVEY POINTS OF INTEREST G> 3/4" PIPE DESTROYED - POSITION REESTABLISHED FROM PREVIOUSLY RELATED POINTS & MEASUREMENTS. CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE GREEN ACRES S/D PLATS. CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE HARMONY HEIGHTS PLATS. FND. 4X4 CM (NO #) - FND T' DIAMETER CAR AXLE - 0.2' N. & 07 E. - FND. V CAR AXLE 0.2'S. & 0.6'E. FND. 4X4 CM NO#) FND 518"IRON ROD & CAP (LB 6674) � FND. 4X4 CM (NO #)1.0' S. & 0.1' W. S.B.T. FIBER OPTIC UNDERGROUND CABLE MARKER 0= 4'HIGH HOG WIRE FENCE MEANDERS ALONG RAW LINE -VARIES FROM VS. OF R(W LINE TO TN. OF RIW LINE. G) = WOOD LIG HT POLE - CONTROL PAN EL ON N. S I DE POLE & UNDERGROUND WIRES ON W. Sl DE. = GUY WIRE ANCHOR IS 37S. & 3.4'E, OF NW CORNER OF PROPERTY. m WOOD ELECTRIC POLE (LINE RUNS FROM NO. 9, THEN TO NO, 12) - U/G CABLE ON SW SIDE OF POLE. = WOOD ELECTRIC POLE = WOOD ELECTRIC POLES ALONG AIRPORT ROAD VARY FROM 0.3'TO 1.0' N. OF THE R/W LINE. = GUY WIRE ANCHOR IS 5.0'N. & 10.0'E. OF S.W. PROPERTY CORNER. = WOOD LIGHT POLE W/ELECTRIC METER & CONTROL PANEL PROPERTY LINE �k2.58 iP. 2 jo, 16-28' &_-Li2 7,9 61 wm wm — 1��_ —7 FT I _T`T6,�91­1 —7 7 F—F LEGEND EXISTING SPOT ELEVATION PROPOSED FLOW ARROW PARKING STALL COUNT EXISTING CONCRETE PROPOSED CONCRETE 0 g"M ' 5m �� 2� PROPOSED ASP HALT F1EXISTING ASPHALT 0 EXISTING UTILITY POLE N.T. 1-5 NEW TREE IN PROPOSED PARKING LOT > z 1�� 0 20 IN FEET ) I inch = 20 ft. DATUM: ALL ELEVATIONS ARE BASED ON NORTH AMERICAN VERTICAL DATUM OF 1988. ) 7 o . ?0o I EX. UTILITY POLE ITYP.) EX. 8' PVC WATER MAIN & 2" 0 WATER SERVICE I'0� 195.67' 0 x 6A STA:24+76.96 STA:24+76.89 OFF:9.13" FF 68 x10 55 v STA:24+66.4ErI3 :X. MIT'E'RED END SECTK_)N lgliD 0 —0 _=_�C_==_ _eo __x — — — — — — OFF:44.29' IN . EL. 16.57 0 — — — --- — — — — — — — X7�1� — — — — — — — — — — — — — — — — — 01 EX, TOP OF BANK X�b 8 0 + A-1885 +'�sl x STA:24+55.47 140 OFF:62.74' 222.35 _____��STA:24+36.811 OFF:59.13' 8 STA:23+96.60 STA:23+97.11 STA:23+96.70 OFF:-39.27' OFF:-174.35' OFF:-54.27' SN im'. N 30.00' PROPOSED STORAGE AREA #2 3,600 SIF FFE=21.28'NAVD 120.00' 48.21' X7� '�b PROPOSED STORAGE AREA #1 6,250 SF FFE=20.20'NAVD 25.00' \01 21.07' STA'�2.3 67. nz, P7 i; !;E7, STA'23+66.76 0 F 174 41� Im OFF:-54.42' 6MR 011- i 41 "J'a­�.11­­­ �jijl MIR 0 -11! 1 L-u — — — — — — — — — — — — 11 1: \,_STA:23+56.66 STA:23 57.0 OFF:-38,85' OFF:-179.93' 1 47.62' C 41.89, X?.A x'10 i'100 T X'j X'j 36 "S�55 I- .'o� 186.08' PROPERTY LINE PROPOSED LANDSCAPE BUFFER 8 15.00' g�% 8 20.00' Z Z In to C0 03 z V) 0) 0: ac 00 ww wm Lo Km 0-) Lo o =) -zr U-5 zw z 0 Co -'t z z _i 0 o C� Lo < F- _j Z < N "t 0 r4 10� LL (0 04 V-) E Lu LIJ - 't I In 0 LLJ LLJ I IN E� F u) �e ( ) IN (.0 0 z z L) 0 F_ w 00 0 CL a z 0 _r 01� Lu 06 LL 0_ m r- w Lu a 0 0 z 2 z z 0 T 0 0 0 z 0 0 z L U. L 0 z z CL Nil m 0 0 L Z L, j Z m Tom 0 z L) 0 N 0 Z R :y v."'. "'i q 4f. R.J., _4NNEDY' #5 1934', COL99T FT. P21 04950- phon 15-251 I I V ( 6 OF 12 d z 0 LU m z C) z LU 0 SURVEY POINTS OF INTEREST 3/4" PIPE DESTROYED - POSITION REESTABLISHED FROM PREVIOUSLY RELATED POINTS & MEASUREMENTS. CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE GREEN ACRES S/D PLATS. CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE HARMONY HEIGHTS PLATS FND. 4X4 CIA (NO #) - FND 3� DIAMETER CAR AXLE - 0.2- N. & 0.7- E. - FND. V CAR AXLE 0.2- S. & 0.6'E. G) = FND. 4X4 CM (NO#) m FND 518' 1 RON ROD & CAP (LB 6674) - FN D. 4X4 CM (N 0 #H.0' S. & 0. 1 � W. = S.B.T. FIBER OPTIC UNDERGROUND CABLE MARKER EX. BUILDING'A' COVERED PRODUCTION AREA 83,200 SF FFE=22.03'NAVD EX. BUILDING "D" EX. 2 STORY C.B.S. BUILDING 4'HIGH HOG WIRE FENCE MEANDERS ALONG R/W LINE - VARIES FROM 1' S. OF R(W LINE TO 3'N. OF RIW LINE, WOOD LIGHT POLE - CONTROL PANEL ON N. SIDE POLE 8 UNDERGROUND WIRES ON W, SIDE. GUY WIRE ANCHOR IS 3.7'S. & 3.4'E. OF N.W. CORNER OF PROPERTY. G= WOOD ELECTRIC POLE (LINE RUNS FROM NO. 9, THEN TO NO, 12) - DIG CABLE ON SW SIDE OF POLE. & = WOOD ELECTRIC POLE S= WOOD ELECTRIC POLES ALONG AIRPORT ROAD VARY FROM O.TTO 1.0- N. OF THE PJW LINE. = GUY WIRE ANCHOR IS 5.0'N. & 10.0'E.OFS.W. PROPERTYCORNER. = WOOD LIGHT POLE W/ELECTRIC METER&CONTROL PANEL MATCHLINE STA: 22+50.00 m m 'A EX. COVERED STORAGE AREA 3,600 SF FFE=21.93' EDGE OF PROPOSED ASPHALT .5% 0 21.50 21.62 X9.0b ME ±20.14 EX. COVERED STORAGE AREA AnHil5l;i I` m 3,600 SF FFE=21.89' 21. EX. 8" PVC WATER MAIN & 2" WATER SERVICE INSTALL 57 LF OF 15" RCP z X,A Zb AT INV. EL. 17.40 lmil ;i"�i 1- ,.1; d, 12" MIN. COVER EX. 6" FIRE _11 1E FL FL FL H Isli FIL ME +19.81 x ?-A oo "mum WN*M Ti EX.FDC N.Ui ws ir)E! 5b lM 40" 50.00' MATE 01 V-9, ±1 ;11 ligm I A E 970 l,K!fl DISTURBED AREAS OF EX. SWALE TO BE REGRADED TO MATCH EX. ELEVATIONS WHERE POSSIBLE 097- PROPOSED STORAGE AREA #1 6,250 SF �,152 ,916 INSTALL RETAINING WALL - ON BACK OF STORAGE AREA BY OTHERS INSTALL MITERED END SECTION INV. EL. 17.40 PER FOOT INDEX #272 (TYP.) EX. FIRE HYDRANT N.T. 3 r-,A\ Q-) CONFLICT #1 PROPOSED 15" RCP INV. 17.40 EX. 8" PVC WATER MAIN CONTRACTOR TO VERIFY DEPTH OF WATER MAIN BEFORE CONSTRUCTION. CONTRACTOR TO RE-ROUTE WATER MAIN IF NECESSARY. x,,951- INSTALL DRAINAGE MANHOLE RIM EL.=21.05 N� INV.=17.40 E. INV.=17.40 W. INV.=17.40 I LEGEND I 21.36 PROPOSED SPOT ELEVATION EXISTING SPOT ELEVATION PROPOSED FLOW ARROW PARKING STALL COUNT EXISTING CONCRETE PROPOSED CONCRETE it i 0, k PROPOSED ASPHALT F] EXISTING ASPHALT 0 EXISTING UTILITY POLE N.T. 1-5 NEWTREE X,9.50 "sAb INSTALL TYPE "C" INLET RIM EL.=20.45 E. INV.=17.40 20.81 S. INV.=17.40 N.T. 2 0 20 IN FEET ) I inch = 20 ft. DATUM: ALL ELEVATI ONS ARE BASED ,ON NORTH AMERICAN VERTICAL DATUM OF 1988. PROPERTY LINE X,9!50 ROW DEDICATION 15'LANDSCAPE BUFFER N.T. 1 7w IvO Z z LLI z 0) 0 LLI Ld w m LID z M F- 0) Lo 5 =) m Lo LZLI Z 0 z _i 0 z M Lo < F- Z < LL 0 N (0 mn Fr LLJ I... w -,t 0 w cj) w u z z W p., (L w 04 L, L� 0 6 00 z co 0 0 0 ca M w LL CL 4- uj a U X z z w 0 2 g 0 z m w m ws ws Hffi s z 00 J.T. 4 HH"Niiti4i co 21.34 ir m, i 101 9 101M E m u ME ±20 48 l t., i 1i 1 19 .......... 00 liri,"p!i;jmg INSTALL CROSSWALK STRIPING 7;! l'? i) I m PER FOOT INDEX #17346 7, lilej li�, , gg�- ll, ME±19.58 :8) '1, �� l'. I N.T. 5 iiii2iiIi mii ir"I" URI$ l:il M�iii 'M 14' llil Fs IN 2 0 fl!Z§ 0) Ijiivv�qi�:ii; I MIR 1.00 7,51M gimum 141" 51 E N . b 0) INSTALL HANDICAP RAMP PER FOOT INDEX #304 19.85 !i��I 2 0 ME ±20 5� 0 XV0 x ligli :mlgg * �11 ME ±20 12 Iliffl E]18 EX. BUILDING �B' PROPOSED BUILDING �E` kim 2 STORY OFFICE 4 "All 35,im,lu'llm 20.04 P F TO P R HR; 1 STORY OFFICE . . . . lik El BUILDING BA E] BUILDING 5,250 SF 'ITH, 421;48 9,920 SF Pi, FFE=21.93'NAVD !�, %Iij ji INSTALL 84 FFE=21.93'NAVD 91 iiiiiIII OF 15" RCP %SMO D 21.93 INV. EL. 17.40 iilip 12 MIN. CUVEK 4s 21.71 ql, XV m ', 40T6 ME ±20.52 ME ±19.46 �A ggmm.ill 21.92 a INSTALL CONCRETE It, R 22.24 FLUME WITH ENERGY F x m ml NtI 21.92 21.51 DISSIPATER PER FD T , j ,5'SIDEWAL P XN9. I - 7' i 1NDEX#216(T 20.92 �ll 21.33 �3 li"Imm �ll -� , X'� - X�s EX. LIFT STATION ME ±20A 0 Aq R 10, 18' -4- ?P 50.00' :giii oo I XV ME ±20 64 D.03 INSTALL HEADER CURB Jig �� ME ±21.19 % �2*1 101ii ;P !im lim 6 I gglilli V MITERED END 'D'CURB PER FOOT INDEX CONTRACTORTO lei i 20.03 M PER FOOT INDEX #272 1.111�� I 11�1. W SECTION INV. EL. 17.40 #300 (TYP.) Rix SWALE IF NEEDED 00 9,4A (TYP.) s 7.2 2 70AX 14 \INSTALL ST IPING AND 1A 21. 2 X?l AND TRANSITION TO TYPE 0 INSTALL L WHEEL STOPS FOR 7 SPOTS 21.87 x 7.0 40.15' 170511 ME ±21.23 ME ±21.16 ME ±21.80 0 INSTALL TYPE'F'CURB PER CONTRACTOR TO CREATED - - - - - - UAT&T FOOT INDEX #300 (TYP.) INVERTED CROWN TO LET THE UAT&T UAT&T - - UAT&T a t - UATJ� SWALE FLOW OVER ASPHALT 0 2�1.61' �0� "60 BP: 20+00.00 9 - ------- 4AT&T- UAT&T I tq�5N 6� VVM - 2+00 1+00 0 0 'IRV 4+00 cv - - - - - I-wm- WM - - UIX UAT- wm WM----- WM - - - - - - wM 7� EX. 8" WATER MAIN x 10 ws x �01 - - - - - - --- - - - - - - - - - - - - 73.17' U-1 FM FM - - - � I- , - - ��0$ �41� , ot xW1 FM FM FM - -�-- - - �i 7, EX. 2" FORCE MAIN 15 18. 