Loading...
HomeMy WebLinkAboutENERGY EFFICIENCY CODE. FORM R405-2017 o-. RESIDENTIAL ENERGY CONSE VATION CODE DOCUMENT,Ai' N�Ga Florida Department of qusiness and Professional Regulation Simulated Perfonman a Alternative (Performance) Method Applications for compliance with the 2017 i residential Simulated Performance Method ❑ This checklist ❑ A Form R405 report that documents R405.3 of the Florida Energy Code. indicating home address, a -ratio and areas and types of components, whe orientation, name and version of the completing the compliance report (or be used for field verification (usually, ❑ Energy Performance Level (EPL) ❑ HVAC system suing and selection ❑ Mandatory Requirements (five pages) Required prior to CO for the Air Barrier and Insulation one page) a Building Code, Energy Conservation via the include: et the Proposed Design complies with Section is form shall include a summary page e pass or fail status along with summary or the home was simulated as a worst -case mpliance software tool, name of individual page) and an input summary checklist that can rr pages/may be greater). Card (one page) on ACCA Manual S or per exceptions provided in Section R403.7 Method: Component Criteria checklist (Table R402.4.1.1 - ❑ A completed Envelope Leakage Test Report (usually one page) ❑ If Form R405 duct leakage type it Form R405 Duct Leakage Test Re 8/13/2018.224:48 PM EnergyGauge® USA 6.0.02 (F es anything other than "default leakage" then a completed (usually one page) { 1) - FlaRes2017 FBC 6th Edition (2017) CompliaYA"Cop Pagel - of 1 2017 EPL DISPLAY CARD ENERGY P ESTIMATED EN The lower the Energy LEVEL (EPL) DISPLAY CARD PERFORMANCE INDEX* = 97 Index, the more efficient the home. 1. New home or, addition 1_ New (From Plans) 12. Ducts, location & insulation level a) Supply ducts R 6.0 2. Single-family or multiple -family 2. in le -family b) Return ducts R 6.0 c) AHU location 2nd Floor 3. No. of units (if multiple -family) 3. 1 4. Number of bedrooms 4. 2 13. Cooling system: Capacity 58.5 a) Split system SEER 16.0 5. is this a worst case? (yes/no) 5. No b) Single package SEER c) Ground/water source SEER/COP 6. Conditioned floor area (sq. ft.) 6. 2479 d) Room unit/PTAC EER 11.0 e) Other 7. Windows, type and area a) U-factor.(weighted average) 7a. 0.575 b) Solar Heat Gain Coefficient (SHGC) 7b. 0.300 14. Heating system: Capacity 58.0 c) Area 7c. 1 395.8 a) Split system heat pump HSPF 9.0 b) Single package heat pump HSPF 8. Skylights c) Electric resistance COP a) U-factor.(weighted average) 8a.T NA d) Gas furnace, natural gas AFUE b) Solar Heat Gain Coefficient (SHGC) 8b. I NA e) Gas furnace, LPG AFUE f) Other 5.80 9. Floor type, insulation level: a) Slab -on -grade (R-value) 9a. 0.0 b) Wood, raised (R-value) 9b. 1 15. Water heating system c) Concrete, raised (R-value) 9c. a) Electric resistance EF 0.95 b) Gas fired, natural gas EF 10. Wall type and insulation: c) Gas fired, LPG EF A. Exterior. d) Solar system with tank EF 1. Wood frame (Insulation R-value) 10Ai. e) Dedicated heat pump with tank EF 2. Masonry (Insulation R-value) 10 4.1 0 Heat recovery unit HeatRec% B. Adjacent: g) Other 1. Wood frame (Insulation R value) 101. 2. Masonry (Insulation R-value) 1062. 16. HVAC credits claimed (Performance Method) 11. Ceiling type and insulation level a) Ceiling fans Yes a) Under attic 11 30.0 b) Cross ventilation No b) Single assembly 11�. c) Whole house fan No c) Knee wallstskylight walls 11 C. d) Multizone cooling credit d) Radiant barrier installed 11 No e) Multizone heating Credit f) Programmable thermostat Yes *Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. I certify that this home has complied with the Flod a Building Code, Energy Conservation, through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL display card will be completed based on installed 7 de compliant features. Builder Signature: Date: Address of New Home: 581 Beach Avenue City/FL Zip: Port St. Lucie, FL 34952 8/13/2018 2:25:28 PM EnergyGauge® USA 3.