Loading...
HomeMy WebLinkAboutPROJECT INFORMATIONRight -Suit Commercial Load Calculation SHOP JOHN FOST R SCANNED (SAO A A ^_ 6, P,',4 N M�& For: HANGARS V%fW IV & V\ FT. PIERCE, FL e: LWH: 30.0 x - 7.0 x 12.8 1. DESIGN CONDITIONS - COOLING Outdoor Conditions Indoor Conditions TOD Correction Di4erence 2. GLAZING SOLAR HEAT GAIN Type Orien Area Tilt n/a 0 n/a 0 0 Job: JUL 17, 2006 Jul 1500 ) )ry Bib RH Moisture Range Wet Bib 90 59 15 78 75 50 63 0 15 61.5 Mult 1.0 Lat 27.45 ON Const Wt M ) JF IntShd SCMult Sc Sens/A Sens 0.00 0.00 0.0 0 3. TRANSMISSION GAINS Type Orien GrArea NtArea Uval Grp CLTD Shad CIr Sens WALL 1 E 346 282 0.065 E 36.5 N D 668 WALL 1 S 384 384 0.065 E 24.8 N D 619 DOOR 2 e 64 64 0.460 14.5 427 FLOR 1 - 57 57 0.810 0.0 0 ROOF I - 810 810 0.050 RC-1 79.5 D 3220 4. INTERNAL HEAT GAIN PEOPLE Activity Schedule ft2/prsn Office 150 8to6 0 Sens Latent Total Sensible Latent # people Btuh/prsn Btuh/prsn 0 5 200 150 1080 810 0 0 0 0 0 0 %"rightSC3ft Right -Suite Commercial 5.8.13IRSC50847 2006-Jul-27 18:24:03 Projectl.rsc Page 1 LIGHTS Type Total Factor Space Schedule W/W W W BtuhM fract Fluorescent 1.50 0 1215 4.10 1.0 4981 8to6 Fluorescent 0.00 0 0 4.10 1.0 0 Fluorescent 0.00 0 0 4.10 1.0 0 Fluorescent 0.00 0 0 4.10 1.0 0 PLUG LOADS / APPLIANCES Application Usage Total Sensible Latent Schedule Btuh Btuh Plug load W/ft2 W 8to6 0.70 0 1.00 567 3 0 1935 #/ft2 # 0.000 0.00 1.00 0 0 0 0 #/ft2 # 0.000 0.00 1.00 0 0 0 0 #/ft2 # 0.000 0.00 1.00 0 0 0 0 #/ft2 # 0.000 0.00 1.00 0 0 0 0 #/ft2 0.000 0.00 1.00 0 0 0 0 MOTORS Power (hp) Load Total Sensible Schedule #/ft2 # factor Btuh 0.00 0.0 1.00 0 0 0 0.00 0.0 1.00 0 0 0 0.00 0.0 1.00 0 0 0 0 0 0 0 0 0 5. INFILTRATION Sens Latent 20 cfm x db Temp Diff 15.0 x 1.10 330 x Moist. Diff 61.5 x 0.69 850 6. SUBTOTAL COOLING LOAD FOR SP�CE 13259 5907 7. SUPPLY DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 8. COOLING FAN SIZING Sum of Duct Gain (7 Line (6 & Drawthru Fan 13504 (L 8 Se�,s (Xfer x Supply TD ) = dm Est Cooling cfm 3504) 1.10 x 20.0 ) = 614 Actual Cooling Fan > = 679 9. VENTILATION 100 cfm x db Temp Diff 15.0 x 1.10 1649 x Moist. Diff 61.5 x 0.69 4248 10. RETURN AIR LOAD FROM LIGHTIP G AND ROOF Lights Total power (W) 0 4981 RA Roof Load from Line 3 0 RA Ceiling Load Credit 1 from Line 3 0 N"ri4gh-tSC3ft Rigtit-suite commercial 5.8.13 SG50847 2006-Jul-27 18:24:03 Projectl.rsc Page 2 11. RETURN DUCT HEAT GAIN Gain factor 0.00 Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQUIP� NT (Btuh) 15153 5907 SPAC HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (inside D13 - Outsi e DB) 14. TRANSMISSION LOSSES Type Expos GrArea NetAr a Uval WALL 1 E 346 292 0.065 WALL 1 S 384 3 �84 0.065 DOOR 2 e 64 1 4 0.460 FLOR 1 57 57 0.810 ROOF 1 810 10 0.050 70 - 42) 28 Mult 1.0 HTD Loss 28.0 513 28.0 699 28.0 824 28.0 1293 28.0 1134 15. INFILTRATION Loss 40 cfm x dbTempDiff 28.0 x 1.10 1231 16. SUBTOTAL HEATING LOAD FOR SP�CE 5693 17. SUPPLY DUCT HEAT LOSS Loss factor 0.00 x Li e 16 Loss 0 18. VENTILATION 100 cfm x dbTempDi fll 28.0 x 1.10 3077 19. HUMIDIFICATION Inside RH desired 4 .0 (Max = 32.0 for 1 pane # of Glazing panes .0 (Max = 52.0 for 2 pane 140 cfm x 3.20 m0cfm/d 4.5 gpd 1694 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x L ne 16 Loss 0 21. TOTAL HEATING LOAD ON EQUPT IENT (Btuh) 10465 vvriqhtS(:)0ft Right -Suite Commercial 5.8.1 RSG50847 2006-Jul-27 18:24:03 Projectl.rsc Page 3 Right-SuK6 Commercial Load Calculation OFFICE 3 JOHN