6 0' X,�.b� I'll, I Ia� AT&T �?o EX. UNDERGROUND ELECTRIC x7o. 20.90' 50 0-0-0-0 o-o-o-6 PROPERTY LINE SOO'10'08"W 1214.06' N 89*48'191, W 35,35' 15.46' J Ivo. RZ %tN 1934' FT. PI phone: 7 w z z z z z r z 0 0 z 9 52 0 w 0 _j LL. ;T m z 0 u LLI L) z cn m E T" 15-251 7 OF 12 d z w 0 0 6 A w c� 0 SURVEY POINTS OF INTEREST 314"PIPE DESTROYED � POSITION REESTABLISHED FROM PREVIOUSLY RELATED POINTS & MEASUREMENTS. CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE GREEN ACRES S/D PLATS. CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE HARMONY HEIGHTS PLATS. FIND. 4X4 CM (NO #) - FND Y DIAMETER CAR AXLE - 02N. & O.V E. � FND. V CAR AXLE 0-2. S. & 0B. E. FND. 4X4 CM (NO #) FIND 5/8" IRON ROD & CAP (LB 6674) - FIND. 4X4 CM (NO #)1.0' S. & 0.1'W. S.B.T. FIBER OPTIC UNDERGROUND CABLE MARKER 21.50 0 = 4- HIGH HOG WIRE FENCE MEANDERS ALONG RIW LINE � VARIES FROM V S. OF RfW LINE TO TN. OF RIW LINE. G)= WOOD LIGHT POLE - CONTROL PANEL ON N. SIDE POLE & UNDERGROUND WIRES ON W. SIDE. GUY WIRE ANCHOR IS 3.7'S & 3.4'E. OF N.W. CORNER OF PROPERTY. WOOD ELECTRIC POLE (LINE RUNS FROM NO. 9, THEN TO NO. 12) - U/G CABLE ON SW SIDE OF POLE. WOOD ELECTRIC POLE WOOD ELECTRIC POLES ALONG AIRPORT ROAD VARY FROM 03TO 1.0'N. OF THE PJW LINE. I GUY WIRE ANCHOR IS 5.0'N. & 10.0'E. OF S.W. PROPERTY CORNER. WOOD LIGHT POLE WIELECTRC METER & CONTI LEGEND 2`1.3 6 PROPOSED SPOT ELEVATION Nq N'� EXISTING SPOT ELEVATION PROPOSED FLOW ARROW PARKING STALL COUNT EXISTING CONCRETE PROPOSED CONCRETE 1mr,11111,1il, PROPOSED ASPHALT POP EXISTING ASPHALT 0 EXISTING UTILITY POLE N.T. 1-5 NEW TREE IN PROPOSED PARKING LOT 0 20 IN FEET ) 1 inch = 20 It DATUM: ALL ELEVATIONS ARE BASED ON NORTH AMERICAN VERTICAL DATUM OF 1988. INSTALL CONCRETE ". g'. a �01'u -- 9� V�r 111-1 CID FLUME WITH ENERGY -11 �:-y `I-� a X�q DISSIPATER PER FDOT 01 INDEX #216 (TYP.) — EX, TOP OF BANK 17.75 X�b 0 ME ±1 9.75 qAb �p x INSTALL 105 LF OF THIGH .5% CHAIN LINK FENCE WITH GATES. 21.62 TIE INTO EX STING FENCE. FtNil ill li.." -M �jMig , 2111!flj�ld 1 8 g ij�l !!.I, PROPOS 21.50 6,250 SF EX. EDGE OF PAVEMENT ED STORAGE AREA #1 0 ME ±20.67 ME ±19.89 m D8 — — — — — — — — — — \_WE ±21 hd �:ii! 7777fli1ii`li!�i,; PEN iml MI-Iii-IiiIi 11 H Ph \\��ME±20 93.'.'�' ASPHALT \- EX. EDGE OF PAVEMENT ROPOSED STORAGE AREA EDGE OF 47.62' PROPOSED �105yl 1 ASPHALT � '05'L .w5 K'400 �s XT� 1� V INSTALL RETAINING WALL ON BACK OF STORAGE AREA BY OTHERS DISTURBED AREAS OF EX. SWALE TO BE REGRADED TO MATCH EX. ELEVATIONS WHERE POSSIBLE X'sip Z U z cn LO Lu 0 C) W Lu w M Z) L0 a) 4 Lo Lr) K 2 c.) z 0 CO "t 04 I LO z -j 0 < F= LL 64 (0 1- C'4 ZO r<4 mn LLJ F-- w LJJ- "1' 014 �uj) . w 0 N (0 It 0 w z z 0 LILI I 04 1, IL L. 00 c: r1- a �� ir < z Lu ad LL 0 CL cu < C-) 0 cz Lu 0 L) w x 5 0 7 - w P z z z w 0 = w 0 w 0 0 0 0 r uj 0 z —i ILL cn z z z [L z Tom 0 w z n, `� I P ;-1A PATIJ 1934 TUci� Lin FT. PIERCE, M34W phone: 772-462-2455 15-251 8 OF 12 C5 0 3: A 0 0 A z 0 0 0 z z 0 0 z 0 z w 0 0 z 0 w 0 z w 0 x 0 A w w A 0 z z w 0 0 w w z 0 z w z 0 Ld w 0 7 Z z A z w z w 0 z 0 w Q 0 0 SURVEY POINTS OF INTEREST 3/4" PIPE DESTROYED - POSITION REESTABLISHED FROM PREVIOUSLY RELATED POINTS & MEASUREMENTS. CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE GREEN ACRES SID PLATS. CORNER FALLS IN CANAL - POSITION ESTABLISHED FROM POINTS RECOVERED IN THE HARMONY HEIGHTS PLATS. FND. 4X4 CM (NO #) - FIND YDIAMETER CAR AXLE - 0.2- N. & 07 E. - FIND. 1- CAR AXLE 0.2- S. & 0.6, E. FND. 04 CM (NO #) G) = FN D 5/8" 1 RON ROD & CAP (LB 6674) - FN D. 4X4 CM (N 0 #)1.0'S. & 0. VW. 0 m S.B.T. FIBER OPTIC UNDERGROUND CABLE MARKER EX. TOP OF BANK EX. DITCH PROPERTYLI EX. SHELL ROAD i lx�' \�iN IN Lo ol E EX. UTILITY PO L 8 12+00 STA:1 1+87.94 OFF:-13.76' r , I. pol 4'HtGH HOG WIRE FENCE MEANDERS ALONG R/W LINE - VARIES FROM 1- S. OF RrW LINE TO 3'N. OF RW LINE. WOOD LIGHT POLE - CONTROL PANEL ON N, SIDE POLE & UNDERGROUND WIRES ON W, SIDE. GUY WIRE ANCHOR IS 3.7'S. & 3.4'E. OF N.W. CORNER OF PROPERTY. WOOD ELECTRIC POLE (LINE RUNS FROMNO. 9,THENTONO. 12)-UIGCABLEON SWSIDEOF POLE. WOOD ELECTRIC POLE WOOD ELECTRIC POLES ALONG AIRPORT ROAD VARY FROM 03TO 1.0'N. OF THE R/W LINE. G) = GUY WIRE ANCHOR IS 5.0'N. & 10.9 E. OF S.W. PROPERTY CORNER. (3 m WOOD LIGHT POLE W/ELECTRIC METER & CONTROL PANE STA:11+87.71 OFF:46.24' m EX. TOP OF BANK PROPERTY LINE DISTURBED AREAS OF EX. SWALE TO BE REGRADED TO MATCH EX. ELEVATIONS EX. BUILDING'C' WHERE POSSIBLE I STORY C.B.S. BUILDING 900 SF FFE=21.16' PROPOSED COVERED STORAGE AREA #3 9,080 SF FFE=21.50- NAVD 11+00 STA:10+51.45 OFF:15.68' STA:10+51.56 LEGEND \C�� EXISTING SPOT ELEVATION PROPOSED FLOW ARROW PARKING STALL COUNT EXISTING CONCRETE PROPOSED CONCRETE 1, rjg!mmj"�� PROPOSED ASPHALT EXISTING ASPHALT 0 EXISTING UTILITY POLE N.T. 1-5 NEW TREE IN PROPOSED PARKING LOT STA:10+21.38 OFF:45.59' > z �i� 0 20 IN FEET ) I inch = 20 ft DATUM: ALL ELEVATIONS ARE BASED ON NORTH AMERICAN VERTICAL DATUM OF 1988. EX. BUILDING'A' COVERED PRODUCTION AREA 83,200 SF FFE=22.03'NAVD STA:10+21.60 OFF:16.59' EX. I" WATER SERVIC 0 0 0 < m EX, 8" WATq � —MAIN 8+01 0+00 9+00 wm 0 m �10 EX. FIRE 27 'o' HYDRANT ' 18 63' EX. CONCRETE FLUME EX, LIFT STATION TOP: 18.85 Flo �"� I i'21 Z Z U) Z' L0 0) w 0 CD (n x w W Ld LLI M Z) Lo 0) -Rt Lo Lo 32 0 =) z Z Z %.Of 0 CY) ';T C� z 0 F= _j LL N (o lzt Z < 0 P14 uj R UJ LUI - LLI .,t I (n o Ld M LLJ Cl) Y 0 o 04 r— 0 < z z 0 D P 6 04 P� o C, IL KJ < z LLI od (y) CY) 0 0 U m [Z F= u- CL 4-- Lu a 0 Is z 2 0 z 0 z w [L U) (n 191, FT. z 0 0 z 0 0 z -i LL z 0. a z .10 Co u Lu z 0 5 F- 0 9 (/) C.) 0 z �Lj 0 a Ab k�NNE4!fl;.": it 15-251 9 OF 12 6 Z `TP 25 Center of Aisle Type I'D" 18' 13' 13' --- 18, Curb Parking Stalls Travel Aisle Travel Aisle F arking Stalls Backfill, Landscape or Sod as Directed by the Landscape Architect 1� 2.0% 2.0% -2- . .. . . . ��I� 777 7 77 X. Y N�' W" >1 �e, cx 8" Limerock or 2" Asph Conc. Coquina Base Type SP-9.5 12" Stab. Subgra a NOTES: 1. Typical pavement to be applied to entire parking lot and entrance driveway. 2. Use 3,000 P,S. I. concrete at 28 days for construction. 3, Subgrade to extend beyond the Type I'D" Curb as shown on detail, 4. Type I'D" Curb to be constructed in accordance with FDOT Index #300. 5. Type I'D" Curb shown oversized in detail for clearity. TYPICAL PARKING LOT SECTION W/ TYPE I'D" CURB Construct Concrete ;tall stripin, )OT Index PARKING AREA DETAILS. (TYPICAL) Install Striping Per FOOT Index No. 17346 NOTES: 1. TOP PORTION OF FTP 25 & 26 SHALL HAVE A REFLECTIVE BLUE BACKGROUND WITH WHITE REFLECTIVE SYMBOL AND BORDER. 2. BOTTOM PORTION SHALL HAVE A REFLECTIVE WHITE BACKGROUND WITH BLACK OPAQUE LEGEND AND BORDER. 3. FTP 25 & 26 MAY BE FABRICATED ON ONE PANEL OR TWO. 4. FTP 25 15 FOR USE IN AREAS WHERE SPACE IS LIMITED. 5. REFER TO FDOT INDEX NO. 17355 FOR HANDICAP SIGN STANDARDS. HANDICAP SPACE DET� WHITE HTE BLUE SPACING OR REQUIRED ROADWAY / PARKING AREA TESTS ITEMS TO BE TESTED DENSITY L.B.R. THICKNESS COMPACTED OR STABILIZED SUBGRADE MAX. SPACING MAX. SPACING MAX. SPACING LIN.FT. SQ.FT. LIN,FT. SQ.FT. LINTT. SQ.FT. 300 10,000 300 10,000 300 10,000 LIMEROCK BASE 300 10,000 300 10,000 300 10,000 SHELLROCK BASE 300 10,000 300 10,000 300 10,000 ASPHALT PER INSP. PER INSP. NOTE: ALL TESTING SHALL BE TAKEN IN A STAGGERED SAMPLING PATTERN FROM A POINT 12" INSIDE THE LEFT EDGE OF THE ITEM TESTED, TO THE CENTER, TO A POINT 12" INSIDE OF THE RIGHT EDGE. I ...... TYPE I'D" 2 00 1�4�14 �'ie— CURB B W ,?� . ..... : 0 X Subgrade NOTES: 1. Use 3,000 P.S. I. concrete at 28 days for construction. 2. Subgracle to extend an additional 6" beyond Type I'D" Curb. 3. Type I'D" Curb and transitions to be constructed in accordance with FDOT Index #300. CONCRETE FLUME PER FDOT INDEX 216 TYPE'D'CURB_ CONCRETE FLUME 4'�O" SET BRICKS APPROXIMATELY HALF WAY INTO CONCRETE — 2" 6" 7J NOTES: 1. CHAMPHER ALL EXPOSED EDGES 3/4" EDGE OF PAVEMENT SLAB SWALE OR DITCH BOTTOM FLUME WITH ENERGY DISSIPATER DETAIL Varies P,,­I,AH. 1 /W fo-, 1 1A 'I —4—C— Compact Subgrade to 98% of the Maximum Density as NOTES: Determined by AASHTO T-99 1. Use 3,000 P.S.I. Concrete At 28 Days for sidewalk construction. 4" THICK SIDEWALK DETAIL. 2" ASPHALT PAVEME FOOT TYPE SP 8" LIMEROCK OR COQUINA BASE ,t_) 98% Modified Proctortes max. dry density, LBR min of at least 100 12" min. STABILIZED SUB -BASE COURSE 98% Modified Proctor test max. dry density Stabilized to an LBR of at least 40 TYPICAL PAVEMENT SECTION_ VARIABLE DEPTH MILL AND REMOVE EX. ASPHALT. BUILD 1 " TYPE SP-9.5 OVERLAY. MATCH TO EX. PAVEMENT NEAT SAWCUT AND START — 1" DEPTH MILLING. 