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Flja[rt o Yge 1 of 1 FORM R405-2017 FLORIDA ENERGY EFFICIEI Florida Department of Business and CODE FOR BUILDING CONSTRUCTION ;sional Regulation - Residential Performance Method Project Name: Yancy Residence EG Builder Name: Street: 581 Beach Avenue Permit Office: City, State, Zip: Port St Lucie, FL , 34952 Permit Number Owner. Yancy Residence Jurisdiction: St Lucie County Design Location: FL, ST LUCIE CO INTL County: St Lucie (Florida Climate Zone 2 ) I) 1. New construction or existing New (From Plan 9. Wag Types (2426.0 sgfL) Insulation Area 2. Single family or multiple family Single-family a. Concrete Block - Int Insul, Exterior R=4.1 2262.00 ftz b. Interior Frame - Wood, Interior R=11.0 164.00 ftz 3. Number of units, if multiple family 1 c- N/A R= ftz 4. Number of Bedrooms 2 d. N/A R= ftz 10. Ceiling Types (2479.0 sgft) Insulation Area 5. Is this a worst case? No a. Under Attic (Vented) R=30.0 2479.00 IF 6. Conditioned floor area above grade (tiz) 2479 b. WA R= fI Conditioned floor area below grade (ftz) 0 c. N/A R= ft2 11. Ducts R ftz 7. Windows(395.8 sgfL) Description Area a. Sup: Attic,.Ret: Attic, AH: 2nd Floor 6 739 a. U-Factor: Dbl, U=0.45 235.33 SHGC: SHGC=0.30 b. U-Factor. Dbl, U=0.76 120.94 12. Cooling systems kBtu/hr Efficiency SHGC: SHGC=0.30 a. Central Unit 46.5 SEER:16.00 b.'PTAC and Room Unit 12.0 EER:11.00 c. U-Factor. Dbl, U=0.75 39.54 SHGC: SHGC--0.30 13. Heating systems kBtu/hr Efficiency d. U-Factor. N/A a. Electric. Heat Pump 46.5 HSPF:9.00 SHGC: I b. PTHP 11.5 COP:5.80 Area Weighted Average Overhang Depth: 3.639 . Area Weighted Average SHGC: 0.300 14. Hot water systems a. Electric Cap: 40 gallons 8. Floor Types (2479.0 sgft.) Insulation Area EF: 0.950 a. Slab -On -Grade Edge Insulation Rro.O 2479.00 if b. Conservation features b. N/A R= None c. N/A R= z 15. Credits CF, Pstat Total Propos Modified Loads: 74.35 Glass/Floor Area: 0.160 PASS Total , aseline Loads: 76.26 I hereby certify that the plans and specifications covered by Review of the plans and 'CBE STgT O �0�, this calculation are in ce Florida Energy specifications covered by this= Code. calculation indicates compliance��.�� °, with the Florida Energy Code. t~ �n,1r,=. '�%. f" ° 0 ' ;. • _ , PREPARED BY: DATE: Before construction is completed tR. this building will be inspected for 0 compliance with Section 553.908 * a I hereby certify that this building, as designed, is in compliance Florida Statutes. cf . COD with the Florida Energy Co yt►�i'� OWNER/AG BUILDING OFFICIAL: DATE: 7.� DATE: - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with 11403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402A.1.2). - Compliance with a proposed duct leakage On requires a Duct Leakage Test Report confirming duct leakage to outdoors, tested in accordance with ANSURESNETACC 380, is not greater than 0.030 On for whole house. 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2010 Compliant Software Page 1 of 6 F-e- Copy FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT PROJECT Tille: Yancy Residence EG BedrooIrrs: 2 Address Type: Street Address Building Type: User Conditioned Area: 2479 Lot # Owner Name: Yancy Residence Total Stories: 1 BlocIdSubdivision: # of Units: 1 Worst 6ase: No PlatBook: Builder Name: Rotate ngle: 270 Street 581 Beach Avenue Permit Office: CrossVentilation: No County: St. Lucie Jurisdiction: St Lucie County Whole I iouse Fan: No City, State, Zip: Port St. Lucie. Family Type: Single-family FL, 34952 New/Existing: New (From Plans) Comment: CLIMATE Design Temp Int Design Temp Heating Design Daily Temp Design Location TMY Site 97.5 % 2.5 % Winter Summer Degree Days Moisture Range FL, ST LUCIE CO INTL FL VERO_BEACH MUNI 39 90 70- 75 299 58 Medium BLOCKS Number Name Area Volu e 1 AHU1 2 AHU2 1852 627 148II16 5016 Number Name Area 1 2nd Floor 130 2 RR KITCHEN 162 3 OFFICE 78 4 ENTRY 117 5 CMD 23 6 M BATH 93 7 M BED 243 8 DINING 206 9 FR KITCHEN 141 10 BED 2 192 11 BATH 2 59 12 M WIC 92 13 LIVING 316 14 COND GARAGE 627 y # Floor Type Space 1 Slab -On -Grade Edge Insulatio 2nd Floor 2 Slab -On -Grade Edge Insulatio RR KITCHEN 3Slab-On-Grade Edge Insulatio OFFICE SPACES Volume Kitchen. Occupants Bedro 1040 No 0 1296 Yes 1 624 No 0 936 No 0 184 No 0 744 No 0 1944 No 0 1 1648 No 0 1128 Yes 0 1536 No 0 1 472 No 0 736 No 0 2528 No 2 5016 No 0 FLOORS Perimeter Perimeter.R--Value Area 23 it 130 ft 14.5 ft 162 ft' 11.3 ft 78 f12 oms InfilID Finished Cooled Heated 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes Joist R-Value Tile Wood Carl 1 0 0 1 0 0 1 0 0 8/13/2018 2.25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017), Compliant Software Page 2 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT FLOORS # Floor Type Space rimeter Perimeter R Value Area Joist R-Value Tile Wood Carpet 4 Slab -On -Grade Edge Insulatio ENTRY 15.9 ft 117 f12 — 1 0 0 5 Slab -On -Grade Edge Insulatio CMD 