FOST, R For: HANGARS WW IV & V FT. PIERCE, FL LWH: 12.0 x 15.0 x 12.8 one: 1. DESIGN CONDITIONS - COOLING Outdoor Conditions Indoor Conditions TOD Correction Difference 1 4 ri - L MUIL 2. GLAZING SOLAR HEAT GAIN Lat 27.45 'N Const Wt M Type Orien Area Tilt hdF IntShd SCMult SC Sens/A Sens GLAZ 1 E 16 90 N 1.00 0.27 16.4 262 Job: JUL 1712006 (Jul 1500) Dry Bib RH Moisture Range Wet Bib 90 59 15 78 75 50 63 0 15 61.5 3. TRANSMISSION GAINS Type Orien GrArea NtArea Uval Grp CLTD Shad CIr Sens GLAZ 1 E 16 1 0.500 14.5 N - 116 WALL 1 E 192 17 0.065 E 36.5 N D 418 FLOR 1 - 15 1 0.810 0.0 0 ROOF 1 - 180 181 1 0.050 RC-1 79.5 D 716 4. INTERNAL HEAT GAIN PEOPLE Activity Schedule ft2/prsn Office 150 8to6 0 Sens Latent Total Sensible Latent # people Btuh/prsn Btuh/prsn 0 1 200 150 240 180 0 0 0 0 0 0 %,ovrightSC)jft Right-Sufte Commercial 5.8.1� RSC50847 2006,Jul-27 18:24:03 Projedl.rsc I Page 1 LIGHTS Type Total Factor Space Schedule W/ft2 W W Btuh/W fract Fluorescent 2.00 0 360 4.10 1.0 1476 8to6 Fluorescent 0.00 0 0 4.10 1.0 0 Fluorescent 0.00 0 0 4.10 1.0 0 Fluorescent 0.00 0 0 4.10 1.0 0 PLUG LOADS / APPLIANCES Application Usage Total Sensible Latent Schedule Btuh Btuh Plug load Wjft2 W 8to6 0.70 0 1.00 126 3 0 430 0 #/ft2 # 0.000 0.00 1.00 0 0 0 0 0 fi#//,ftU2 0.000 0.00 1.00 0 0 0 0 0 #/ft2 0.000 0.0 1.00 0 0 0 0 0 #/ft2 0.000 0.0 1.00 0 0 0 0 0 #/ft2 0.000 0.0 1.00 0 0 0 0 0 MOTORS Power (hp) Load Total Sensible Schedule #fft2 factor Btuh 0.00 0.0 1.00 0 0 0 0.00 0.0 1.00 0 0 0 0.00 0.0 1.00 0 0 0 5. INFILTRATION Sens Latent 0 cfm x db Temp Diff 15.0 x 1.10 0 x Moist. Diff 61.5 x 0.69 0 6. 1 SUBTOTAL COOLING LOAD FOR SP�CE 3657 1199 7. SUPPLY DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 8. COOLING FAN SIZING Sum of Duct Gain (7), ine (6 & Drawthru Fan 3725 (L 8 S ns ) (Xfer x Supply TD ) = Cfm Est Cooling cfm 3725) 1.10 x 20.0 ) = 169 Actual Cooling Fan > = 188 9. VENTILATION 24 cfm x db Temp Diff 15.0 x 1.10 396 X Moist. Diff 61.5 x 0.69 1019 10. RETURN AIR LOAD FROM LIGHTI�,G AND ROOF Lights Total power (W) 0 1476 RA Roof Load from Line 3 0 RA Ceiling Load Credit from Line 3 1 0 NAiFri4ghtSC3ft Right -Suite Commercial 5.8.1 IRSC50847 2006-Jul-27 18:24:03 Projectl.rsc I Page 2 11. RETURN DUCT HEAT GAIN Gain factor 0.00 1 x Line 6 Sensible Gain 0 . 12. TOTAL COOLING LOADS ON EQUIPM� NT (Btah) SPA4 HEATING LOAD CALCULATION 4120 1199 13. HEATING DESIGN TEMPERATURE le Heating TD = (inside DB - Outs ide DB) 70 - 42) 28 Mult 1.0 14. TRANSMISSION LOSSES Type Expos GrArea NetAr a Uval HTD Loss GLAZ 1 E 16 .16 0.500 28.0 224 WALL 1 E 192 76 0.065 28.0 320 FLOR 1 15 15 0.810 28.0 340 ROOF 1 180 80 0.050 28.0 252 15. INFILTRATION Loss 12 cfm x dbTempDiffl 28.0 x 1.10 354 1 16. SUBTOTAL HEATING LOAD FOR SP�CE 1491 17. SUPPLY DUCT HEAT LOSS Loss factor 0.00 x Li e 16 Loss 0 18. VENTILATION 24 cfm x db Ternp Diff 28.0 x 1.10 739 19. HUMIDIFICATION Inside RH desired 4 .0 (Max = 32.0 for 1 pane # of Glazing panes .0 (Max = 52.0 for 2 pane 36 cfm x 3.20 /1 00cfm/d 1.1 gpd 430 20. RETURN DUCT BEAT LOSS Loss factor 0.00 x ine 16 Loss 0 21. TOTAL HEATING LOAD ON EQUP iENT (Btuh) 2659 1 I %,PvrightS(:3ft Right -Suite Commercial 5.8.1 RSC50847 ProjectInc 2006-Jul-27 18:24:03 Page 3 Right -Suit Commercial Load Calculation OFFICE I JOHN FOSTER Job: JUL 17,2006 For: HANGARS WW IV & V FT. PIERCE, FL �FFI�Cf­ 12.0 x 12.8 LWH: 12.0 x 1. DESIGN CONDITIONS - COOLING Jul 1500 Dry Bib RH Moisture Range Wet Bib Outdoor Conditions 