1/4" DEPTH MILLING 3/4" to 2" DEPTH TYPE F SP-9.5 OVERLAY FULL 2" DEPTH TYPE SP-9.5 OVERLAY EX. SUBGRADE -J J EX. BASE EX.ASPHALT J 25' NOTE: THIS SPLICE DETAIL IS TO BE USED AT ALL SEAMS WHERE MATCH TO EXISTING PAVEMENT IS REQUIRED. PAVEMENT SPLICE DETAIL (FEATHERING TO EX. PAVEMENT) rII i PrIl CD 7y"' Std. 6" Min. 2'— 0 *Note: When used on high side of roadways, the cross slope of the gutter shall match the cross slope of the adjacent pavement the thickness of the lip shall be 6", unless otherwise shown on plans. TYPE'F'CURB. Z (j 0 Z Lo Cn 2f LLI W Cc 0 LLI LLI L0 a) Lo 0 "t L0 ZW Z Z 0 (y) lcl- q � Z0 D C� Z _J LO < ILL C\I It 0 r-4 (.0 C\I On rr LU LU - '44, 1 00 LLJ CI) W 1 04 [� F �e (-) C\J (0 0 D Z Z Q III— �t M < I 0L 04 W L, 0 ULI 00 0 IX < 0 Z CY) F-: = < 0 CY) M IZ UJ 06 LL CL LU a U M 0 W Z 2 C 42 Z 0 X Z Z 0 0 Z 0 LO W < 0 Z -J LL C0 a LLJ Cl) Z LLI Z LLI Z LLI -J I-- Z NO -- 4218 R.X--!(tNNEDYR.E. 1934tUe,K zr )54 T FT. PIE ST phone: 7' 645 GX� 15-251 10 OF 12 � I HEAVY DUTY REINFORCING DOUBLE STITCHED HEM DRAWCOR M 42 STAKES POLYPROPYLENE R FABRIC �A 1 18' , V, E ISLT�NG EN L RECOMMENDED TOE -IN EX. 7'CHAIN LINK FENCE EP! 2 +32.58 4 NOTES: . . . . . . OF CONSTRUCTION AND SHALL NOT BE REMOVED UNTIL CONSTRUCTION IS COMPLETE. _R 1. SILT FENCE SHALL BE INSTALLED PER MANUFACTURES SPECIFICATIONS PRIOR TO THE START RAIN EVENT AND 0 REMOVE SEDIMENT WHEN NECESSARY. 2. THE CONTRACTOR SHALL INSPECT AND REPAIR THE SILT FENCE AFTER EACH _IU — . — . I . 3. REMOVED SEDIMENT SHALL BE DEPOSITED IN AN AREA THAT WILL NOT CONTRIBUTE SEDIMENT F—F I—F I —T-1 T—T FT I _T_rN__1 FT 1-71 77-1 1 --- 71 7-T I OFFSITE AND CAN BE PERMANENTLY STABILIZED. a_ I T 4. THE SILT FENCE SHALL BE PLACED ON SLOPE CONTOUR TO MAXIMIZE ITS PONDING EFFICIENCY. Fj- SILT FENCE DETAIL ci I In -1 -1 -1 -1 T -I F I Li -1 1 T I FF-1 ---------- --- --------------------------- — A i H. 0 2 ( E01 I / / t!) EX. STABILIZED AREA INSTALL SILT FENCE OR FILTER SOCK INSTALL SILT FENCE 11 I L I rn I w 0 C r- 1�rn ----- ---------------------- i i § — — — — — — — — ---------------------- �;u PROPERTY LINE 0 2 0 00 1 I 71 0 > I 4V 1 1111-21 11 71 4W 1 L _j 0 INSTALL SILT FENCE I I + 7E -LING EX. FDC INSTALL SILT FENCE OEM INSTALL SILT FENCE OR FILTER SOCK j, 0 & ---------------- ----------- _j EX. SIGN I D EX. SIGN F TQf- 4— --1 9+00 opou ------ �6+00 ---- Z+00 -------- --- =—ItAp )Oil 10+00 11+00 It 12+00 1 *1 4_� M w j7VInyl Sheathed EAW Steel Cable (9800 Lbs. Breaking Strength) With 0 Galvanized Connectors (Tool Free Disconnect) Z w Slotted PVC Connector Pipe (Metal Collar Reinforced) Closed Cell Solid Plastic Foam Flotation (8" Dia. Equiv.) (17 las. Per Ft. Buoyancy)-,' Z1 r Z lw < w x r18 CT Reinforced Rein fo w Oz. Nylon Reinforced =(300 18 Of N YI on rced 18 Oz. Nylon =Fab3 Ic ( psi Tes PVC Fabric Stress Plate Chain ( 00 PVC Fabric (300 psi PVC ric ps i%Galvanized Test) With Lacing Gromm E Test) With Lacing Gromm� Z w w Z TYPE TYPE Z D, =5' Std. (Single Panel For Depths 5' or Less). w D2=5' Std. (Additional Ponel For Dep,*hs 5'). Z < Curtain To Reach Bottom Up To Depths Of 10 Feet. Two(2) Panels To Be Used For Depths Greater Than w 10 Feet Unless Special Depth Curtains Specifically Called 0 Z For In The Plans Or As Determined By The Engineer. 0 0 w NOTICE: COMPONENTS OF TYPES — AND -- MAY BE SIMILAR OR IDENTICAL TO PROPRIETARY DESIGNS. ANY INFRINGEMENT ON THE PROPRIETARY RIGHTS OF THE DESIGNER SHALL BE THE SOLE RESPONSIBILITY OF THE USER, SUBSTITUTIONS FOR TYPES — AND SHALL BE AS w APPROVED BY THE ENGINEER. w 0 FLOATING TURBIDITY BARRIERS 01 FILTER FABRIC TO EXTEND 8" METAL INLET GRATE MIN. FROM GRATE SIDES Closed Cell Solid Plastic Foam Flotation (6" Dia. Equiv.) (12 Lbs. Per Ft. Buoyancy) PREDOMINATE FLOW, all ------------------ Paloiyp ro R op e - ----- ----- --- - - ----- - ypro Rope (600 Ila. Breaking ---------- 9� V" N, S t 6 t Strength) Z: FILTER FABRIC TO 4 Galvanized Choi ..... C T U U CONTINUE UNDER E "Tior: _0 ATr: NTIRE GRATE. lc� 40- 0 80 IN FEET I inch = 60 ft. LEGEND EXISTING SPOT ELEVATION PROPOSED FLOW ARROW PARKING STALL COUNT EXISTING CONCRETE PROPOSED CONCRETE PROPOSED ASPHALT EXISTING ASPHALT EXISTING LIGHT POLE FILTER FABRIC TO EXTEND 8" 'RATE SIDES 11 1 �e � 4, " GENERAL NOTES PICTORIAL VIEW 1. THIS INLET IS DESIGNED WITH FILTER FABRIC PROTRUDING 8" FROM SIDES FOR GRIPPING WHEN SEDIMENT NEEDS TO CLEARED AFTER FINAL CONSTRUCTION. 2. FILTER FABRIC TO BE INSTALLED AND TRIMMED BEFORE GRATE IS INSET. FILTER FABRIC DETAIL U =I N UN IN Z Z co to PO 00 w I w w CO 0 L) 0) Lo L0 Z Z w Z 0 6 (y) U-) � Z0 < F= _j LL Z < 0 N Lu P Lu - W 4 I 1 V) C) J� F LJU cl) (0 0 =1 < Z Z 04 r� U_ 00 50 [L c 1�- 0 W M < Z 06 M 0*) LL 0 < 0 0 If M 0_ Uj a (M) 'a w w C3 U) Cl) TOM 1934 T,1 FT. PIE phone: Z 0 F- Z IL 0 CL Z w 0 w I-- Z w > w [L 0 U) 12 Z 0 0 Z 0 0 _j LL 9 mi Z 0 0 UJI F- Z R U) ' I" 'VU _%.(IJA�V ftle 15-251 11 OF 12 . . . . GENERALNOTES 6. ALL PROPOSED ELEVATIONS REFER TO FINISHED GRADES. 1. ANY DISCREPANCIES ON THE DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE COMMENCING WORK. NO FIELD CHANGE OR DEVIATIONS FROM THE DESIGN ARE TO BE MADE WITHOUT PRIOR APPROVAL OF THE 7. THE CONTRACTOR MUST OBTAIN A WATER USE FERMI r PRIOR TO CONSTRUCTION DEWATERING UNLESS THE WORK ENGINEER. QUALIFIES FOR A GENERAL PERMIT PURSUANT TO SUBSECTION 40E-20 302(4), F. A C. 2. THE CONTRACTOR SHALL CONTACT ENGINEER OF RECORD, THE APPROPRIATE GOVERNMENTAL JURISDICTIONAL AGENCY AND ALL OTHER CONCERNED UTILITIES AT LEAST 2 FULL BUSINESS DAYS IN ADVANCE OF CONSTRUCTION OPERATIONS. 8. ALL CURB AND CURB TRANSITIONS ARE TO COMPLY wi rH CURRENT FOOT STANDARDS INDEX #300. 3. THE LOCATION AND SIZE OF ALL EXISTING UTILITIES SHOWN ON THE PLANS ARE APPROXIMATE AND ARE BASED ON THE STORM SEWER NOTES BEST AVAILABLE INFORMATION. ADDITIONAL UTILITIES MAY EXIST WHICH ARE NOT SHOWN ON THE PLANS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PHYSICALLY LOCATING ALL EXISTING UTILITIES. THE CONTRACTOR SHALL VERIFY ALL UTILITIES BY ELECTRONIC METHODS AND BY HAND EXCAVATION IN COORDINATION WITH ALL UTILITY 1. STANDARD SEPARATION FOR ALL WATER AND/OR WAS EWATER MAINS, HORIZONTAL AND VERTICAL, SHALL BE PER FDEP COMPANIES, PRIOR TO BEGINNING ANY CONSTRUCTION OPERATIONS. ANY AND ALL CONFLICTS OF EXISTING UTILITIES REQUIREMENTS, PROVISIONS OF F.A.C. RULE 62.604 AND TEN STATES STANDARD OR LOCAL MUNICIPALITIES, WHICHEVER WITH PROPOSED IMPROVEMENTS SHALL BE RESOLVED BY THE ENGINEER AND THE OWNER PRIOR TO BEGINNING ANY IS MORE STRINGENT. d CONSTRUCTION OPERATIONS, THIS WORK BY THE CONTRACTOR SHALL BE CONSIDERED INCIDENTAL TO THE CONTRACT z AND NO ADDITIONAL COMPENSATION SHALL BE ALLOWED. 2. ALL DISTURBED OUTFALL DRAINAGE AREAS SHALL BESODDED UPON COMPLETION OF GRADING AFTER AS -BUILT GRADE (5 a ELEVATIONS ARE APPROVED BY THE ENGINEER. w 4. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THEIR COMPLETE FAMILIARITY WITH THE PROJECT SITE AND 0 �_ COMPONENTS TO INCLUDE SUBSURFACE CONDITIONS OF SOIL AND GROUNDWATER TABLE. BY SUBMITTAL OF A BID FOR � THIS PROJECT, THE CONTRACTOR ACKNOWLEDGES THEIR COMPLETE UNDERSTANDING AND RESPONSIBILITIES WITH 3. PRIOR TO FINAL PAYMENT FOR RETENTION ' DETENTIOP AND DRAINAGE DITCH QUANTITIES, ALL SLOPES AND SWALES � RESPECT TO THE CONSTRUCTION ACTIVITIES REQUIRED UNDER THE SCOPE OF THIS PROJECT. SHALL BE SODDED TO AVOID EROSION. � � � 5. THE "TRENCH SAFETY ACT" SHALL BE INCORPORATED INTO THIS CONTRACT AS ENHANCED BY THE LEGISLATURE OF THE 4. THE CONTRACTOR SHALL CONSTRUCT THE STORMWA ER MANAGEMENT SYSTEM IN A MANNER SO AS TO MINIMIZE ANY 0 F STATE OF FLORIDA TO BE IN EFFECT AS OF OCTOBER 1, 1990. ADVERSE IMPACTS OF THE WORKS ON FISH, WILDLIFE, NATURAL ENVIRONMENTAL VALUES AND WATER QUALITY ON OR 9 OFF -SITE. THE CONTRACTOR SHALL INSTITUTE NECE SARY MEASURES DURING THE CONSTRUCTION PERIOD, INCLUDING w 6. AS -BUILT PLANS: THE CONTRACTOR SHALL PROVIDE ONE (1) REPRODUCIBLE MYLAR COPY, FOUR (4) BLACK LINE COPIES FULL COMPACTION OF ANY FILL MATERIAL PLACED AR LIND NEWLY INSTALLED STRUCTURES TO REDUCE EROSION, m AND ONE (1) DIGITAL FORMAT OF A CERTIFIED AS -BUILT SURVEY. DRAWINGS SHALL BEAR THE ORIGINAL SIGNATURE AND TURBIDITY, NUTRIENT LOADING AND