1 ft 23 ft2 _ 1 0 0 6 Slab -On -Grade Edge Insulatio M BATH 16.1 ft 93 ft2 _ 1 0 0 7 Slab -On -Grade Edge Insulatio M BED 25.2ft 243 ft2 _ 1 0 0 8 Slab -On -Grade Edge Insulatio DINING .8ft 206 ft2 — 1 0 0 9 Slab -On -Grade Edge Insulatio FR KITCHEN 1 .5 ft 141 f12 _ 1 0 0 10SIab-On-Grade Edge Insulatio BED 2 3D.5 ft 192 ff? — 1 0 0 11Slab-On-Grade Edge Insulatio BATH 2 1 It 59 ft2 _ 1 0 0 12SIab-On-Grade Edge Insulatio M WIC 1 ft '92 ft2 _ 1 0 0 13SIab-On-Grade Edge Insulatio LIVING ft 316 ft2 — 1 0 0 14SIab-On-GradeEdge Insulatio COND GARAGE 84.7 ft 627 ft2 _ 1 0 0 ROOF Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch # Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg) 1 Hip Composition shingles 2613f12 0 ft2 Light N 0.5 No 0.9 No 0 18.4 ATTIC V # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Full attic Vented 300 2479 ft2 N N CEILING # Ceiling Type Space R Value Ins Type Area Framing Frac Truss Type 1 Under Attic (Vented) 2nd Floor 30 Blown 130 fie 0.11 Wood 2 Under Attic (Vented) RR KITCHEM 30 Blown 162 ft2 0.11 Wood 3 Under Attic (Vented) OFFICE 30 Blown 78 112 0.11 Wood 4 UnderAttic(Vented) ENTRY 30 Blown 117ft2 0.11 Wood 5 Under Attic (Vented) CMD 30 Blown 23 ft2 0.11 Wood 6 Under Attic (Vented) M BATH 30 Blown 93 ft2 0.11 Wood 7 Under Attic (Vented) M BED 30 Blown 243 W 0.11 Wood 8 Under Attic (Vented) DINING 30 Blown 206 ft2 0.11 Wood 9 Under Attic (Vented) FR KrrCHE 4 30 Blown 141 ft2 0.11 Wood 10 Under Attic (Vented) BED 2 30 Blown 192 ft2 0.11 Wood 11 UnderAttic (Vented) BATH 2 30 Blown 59 ft2 0.11 Wood 12 Under Attic (Vented) M WIC 30 Blown 92 ft2 0.11 Wood 13 Under Attic (Vented) LIVING 30 Blown 316 ft2 0.11 Wood 14 Under Attic (Vented) COND GARAGE 30 Blown 627 ft2 0.11 Wood 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) T FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 6 , IN IN IN IN IN IN IN li I� li li li li I� li li li I I I I I I I I I G`iJ �' O N w v+ A W IV Z �! W N i # C C UP m Z cn m cn In Z m Z cn m z I cn II cn II I cn II co * II m II 0 m m m O U1 m z V V V V y V V V V V V y V V V can m m m m o cn m CO m* cyn cn cn m z to m m (n m m z m m m Z o to w z z Z Z 0 0 a i w co 0 cn cm -• C G m 11 7. 7. o, Q. 7. 7. 7. Q. 7. 7. 7. Q. v O• v Q. 7. O. 7. 7. v 01 >= v 1 � 7. o Q. 0 Q. 0 0 7. 0 0 7. 0 0 0 0 0 0 0 0 0 0 0 0 v 0 0 0 0 0 m y y d =j d ^I =j O 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 CD a3 > �' > a > > > > > > > 0 > > > > > > > > >. m. > > > > > r O r Q r O r O r O r O o N N O fD N fD N � fD fa N N N N fD fa W N o � 0 0 C A N C C C y C O N N ET fD lD N fD W N N iD ED ar tD N ar fD TI N -1 T ID N N E'D iD m m m m m o d �+ W m m W 0o W m o0 177 m oo aw m oo ao m w 3 a)@ 3 is 9 m m aw w Z 0 0 0 0 0 0 0 0 fD 0 m o � 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 o i c �' 0 m R. RL RL RL RL RL RL R- RL RL 6P RL 9 9 x RLRL & N a CD Q Eo Q <D N Q fD O. I i 1 1 1 1 i 1 1 i 1 1 1 1 1 1 1 1 1 1 1 1 1 C a O O w O w � > NQ > a o � > > > > > _ � > _ > N > > > � a 06 N CD 0 N N N rn H N N N rn N N N ° z mo m Z v z v cn �o z v z v z v z v r' W my m m m m 0 Z 0 Z O O O v@+ ego�° n y y m m m m D D —0t7 G� O�O z N N N � z O z O m v m v m v m v � -C O n n o 0 p 12 m m m m m o o �f7 m o 0 0 0 0 J Qi 0 %i �i 0 - i - i - — - - i i - i - i J J -► '� J i i i i A � h i A i 1 03i C ci a z O � ca rn 11 o o Cl) V O 0 4 TI O l'A O E.W O G1 O CW O f+1 O G1 = In n 'w Y, A 00 p p � N N w A N 01 N i t„n w w p w 01 OI ,.. N N W O Y, S 0) CO) r m z z z c N .. G > > > w G V O O O O T O w W C w y wwwwwwwwwwwwwwwwwwww�Dwwwww rn iv V W 0 V C71 p = O O O O O O O O O O O O O O O O O O O O O O O O O O � O. M OD A W A i+. N C71 -� O -• w O m OOo co ? O~1 w ? C :1 v V V i4 Eat G W Op 0 C J4 p N v O 'J v C O O O C O V W W O 7 7 O i A 7 7 7 N O. m W W .+ (/) O CD O CDW O O Q y Q. � O O O O O 0 N to N CD y > > > > > > C O O O O O O O O O O O O O O O O O O O O O O O O O O N O 7 47 T1 K co w Co T ~� O O O O O CD O CD O O O O O O O O N O O N O N O CD O O {U a Z Z Z Z Z Z f0 Wcil 7 m 7 m 7 cD 7 cD 7 m 7 m a � r. cin CD o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 o p o 0 0 0 0 0 d b� b� it ct b� it b� bo bo b� in b� 0 0 it 0) m En m m m m 0 En b� � CD 0 _ N 00 N A N A a , w N N N fD fD fD � O 0 O 0 0 0 O 0 0 O 0 O O O 0 O 0 0 0 0 0 0 O 0 0 0 e FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT WINDOWS Orientation shown is the entered orientation => changed to As Built rotated 270 degrees). Wall Overhang # Omt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 