90 59 15 78 Indoor Conditions 75 50 63 TOD Correction 0 Difference 15 61.5 Mult 1.0 2. GLAZING SOLAR HEAT GAIN Lat 27.45 a N Const Wt M Type Orien Area Tilt hdF IntShd Scmult SC Sens/A Sens GLAZ 1 E 16 90 N 1.00 0.27 16.4 262 3. TRANSMISSION GAINS Type Orien GrArea NtArea Uval Grp CLTD Shad Cir Sens GLAZ I E 16 1 0.500 14.5 N - 116 WALL 1 E 154 13 0.065 E 36.5 N D 326 FLOR 1 - 12 1 0.810 0.0 0 ROOF I - 144 14 0.050 RC-1 79.5 D 572 4. INTERNAL HEAT GAIN Sens Latent PEOPLE Activity Total Sensible Latent Schedule ftl/prsn # people Btuh/prsn Btuh/prsn Office 150 0 1 200 150 192 144 8to6 0 0 0 0 0 0 0 'w"rj4ghtSC)ft Right-SuiteGammercial5.8.1�RSC50847 2006-Jul-27 18:24:03 Projectlsse I Pagel LIGHTS Type Total Factor Space Schedule W/ft2 W W BtuhNV fract Fluorescent 2.00 0 288 4.10 1.0 1181 8to6 Fluorescent 0.00 0 0 4.10 1.0 0 Fluorescent 0.00 0 0 4.10 1.0 0 Fluorescent 0.00 01 0 4.10 1.0 0 PLUG LOADS / APPLIANCES Application Usage Total Sensible Latent Schedule Btuh Btuh Plug load W/ft-2 8to6 0.70 1.00 101 3 0 344 0 #Ift2 0.000 0.0 1.00 0 0 0 0 0 #/ft2 0.000 O.Ot 1.00 0 0 0 0 0 fflff2 4E 0.000 0.00 1.00 0 0 0 0 0 #/ft2 0.000 0.01 1.00 0 0 0 0 0 #/ft2 0.000 0.0 1.00 0 0 0 0 0 MOTORS Power (hp) Load Total Sensible Schedule #/ft2 factor Btuh 0.00 0.0 0 1.00 0 0 0 0.00 0.0 0 1.00 0 0 0 0.00 0.0 0 1.00 0 0 0 5. INFILTRATION Sens Latent 0 cfm x db Temp Diff 15.0 x 1.10 0 x 1 Moist. Diff 61.5 x 0.69 0 6. SUBTOTAL COOLING LOAD FOR S�CE 2994 960 7. SUPPLY DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 8. COOLING FAN SIZING Sum of Duct Gain (7), ine (6 & Drawthru Fan 3049 (L 8 S ns ) (Xfer x Supply TD ) = cfm Est Cooling cfm 3049) 1.10 x 20.0 ) = 139 Actual Cooling Fan > = 154 9. VENTILATION 19 cfm x db Temp Diff 15.0 x 1.10 317 x Moist. Diff 61.5 x 0.69 816 10. RETURN AIR LOAD FROM LIGHT GANDROOF Lights Total power (W) 0 1181 RA Roof Load from Line 3 0 RA Ceiling Load Credit from Line 3 0 VvrjghtSC�ft Right -Suite commercial 5.8.1 RSCS0847 2006--Jul-27 18:24:0: Irojectl.rsc Page 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 . 12. TOTAL COOLING LOADS ON EQUIP� NT (Btah) SPAC� HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (inside D13 - Out ide DB) 14. TRANSMISSION LOSSES Type Expos GrArea NetAr a Uval GLAZ 1 E 16 .16 0.500 WALL 1 E 154 38 0.065 FLOR 1 12 .12 0.810 ROOF 1 144 144 0.050 3365 960 70 - 42) 28 Mult 1.0 HTD Loss 28.0 224 28.0 250 28.0 272 28.0 202 15. INFILTRATION Loss 9 cfm x dbTempDiff 28.0 x 1.10 284 16. SUBTOTAL HEATING LOAD FOR SP4CE 1232 17. SUPPLY DUCT HEAT LOSS Loss factor 0.00 x Line 16 Loss 0 18. VENTILATION 19 cfm x db Temp Di fl� 28.0 x 1.10 591 19. HUMIDIFICATION Inside RH desired 4 .0 (Max = 32.0 for 1 pane # of Glazing panes .0 (Max = 52.0 for 2 pane 28 cfm x 3.20 /1 00cfm/d 0.9 gpd 344 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x Line 16 Loss 0 21. TOTAL HEATING LOAD ON NT (Btuh) 2166 %4VrjghtSC)ft might-SufteGommerclal&8.13 SG50847 2006-Jul-27 18:24:03 Projectl.rsc Page 3 Right-Sui e Commercial Load Calculation OFFICE 2 Job: JUL 17,2006 JOHN FOST R For: HANGARS WW IV & V FT. PIERCE, FL LWH: 12.0 x 12.0 x 12.8 1. DESIGN CONDITIONS - COOLING Outdoor Conditions Indoor Conditions TOD Correction Difference 2. GLAZING SOLAR HEAT GAIN Type Orien Area Tilt n/a 0 n/a 0 0 F- ( Jul 1500 ) Dry Bib RH Moisture Range Wet Bib 90 59 15 78 75 50 63 0 15 61.5 ----[ Mult 1.0 Lat 27.45 ON Const Wt = M ) dF IntShd SCMult SC Sens/A Sens 0.00 0.00 0.0 0 3. TRANSMISSION GAINS —[ 0.050 RC-1 79.5 D 572 Type Orien GrArea NtArea Uval Grp CLTD Shad Cir Sens ROOF 1 - 144 1; 4. INTERNAL HEAT GAIN PEOPLE Activity Schedule ft2/prsn Office 150 8to6 0 LIGHTS Type Schedule W/ft2 Fluorescent 2.00 8to6 Fluorescent 0.00 Fluorescent 0.00 Fluorescent 0.00 Sens Latent Total Sensible Latent �# people Btuh/prsn Btuh/prsn 0 1 200 150 192 0 0 0 0 0 Total Factor Space W W Btuh/W fract 0 288 4.10 1.0 1181 0 0 4.10 1.0 0 0 0 4.10 1.0 0 0 0 4.10 1.0 0 144 0 %,;vrightSC>ft Right -Suite Commercial 5.8.1 RSC50847 2006-Jul-27 18.,24:03 ProjectInc Page 1 PLUG LOADS / APPLIANCES Application Usage Total Sensible Latent Schedule Btuh Btuh Plug load W/ft2 W 8to6 0.70 0 1.00 101 3 0 344 0 #/ft2 # 0.000 0.00 1.00 0 0 0 0 0 #/ft2 # 0.000 0.00 1.00 0 0 0 0 0 #/ft2 # 0.000 0.00 1.00 0 0 0 0 0 #/ft2 # 0.000 0.00 1.00 0 0 0 0 0 #/W # 0.000 0.00 1.00 0 0 0 0 0 MOTORS Power (hp) Load Total Sensible Schedule #/ft2 # factor Btuh 0.00 0.0 1.00 0 0 0 0.00 0.0 1.00 0 0 0 0.00 0.0 1.00 0 0 0 5. INFILTRATION Sens Latent 0 CfM x db Temp Diff 15.0 x 1.10 0 x Moist. Diff 61.5 x 0.69 0 6. SUBTOTAL COOLING LOAD FOR SPA' CE 2289 960 7. SUPPLY DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 8. COOLING FAN SIZING Sum of Duct Gain (7), Li ie (6 & Drawthru Fan 2331 (L 8 Se s ) (Xfer x Supply TD ) = Gfm Est Cooling cfm 2331) 1.10 x 20.0 ) = 106 Actual Cooling Fan > = 117 9. VENTILATION 19 CfM x db Temp Diff 15.0 x 1.10 317 x Moist. Diff 61.5 x 0.69 816 10. RETURN AIR LOAD FROM LIGHT ING AND ROOF Lights Total power ( W 0 1181 RA Roof Load from Line 3 0 RA Ceiling Load Credit from Line 3 0 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQ MENT (Btah) 2648 960 vvriqhtSC)oft Right -Suite Commercial 5.8.13 SG50847 2006-M-27 18:24:0.' 3rojectl.rsc Page SPACEIHEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (inside DB - Outsi - e D13) 70 - 42) 28 Mult 1.0 14. TRANSMISSION LOSSES Type Expos GrArea NetAre Uval HTD Loss ROOF 1 144 1 0.050 28.0 202 15. INFILTRATION Loss 9 cfm x dbTempDiff 28.0 x 1.10 284 16. 1 SUBTOTAL HEATING LOAD FOR SPA�E 485 17. SUPPLY DUCT BEAT LOSS I Loss factor 0.00 x Line 16 Loss 0 18. VENTILATION 19 cfm x db Ternp Diff 28.0 x 1.10 591 19. HUMIDIFICATION Inside RH desired 400 (Max = 32.0 for I pane #of Glazing panes .0 (Max = 52.0 for 2 pane 28 cfm x 3.20 9f 1 00cfm/d 0.9 gpd 344 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x Lit le 16 Loss 0 21. TOTAL HEATING LOAD ON EQUPM�NT (Btuh) 1420 vvrightSC3ft Right -Suite Commercial 5.8.1 RSC50847 2006-Jul-27 18:24:03 Projectl.rsc I Page 3 Right-Sui Commercial Load Calculation ACCM Job: JUL 17, 2006 E JOHN FOSTI R For: HANGARS WW IV & V FT. PIERCE, Fl- Zone: ACCM LWH: 6.0 x 7.0 x 12.8 1. DESIGN CONDITIONS - COOLING Jul 1500 Dry Bib RH Moisture Range Wet Bib Outdoor Conditions 90 59 15 78 Indoor Conditions 75 50 63 TOD Correction 0 Difference 15 61.5 Mult 1.0 2. GLAZING SOLAR HEAT GAIN Lat 27.45 ON Const Wt M Type Orien Area Tilt hdF IntShd Scmult SC Sens/A Sens n/a 0 n/a 0 0 0.00 0.00 0.0 0 3. TRANSMISSION GAINS I Type Orien GrArea NtArea Uval Grp CLTD Shad Cir Sens ROOF 1 - 42 4 0.050 RC-1 79.5 D 167 4. INTERNAL HEAT GAIN PEOPLE Activity Schedule ftl/prsn Restroorn 150 8to6 0 LIGHTS Type Schedule W/ft2 Fluorescent 1.00 8to6 Fluorescent 0.00 Fluorescent 0.00 Fluorescent 0.00 Total # people 0 0 0 0 Total w w 0 42 0 0 0 0 0 0 Sens Latent Sensible Latent Btuh/prsn Btuh/prsn 150 50 42 0 0 0 Factor Space BtuhNV fract 4.10 1.0 172 4.10 1.0 0 4.10 1.0 0 4.10 