SEDIMENTATION 11 THE RECEIVING WATERS. � EMBOSSED SEAL OF THE SURVEYOR AND SHALL BE SUBMITTED AFTER THE COMPLETION OF CONSTRUCTION, BUT PRIOR 0. TO FINAL APPROVAL. THE AS -BUILT SURVEY SHALL BE PREPARED IN PLAN AND PROFILE FORMAT BY A LICENSED 5. WITHIN THIRTY (30) DAYS AFTER COMPLETION OF CON TRUCTION OF THE SURFACE WATER MANAGEMENT SYSTEM, THE Q z PROFESSIONAL LAND SURVEYOR REGISTERED IN THE STATE OF FLORIDA AND SHALL COMPLY WITH APPLICABLE CONTRACTOR SHALL ASSIST THE DESIGN ENGINEER To PROVIDE A WRITTEN STATEMENT OF COMPLETION. THESE PROVISIONS OF THE FLORIDA ADMINISTRATIVE CODE AND CHAPTER 472 OF THE FLORIDA STATUES. THE DRAWINGS SHALL STATEMENTS MUST SPECIFY THE ACTUAL DATE OF CO qSTRUCTION COMPLETION AND MUST CERTIFY THAT ALL FACILlTIES (5 0 BE AT A SCALE COMPARABLE TO THE DESIGN DRAWINGS PREPARED BY THE ENGINEER AND SHALL REFERENCE THE BASE HAVE BEEN CONSTRUCTED IN SUBSTANTIAL CONFORMANCE WITH THE PLANS AND SPECIFICATIONS. THE CONSTRUCTION w LINE OF SURVEY APPEARING ON THE ENGINEERING DRAWINGS. THE HORIZONTAL AND VERTICAL LOCATION OFTHE COMPLETION CERTIFICATION MUST INCLUDE, AT A MIN MUM EXISTING ELEVATIONS, LOCATIONS AND DIMENSIONS OF THE � ROADWAYS, DRAINAGE FACILITIES AND ALL APPURTENANCES SHALL BE ACCURATELY DEPICTED TO SCALE AND SHALL BE COMPONENTS OF THE SURFACE WATER MANAGEMENI FACILITIES. ADDITIONALLY, IF DEVIATIONS FROM THE APPROVED z 0 IDENTIFIED RELATIVE TO THE BASE LINE AND TO READILY IDENTIFIABLE PERMANENT OR SEMI -PERMANENT REFERENCE DRAWINGS ARE DISCOVERED DURING THE CERTIFICAT ON PROCESS, THE CERTIFICATION MUST BE ACCOMPANIED BY A ff 0 POINTS EXISTING AFTER THE COMPLETION OF CONSTRUCTION. LOCATIONS SHALL BE SHOWN FOR ALL FITTINGS, VALVES, HYDRANTS, MANHOLES. SAMPLE POINTS, AIR RELEASES, ETC., BOTH HORIZONTAL AND VERTICAL, AND THE LOCATION OF COPY OF THE APPROVED PERMIT DRAWINGS WITH DEVIATIONS NOTED. SEE ALSO AS -BUILT REQUIREMENTS. Q THE MAIN AT EACH BASELINE STATION AS SHOWN ON THE PLANS (100 FEET MAXIMUM) BOTH HORIZONTAL AND VERTICAL. 0 � UNDERGROUND FACILITIES (I.E., DRAINAGE, GAS, ELECTRIC, TELEPHONE, ETC,) CROSSING THE MAINS SHALL BE AND 6. A STABLE PERMANENT AND ACCESSIBLE ELEVATION R FERENCE SHALL BE ESTABLISHED ON OR WITHIN ONE HUNDRED ACCURATELY SHOWN BOTH HORIZONTAL AND VERTICAL AND SHALL IDENTIFY SIZE, TYPE, FACILITY, MATERIAL (100) FEET OF ALL PERMITTED DISCHARGE STRUCTURE S NO LATER THAN THE SUBMISSION OF THE CERTIFICATION TO THE z 9 CLEARANCE. ALL INFORMATION SHALL BE BASED UPON MEASUREMENTS AND OBSERVATIONS MADE IN THE FIELD BY THE WATER MANAGEMENT DISTRICT. THE LOCATION OF TF E ELEVATION REFERENCE MUST BE NOTED ON OR WITHIN THE � SURVEYOR CERTIFYING THE SURVEY OR BY PERSONNEL UNDER THEIR EMPLOYMENT, DIRECTION AND SUPERVISION. THE CERTIFICATION REPORT. COST FOR PREPARING AND MAINTAINING THE AS -BUILT PLANS SHALL BE INCIDENTAL TO THE CONSTRUCTION COST. 0: 0 F 7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING PROPER TRAFFIC MAINTENANCE AND CONTROLS IN 7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CORRECTION OF ANY EROSION OR SHOALING OF THE WATER � ACCORDANCE WITH THE FHWA."MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES" AND THE FOOT "ROADWAY AND QUALITY MANAGEMENT SYSTEM. z w TRAFFIC DESIGN STANDARDS". OPEN TRENCHES SHALL BE MARKED OR BARRICADED AND SHALL NOT BE LEFT OPEN � DURING NIGHTTIME HOURS, ACCESS TO RESIDENCES INCLUDING WASTE DISPOSAL AND POSTAL SERVICES SHALL BE 8.INLETS: INCLUDES THE LIST OF MATERIALS/ INSTALLArION / DEWATERING STABILIZATION /AS -BUILT SURVEYING/ � PROVIDED AT ALL TIME. TESTING. ALL STRUCTURES WILL REQUIRE THREE (3) COMPACTION TESTS AT DIFFERENT LOCATIONS AND UNDER t STRUCTURES OR PER LOCAL APPROVING AUTHORITY, NHICHEVER IS MORE STRINGENT. 0 8. ALL CONSTRUCTION IS TO BE IN ACCORDANCE WITH FLORIDA DEPARTMENT OF TRANSPORTATION STANDARDS AND = � SPECIFICATIONS, ORTHE LOCAL JURISDICTIONAL MUNICIPALITY, WHICHEVER IS MORE STRINGENT. § 9. PIPE CULVERTS AND STORM SEWERS SHALL BE CONS"RUCTED AND INSTALLED IN ACCORDANCE WITH SECTION 430 FDOT � STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION. w 2 9. ALL UNDERGROUND MUNICIPAL UTILITIES, FIBER OPTIC, TELEPHONE. FPL, LOCAL CABLE AND ALL OTHER LOCAL UTILITY =) COMPANY LOCATIONS SHOWN ARE TAKEN FROM INFORMATION PROVIDED BY THAT UTILITY COMPANY. THESE LOCATIONS 8 HAVE NOT BEEN VERIFIED IN THE FIELD. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL UTILITY LOCATIONS 10, HOPE (HIGH DENSITY POLYETHYLENE) CULVERT SF ALL BEADS N-12 OR APPROVED EQUAL AND INSTALLED PER 0 PRIOR TO CONSTRUCTION. THE CONTRACTOR SHALL EXPOSE ALL CROSSINGS WITH PUBLIC & PRIVATE UTILITIES PRIOR MANUFACTURER RECOMMENDATIONS. w m TO BEGINNING CONSTRUCTION AND DELIVERY OF PIPE. THE CONTRACTOR SHALL USE EXTREME CAUTION WITHIN THE �_ VICINITY OF PUBLIC & PRIVATE UTILITY FACILITIES, THE CONTRACTOR WILL REQUEST THE PRESENCE OF THE RESPECTIVE z 0 UTILITY REPRESENTATIVES DURING CONSTRUCTION IN THE VICINITY OF THEIR FACILITIES EVEN IF A PROFILE OF THE 11, REINFORCED CONCRETE PIPE SHALL BE ASTM C-7E CLASS 111 IN ACCORDANCE WITH SECTION 941 OFTHE FOOT � UTILITY FACILITIES IS PROVIDED IN THESE DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR CONTACTING THE PUBLIC STANDARD SPECIFICATIONS. z & PRIVATE UTILITIES AND VERIFYING / OBTAINING THE LOCATION(S) OF THESE FACILITIES. 5 � w FILTER FABRIC (STORM PIPE JOINTS) m a 10. ANY NGVD 29 AND NAVD 88 MONUMENT WITHIN THE LIMITS OF CONSTRUCTION IS TO BE PROTECTED. IFINDANGEROF w � DAMAGE, THE CONTRACTOR SHOULD NOTIFY: THE CONTRACTOR SHALL WRAP ALL STORM PIPE JOINTS, CONSTRUCTION SHALL BE PER F.D.O.T. INDEX NO. 280 WITH w WOVEN GEOTEXTILE TYPE D-3 (F.D.O.T. INDEX NO. 199), E ECURED W I STRAPPING. ALL JOINTS SHALL BE WRAPPED FOR A � 2 MINIMUM OF 178 INCHES FROM THE BAND OR JOINT OR 8 ELL AND SPIGOT AS APPLICABLE. GEODETIC INFORMATION CENTER E � ATTN: MARK MAINTENANCE CENTER � ATTN: MICG - 162 DEWATERING 0 w 6001 EXECUTIVE BOULEVARD 0 D ROCKVILLE, MID 20852 STORM SEWER PIPES AND STRUCTURES AND UTILITIES E HALL BE LAID "IN THE DRY", UNLESS OTHERWISE APPROVED IN � WRITING BY THE UTILITY AND ENGINEER OF RECORD. T CONTRACTOR, AT NO DIRECT COST TO THE OWNER. SHALL TELEPHONE: (301)443-8319 PERFORM ALL DEWATERING ACTIVITY. TRENCH EXCAVA IONS SHALL BE DEWATERED BY USING ONE OR MORE OF THE d w FOLLOWING METHODS: SOCK DRAINS, WELL POINT SYS' EM, SUMP PUMPS OR OTHER METHOD(S) AS APPROVED BY THE i RON HARRIS, PLS ENGINEER. DEWATERING SYSTEMS SHALL BE UTILIZED I I ACCORDANCE WITH GOOD STANDARD PRACTICE AND MUST BE COUNTYSURVEYOR EFFICIENT ENOUGH TO LOWER THE WATER LEVEL IN AD) NNCE OF THE EXCAVATION AND MAINTAIN IT CONTINUOUSLY TO Ir � 2300 VIRGINIA AVENUE KEEP THE TRENCH BOTTOM AND SIDES FIRM AND DRY. I THE MATERIAL ENCOUNTERED AT TRENCH GRADE IS SUITABLE FT. PIERCE, FLORIDA 34982 FOR THE PASSAGE OF WATER WITHOUT DESTROYING Tl­ : SIDES OR UTILITY FOUNDATION OF THE TRENCH, SUMPS MAY BE 3'r (772) 462-1707 PROVIDED AT INTERVALS AT THE SIDE OF THE MAIN TRE CH EXCAVATION, WITH PUMPS USED TO LOWER THE WATER LEVEL BY TAKING THEIR SUCTION FROM SAID SUMPS. DISCHAF 3E FROM DEWATERING SHALL BE DISPOSED OF IN SUCH A MANNER = 0 11. CONTRACTOR TO UTILIZE "APPROVED FOR CONSTRUCTION" PLANS ONLY. ANY PLANS NOT"APPROVED FOR THAT IT WILL NOT INTERFERE WITH NORMAL DRAINAGE F THE AREA IN WHICH THE WORK IS BEING PERFORMED, CREATE A T 3: CONSTRUCTION" SHALL BE CONSIDERED PRELIMINARY AND SHOULD NOT BE USED FOR BIDDING OR CONSTRUCTION. PUBLIC NUISANCE OR FORM PONDING. ALL DISCHARGE OPERATIONS SHALL NOT CAUSE INJURY TO ANY PORTIO HALL BE IN ACCORDANCE WITH ANY SFWMD ISSUED PERMITS. THE 4 OF THE WORK COMPLETED OR IN PROGRESS OR TO THE SURFACE w 0 OF STREETS OR TO PRIVATE PROPERTY. THE ENGINEEF OF RECORD AND NECESSARY REGULATORY AGENCIES. PRIOR TO . I � 12. SHOP DRAWINGS FOR ALL STRUCTURES SHALL BE SUBMIT -FED TO ENGINEER FOR REVIEW AND APPROVAL PRIOR TO CONSTRUCTION, SHALL APPROVE THE PROPOSED DEWA TIERING METHOD(S) AND SCHEDULE. ADDITIONALLY, WHERE PRIVATE PROPERTY WILL BE INVOLVED. THE CONTRACTOR SHALL OBTAIN ADVANCE PERMISSION FROM THE PROPERTY !m � ORDERING. OWNER. 