7 S=>E 10 TIM Low-E Double Yes 0.75 0.3 Y 4.7 ft2 7ft 7 in 0 ft 0 in None None 8 W=>S 11 TIM Low-E Double Yes 0.75 0.3 Y 9A ft2 4 ft 0 in 0 ft 0 in None None 9 W=>S 11 TIM Low-E Double Yes 0.75 0.3 Y 4.9 ft2 4.ft 0 in 0 ft 0 in None None 10 N=>W 12 TIM Low-E Double Yes 0.45 0.3 Y 47.3 ft' 3 ft 5 in 0 It 0 in None None 11 NW=>SW17 TIM Low-E Double Yes 0.76 0.3 Y 38.0 ft2 1 ft 6 in oft 0 in None None 12 NW=>SW17 TIM Low-E-Double Yes 0.76 0.3 Y 19.5 ft2 1 ft 6 in 0 ft 0 in None None 13 NW=>SW17 TIM Low-E Double Yes 0.45 0.3 Y 72.0 ftZ 3 It 5 in 0 ft 0 in None None 14 NW=>SW18 TIM Low-E Double Yes 0.45 0.3 Y 72.0 ft? 3 ft 5 in 0 ft 0 in None None 15 NE=>NW19 TIM Low-E Double Yes 0.76 0.3 Y 49.3 ft2 1 ft 6 in 0 tt 0 in None None 16 NE=>NW 1 TIM Low-E Double Yes 0.75 0.3 Y 20.6 ft2 3 ft 11 in 0 ft 0 in None None INFILTRATION # Scope Method SLA C�M 50 ELA EgLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000254 1152.7 90.73 170.63 .0881 5 HATING SYSTEM # System Type Subtype Eitidency Capacity Block Ducts 1 Electric Heat Pump/ Split HSPF:9 46.5 kBtu/hr 1 sys#1 2 PTHP/ None COP:5.8 11.5 kBtu/hr 2 Ductless C60LING SYSTEM # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit/ Split SEER:16 46.5 kBtu/hr 1550 cfm 0.,8 1 sys#1 2 PTAC and Room Unit/ Through the Wall Single) SEER: 11 12 kBtu/hr 370 ctrn 0.8 2 Ductless HOT WATER SYSTEM # System Type SubType Location JEF Cap Use SetPnt Conservation 1 Electric None 2nd Floor 0.95 40�gal 60.9 gal 120 deg None SOLAR HOT WATER SYSTEM i FSEC Collector Storage Cert # Company Name m Model # Collector Model # Area Volume FEF None None ft2, 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 6 FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT DUCTS — Supply — — Return — Air CFM 25 CFM25 HVAC # # Location R Value Area Location Area Leakage Type Handler TOT OUT QN' RLF Heat Cool 1 Attic 6 739 IF Attic 739 IF Prop. Leak Free 2nd Floor — cfm 55.6 cfm 0.03 0.50 1 1 �17MPERATURES Programable Thermostat Y Ceil Fans: Coolin an Feb Heat HJan Feb Mar Mar A r r Apr a a Jun Jul Jun Jul AugSe Auge Oct Oct Nov Nov Dec HDec Venting Jan Feb Mar ay Jun Jul Aug Sep Oct Nov Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling (WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating (WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 MASS Mass Type Area Thickness Furniture Fraction Space Default(8 Ibs/sq.fL 0 ftZ Oft 0.3 2nd floor Default(8 Ibs/sgA ft' ft 0.3 RR KITCHEN Default(8 Ibs/sq.fL ft2 ft 0.3 OFFICE Default(8 lbs/sq.ft. ftz ft 0.3 ENTRY Default(8 lbs/sq.fL ftZ ft 0.3 CMD Default(8 ibs/sq.f . ftZ It 0.3 M BATH Default(8 Ibs/sq.fL ftZ ft 0.3 M BED Default(8 Ibs/sq.fL ftZ ft 0.3 DINING DefauH(8 Ibs/sq.ft. ftZ It 0.3 FR KITCHEN Default(8 Ibs/sq.ft. ftZ ft 0.3 BED 2 Default(8 Ibs/sq.ft. ftZ ft 0.3 BATH 2 Default(8 lbs/sq.ft. ftZ ft 0.3 M WIC Default(8 Ibs/sq.ft. ftZ It 0.3 LIVING Defhn1 8 Ibs/s .ft. ftZ It 0.3 COND GARAGE 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) -1 FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 6 of 6 Florida Building Code, atory Reauirements for Re ergy Conservation, 6th Edition (2017) Intial' Performance, Prescriptive and ERI Methods IADDRESS: 5 Port each A a u, 34952 I Permit Number. I .MANDATORY REQUIREMENTS See SECTI code sections for full details. R401 GENERAL R401.3 Energy Performance Level (EPL) display card (MiIndatory)3 he building official shag require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate -and cored before final approval of the building for occupancy. Florida law (Section 553.9085, Florida Statutes) requires the EPL displa� card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contai s information indicating the energy performance level and efficiencies of components installed in a dwelling unit The building official shag verify th t the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compfian for the building. A copy of the EPL display card can be found in Appendix RD. R402.4 Air leakage (Mandatory). The building thermal envelope shag be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancie$ and multiple attached single family dwellings shall be permitted to comply with Section C402.5. R402.4.1 Building thermal enveldjw- building therma envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shag allow for differential expansion and contraction. R402A.1.1 lnstallation.The components of the buildino thermal envelope as listed in Table R402.4.1.1 shall.be installed in accordance with the manufacturer's instructions and the criteria listeo in Table R402A.