1.0 0 14 0 vvrightS(:3ft Right -Suite Commercial 5.8.1 RSC50847 2006-Jul-27 18:24:03 Pmjectl.rsc Page 1 PLUG LOADS / APPLIANCES Application Schedule 0 W/ft2 W 8to6 0.00 0 #/ft2 4 0.000 0.00 #/ft2 4 0.000 0.00 #/ft2 h 0.000 0.00 #/ft2 h 0.000 0.00 #/ft2 h 0.000 0.00 MOTORS D-r thm! Usage Total Sensible Latent Btuh Btuh 1.00 0 0 0 0 0 1.00 0 0 0 0 0 1.00 0 0 0 0 0 1.00 0 0 0 0 0 1.00 0 0 0 0 0 1.00 0 0 0 0 0 1 nnri Tntnl Sensible Schedule #/fl:2 factor Btuh 0.00 0.0 1.00 0 0 0 0.00 0.0 1.00 0 0 0 0.00 0.0 1.00 0 0 0 5. INFILTRATION Sens Latent 0 Cfrn x db Temp Diff 15.0 x 1.10 0 x Moist. Diff 61.5 x 0.69 0 6. SUBTOTAL COOLING LOAD FOR S4CE 381 609 7. SUPPLY DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 8. COOLING FAN SIZING Sum of Duct Gain (7) L ne (6 & Drawthru Fan 388 (1-8se S ) (Xfer x Supply TD ) = cfm Est Cooling cfm 388) (1-10 x 20.0 ) = 18 Actual Cooling Fan > = 20 9. VENTILATION 14 cfm x db Temp Diff 15.0 x 1.10 231 x Moist. Diff 61.5 x 0.69 595 10. RETURN AIR LOAD FROM LIGHTI G AND ROOF Lights Total power (W) 0 172 RA Roof Load from Line 3 0 RA Ceiling Load Credit from Line 3 0 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQU PMENT (Btuh) 619 609 wrpghtSC)ft Right-Sufte Commercial 5.8.1 RSC50847 2006-Jul-2718:24:0: 3rojectl.rsc Page SP, 13. HEATING DESIGN TEMPERATURE Heating TD = (inside DB - C 14. TRANSMISSION LOSSES Type Expos GrArea Nei ROOF 1 42 15. INFILTRATION 3 cfm x dbTempDiff 16. SUBTOTAL HEATING LOAD FOR SPA 17. SUPPLY DUCT BEAT LOSS Loss factor 0.00 x Lir 18. VENTILATION 14 cfm x db Temp Diff 19. HUMIDIFICATION Inside RH desired 4( # of Glazing panes 17 cfm x 3.20 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x L0 21. TOTAL HEATING LOAD ON EQUPM TING LOAD CALCULATION DB) 70 - 42) 28 [ Mult 1.0 Uval 0.050 28.0 x 1.10 16 Loss 28.0 x 1.10 HTD 28.0 0 (Max = 32.0 for 1 pane 0 (Max = 52.0 for 2 pane I 00cfm/d 0.5 gpd 16 Loss r (Btuh) Loss 59 Loss 83 142 0 431 202 I If 774 ,wrightS(:3ft Right -Suite Commercial 5.8. 3RSC50847 2006-Jul-27 18:24:03 Projectl.rsc I Page 3 A&Q-1 Right -Suit Commercial Load Calculation ACCW JOHN FOST R Job: JUL 17, 2006 For: HANGARS WW IV & V FT. PIERCE, FL --Zone: __ACCW LWH: 6.0 x 8.0 x 12.8 1. DESIGN CONDITIONS - COOLING Outdoor Conditions Indoor Conditions TOD Correction Difference 2. GLAZING SOLAR BEAT GAIN Type Orien Area Tilt n/a 0 n/a 0 0 Jul 1500 ) Dry Bib RH Moisture Range Wet Bib 90 59 15 78 75 50 63 0 15 61.5 MUlt 1-0 Lat 27.45 'N Const Wt M 3hdF IntShd Scmult SC Sens/A Sens 0.00 0.00 0.0 0 3. TRANSMISSION GAINS Type Orien GrArea NtAre Uval Grp CLTD Shad Cir Sens ROOF 1 - 48 4 0.050 RC-1 79.5 D 191 4. INTERNAL HEAT GAIN PEOPLE Activity Schedule ft2/prsn Restroorn 50 8to6 0 LIGHTS Type Schedule W/ft2 Fluorescent 1.00 8to6 Fluorescent 0.00 Fluorescent 0.00 Fluorescent 0.00 Sens Latent 1 Total Sensible Latent # people Btuh/prsn Btuh/prsn 0 1 150 50 144 48 0 0 0 0 0 0 Total Factor Space W W Btuh/W fract 0 48 4.10 1.0 197 0 0 4.10 1.0 0 0 0 4.10 1.0 0 0 0 4.10 1.0 0 'w"riohtS(:>ft Right-SulteCommerclal&8 3 RSC50847 2006-Jul-27 18:24:03 ProjectUsc Page I PLUG LOADS / APPLIANCES Application Usage Total Sensible Latent Schedule Btuh Btuh 0 W/ft2 W 8to6 0.00 0 1.00 0 0 0 0 0 #/ft2 # 0.000 0.00 1.00 0 0 0 0 0 #/ft2 # 0.000 0.00 1.00 0 0 0 0 0 #/ft2 # 0.000 0.00 1.00 0 0 0 0 0 ft2 I 0.000 0.00 1.00 0 0 0 0 0 #9//f-t,2 0.000 0.0 1 1.00 0 0 0 0 0 MOTORS Power (hp) Load Total Sensible Schedule #/ft2 factor Btuh 0.00 0.0 0 1.00 0 0 0 0.00 u.0 1 v 1.00 0 0 0 0.00 0.0 1.00 0 0 0 5. INFILTRATION Sens Latent 0 cfm x db Temp Diff 15.0 x I 1.10 0 x Moist. Diff 61.5 x 0.69 0 6. SUBTOTAL COOLING LOAD FOR SP�CE 532 2087 7. SUPPLY DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 S. COOLING FAN SIZING Sum of Duct Gain (7), ine (6 & Drawthru Fan 541 (L 8 S ns ) (Xfer x Supply TD ) = cfm Est Cooling cfm 541) 1.10 x 20.0 ) = 25 Actual Cooling Fan > = 27 9. VENTILATION 48 cfm x db Temp Diff 15.0 x 1.10 791 x Moist. Diff 61.5 x 0.69 2039 10. 