0 a 13. SHOP DRAWINGS ARE REQUIRED ON ALL STRUCTURES. THE ENGINEER REQUIRES FIVE (5) BUSINESS DAYS TO REVIEW � SHOP DRAWINGS AFTER RECEIPT. ADDITIONAL TIME MAY BE REQUIRED IF LOCAL GOVERNMENT OR MUNICIPALITIES CONFLICTS w� w 0 REQUIRE AN INTERNAL REVIEW AND APPROVAL PROCESS. � x IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR rO BECOME ACQUAINTED WITH EXISTING CONDITIONS AND TO :) LOCATE STRUCTURES AND STORM PIPES ALONG THE PR DPOSED STORM PIPE ALIGNMENT IN ORDER TO AVOID CONFLICTS. m 0 14. CONCRETE SHALL BE CLASS 1 3,000 PSI MINIMUM COMPRESSIVE STRENGTH UNLESS NOTED OTHERWISE, REINFORCING WHERE ACTUAL CONFLICTS ARE UNAVOIDABLE, WORKS iALL BE COORDINATED WITH THE FACILITY OWNER AND �6 SHALL BE GRADE 60 DEFORMED STEEL BARS IN ACCORDANCE ASTM A-615. PERFORMED SO AS TO CAUSE AS LITTLE INTERFERENCE AS POSSIBLE WITH THE SERVICE RENDERED BY THE FACILITY 0 w DISTURBED. ALL AFFECTED UTILITIES SHALL BE NOTIFIE D PRIOR TO EXCAVATION IN THEIR VICINITY. CONTRACTOR TO m 0 15. CONTRACTOR SHALL PROTECT ALL EXISTING ABOVE OR UNDERGROUND STRUCTURES, LANDSCAPE FEATURES, TREES POTHOLE ALL CONFLICTS OF EXISTING UTILITIES AND PFOPOSED IMPROVEMENTS AT LEAST 10 DAYS PRIOR TO w m AND UTILITIES NOT SHOWN ON THE PLANS, THE CONTRACTOR SHALL REPAIR OR REPLACE ANY ITEM DAMAGED BY CONSTRUCTION TO CONFIRM CONFLICT RESOLUTION SI­ OWN ON THE PLANS. � w CONSTRUCTION ACTIVITY TO MEET ALL APPLICABLE CURRENT CODES. ANY REPAIRED / REPLACED ITEMS ARE SUBJECT TO 0 � REVIEW AND APPROVAL BY APPLICABLE LOCAL JURISDICTIONAL AGENCY. SOD >� z 0 16. ALL PROPOSED UTILITY MATERIALS, CONSTRUCTION METHODS. TESTING AND DISINFECTION SHALL CONFORM TO THE 1. THE SOD SHALL BE FREE FROM WEEDS, FUNGUS, INS CTS AND DISEASE OF ANY KIND. ALL SODDED AREAS SHALL BE a w REQUIREMENTS OF THE CURRENT LOCAL UTILITY COMPANY STANDARDS AND AWWA CURRENT STANDARD. IT SHALL BE GRASSED AS SPECIFIED ON PLANS AND SURVIVAL GU) ,RANTEED FOR NINETY DAYS FROM DATE OF REPLACEMENT. 0 z THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN AND UTILIZE A CURRENT COPY OF THE LOCAL REGULATING UTILITY SURVIVAL OF ALL RELOCATED TREES SHALL BE GUAR kNTEED FOR 1 YEAR AFTER TRANSPLANTING. w 9 COMPANY STANDARDS AND ENSURE ALL CONSTRUCTION IS IN ACCORDANCE WITH THEIR STANDARDS. ANY CONFLICT 0 WITH THE CONSTRUCTION DRAWINGS AND THE LOCAL UTILITY COMPANY SHALL BE RESOLVED UTILIZING THE MOST 2. SODDING SHALL CONSIST OF SITE PREPARATION, FUR 41SHING AND PLACING SOD, STAPLES AND FERTILIZER AND w - STRINGENT DIRECTIONS. IRRIGATING. S? � w 17. ALL HORIZONTAL AND VERTICAL SURVEY CONTROL POINTS SHALL BE PROTECTED AND UNDISTURBED. IN THE EVENT 3. SOD SHALL MATCH THE EXISTING YARD WITH ARGENT NE BAHIA GRASS OR ST. AUGUSTINE FLORATAM AND SHALL BE 0 � THAT A CONTROL POINT IS DISTURBED OR DESTROYED, THE POINT SHALL BE RE-ESTABLISHED BY A FLORIDA REGISTERED 12-INCH BY 12-INCH SQUARES OR OTHER COMMERCIA AVAILABLE RECTANGLES, THE SOD SHALL BE SUFFICIENTLY 0 � LAND SURVEYOR. THE METHOD TO RE-ESTABLISH THE POINT SHALL BE APPROVED BY THE CITY I COUNTY ENGINEER AT THICK (MINIMUM THICKNESS OF 2 INCHES) TO PROVID A DENSE STAND OF LIVE GRASS. THE SOD SHALL HAVE BEEN BE w THE EXPENSE OF THE CONTRACTOR. GROWN ON MINERAL SOIL. SOD SHALL BE LIVE, FRESI 1, AND UNINJURED AT THE TIME OF PLANTING AND SHALL 2 PROTECTED FROM DRYING OUT BY SHADING AND WAI ERING FROM THE TIME IT IS DUG UNTIL PLANTING. R t; PAVING, GRADING AND DRAINAGE NOTES 9 � 1. ALL UNSUITABLE MATERIALS, SUCH AS MUCK, ORGANIC MATERIAL AND OTHER DELETERIOUS MATERIAL AS CLASSIFIE 0 BY 4. SOD SHALL BE PLACED SUFFICIENTLY BELOW FINISHED DRAIN, GRADING SHALL ACCOMMODATE SOD HEIGHT - ROADWAY AND DRIVEWAY GRADES TO ALLOW THESE AREAS TO -0 ALLOW FOR PROPER DRAINAGE. AASHTO M-145, FOUND SHALL BE REMOVED DOWN TO ROCK OR SUITABLE MATERIAL, AND REPLACED WITH THE SPECIFIED � 2� FILL MATERIAL IN MAXIMUM 12 INCH LIFTS COMPACTED TO NOT LESS THAN 100% MAXIMUM DRY DENSITY AT OPTIMUM MOISTURE IN ACCORDANCE WITH AASHTO T-99. THICKNESS OF LAYERS MAY BE INCREASED, PROVIDED THAT THE 6. STAPLES FOR SOD PLACED ON SIDE SLOPES 3:1 & STE EPER SHALL BE BLACK IRON WIRE NOT SMALLER THAN 14 GAUGE, w x EQUIPMENT AND METHODS USED ARE PROVEN BY FIELD DENSITY TESTING AND CAPABLE OF COMPACTING THICK LAYERS AND SENT FROM A LENGTH OF WIRE AT LEAST 25 INCHES LONG INTO A'U'WITH A I INCH WIDTH AT THE CROWN. COS TOF w m TO SPECIFIED DENSITIES. STAPLES SHALL BE INCIDENTAL TO THE SOD UNIT PRICE, a w THIS SHALL CONSIST OF THE COMPLETE � 2. ALL AREAS SHALL BE CLEARED AND GRU1313ED PRIOR TO CONSTRUCTION. 6. WATER USED FOR IRRIGATION MAYBE OBTAINED FROM ANY APPROVED SOURCE. IT SHALL BE FREE OF EXCESSAND w REMOVAL AND DISPOSAL OF ALL TREES, BRUSH. STUMPS, GRASS, WEEDS, RUBBISH AND ALL OTHER OBSTRUCTIONS HARMFUL CHEMICALS, ACIDS, ALKALIES, OR ANY SUB,c TANCE, WHICH IS HARMFUL TO PLANT GROWTH. � RESTING ON, OR PROTRUDING THROUGH THE SURFACE OF THE EXISTING GROUND TO A DEPTH OF ONE (1) FOOT. ITEMS DESIGNATED TO REMAIN, TO BE RELOCATED, OR TO BE ADJUSTED SHALL BE SO DESIGNATED ON THE DRAWINGS. U) z 7. WHERE SODDING WILL BE DONE, ALL LOOSE ROCK .... ODY MATERIAL, AND OTHER OBSTRUCTIONS THAT WILL INTERFERE 0 WITH SODD ING SHALL BE REMOVED AND THE AREA SHALL BE REASONABLY SMOOTH AND UNIFORM. LIME AND FERTILIZER w w 3. FILL MATERIAL SHALL BE CLASSIFIED AS A-1, A-3, OR A-2-4 IN ACCORDANCE WITH AASHTO M-145 AND SHALL BE FREE FROM WILL BE APPLIED IN THE SAME QUANTITY AND MANNER AS SPECIFIED BY THE MANUFACTURER. a a VEGETATION AND ORGANIC MATERIAL NOT MORE THAN 12% BY WEIGHT OF PILL MATERIAL SHALL PASS THE NO. 200 SIEVE. 8. THE SOD STRIPS SHALL BE LAID IN A STAGGERED PATrERN WITH SNUG EVEN JOINTS. ALL JOINTS SHALL BE BUTTED TIGHT E� 4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING CERTIFIED MATERIAL TEST RESULTS TO THE ENGINEER OF TOPREVENTVOIDS. IMMEDIATELY FOLLOWING SOD FLACEMENT, IT SHALL BE ROLLED OR TAMPED TO INSURESOLID 0 THE RECORD PRIOR TO THE RELEASE OF FINAL CERTIFICATION BY THE ENGINEER, TEST RESULTS MUST INCLUDE, BUT CONTACT OF ROOT MATTO SOIL SURFACE. THE SOD: 5HALL BE SECURELY ANCHORED To THE SOIL BY PINNING WITH z MAY NOT BE LIMITED TO, DENSITIES FOR SUBGRADE AND BASE DENSITIES AT UTILITY CROSSINGS, MANHOLES, INLETS, STAPLES OR WOODEN PEGS WHEN PLACED ON SLOPE S 3:1 OR STEEPER. COST OF STAPLES AND PEGS SHALL BE 8 AND STRUCTURES. TEST SHALL INCLUDE ASPHALT GRADATION REPORTS, CONCRETE CYLINDERS. ETC. DENSITY TESTS INCIDENTAL TO THE SOD UNIT PRICE, PIN OR PEG EACH SEPARATE PIECE OF SOD PLACED OR EVERY 3 FEETALONG EACH w � SHALL BE PERFORMED AT THREE (3) LOCATIONS AROUND ANY STRUCTURE. BEGIN TESTING IN THE FIRST FOOT ABOVE CONTINUOUS STRIP OF SOD. THE BOTTOM OF THE STRUCTURE AND THEN EVERY TWO FEET TO WITHIN TWO FEET OF THE FINISH GRADE; THESE iDENSITY REQUIREMENTS ARE THE MINIMUM. THE CONTRACTOR SHALL VERIFY DENSITY REQUIREMENTS AND PROTOCOL$ c� WITH THE LOCAL APPROVING AUTHORITY PRIOR TO CONSTRUCTION OR BIDDING OF THE PROJECT. SOIL EROSION PLAN F W= w Q 5. ALL INLETS AND PIPE SHALL BE PROTECTED DURING CONSTRUCTION TO PREVENT SILTATION IN THE DRAINAGE SYSTEMS 1. NO POLLUTION OR EROSION CAUSED BY THIS PROJEC T WILL BE ALLOWED IN THE STORMWATER DRAINAGE SYSTEM. THE p BY WAY OF TEMPORARY PLUGS AND PLYWOOD OR PLASTIC COVERS OVER THE INLETS. THE ENTIRE DRAINAGE SYSTEMS CONTRACTOR SHALL INSTALL ANY DEVICES NECESSA �Y TO PREVENT POLLUTION OR EROSION. THE COST OF POLLUTION � SHALL BE CLEANED OF ALL DEBRIS PRIOR TO FINAL ACCEPTANCE. ALL CONCRETE SHALL BE A MINIMUM 3,000 PSI. SOME I AND EROSION CONTROL SHALL BE INCIDENTAL TO TH� COST OF THE CONSTRUCTION, w LOCAL GOVERNMENT STORMWATER PROJECTS MAY REQUIRE TELEVISING OF THE STORM SEWER. CONTRACTOR SHOULD 2 BE KNOWLEDGEABLE OF THIS REQUIREMENT PRIOR TO BIDDING OF THE PROJECT. 2. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL SUBMIT A SITE SPECIFIC SOIL EROSION CONTROL PLAN. IN GENERAL, THE SOIL EROSION CONTROL PLAN SHALL REQUIRE THAT ALL ON -SITE SOILS WILL REMAIN ON -SITE AND WILL NOT ERODE INTO THE ADJACENT ROADSIDE SWALES, ADJACENT PROPERTIES OR RETENTION DITCHES, ALL EXISTING SWALES SHALL REMAIN SODDED DURING CONSTRUCTION. THE CONTRACTOR SHALL SCARIFY ONLY AS NECESSARY TO CONSTRUCT THE PROJECT, THE CONTRACTOR SHALL SCARIFY AREAS TO PLACE VARIOUS PIPE WORK. AFTER PLACEMENT OF THE PIPE, THESE TRENCHES SHALL BE BACKFILLED AND COMPACTED TO 98% MODIFIED PROCTOR AASHTO T-1 80. PRIORTO DISCHARGE FROM THE SITE, SILTATION BARRIERS AND HAY BALES SHALL BE UTILIZED AS PER FDOT INDEX 102. THE DRAINAGE WHICH OUTFALLS TO THE RETENTION AREAS SHALL BE STABILIZED AND SODDED IMMEDIATELY UPON COMPLETION OF CONSTRUCTION. ANY DEWATERING OR PUMPING OF WATER INTO THE ROADSIDE SWALES OR RETENTION SWALES SHALL BE STAKED WITH BALED HAY AND SILTATION FENCES AS PER FOOT INDEX 102 TO AVOID FILLING THESE AREAS. UPON COMPLETION OF THE SITE WORK, ALL AREAS SHALL BE SODDED TO AVOID EROSION. CONTRACTOR IS REQUIRED TO COMPLY WITH ALL STATE WATER QUALITY CRITERIA. SPECIFICALLY, NO OFF -SITE DISCHARGES WILL BE ALLOWED WHICH EXCEED THE STATE TURBIDITY CRITERIA. WATER QUALITY NOTES 1. THE CONTRACTOR MUSTMAINTAIN A COPY OF THE LATEST LOCAL WATER MANAGEMENT DISTRICT SURFACE WATER PERMIT, COMPLETE WITH ALL CONDITIONS, ATTACHMENTS, EXHIBITS AND PERMIT MODIFICATIONS IN GOOD CONDITION AT THE CONSTRUCTION SITE. THE COMPLETE PERMIT MUST BE AVAILABLE FOR REVIEW UPON REQUEST BY DISTRICT REPRESENTATIVES. THE CONTRACTOR SHALL REVIEW THE COMPLETE PERMIT PRIOR TO COMMENCEMENT OF THE ACTIVITY AUTHORIZED BY THE PERMIT. 2. ALL ACTIVITIES SHALL BE IMPLEMENTED AS SET FORTH IN THE PLANS, SPECIFICATIONS AND PERFORMANCE CRITERIA AS APPROVED BY LOCAL SURFACE WATER PERMIT. ANY DEVIATION FROM THE PERMITTED ACTIVITY AND THE CONDITIONS FOR UNDERTAKING THAT ACTIVITY SHALL BE CONSIDERED A VIOLATION OF THE PERMIT. PRIOR TO ANY WORK COVERED BY A PERMIT FROM SOUTH FLORIDA WATER MANAGEMENT DISTRICT (SFWMD), A NOTICE OF CONSTRUCTION COMMENCEMENT (FORM 0960) MUST BE SUBMITTED TO SFWMD BY THE PERMITTEE OR AUTHORIZED AGENT, 3. THE LOCAL WATER MANAGEMENT DISTRICT AUTHORIZED STAFF, UPON PROPER IDENTIFICATION, MUST BE GRANTED PERMISSION TO ENTER, INSPECT AND OBSERVE THE SYSTEM TO INSURE CONFORMITY WITH THE PLANS AND SPECIFICATIONS APPROVED BY THE PERMIT. 4. PRIOR TO AND DURING CONSTRUCTION, THE CONTRACTOR SHALL IMPLEMENT AND MAINTAIN ALL EROSION AND SEDIMENT CONTROL MEASURES (BEST MANAGEMENT PRACTICES) REQUIRED TO RETAIN SEDIMENT ON -SITE AND TO PREVENT VIOLATIONS OF STATE WATER QUALITY STANDARDS. ALL PRACTICES MUST BE IN ACCORDANCE WITH THE GUIDELINES AND SPECIFICATIONS IN CHAPTER 6 OF THE FLORIDA LAND DEVELOPMENT MANUAL: A GUIDE TO SOUND LAND AND WATER MANAGEMENT (FLORIDA DEPARTMENT OF ENVIRONMENTAL REGULATIONS 1988), WHICH ARE HEREBY INCORPORATED BY REFERENCE, UNLESS A PROJECT's SPECIFIC EROSION AND SEDIMENT CONTROL PLAN IS APPROVED AS PART OF THE SFWMD PERMIT, IN WHICH CASE THE PRACTICES MUST BE IN ACCORDANCE WITH THE PLAN. IF SITE's SPECIFIC CONDITIONS REQUIRE ADDITIONAL MEASURES DURING ANY PHASE OF CONSTRUCTION OR OPERATION TO PREVENT EROSION OR CONTROL SEDIMENT, BEYOND THOSE SPECIFIED IN THE EROSION AND SEDIMENT CONTROL PLAN, THE CONTRACTOR SHALL IMPLEMENT ADDITIONAL BEST MANAGEMENT PRACTICES AS NECESSARY, IN ACCORDANCE WITH THE SPECIFICATIONS IN CHAPTER 6 OF THE FLORIDA LAND DEVELOPMENT MANUAL: A GUIDE TO SOUND LAND AND WATER MANAGEMENT (FLORIDA DEPARTMENT OF ENVIRONMENTAL REGULATION 1988). THE CONTRACTOR SHALL CORRECT ANY EROSION OR SHOALING THAT CAUSES ADVERSE IMPACTS TO THE WATER RESOURCES AT NO ADDITIONAL COST TO OWNER. 1 5. WITHIN 30 DAYS AFTER COMPLETION OF THE STORMWATER SYSTEM, THE CONTRACTOR MUST ASSIST IN SUBMITTING TO THE SOUTH FLORIDA WATER MANAGEMENT DISTRICT THE FOLLOWING: DISTRICT FORM EN-45 (AS -BUILT CERTIFICATION BY A REGISTERED PROFESSIONAL), SIGNED AND SEALED BY AN APPROPRIATE PROFESSIONAL REGISTERED IN THE STATE OF FLORIDA AND TWO SETS OF AS -BUILT DRAWINGS WHEN, A) REQUIRED BY A SPECIAL CONDITION OF THIS PERMIT; B) THE PROFESSIONAL USES AS -BUILT DRAWINGS TO SUPPORT THE AS -BUILT CERTIFICATION: OR C) WHEN THE COMPLETED SYSTEM SUBSTANTIALLY DIFFERS FROM PERMITTED PLANS, THIS SUBMITTAL WILL SERVE TO NOTIFY THE DISTRICT STAFF THAT THE SYSTEM IS READY FOR INSPECTION AND APPROVAL. 6. STABILIZATION MEASURES SHALL BE INITIATED FOR EROSION AND SEDIMENT CONTROL ON DISTURBED AREAS AS SOON AS PRACTICABLE IN PORTIONS OF THE SITE WHERE CONSTRUCTION ACTIVITIES HAVE TEMPORARY OR PERMANENTLY CEASED, BUT IN NO CASE MORE THAN SEVEN (7) DAYS AFTER THE CONSTRUCTION ACTIVITY IN THAT PORTION OF THE SITE HAS TEMPORARILY OR PERMANENTLY CEASED. 7. THE STORMWATER MANAGEMENT SYSTEM MUST BE COMPLETE IN ACCORDANCE WITH THE PERMITTED PLANS AND PERMIT CONDITIONS PRIOR TO THE INITIATION OF THE PERMITTED USE OF SITE INFRASTRUCTURE. THE SYSTEM MUST BE COMPLETED IN ACCORDANCE WITH THE PERMITTED PLANS AND PERMIT CONDITIONS PRIOR TO TRANSFERRING RESPONSIBILITY FOR OP7RATION AND MAINTENANCE OF THE STORMWATER MANAGEMENT SYSTEM TO A RESPONSIBLE ENTITY. 8. IF DEWATERING IS TO OCCUR DURING ANY PHASE OF CONSTRUCTION OR THEREAFTER AND THE SURFACE WATER PUMP(S), WELL(S) OR FACILITIES ARE CAPABLE OF WITHDRAWING ONE MILLION GALLONS OF WATER PER DAY OR MORE OR AN AVERAGE OF 1700,000 GALLONS PER DAY OR MORE OVER A YEAR AND ANY DISCHARGE IS TO BE OFF -SITE, THE CONTRACTOR MUST APPLY FOR AND OBTAIN A CONSUMPTIVE USE PERMIT (40C-2) FROM THE SFWMD. CONTRACTOR SHALL NOTIFY ENGINF-F.7 IF ADDITIONAL INFORMATION OR APPLICATION MATERIALS ARE NEEDED. 9. WATER QUALITY MONITORING SHALL BE PERFORMED DAILY WHILE DEWATERING. SAMPLING SHALL BE PERFORMED IN THE MIDDLE OF ADJACENT CHANNELS MEASURING FOR TURBIDITY, 100 FEET UPSTREAM AND 100 FEET DOWNSTREAM OF DISCHARGES. WHEN TURBIDITY EXCEEDS 29 NTU'S ABOVE BACKGROUND LEVELS AT A SAMPLE POINT 100 FEET UPSTREAM OF DISCHARGES AND / OR 0 NTU'S ABOVE BACKGROUND LEVELS AT A SAMPLE POINT 100 FEET DOWNSTREAM OF DISCHARGES, WORK MUST CEASE AND REMEDIAL MEASURES MUST BE PERFORMED TO RETURN CONDITIONS TO ACCEPTABLE TURBIDITY LEVELS. CONTRACTOR MUST RECEIVE ENGINEERS APPROVAL PRIOR TO RESTARTING WORK. SAMPLE POINT LOCATIONS ARE IDENTIFIED IN THE SFWMD PERMITS. 10. THE CONTRACTOR SHALL PLACE TURBIDITY BARRIERS AT ALL OUTFALLS PRIOR TO CONSTRUCTION. ALL CUT I FILL WILL BE RELOCATED WITHIN THE EXISTING SITE AND THEREFORE HAULING OF MATERIAL WILL NOT BE REQUIRED, UNLESS APPROVED BY THE OWNER. CONTRACTOR SHALL INSTALL TURBIDITY CONTROL MEASURES PRIOR TO COMMENCEMENT OF CONSTRUCTION, MAINTAIN SAID CONTROLS IN WORKING ORDER THROUGHOUT THE CONSTRUCTION PERIOD, ASSURE THAT TURBID DISCHARGES FROM THE PROJECT TO PROTECTED WATERS AND WETLANDS DO NOT EXCEED LIMITS STATED IN NOTE 9 AND REMOVE SAID CONTROLS AFTER COMPLETION OF CONSTRUCTION. EARTHWORK AND RELATED OPERATIONS 1. THE CONTRACTOR SHALL PROVIDE A QUALITY CONTROL PLAN FOR MONITORING OF ALL EARTHWORK AND RELATED OPERATIONS. THE QUALITY CONTROL PLAN SHALL INCLUDE AS A MINIMUM, ALL TESTS THAT WILL BE PERFORMED INCLUDING THE PROPOSED TEST FREQUENCIES, ALL MATERIAL SOURCES, THE NAME AND BACKGROUND OF THE PERSON THAT THE CONTRACTOR WILL DESIGNATE AS THE CONTRACTOR'S QUALITY CONTROL MANAGER. THE NAME AND QUALIFICATIONS OF THE TESTING LABORATORY THAT WILL BE PERFORMING QUALITY CONTROL TESTING AND THE NAMES AND QUALIFICATIONS OF THE TESTING LABORATORY PERSONNEL THAT WILL BE PERFORMING THE QUALITY CONTROL TESTING. 2. THE TESTING LABORATORY THAT IS RETAINED TO PERFORM THE CONTRACTOR'S QUALITY CONTROL TESTING MUST BE CERTIFIED BY A RECOGNIZED QUALIFYING AGENCY SUCH AS FOOT, CMEC OR AASHTO FOR THE TYPE OF WORK TO BE PERFORMED. 3. THE QUALITY CONTROL PLAN SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW AND APPROVAL PRIOR TO THE START OF ANY EARTHWORK OR RELATED OPERATION. 4. UTILIZATION OF MATERIALS WITHIN ANY ROADWAY CROSS-SECTION SHALL BE IN ACCORDANCE WITH FDOT ROADWAY AND TRAFFIC DESIGN STANDARDS (LATEST EDITION) UNLESS OTHERWISE SHOWN ON THE PLANS. 5. IF THE EXISTING FILL 18 CLASSIFIED AS A-24 BASED ON AASHTO M-145 CRITERIA, THE MAXIMUM PERMISSIBLE MOISTURE CONTENT SHALL BE 2 PERCENT ABOVE THE OPTIMUM MOISTURE CONTENT. COMPACTION 1. WHERE THERE ARE EXISTING STRUCTURES ADJACENT TO THE SITE THAT MAY BE AFFECTED BY THE SELF-PROPELLED STEEL DRUM VIBRATORY EQUIPMENT, DENSIFICATION MUST BE PERFORMED USING EQUIPMENT THAT WILL SATISFY THE REQUIRED DENSIFICAT10N WITHOUT THE RISK OF DAMAGE TO THE EXISTING STRUCTURE(S). 2. LOADERS AND HEAVY PLATE COMPACTORS ARE TWO TYPES OF EQUIPMENT THAT HAVE BEEN USED SUCCESSFULLY. 3. DENSIFICATION PROCEDURES MUST COMPLY WITH THE CAPABILITY OF THE EQUIPMENT EMPLOYED. 