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. r R402-4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNETACC 380 and reported ai a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i) or an approved third party, A written report of the results oflthe test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, buildings in which the new construction is less than 85 During testing: 1. Exterior windows and doors, fireplace and stove door other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back infiltration control measures. 3. Interior doors, if installed at the time of the test, shall 4. Exterior doors for continuous ventilation systems and 5. Heating and cooling systems, if installed at the time c 6. Supply and return registers, if installed at the time of renovations, or repairs, of the building thermal envelope of existing the building thermal envelope. be dosed, but not sealed, beyond the intended weatherstripping or and flue dampers shall be dosed, but not sealed beyond intended open. at recovery ventilators shag be dosed and sealed. ie test, shall be turned off. test, shall be fully open. R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on.fadory-built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces,lthe doors shall be listed and labeled in accordance with UL 907. 11402:4.3 fenestration air leakagdlYndows, skylights and sliding glass doors shall have amairinfiltration rate of no more than 0.3 ctm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 fin per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101A.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (C R402.4.4 Rooms containing fuel -burning appliances. In C11mate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in,a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall met not less than the basement wall R value requirement The door into the room shall be fully gasketed and any water fines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake anq exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Se on R402.4.2 and Section R1006 of the Florida Building Code, Residential. R402A.5 Recessed lighting. Recessed luminaires installed i� the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed lu maires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the h using and the interior wall or ceiling covering. R403.1 controls. SECT ON R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat op ration when the heat pump compressor can meet the heating load. R403.3.2 Sealing (Mandatory) All duds, air handlers, liter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered duds o plenum chambers, shall be constructed and sealed in accordance with Section C4032.9.2 of the Commercial Provisions of this code and shall be shown to meet dud tightness criteria below. Duct -tightness shall be verified by testing in accordan with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(1), (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. n R403.3.2.1 Sealed air handler. Air handlers shalt' have a manufacturer's designation for an air leakage of no more than 2 percent JJ of the design airflow rate when tested in accordance with ASHRAE 193. ❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1, Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if in talled at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacture air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be wired where the duds and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buil ings complying by Section 405 of this code. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ❑ R403.3.5 Building cavities (Mandatory). Building framing cavr Ies shall not be used as duds or plenums. R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105'F (41 °C) or below 55'F (13°C) shall be insulated to a minimum of R-3. ❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory)Heated water circulation systems shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return ❑ pipe shall be a dedicated return pipe or cold water supply pipe. Gravity and thernosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turd off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat ttrace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in thq occupancy. 