HomeMy WebLinkAboutENERGY EFFICIENCY CODE. FORM R405-2017
o-.
RESIDENTIAL ENERGY CONSE VATION CODE DOCUMENT,Ai' N�Ga
Florida Department of qusiness and Professional Regulation
Simulated Perfonman a Alternative (Performance) Method
Applications for compliance with the 2017 i
residential Simulated Performance Method
❑ This checklist
❑ A Form R405 report that documents
R405.3 of the Florida Energy Code.
indicating home address, a -ratio and
areas and types of components, whe
orientation, name and version of the
completing the compliance report (or
be used for field verification (usually,
❑ Energy Performance Level (EPL)
❑ HVAC system suing and selection
❑ Mandatory Requirements (five pages)
Required prior to CO for the
Air Barrier and Insulation
one page)
a Building Code, Energy Conservation via the
include:
et the Proposed Design complies with Section
is form shall include a summary page
e pass or fail status along with summary
or the home was simulated as a worst -case
mpliance software tool, name of individual
page) and an input summary checklist that can
rr pages/may be greater).
Card (one page)
on ACCA Manual S or per exceptions provided in Section R403.7
Method:
Component Criteria checklist (Table R402.4.1.1 -
❑ A completed Envelope Leakage Test Report (usually one page)
❑ If Form R405 duct leakage type it
Form R405 Duct Leakage Test Re
8/13/2018.224:48 PM EnergyGauge® USA 6.0.02 (F
es anything other than "default leakage" then a completed
(usually one page)
{
1) - FlaRes2017 FBC 6th Edition (2017) CompliaYA"Cop Pagel - of 1
2017 EPL DISPLAY CARD
ENERGY P
ESTIMATED EN
The lower the Energy
LEVEL (EPL) DISPLAY CARD
PERFORMANCE INDEX* = 97
Index, the more efficient the home.
1. New home or, addition
1_
New (From Plans)
12. Ducts, location & insulation level
a) Supply ducts R
6.0
2. Single-family or multiple -family
2.
in le -family
b) Return ducts R
6.0
c) AHU location 2nd Floor
3. No. of units (if multiple -family)
3.
1
4. Number of bedrooms
4.
2
13. Cooling system: Capacity
58.5
a) Split system SEER
16.0
5. is this a worst case? (yes/no)
5.
No
b) Single package SEER
c) Ground/water source SEER/COP
6. Conditioned floor area (sq. ft.)
6.
2479
d) Room unit/PTAC EER
11.0
e) Other
7. Windows, type and area
a) U-factor.(weighted average)
7a.
0.575
b) Solar Heat Gain Coefficient (SHGC)
7b.
0.300
14. Heating system: Capacity
58.0
c) Area
7c.
1 395.8
a) Split system heat pump HSPF
9.0
b) Single package heat pump HSPF
8. Skylights
c) Electric resistance COP
a) U-factor.(weighted average)
8a.T
NA
d) Gas furnace, natural gas AFUE
b) Solar Heat Gain Coefficient (SHGC)
8b.
I NA
e) Gas furnace, LPG AFUE
f) Other
5.80
9. Floor type, insulation level:
a) Slab -on -grade (R-value)
9a.
0.0
b) Wood, raised (R-value)
9b.
1
15. Water heating system
c) Concrete, raised (R-value)
9c.
a) Electric resistance EF
0.95
b) Gas fired, natural gas EF
10. Wall type and insulation:
c) Gas fired, LPG EF
A. Exterior.
d) Solar system with tank EF
1. Wood frame (Insulation R-value)
10Ai.
e) Dedicated heat pump with tank EF
2. Masonry (Insulation R-value)
10
4.1
0 Heat recovery unit HeatRec%
B. Adjacent:
g) Other
1. Wood frame (Insulation R value)
101.
2. Masonry (Insulation R-value)
1062.
16. HVAC credits claimed (Performance Method)
11. Ceiling type and insulation level
a) Ceiling fans
Yes
a) Under attic
11
30.0
b) Cross ventilation
No
b) Single assembly
11�.
c) Whole house fan
No
c) Knee wallstskylight walls
11 C.
d) Multizone cooling credit
d) Radiant barrier installed
11
No
e) Multizone heating Credit
f) Programmable thermostat
Yes
*Label required by Section R303.1.3 of the Florida
Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has complied with the Flod
a Building Code, Energy Conservation, through the above energy
saving features which will be installed (or exceeded)
in this home before final inspection. Otherwise, a new EPL
display card will be completed based on installed
7
de compliant features.