4. WHEN SELF-PROPELLED STEEL DRUM VIBRATORY EQUIPMENT CANNOT BE USED AS SPECIFIED, VIBRATORY PLATE COMPACTORS MAY BE USED. WHEN THIS CONDITION OCCURS, THE OVERALL DENSIFICATION PROCEDURE MUST BE REVISED TO COMPLY WITH THE CAPABILITY OF THE EQUIPMENT EMPLOYED. IN GENERAL, SMALL PLATE COMPACTORS WILL BE EFFECTIVE TO A MAXIMUM DEPTH OF 6 TO 8 INCHES. SOIL RECOMMENDATION AND REQUIREMENTS 1. STRIPPING AND GRUBBING: DURING THE GRUBBING OPERATION, ROOTS WITH A DIAMETER GREATER THAN % INCH, OR SMALL ROOTS IN A DENSE STATE, SHOULD BE GRUBBED AND COMPLETELY REMOVED. PROOF -ROLLING THE CLEARED SURFACE IS RECOMMENDED TO LOCATE ANY UNFORESEEN SOFT AREAS OR UNSUITABLE SURFACE OR LOOSE TO LOOSE FINE SAND SOILS WITHIN THE TOP 3 TO 4 FEET, AND TO PREPARE THE EXISTING SURFACE FOR THE ADDITION OF THE FILL SOILS (AS REQUIRED). ONE COVERAGE CONSISTS OF PARALLEL PASSES OF THE VIBRATORY ROLLER TRAVELING AT"WALKING SPEED". EACH PASS SHOULD OVERLAP THE PRECEDING PASS BY 30% TO INSURE COMPLETE COVERAGE, SUBSEQUENT COVERAGES SHOULD BE CONDUCTED IN A DIRECTION PERPENDICULAR TO THE PRECEDING COVERAGE. IN AREAS THAT CONTINUE TO "YIELD" REMOVE ALL DELETERIOUS MATERIAL AND REPLACE WITH A CLEAN, COMPACTED SAND BACKFILL. THE PROOF ROLLING SHOULD PRODUCE A DENSITY EQUIVALENT TO 95% OF THE MODIFIED PROCTOR (ASTM D-1557) MAXIMUM DRY DENSITY VALUE FOR A DEPTH OF 2 FEET IN THE BUILDING AREA. ADDITIONAL PASSES MAY BE REQUIRED IF THESE MINIMUM DENSITY REQUIREMENTS ARE NOT ACHIEVED. 2, FILL REPLACEMENTS: - WHERE FILL IS TO BE PLACED ON NATURAL GROUND, THE SURFACE MUST FIRST BE PREPARED AS OUTLINED ABOVE. THE FILL AT GRADE SHOULD EXTEND A MINIMUM OF FIVE FEET (5') BEYOND THE STRUCTURE OUTLINE. - FILL SHOULD BE A UNIFORM FREE DRAINING GRANULAR SOIL (CLEAN SAND) AND BE PLACED IN LAYERS NOT TO EXCEED 12 INCHES LOOSE MEASURE AND COMPACTED AS OUTLINED ABOVE. SUFFICIENT COMPACTIVE EFFORT SHOULD BE APPLIED TO OBTAIN A MINIMUM OF 98% OF THE MODIFIED PROCTOR (ASTM D-1 557) MAXIMUM VALUE. 3. EXCAVATION AND BACKFILLING: - WHERE EXCAVATION AND BACKFILLING ARE REQUIRED, THE SOILS SHOULD BE REMOVED TO THE SPECIFIED DEPARTMENT SUFFICIENT COMPACTIVE EFFORT MUST THEN BE APPLIED TO THE EXCAVATED SURFACE TO OBTAIN A MINIMUM OF 95% OF THE MODIFIED PROCTOR (ASTM D-1557) MAXIMUM VALUE. BACKFILL SHALL BE UNIFORM FREE DRAINING GRANULAR SOIL (CLEAN SAND) AND BE PLACED IN LAYERS NOT TO EXCEED 15 INCHES LOOSE MEASURE. SUFFICIENT COMPACTIVE EFFORT SHOULD BE APPLIED TO EACH LAYER TO OBTAIN A MINIMUM OF 95% OF THE MODIFIED PROCTOR (ASTM D-1557) MAXIMUM VALUE. THE EXCAVATED SURFACE AND EACH LAYER OF BACKFlLL SHOULD BE COMPACTED WITH A SELF�PROPELLED STEEL DRUM VIBRATORY ROLLER HAVING A MINIMUM TOTAL APPLIED FORCE OF 170 TONS. 4. FOOTING EXCAVATION: SEE SOILS LABORATORY RECOMMENDATIONS. S. GROUNDWATER: - HEAVY RAINFALL AND / OR A HIGH WATER TABLE MAY OCCUR BEFORE THE EARTHWORK COMMENCES, OR DURING THE EARTHWORK OPERATION. WHEN THESE CONDITIONS OCCUR AND THE SITE PREPARATION CANNOT BE ACHIEVED AS SPECIFIED, AN EXCAVATION OF THE EXISTING CONDITIONS SHOULD BE CONDUCTED AND THE SPECIFICATIONS REVISED ACCORDINGLY. � 6. PAVING AREAS SUITABLE FILL MATERIAL AND THE COMPACTION OF FILL SOILS: - ALL FILL MATERIAL SHOULD BE FREE OF ORGANIC MATERIALS, SUCH AS ROOTS AND VEGETATION AS A GENERAL GUIDE TO AID THE CONTRACTOR, USE FILLINGS WITH 3 TO 12 PERCENT BY DRY WEIGHT OF MATERIAL PASSING THE U.S. STANDARDS NO. 200 SIEVE SIZE. WITH PROPER MOISTURE CONTROL. THESE SOILS SHOULD DENSIFY USING VIBRATORY COMPACTION METHODS. SOILS WITH MORE THAN 12% PASSING THE NO. 200 SIEVE WILL BE MORE DIFFICULT TO COMPACT. EXCAVATION FOR STRUCTURES AND PIPES 1. EARTHWORK AND RELATED OPERATIONS PERFORMED ON STRUCTURES AND PIPES SHALL BE CONDUCTED IN ACCORDANCE WITH SECTIONS 125 AND OTHER APPLICABLE SECTIONS OF THE F.D.O.T, STANDARD SPECIFICATIONS FOR ROADWAY AND BRIDGE CONSTRUCTION (LATEST EDITION) UNLESS OTHERWISE SHOWN ON THE PLANS. 2. REMOVAL OF UNSUITABLE, ORGANIC OR PLASTIC MATERIAL SHALL BE PERFORMED AT THE CONTRACTOR'S EXPENSE AND SHALL BE INCIDENTAL TO OTHER WORK. 3. UTILIZATION OF MATERIALS WITHIN THE WORK LIMITS SHALL BE AS DIRECTED BY THE GEOTECHNICAL ENGINEER UNLESS OTHERWISE SHOWN ON THE PLANS. PIPE AND STRUCTURE BACKFILL 1. IT IS THE CONTRACTORS RESPONSIBILITY TO DETERMINE IF EXCAVATED SOILS MEET THE REQUIREMENTS OF THE PROJECT PLANS AND SPECIFICATIONS RELATIVE TO MATERIAL CLASSIFICATION. PIPE AND STRUCTURE BACKFILL MATERIAL SHALL BE LIMITED TO MATERIAL CLASSIFIED AS A-1, A-3 AND A-2-4 IN ACCORDANCE WITH AASHTO M-145 AND SHALL BE COMPACTED IN ACCORDANCE WITH F.D.O.T. SECTION 125 REQUIREMENTS. . CLEAN-UP 1. THE CONTRACTOR SHALL MAINTAIN THE JOB SITE IN A NEAT CONDITION AT ALL TIMES AND SHALL RESTORE / REPAIR ALL DRIVEWAYS, SIDEWALKS, UTILITIES, LANDSCAPING, IRRIGATION SYSTEMS, ETC., AFFECTED BY CONSTRUCTION ACTIVITIES. 2. THE CONTRACTOR SHALL REMOVE ALL EXCESS MATERIALS, DEBRIS, EQUIPMENT, ETC., FROM THE JOBSITE IMMEDIATELY AFTER COMPLETION OF CONSTRUCTION OPERATIONS. 3. UNLESS OTHERWISE SPECIFIED OR NOTED; ALL DISTURBED AREAS TO BE RESTORED BY CONTRACTOR TO PRE -CONSTRUCTION CONDITION OR BETTER PRIOR TO ACCEPTANCE BY THE OWNER OR LOCAL APPROVING AUTHORITY. PAVEMENT MARKING AND SIGNAGE 1. PAVEMENT MARKINGS: THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MATERIALS AND LA13OR REQUIRED TO COMPLETE THE PROJECT WORK IN THIS SECTION. MATERIALS AND CONSTRUCTION METHODS FOR APPLYING PAINTED TRAFFIC STRIPES AND MARKINGS, COMPLETE WITH REFLECTIVE GLASS SPHERES, SHALL CONFORM TO THE REQUIREMENTS OF SECTION 710, FOOT SPECIFICATIONS. TRAFFIC PAINT SHALL BE APPLIED IN ALL LOCATIONS SHOWN ON THE PLANS. USE THERMOPLASTIC STOP BARS. 2. SIGNAGE: THE CONTRACTOR SHALL PROVIDE ALL MATERIALS AND LABOR NEEDED, INCLUDING ALL SUPPORTING ELEMENTS, TO INSTALL SIGNS AT THE LOCATIONS SHOWN ON THE PLANS. MATERIALS AND CONSTRUCTION METHODS SHALL CONFORM TO SECTION 700, FDOT SPECIFICATIONS. STOP SIGNS ARE TO BE HIGH INTENSITY REFERENCE PER FOOT STANDARDS, LOCAL COUNTY/CITY STANDARD AND THE MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES. AT NO TIME SHALL ANY SIGNS NOT MEET THE SAFETY REQUIREMENTS SET FORTH BY FOOT. FILE COP*' : Z . C.) (.D Z . cn ;i Lo F) 0) � LLI (1) ix cr cl0 �_ 0� C:) L0 w w w m z :E 0 �- 0 D O-) -t L0 L0 't 5 :D LZI Z z M o ( m C'4 I -t Lo z � C) < F= . W 0� _5 0� _j LL c\I (D -t C\j zo r<4 I, zz LLI �. LL, LLi .'T I I N (n 0 Ld Lo, Lu in �e (-) , �J C-4 r� (O ,,I- F Of D < z z 0 ::) �_ 0� �j r-_ I 04 r, a- � � 00 Z5 L) "t 0- (1) a r'- a W ft < z Lu 06 M 0) � _: 0 j_- �� M < u 0 m � FZ � LL 0_ 4- w 0 11 w Lu a (0) ,_ _____ - - . . __ X __ 0 3: __ _q � m m � - w 0 w m .E m I . z 0 2 < 8 , � � D 0 0 . tR � 4� . z � 2 z S 0 � z W . , � 0 � :� w . . =� 0 , < 0 � < 0 � - w 0 a �; 1� . - V) U) z 0 U) F_ =) < w 0 F_ M T� 0 < Lu 0. (1) �\� P I 2 �. . ��- W " No %,,�_ I � . RJ I . ](h N N E 6 Y",'?ft. 4 It � I * : #56:98 SN:i� jo * 1934 " , KJ=-R C&RT /_ FT. =_cr.%CWRSKA�� � wo I w � z w N 2 0 0 z 0 �2 > w m < a w 0 -i LL >_ F_ z :) 0 0 w u M _j F_ z < U) . I W/I I I I 111\1'10_�� V�' � 'L 15-251 ' , ,_ � , _77__) _ _ _ _ _ _ _ _ ___:�_ 12 OF 12 9 � I z bj NOTE: ALL TRUSS TO WALL AND/OR TRUSS TO LEDGER CONNECTIONS BY BUILDER (UNLESS NOTED OTHERWISE) E NOTE: ALL CEILING DROPS BELOW BEAM ARE BY BUILDER (UNLESS NOTED OTHERWISE) NOTE: THIS TRUSS PLACEMENT DIAGRAM IS TO SHOW TRUSS I.D. AND TRUSS LOCATION ONLY. THE BUILDING DESIGNER IS REPSONSIBLE FOR THE 9 9 2 STRUCTURAL STABILITY OF THE ENTIRE STRUCTURE. 62'(y REFER TO THE INDIVIDUAL TRUSS ENGINEERING 50.0.1 NOTE: ALL FLAT CEILINGS DRAWINGS FOR GRAVITY AND UPLIFT LOADS. NOTE: ALL WALLS SHOWN FOR BRACING & ERECTION DETAILS REFER ON LAYOUT ARE BEARING. TO BCSI-03 AND/OR ENGINEER OF RECORD BEARING ELEVATIONS P E HIS TRUSS PLACE' R D AND TR OT ' T SHOW T USS I U THE BU ILD ING DESIGNER IS F STRUCTU RAL STABILITY OF T� REFER To THE I NDIVIDUAL DRAWINGS FOR G VITY 7/ �,,777,—,777/—/— h�L 101811 fl iN. EXISTI�N�GWALL 7_ L / ''/ 7/ HGTT 72� '41 7 < REPRESENTS THE LEFT SIDE OF & 10P811 EACH TRUSS DRAWING 7 j �g . 