Loading...
HomeMy WebLinkAboutRESPONSE TO PLAN EXAMINERJ; , John M. Foste -Architect 11205 Ridge Aven e Ft. Pierce, Florida 344982 (772) 370-9464 Fax (77 878-7359 Florida Registration # 8 5 11 march 9, 2007 Mr. Carl Peterso, I , Plans Examiner St. Lucie County Code Compliance Division 1 2500 Virginia Ave ue Ft. Pierce, FL 3498 MEMO Response 0 Plans Examiner Comments 2/05/07 Permit .701-00218 - 3180 Airmen's Drive , information on Cover Sheet revised to show use as NFPA . Hangar. 2. Please see Product Review Affidavit included on the bottom right-hand I comer of Cover Sheet Note that all data and certification statement shown on this form are include, . 3. Per FBC 412.2.6 " i craft hangars shall be provided with fire suppression as required in NFPA 409 " Review of NFPA 409 for Group III aircraft hangars does not indicate require ents for fire suppression system as is required for Group 2 1 or Group II aircraft hangars. X 4. See revised Sheet -, 3 and P-1 for emergency.eyewash & shower. 5. see revised She t P-1 showing top feed water heater, not requiring vacuum breaker. 6. Please see Sheet P- which shows a separate shut-off valve for each hose bibb. 7. Note that FD-1 has "deep seal" trap and flows through cast iron pipe to an ator before joining to the sanitary service outfall. underground oil sep 8. Not used by reviewer. 9a. Please see revised Sheet E-2 showing disconnect at A/C condenser. 9b. Please see revised Sheet E-1 for additional exit sign in hall. 9c. Please see revised, heet E-2 for additional GFCI outlet near A/C condenser. 9d. Note that the 277 v If you have any ques numbers listed above. Sincerely C John M. FosS&+, note has been removed Fixture type "A" - regarding this information, please call me at the e FILE C"Ol'OPY