8/1312018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heateml not equipped with integral heat traps and having vertical pipe risers shall have ' heat traps installed on both the inlets and outlets. External hat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'h inches (89 mm) n the hot waterdistribution line and cold water line located as close as possible to the storage tank. a R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service wate -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acre;table temperature settings for the intended use. The minimum temperature setting range shall be from 100"F to 140OF (380C 13 600C). ❑ 11403.5.6.1.2Shut-down. A separate switch or early,marked circuit breaker shall be provided to permit the power supplied to electric service systems to be tamed off. A separa a valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned oil R403.5.6.2 Water -heating equipment. Water-hgafing equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building ode, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall i neet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy facto of a -system shall be determined from the Florida Solar Energy Center Directory of. Certified Solar Systems. Solar collectors shi ill be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic of Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a till angle between 1 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The bui ding shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Cc ide, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outc oor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy require ents of Table R403.6.1. Exception: Where whole -house mechanical entilaflon fans are integral to tested and listed HVAC equipment, they shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings desf fined to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums r residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system male -up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or�utdoor spaces adjacent to swimming pools or spas. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceili i �ig shall be insulated to a,minimum of R-19, space permitting, or RA 0 otherwise. R403.7 Heating and cooling equipment (Mandatory). R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with �CCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does no# allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculatiops shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TAB4E R403.6.1 WHOLE-F[OUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) Range hoods Any I 2.8 cfm/wat Any In4ine fan Any 2.8 ckn/wat Any Bathroom, utility room 10 1.4 chn/wat <90 Bathroom, utilityroom 90 2.8 cfin/wat Any For SI: 1 cfm = 28.3 Umin. a. 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. en tested in accordance with HVI Standard 916 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ,❑R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.7, or the closest available size provided by the v rianufacturer's product lines. The corresponding latent capacity of the i equipment shall not -be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rabng-test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling my equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water tern rature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance w� good design practice. R403.7.1.2 Heating equipment capacity. ❑ 11403.7.1.2.1 Heat pumps. Heat pump,sizinj 1 shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacit shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than tha design Cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Eled ric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. - ❑ R403.7.1.2.3 Fossil fuel heating equipment The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in a . Man ce with Section R403.7.1. 