5 E IN EXISTING WALL VERIFY = . = a, EXISTING ONE STORY BUILDING N HGT. WALL HGT. E= 0 8C `111�1�1 I � '119 r 4'1' 4" 1'j" 1'4" 1- 4"['T'� 9" 1'11" 1'4'J�1'4`� 1- 4-'� 1- 4" 1'4f '4" U�4- &41'4 - 4� '4" TOP @ 10-811 MECH. I ROOM I ELEVATOR 18- 5" OPEN TO ABOVE ----------- STAIRWAY OPENING N N � IN 2 1- 4" B IN B N'l I C.L. of C ASI T �7 ' "M� IL M I SP CI G S A: 4.1 1-4" 1- 1-4`W41' 1'4" P 4"" 1 111.1 1- 41' 1141 1'4" 11 4� 1P 4" 1'4' 62- Opp 112F 4 [IM1111 I Z— ZL 9 r IS NEW GIRDER TO SUPPORT EXISTING ROOF & WALL A DASHED LINES = EXISTING TRUSSES I/NEW GIRDER TO SUPPORT / EXISTING ROOF & WALL A 10'8" WALL HGT & CEILING HEIGHT T— FIRST FLOOR. CA OH --- 137' W A, HS 1 12 - MUS28 1e 1 i K) --- /D) 10 24'0" WALL HGT t5 -THD28 E�/ 2� 79 :F) 6 - TH D28-2 CN) --- OVE NJ �nNG GIRDER ---------------- NEW GIRDER TO SUPPORT F-Z 2:9 -E J.; '9 LOADING ROOF FLOOR WIND LOAD LIVE LOAD 30 80 ASCE 7-10 0 0 DEAD LOAD 15 15 170 MPH � EXp C LIVE LOAD 10* 0 rATCf-%n0V III E WALL & GABLE ABOVE ONLY 00 4- DEAD LOAD 10 5 ENCLOSED — SINGLE LEDGER REQ.BY BLDR. TOP @ 132" 3 E TOTAL LOAD 55 100 FBC-2014 DOUBLE 2X LEDGER REQUIRED BY BUILDER, TOP @ 12'8-1/2" Z t DURATION FACTOR 1.00 1.00 TPI - 2007 Z rN, By 0) = PLUMBING CHASE TO REV DATE BY REMARKS BE VERIFIED IN FIELD COLUM '0 T'O 019.10., E BEFORE SETTING TRUSSES. 4/5/16 LUA ADJUSTED COLUMN LOCATIONSTO 19-10". Z 2 4/13/16 LA ADJUSTED FOR DUCT CHASES. HAND-F3AME ## = HANGER REQUIRED VALLEY'S BY BUILDER. A 4 8� '2 I E EXISTING ONE STORY BUILDING z- 7S 2. E E It is understood that above conditions have been reviewed APPROVED & are acceptable for the 4 — fabrication at trusses, APPROVED AS NOTED E 49 5- f elevations, pitches, overhangs, REVISE AND RESUBMIT —8 fascias,ceiling elevations/p itches, bearing REJECTED iconditions & all detail pertaining �to this truss placement plan. No 2� back charges will be accepted D-A—TE IRG GIRDER without previous written g Na approval from an A-1 Roof Trusses representative. REVIEWED BY PLAN DATE ARCH: N/A STRUCT: N/A CUSTOMER JOHN HERRING �E z JOB NAME A-1 ROOF TRUSSES ADDITION GE E0 LOCATION FT PIERCE1 ST L LICIE -.20 ? NOTE: VERIFY SETBACK FOR COMMNTY \ ST L LICIE& VD. j EXISTING #1 HIP GIRDER!!! LOT # % FILE COPY BLOG BLDG EXISTING ONE STORY BUILDING I , - - 4= = - -a. 0 # 2 -2 A7 -zz ;-i - ASSUMED 6/12 PITCH WITH 2X6 HEEL H.GT. & 2'0" OVERHANGS. ic 1B # 64215 MASTER PAGE 1of2 t;g Z t E- � --E = -1 -�r g := . L- "a -..E E DRAWN SCALE 77 D.1 'a.11y signed by Anthony T. DATE MARCH 11, 2016 & T 11D Anthony DIN: �-Ijs , st=Florida, ]=Fort L VA N. TS. "Orce, o-Whole House Engineering, cn=AnthonyT. Z T.Toombol Tornbo, 111, T T6A40'11.. ennaII=Anthony.Tornbo@when E 50'0" gineering.net 1:14%, Date: 2016.04.26 13:35:52 -N %IN . X S �= V -0001 NO T. z N "t6a b SERIAL #: 3B BC A2 2100 00 00094C 12 87 DF 11 CA CALC FLOOR 0 ft2— ROOF —TAS—CIA 12191.68 --36-6.59,, HIP LINE 162 It VALLEY LINE 159.09, SHEETING AREA UNDER VALLEY TRUSSES AND WASTE mATERIAL NOT INQUDED BLDR TO VERIFY MAwl ROOF MAwl ROOF �2 M TRUSSES iitw !g i --.1 20�0. �- C A FLORIDA CORPORATION wa 4.Z Ph 772-409-1010 / Fax 772-409-1015 httn'11wwwa1f-- --- =--5 LCLANTIONS cc 0 = — � - �' VUDISISSD JOJ 0 tO i-60k-ZLL 11D) NOW 'as oqt is luoin pozijo4loo s,jeumo oqt lieumo oql Aq p9jinbei sin 1. asuloue uIll SOP SSnJJ 811110 liom Is ado3s oy op1sIno IssmAjos Ouposuillue Ann 11 -6u!pl!nq An jai is u / u ------I—ulpll-- qw—�4 'oqwoi AuoqiuV jou sesswi lool [V joql!ON qljol us pun sessnit By )a U61SOP OqJ Ul I Bu'4!)Ods 'ssnil 9q1 ol wflj)jqdi7,p —iool, D quill 3 is elsoa WOJSAS ssnjI 10 iquillsoc nq oql Paso spool aq Jo/pun JooJ 10 U0,138m) loulpl!flq 94110 swoojqdoip moll jo/puD looi eqj in sisAlouV 'pos pun uoilopunol sill jo AM 'UOIIDPUnOl Diff 01 UmOP spool Imilm lo jolsunil 'weisAs jooll Jo/"puo looi eqj ui paimbai Oupoiq Apl!qu4s Buipl!nq lueuDwied pun Aiojodwial 'sijoddns Ruposcl 91filo disea 'lioddos Oupoeq aq; o4 sassnil in uoil3auuo) 's1lom jDOqs 8qJ at I'm aqi wojj pool iDiaml is joisunil :at pol!wil jou tnq hulpripul ou[molloj pql jai alq!suodsoi ION sl JOH169 ufi]sQG ssflJ1 041 '1 ldi JOd s0di Aun OPIAoid pun sluguodwo) 6ul 'SOP OqJ qJ!M' JOAD8 SJ! GP!AOJd' Illm sessnil lool [V U01404ou sly 10 amas , R -1- pl!nq li inpni4s lonp!Aipui u6isep ol quqLUMOP U011MISUO) Oq1 JOd 'POSA SUO11dUJflSSD Ufij qa qq4 Ul '(MOIABJ J01 UJnJOJ 01 PUD POJOU SUM loijoi )i pods slow oi jo) lluippnq ay in ullisop oqI qpm 9)uuwjojuoi lojoud ui eq ol punoj ugbq QAoq sJummop pgMR!AOJ 944 JDqJ BU1ID)1PUl UOIJUJOU 1) Opnl)ui Iloqs maim siql -sjuewmp IDII!wqns posoqd pun sluown)op Iollpiqns poijolop ; sl'410'Aq P§jodojd sluawnio*p iojl!wqns Buipolm 19jolmils is Buippoirl eip jo uffisop Dili qj!m Al!l!q!lodwo) joj as Bill Aq p*omolAoj aq lloqs (soulmaip doqs IojolinjjS -sluaweiinbei 11upeouillue uallpm may ql!m Al!llq!lDdwo) JOI adi Slql Pon Saal Oql MOIAOJ Pon OIDUIPIO03 lloqs pun Jai elyguods9i si joullisea 6uipl!ng 9q1 -1 Idl In uoism lso4ol aill qt!m emoildwo) ui poluej) uaeq soq adl ioqt Allwqpeds saloullisap loss TJ 'oqwoi Auoq4uV -6uiuoi1!sod lo'q4 q)*IDw shimp pe'utaialej qqJ uo'umoqs spool Pun suoisuawip ey joy put) um04s Buiuoij!sod ey us p8sDq OJD SUOISOP SSnJJ 10np!AIPUI 941 JDqJ S91111M adl ADD UO [DOS s,*3'd 'oqwol Auoq1uV -jal Auo in loss oql aiinbei ;ou soup 4! 'ucljolln4sul ssni, jai op!nP a so Aluo SOAJOS (sliumcip doqs is slon!wqns lainpnils wi) OdI. oql ugqtA 'POPIADJd S1 Isluawnlop 130JIU03 I)olojd Dill Is momaj sp On pasoq sessmijooll' IV Aq pownsso so Issoil yno In uoilmol sill UwAiguop! adi a Isuo!*Io)i * ypads Ann Buipnim 'Sloewniop uoil)njlsuoi is 1)oj4uoi 4ioloid 9qI Aq pamobai ojoqM -Aloo Gal oy no palijdap ssnil alfluis aql is ullisop sq1 jai 14!1!q!suodsoi OupoQuillue Icuoissoloid Is q3UDJdq)3n up s4uesojdoj Gal Auo UO PUD OJI94 POPIAoid loss ey 'jasuillu] Msoa ssnil aq1 sV -sloiquiqns pesnqd jo poij jap'speloid aq1 snil loo-S IV Aq Td BA04 U1QJQqJ DIJ94y) U61sep . 041 -liom 04110 JBI)ojoy Pun alfl4ou 04' lo liod Oq Aow pun suBisep lueuodwo) loinlinig A41opeds ajo (,,siuown)oa lluijoeuil)q paidelea lojni)nj4S,, so sewil in 04 PDJJOIQJ Oslo) Saal JIV 'SOS 'oqwoi Au041AV 01 PGJJO)suuJi MCI flugm1pul as aql Aq PBP!Aoid sjuawwop uoi4ini4suo) sq1 no posoq pajodejd uooq 9ADq pomejejej (Gji) wDjooi )GGIJ Won' Buipling Dill jai as ag Aq 6' 04 poqsiujnj uaoq QADq 4D4t suoi4omlpods Ann lluipnlm sluawnioa On' OBUIBU3 loiniiinjis, so sawii in oi poijejoi osl s4uowA)op a Pn .0 luawwola ssnil , no [(s MDJG U01log ssnil oqi U111im ul sessnil long IV P u I j4suoi pop 4mwo) t)olojd is ssoustoldwo3 pun A)ojn)io sy uOdn Alai ol P041!wjo Td 'oqwoi Auoq1uV Poo sessnij laq IV '(I Idl) I 1JI/ISNY Pun OPD) Bui linq In 41 )Bl OqJ ml O� I )a 4 Duloisq) JOUDISOO oul linq In 1 9 xaluo) q4 01 (as Jai) pl!nH 044 is ;U961) OZIJ04400 S,jqumO ey joumo oql Is Alll!qlsuodsoi oql si Duipl!ng Ann jai (-)49 Isessnil -0-9) slu uodwo) Buipl!nq loin4mils Is asn pui) /411!qot!os 'sq1Dd pool Isuoi ipuo) Buipool Isuoildwosso .1. uI11sOP 9111 :31ON WYNOVIC! INIM-33-VU—SS-n-Iff LU Uj LU >- 0 LLJ , 0 M: of co F- LLi F- >- F- D LL UJ z J l.- Z 0 CD U) CQ Z W 0 EE 0 CC 0 Ui 0 r, 0 0 00 =) LU < LLJ (r LU 0 r2 CC 0 0 z In ILLI UJ LL of LU 0 LL 0 0 (D J 0 C4 N Lm F-- z w l.- z -j UJ 65 K a a -J EU> .4 LLI < w U Q w U) F- 0 w z z Of , F- U) z U) U) ix LL U. w UJ C2 0 0 3: 0 0 P 10 LU LL w < W CD 0 ED 2 0 > > I CL 7 0 0 DOZ= IL 0 -J F= cc Ln CD 0 to LU 0 0 �j 0 D ts 0 Z >- Ld z -J U) LLJ U) C3 LU x a: 3 Q. CL L) CN n w U) Ui < < C) LU U) 5 z Ui D 0: z y) U) Z U) LU LJJ Of < z 2 -< vi 0 a LO to z LU CL W O� M F- z 0 El E El L-1 P= x 0 0 00 -1 a .9 _j J i 4 _J CID co co P (5 z LL 0 LL F- 1-- 2 — LL < w 0 0 U.1 w 0 3 5: 0 z CD C6 r -0 4�4 "no Z < 0 L) 0 cm cm U) LU 0 0 Z w LL > a) 0 LL. ry ry Lf) (D CIO 0 0. -r- C6 cc U) z W z M < z > > m r cc a) > V) ca LU a) CL C.) (n Z U) - (.9 5 23 (9 w 0 EL 0 0 U) CL) Q) ca z cz to Z) 0 0 =sl it :5 0 Z it C U) > Mm CL C14 7 Cc c Ln ch, U0. F- z g g w w *0 Z W LU of —' w < — 0 0 Z U) 0 l.- LU LL z < 0) a) 2 0 (D Un -.1 LU En (6 0) a) 0 M a) 0 F" x 0 -9 E m -0 m m 0 0 = .0 8 " m 04 —1 (3 W Z 00 0 cl < -1 00 0 _J 0 co w C14 cli -J > 0 0 m CC) < 0 0 z F 0 z U) i A - F- F- m L) U) M L) -05 L.L1 I >- 0 z LLJ CAD CJ CL Cl (D CL WI—j � L� Co Lij D IH .6 D (n U) CL cr W (6 cc w U) a) w D 1-- w < -J !R LU 0 0 U) (D in 0 0 .0 2 A 0 z W LL lu 0 — 2 0 < CID 2 LL 00 z U) LU > 0 z zi T (18OH3 (MOHO od 8:1-- z 'a =- 8 2 OM *CO (�Q) 0 w Cc m V) CC) 5 9 0 ca 0 z 0 0-0 CL 0 U) dOi i0e U 0 U big �7 z U ti d �r. z Lo z U R 2 ca 0 0 z 0 z z 0 go z b LL U- 0 0 0 E 0 -C E 6H, ai;8 :91 to 20 1 12 � E 9 0 o E 0 < Ln rq t6 w to —I ci in rq m LIJ ILLI cr 0 0 < a LzJ =i z .cr Lt. 0 w * LL CL U U m