1 RETURN AIR LOAD FROM LIGHTING AND ROOF Lights Total power (W) 0 197 RA Roof Load from Line 3 0 RA Ceiling Load Credit from Line 3 0 11. RETURN DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 12. TOTAL COOLING LOADS ON EQ MENT (Btuh) 1333 2087 %FVrjqhtS(:)oft Right -Suite Commercial 5.8. 3 RSC50847 2006-Jul-27 18:24:03 Project'l.rsc Page 2 SPACEIHEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE Heating TD = (Inside D13 - Outsi e DB) 70 - 42) 28 Mult 1.0 14. TRANSMISSION LOSSES Type Expos GrArea NetAr 9 a Uval HTD Loss ROOF 1 48 48 0.050 28.0 67 15. INFILTRATION Loss 3 cfm x db Terrip Diff 28.0 x 1.10 95 16. SUBTOTAL HEATING LOAD FOR SPAFE 162 17. SUPPLY DUCT BEAT LOSS Loss factor 0.00 x Li�e 16 Loss 0 18. VENTILATION 48 cfm x db Ternp Diffl 28.0 x 1.10 1477 19. HUMIDIFICATION I Inside RH desired 40.0 (Max = 32.0 for 1 pane # of Glazing panes 6.0 (Max = 52.0 for 2 pane 51 cfm x 3.20 �/l 00cfm/d 1.6 gpd 618 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x L ne 16 Loss 0 21. TOTAL HEATING LOAD ON EQUP�ENT (Btub) 2257 VVrjghtSC3ft Right-Sutte Commercial 5.03 RSC50847 2006-Jul-27 18:24:03 Projectl.rsc -I Page 3 AftiL� Right -Suite Commercial Load Calculation OPEN JOHN FOST R Job: JUL 17, 2006 For: HANGARS WW IV & V FT. PIERCE, FL Zone: OPEN LWH: 642.0 x 1 1.0 x 12.8 1. DESIGN CONDITIONS - COOLING Outdoor Conditions Indoor Conditions TOD Correction Jul 1500 ) Dry Bib RH Moisture Range Wet Bib 90 59 15 78 75 50 63 0 Difference 15 61.5 [I MUlt 1-0 2. GLAZING SOLAR HEAT GAIN Lat 27.45 *N Const Wt M ) Type Orien Area Tilt ShdF IntShd SCMult SC Sens/A Sens 012 GLAZ 1 E 24 90 --- N 1.00 0.27 16.4 VIP 3. TRANSMISSION GAINS Type Orien GrArea NtAre Uval Grp CLTD Shad Clr Sens GLAZ 1 E 24 24 0.500 14.5 N - 174 WALL 1 N 384 3i 4 0.065 E 16.5 N D 412 WALL 1 E 166 1 118 0.065 E 36.5 N D 281 DOOR 1 e 24 �4 1.100 14.5 383 FLOR 1 - 43 3 0.810 0.0 0 ROOF 1 - 642 612 0.050 RC-11 79.5 D 2552 4. INTERNAL HEAT GAIN PEOPLE Activity Schedule ftl/prsn Office 150 8to6 0 Sens Latent Total Sensible Latent # people Btuh/prsn Btuh/prsn 0 4 200 150 856 642 0 0 0 0 0 0 rightSC:)ft Right-SufteCommerclal&8 3RSC50847 2006-Jul-27 18:24:03 ProjectIne Page I LIGHTS Type Total Factor Space Schedule W/ft2 W W Btuh/W fract Fluorescent 2.00 0 0 1284 4.10 1.0 5264 8to6 Fluorescent 0.00 0 0 4.10 1.0 0 Fluorescent 0.00 0 0 4.10 1.0 0 Fluorescent 0.00 0 0 4.10 1.0 0 PLUG LOADS / APPLIANCES Application Usage Total Sensible Latent Schedule Btuh Btuh Plug load W/ft2 8to6 0.70 1.00 449 3 0 1533 1 1.00 0 0 0 0 #/ft2 0.000 0.0 1.00 0 0 0 0 #/ft2 0.000 0.00 1.00 0 0 0 0 #/ft2 # 0.000 0.00 1.00 0 0 0 0 #/W P 0.000 0.0 1.00 0 0 0 0 MOTORS Power (hp) Load Total Sensible Schedule #ff factor Btuh 0.00 0.0 0 1.00 0 0 0 0.00 0.0 0 1.00 0 0 0 0.00 0.0 ro 1.00 0 0 0 0 0 0 0 0 0 5. INFILTRATION Sens Latent 10 cfm x dbTempDiff 15.0 x 1.10 165 x Moist. Diff 61.5 x 0.69 425 6. SUBTOTAL COOLING LOAD FOR S ACE 12013 4703 7. SUPPLY DUCT HEAT GAIN Gain factor 0.00 x Line 6 Sensible Gain 0 8. COOLING FAN SIZING Sum of Duct Gain (7), ine (6 & Drawthru Fan 12235 (L 8 S ns ) (Xfer x Supply TD ) = cfm Est Cooling cfm 12235) 1.10 x 20.0 ) = 557 Actual Cooling Fan > = 615 9. VENTILATION 86 cfm db Temp Diff 15.0 x 1.10 1411 Moist. Diff 61.5 x 0.69 3636 10. RETURN AIR LOAD FROM LIGHTING AND ROOF Lights Total power (W) 0 5264 RA Roof Load from Line 3 0 RA Ceiling Load Credit 1 from Line 3 0 'WnightSC)ft Right -Suite commercial 5.8. 