'r— I R403.7.1.3 Extra capacity required for special occas�ons. Residences requiring excess cooling or heating equipment capacity on an LJ intermittent basis, such as anticipated additional load caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within tht space by or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ C403 and C404 of the IECC--Commercial Provisions in Iir u of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) now- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off a system when the pavement temperature is above 50'F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. ❑ R403.10.1 Heaters. The electric powe to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the I eater thermostat Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other Co ritroll methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors thathave built in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-h 2. Pumps that operate solar- and waste-heat-i 3. Where pumps are powered exclusively from R403.10.3 Covers. Outdoor heated swimming pool ❑ the water surface or a liquid cover or other means p Exception: Where more than 70 percen energy, such as from a heat pump or sola R403.10.4 Gas- and oil -fired pool and spa heaters. ❑ efficiency of 82 percent for heaters manufactured on c heaters fired by natural or LP gas shall not have contii ur pump operation. icovery pool heating systems. on -site renewable generation. and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at Dvento reduce heat loss. of the energy for heating, computed over an operation season, is from site -recovered energy source, covers or other vapor -retardant means shall not be required. All gas- and oil -fired pool and spa heaters shall have a minimum thermal after April 16, 2013, when test4idAccordance with ANSI Z 21.56. Pool uously burning pilot lights. 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1)1- FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5 r R403.10.5 Heat pump pool heaters. Heat pump with AHRI 1160, Table 2, Standard Rating Conditions required to verify procedure compliance. Geothermal • 0 R403.11 Portable spas (Mandatol%e energy consumption i requirements of APSP-14. ELECTRICAL POWER AND LIGHTING SN R404.1 Lighting equipment (Mandatory). Not less thi high -efficacy lamps or not less than 75 percent of the permar Exception: Low -voltage fighting. R404.1.1 Lighting equipment (Mandatory)Fuel ool heaters shall have a minimum COP of 4.0 when tested in accordance ow Air Temperature. A test report from an independent laboratory is rimming pool heat pumps are not required to meet this standard. electric -powered portable spas shall be controlled by the R404 75 percent of the lamps in permanently installed lighting fixtures shall be ntly installed lighting fodures shall contain only high -efficacy lamps. lighting systems shall not have continuously burning pilot lights. 8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2917 FBC 6th Edition (2017) Compliant Software Page 5 of 5 2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA ABLE 402.4.1.1 AIR BARRIER AND INSULA1i`ION INSPECTION COMPONENT CRITERIA Project Name: Yancy Residence EG Builder Name: Street: 581 Beach Avenue Permit Office: City, -State, Zip: Port St Lucie, FL, 34952 Permit Number. Y w Owner. Yancy Residence Jurisdiction: St. Luse County = Design Location: FL, ST LUCIE CO INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be instal in the building envelope. Air -permeable insulation shall The exteriorthernal envelope containtb,e continuous air barrier not be used as a sealing material. requirements Breaks or joints in the air barrier shall sealed. Ceiling/attic The air barrier in any dropped ceiling1si M shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air b irrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or I nee wall doors to unconditioned attic spaces shall be se led. Walls The junction of the foundation and sill 1 late shall'be sealed. Cavities within comers and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/door jambs and framing, and and -doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any axposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spa s shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overtappirig joints taped. shall be permanently attached to the crawlspace Shafts, penetrations 'Dud shafts, ufifity penetrations, and flub exterior or unconditioned space shall be shafts opening to sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between a garage and conditioned spac 3s. Recessed lighting Recessed light fixtures installed in the ¢uilding thermal envelope Recessed fight fixtures installed in the building shall be sealed to the drywall. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring, Shower/tub The air barrier installed at exteriorwal4 adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the shovers and tubs. be insulated. Electrical/phone'box or The air barrier shall be installed behindl electrical or communication exteriorwalls boxes or air -sealed boxes shall be instilled. HVAC:register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -floor or drywall. Concealed When required to be seated, concealed fife sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall between fire sprinkler cover and not used to fill voids 6alls or ceilindk- ' I a. In aoginon, mspecuon or tog waus snau be in accoraance witty the pmvrsions otac:c:-auu. 8/13/2018 225 PM EnergyGauge® USA 6.0.02 (Rev. 1) flaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2017 Florida Building Code, Energy Conservation, 6th Edition Jurisdiction: St. Lucie County Permit #: } 'lA aa. fi.«3`s�,'r'Sptlfiirrf''y�� �`p.� ''ilh+; t.� Via;..,"p �'�•Cf h 9 rx';{y'2l C tai4xagP'��s ""+� 5 ` r:.; r,(srk7,,�'4n,y n•,*. ..t&,7.F,. Job iafarntatton r 4a« t f �3 j M rmx:"i'.A. "N �._Z.,. .rc✓�. �c''.`�� ,^h''t3��� 1,�s�,.�.. wc"+�.x'a_ y d��5v �J ����4,�t•. 1'd `�.�v'R.�Z ..fns�'; �F�!„r5.. �l;a�xl' i�i...2� ry�6C.. i, .C'9xXt^:_ Builder: Community: Lot: NA Address: 581 Beach Avenue City: Port St. Lucie State: FL Zip: 34952 .,�' .. r.. s ,'.r'" `r .r,:a v:3�eia;,. z Nil' 'i"z:Tic�t•k::,.. F ksr§x5�,�� A>Ir Leakage tat esc ttst "'Passg�rtgv result 4C y� S'.'kktY4`� ;r s .. ., fft'k3Yly+3 J' i y fi .,,r it us 'meet erther fate e'er orrrlance i'fes npt�v or €Rl Method ;F , 4.J" FL ilk vv u�, pRESCRIt�TNE METHO�T�e budding'�oi+dwetlm�urfshalfb��teste�ancCwenfiect,asxhavrtig a'� ieakag� rate of;notexceedmg 7 air as W ` -� changes per hour at4a presstirQft} 2 mch w g58 Pascals) in+Climate Zones 1 and.2 f a ..t .1m'.R$ �:�.fi .�.? i. ?".:�:wta s�'•;l.r'.'.-:�:,a��. �:�.i�.:kM l:.�'-. >kut: �.x.t .�s'aiAa 3+�Ni�„=dz.: _,t,a t,.1.�1�( '.Trv,`s, A a.+s ..,- wE.'�`.y;'- , Te�dmg f :�.{'r Fr.' .✓'' 'It .r O hale fne tested and raieof y0s ; PERFQRMA(�CE orF(ERI METN+�D ofr ellmg urf 0,00 �avmg an aarteakage noteceetlulg ihef5elected"AC t.(50) va7ue� as shown bn l ortn Rot)5 201 Pe farmar iej orR406-2077 (ERl), secGorrtabeteS as;inflftff nyaub sgctionPACH50.' _ < "yACI 1(50) specrfied on dorm F40r20 .. '.eY.rn) ,C ti 3 e� r h 7 FriergyCatc((�erFcrrrdnce}�rR40fr2017 (ER!) 5.000 x 60 _ 19832 — Method for calculating building volume: CFM(50) Building Volume ACH(50) 0 Retrieved from architectural plans 1-1 PASS •Code software calculated When ACH(50) is less than 3,'Mechanical ventilation installation O Field measured and calculated must be verified by building department R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSURESNETACC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f) (g), or () or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode offrciaL Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors sh ill be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open_ 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be dosed and sealed. 5. Heating and cooling systems, if installed at the time of theltest, shall be tamed off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. - '� i ,°c't'1 t 1 pad £y;''ur�„ ! l.fr.r' fl"w'�T3,�?«�{ t %`it'��� :� �ryry�ai'L "�rt�f A'�'i ye �✓3 _.i?_ �}wl•�� r}'� fx'u H','g�'�'(fr�r� °n. ,L �v"%fi /.,,f ¢`°�t :! `�3R `�:` f p:.�? Company Name: Phone: 1 hereby verify that the above Air Leakage results area in accordance with the 2017 6th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above, Signature of Tester. Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 8/13/2018 2:25:50 PM EnergyGauge® USA 60.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 E Duct LeAage Test Report I Residential Prescriptive, Performance or ERI Method Compliance 2017 Florida Building Cade, Energy Conservation, 6th Edition Jurisdiction: St Lucie County Permit #-- IMP, Builder: Community: Lot: NA Address: 581 Beach Avenue City: Port St. Lucie State: FL Zip: 34952 System 1 cfm25 System 2 cfm25 System 3 cfm25 Sum of any cfm25 Total of all cfm25 + 2479 Total -of all Total Conditioned systems Square Footage PASS FAll Proposed Leak Free 0.03 L-1 Duct tightness shall be verified by testing in accordance with ANSURESNETI[CC380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licen' sed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes. W, d Company Name: Phone: I hereby verify that the above duct leakage testing.1'esufts are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. Signature of Tester. I Date of Test Printed Name of Tester: License/Certification #: Issuing Authority: 8/13/2018 225:57 PM EnergyGauge@ USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1