3RSC50847 2006-Jul-27 18:24:03 Projectl.rsc Page 2 11. RETURN DUCT HEAT GAIN Gain factor 0.00 Line 6 Sensible Gain 0 (Btuh) 13646 4703 SPA4 HEATING LOAD CALCULATION 13. HEATING DESIGN TEMPERATURE I Heating TD = (inside D13 - Outside DB) 14. TRANSMISSION LOSSES Type Expos GrArea NetAr a Uval GLAZ 1 E 24 "24 0.500 WALL 1 N 384 84 0.065 WALL 1 E 166 18 0.065 DOOR 1 e 24 24 1.100 FLOR 1 43 43 0.810 ROOF 1 642 642 0.050 70 - 42) 28 Mult 1.0 HTD Loss 28.0 336 28.0 699 28.0 215 28.0 739 28.0 975 28.0 899 15. INFILTRATION Loss 61 cfm x db Ternp Di 28.0 x 1.10 1880 16. 1 SUBTOTAL HEATING LOAD FOR SP�CE 5743 17. SUPPLY DUCT HEAT LOSS L Loss factor 0.00 X ne 16 Loss 0 18. VENTILATION 86 cfm x db Temp Di 28.0 x 1.10 2634 19. HUMIDIFICATION Inside RH desired 40 * 0 (Max = 32.0 for 1 pane # of Glazing panes 2.0 (Max = 52.0 for 2 pane 147 cfm x 3.20 g/1 00cfm/d 4.7 gpd 1775 20. RETURN DUCT HEAT LOSS Loss factor 0.00 x ine 16 Loss 0 21. TOTAL HEATING LOAD ON EQUP ENT (Btuh) 10152 ,W"rightS(:),ft Right-S.ite Commercial 5.813 RSG50847 2006-Jul-27 18:24:03 Projectl.rsc Page 3 ANIL] Right-S AM JOHNFO For: HANGARS WW IV & V FT. PIERCE, FL Htg CIg Outside db (OF) 42 90 Outside RH (%) - 59 Outside wb (OF) - 78 Daily range (OF) - 15 Moisture diff. (gr/lb) - 61 Heating Equipment Make Model Type Efficiency / HSPF Heating Input Heating Output Humidifier Leaving Air Temp Actual Heating Fan 1 Commercial Short Form )00 MBtuh 0.0 MBtuh 0.0 gpd 0.0 OF 0 cfm Equipment LPcation System Typ� Fan Motor Heat Type F . an & Motor Combined Efficiency Static Press ��re Across Fan Job: JUL 17, 2006 Htg Cig Inside db (OF) 70 75 Inside RH N - 50 I nside wb (OF) - 63 Design TD (OF) 28 15 Cooling Equipment Make TRANE Model 2TTR3060A Type STRAIGHT COOL COP/EER/SEER 13.0 Sensible Cooling 41500 MBtuh Latent Cooling 16500 MBtuh Total Cooling 58000 MBtuh Leaving Air Temp 55.0 OF Actual Cooling Fan 1800 cfm Ahl VAV DRAWTHRU 10.0 % 0.1 in H20 NAME Area Heat ft2 1. Loss Sensible Gain Latent Gain Htg cfm Cig cfm Time SHOP 810 10465 15153 5907 0 679 Jul 1500 OFFICE 3 180 2659 4120 1199 0 188 Jul 1500 OFFICE 1 144 2166 3365 960 0 154 Jul 1500 OFFICE 2 144 1420 2648 960 0 117 Jul 1500 ACCM 42 774 619 609 0 20 Jul 1500 ACCW 48 2257 1333 2087 0 27 Jul 1500 OPEN 1 6421 1 10152 1 13646 1 4703 1 01 615 ' Jul 1500 Ahl 1 20101 1 29894 1 40885 1 16424 1 01 18001 Jul 1500 �'Z Right -Su AM JOHN FOS' For: HANGARS WW IV & V FT. PIERCE, FL 1. DESIGN CONDITIONS Inside: 75 OF RH: 50 % 2. SOLAR RADIATION T11 3. TRANSMISSION GAINS Walls: Glass: Doors: Partitions: Floors: Roofs/Ceilings: Return Air Ceiling: 4. INTERNAL HEAT GAI Occupants: Lights: Motors: Appliances: 5. INFILTRATION: 6. SUBTOTAL: Space c 7. SUPPLY DUCT 8. SUBTOTAL: Bldg Actual cfm: 9. VENTILATION: 10. RETURN AIR LOAD: 11. RETURN DUCT 12. TOTAL LOADS ON E 13. DESIGN CON�rrl( Inside: 70 OF 14. TRANSMISSION Ll Walls: Glass: Doors: Partitions: Floors: Roofs/Ceilings: Return Air Roof: 15. INFILTRATION: 16. SUBTOTAL: Buil 17. SUPPLY DUCT: 18. VENTILATION: 19. HUMIDIFICATIOli 20. RETURN DUCT 21. TOTAL HEATING Commercial Load Summary Job: JUL 17,2006 at Jul 1500 Peak load at Jul 1500 lutside: 90 OF TD: 15 OF 61.5 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent GLASS 917 Sensible 11929 2724 - 406 810 0 0 7990 0 Sensible Latent 21784 1982 2746 1982 - - 14452 - 0 4586 0 - - Outside air cfm: 30 495 1274 ad 35125 3256 0 imp's and supply duct 35774 1800 at Supply TD: 20 - I - Make-up air cfm: 310 5110 13168 Lighting & roof (net) 0 0 JTPMENT 40885 16424 S Mult: 1.0 Outside: 42 OF TD: 28 OF 3SES 10738 2697 - 784 1564 0 2880 2814 0 Outside air cfm: 137 4210 ng components 14948 0 Make-up air cfrn: 310 9539 5406 0 DAD ON EQUIPMENT 29894 VVrjghtSC3ft Right-SuiteCommercial 8. 13 RSC50847 2006-Jul-27 18:23:41 Projeattirsc Page I Right Ahl JOHN I For: HANGARS WW IV & V FT. PIERCE, FL Htg CIg Outside db (OF) 42 90 Outside RH (%) - 59 Outside wb (OF) - 78 Daily range (OF) - 15 Moisture diff. (gr1lb) - 61 Heating Equipment Make Model Type Efficiency / HSPF Heating Input Heating Output Humidifier Leaving Air Temp Actual Heating Fan System T� Fan Motor Fan & Mot Static PreE Commercial Short Form 100.0 !4000 MBtuh 0.0 MBtuh 0.0 gpd 70.0 OF 0 cfm Location )e leat Type ir Combined Efficiency wre Across Fan Job: JUL 17,2006 Htg Cig Inside db (OF) 70 75 Inside RH N - 50 Inside wb (OF) - 63 Design TD (OF) 28 15 Cooling Equipment Make TRANE Model 2TTR3060A Type STRAIGHT COOL COP/EER/SEER 13.0 Sensible Cooling 41500 MBtuh Latent Cooling 16500 MBtuh Total Cooling 58000 MBtuh Leaving Air Temp 55.0 OF Actual Cooling Fan 1800 cfm Ahl VAV DRAWTHRU 10.0 % 0.1 in H20 NAME Area fF Heat Loss Sensible Gain Latent Gain Htg cfm CIg cfm Time SHOP 81 10465 15153 5907 0 679 Jul 1500 OFFICE 3 18- 2659 4120 1199 0 188 Jul 1500 OFFICE 1 1 2166 3365 960 0 154 Jul 1500 OFFICE 2 1 1420 2648 960 0 117 Jul 1500 ACCM 2 774 619 609 0 20 Jul 1500 ACCW 8 2257 1333 2087 0 27 Jul 1500 OPEN 112 1 10152 13646 1 4703 1 01 615 Jul 1500 Ahl 1 2010 29894 1 40885 1 16424 1 01 18001 Jul 1500 1 Right-Suil AM JOHN FOST For: HANGARS WW IV & V FT. PIERCE, FL F16 -n-6-. 1. DESIGN CONDITIONS Inside: 75 OF RH: 50 % 2. SOLAR RADIATIONA H 3. TRANSMISSION GAINS Walls: Glass: Doors: Partitions: Floors: Roofs/Ceilings: Return Air Ceiling: 4. INTERNAL HEAT GAI Occupants: Lights: Motors: Appliances: 5. INFILTRATION: 6. SUBTOTAL: Space I 7. SUPPLY DUCT 8. SUBTOTAL: Bldg cc Actual cfm: 9. VENTILATION: 1 10. RETURN AIR LOAD: 11. RETURN DUCT 12. TOTAL LOADS ON E -1 13. DESIGN CONDITIC Inside: 70 OF 14. TRANSMISSION L( Walls: Glass: Doors: Partitions: Floors: Roofs/Ceilings: Return Air Roof: 15. INFILTRATION: 16. SUBTOTAL: Builc 17. SUPPLY DUCT: 18. VENTILATION: 19. HUMIDIFICATION 20. RETURN DUCT 21. TOTAL HEATING I Commercial Load Summary Job: JUL 173 2006 at Jul 1500 Peak load at Jul 1500 tside: 90 OF TD: 15 OF lbisture: 61.5 gr/lb Mult: 1.0 Ins.wb 63 OF Sensible Latent UGH GLASS 917 Sensible 11929 2724 - 406 810 0 0 7990 0 Sensible Latent 21784 1982 2746 1982 - - 14452 - 0 4586 0 - - Outside air cfm: 30 495 1274 ad 35125 3256 0 imp's and supply duct 35774 1800 at Supply TD: 20 - - Make-up air cfm: 310 5110 13168 Lighting & roof (net) 0 - 0 JTPMENT 40885 16424 Outside: _14_ffAT_1i&0jK6 Mult: 1.0 42 OF TD: 28 OF 10738 2697 784 1564 0 2880 2814 0 Outside air cfm: 137 components Make-up air cfm: 310 ON EQUIPMENT 4210 14948 0 9539 5406 0 29894 %"rvghtSC)ft Right-SuiteCommerdlal& 13RSCS0847 2006-Jul-27 18:23:15 Projecti.irsc I. Page 1