Builder Signature:
Date:
Address of New Home: 581 Beach Avenue
City/FL Zip: Port St. Lucie, FL 34952
8/13/2018 2:25:28 PM EnergyGauge® USA 3.0.02
(Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Flja[rt o Yge 1 of 1
FORM R405-2017
FLORIDA ENERGY EFFICIEI
Florida Department of Business and
CODE FOR BUILDING CONSTRUCTION
;sional Regulation - Residential Performance Method
Project Name: Yancy Residence EG
Builder Name:
Street: 581 Beach Avenue
Permit Office:
City, State, Zip: Port St Lucie, FL , 34952
Permit Number
Owner. Yancy Residence
Jurisdiction: St Lucie County
Design Location: FL, ST LUCIE CO INTL
County: St Lucie (Florida Climate Zone 2 )
I)
1. New construction or existing New (From Plan
9. Wag Types (2426.0 sgfL) Insulation Area
2. Single family or multiple family Single-family
a. Concrete Block - Int Insul, Exterior R=4.1 2262.00 ftz
b. Interior Frame - Wood, Interior R=11.0 164.00 ftz
3. Number of units, if multiple family 1
c- N/A R= ftz
4. Number of Bedrooms 2
d. N/A R= ftz
10. Ceiling Types (2479.0 sgft) Insulation Area
5. Is this a worst case? No
a. Under Attic (Vented) R=30.0 2479.00 IF
6. Conditioned floor area above grade (tiz) 2479
b. WA R= fI
Conditioned floor area below grade (ftz) 0
c. N/A R= ft2
11. Ducts R ftz
7. Windows(395.8 sgfL) Description Area
a. Sup: Attic,.Ret: Attic, AH: 2nd Floor 6 739
a. U-Factor: Dbl, U=0.45 235.33
SHGC: SHGC=0.30
b. U-Factor. Dbl, U=0.76 120.94
12. Cooling systems kBtu/hr Efficiency
SHGC: SHGC=0.30
a. Central Unit 46.5 SEER:16.00
b.'PTAC and Room Unit 12.0 EER:11.00
c. U-Factor. Dbl, U=0.75 39.54
SHGC: SHGC--0.30
13. Heating systems kBtu/hr Efficiency
d. U-Factor. N/A
a. Electric. Heat Pump 46.5 HSPF:9.00
SHGC:
I
b. PTHP 11.5 COP:5.80
Area Weighted Average Overhang Depth: 3.639
.
Area Weighted Average SHGC: 0.300
14. Hot water systems
a. Electric Cap: 40 gallons
8. Floor Types (2479.0 sgft.) Insulation Area
EF: 0.950
a. Slab -On -Grade Edge Insulation Rro.O 2479.00 if
b. Conservation features
b. N/A R=
None
c. N/A R=
z
15. Credits CF, Pstat
Total Propos
Modified Loads: 74.35
Glass/Floor Area: 0.160
PASS
Total
, aseline Loads: 76.26
I hereby certify that the plans and specifications covered by
Review of the plans and 'CBE STgT
O
�0�,
this calculation are in ce Florida Energy
specifications covered by this=
Code.
calculation indicates compliance��.��
°,
with the Florida Energy Code. t~ �n,1r,=. '�%. f" ° 0
' ;. • _ ,
PREPARED BY:
DATE:
Before construction is completed tR.
this building will be inspected for 0
compliance with Section 553.908 * a
I hereby certify that this building, as designed, is in compliance
Florida Statutes. cf .
COD
with the Florida Energy Co
yt►�i'�
OWNER/AG
BUILDING OFFICIAL:
DATE: 7.�
DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with 11403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402A.1.2).
- Compliance with a proposed duct leakage On requires a Duct Leakage Test Report confirming duct leakage to outdoors,
tested in accordance with ANSURESNETACC 380, is not greater than 0.030 On for whole house.
8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2010 Compliant Software Page 1 of 6
F-e- Copy
FORM R405-2017
INPUT SUMMARY
CHECKLIST REPORT
PROJECT
Tille:
Yancy Residence EG BedrooIrrs:
2
Address Type:
Street Address
Building Type:
User
Conditioned
Area: 2479
Lot #
Owner Name:
Yancy Residence
Total Stories:
1
BlocIdSubdivision:
# of Units:
1
Worst
6ase: No
PlatBook:
Builder Name:
Rotate
ngle: 270
Street
581 Beach Avenue
Permit Office:
CrossVentilation:
No
County:
St. Lucie
Jurisdiction:
St Lucie County
Whole I
iouse Fan: No
City, State, Zip:
Port St. Lucie.
Family Type:
Single-family
FL, 34952
New/Existing:
New (From Plans)
Comment:
CLIMATE
Design Temp Int Design Temp Heating Design Daily Temp
Design Location
TMY Site
97.5 % 2.5 % Winter Summer Degree Days Moisture Range
FL, ST LUCIE CO INTL
FL VERO_BEACH MUNI
39 90 70- 75 299 58 Medium
BLOCKS
Number Name
Area
Volu
e
1 AHU1
2 AHU2
1852
627
148II16
5016
Number
Name
Area
1
2nd Floor
130
2
RR KITCHEN
162
3
OFFICE
78
4
ENTRY
117
5
CMD
23
6
M BATH
93
7
M BED
243
8
DINING
206
9
FR KITCHEN
141
10
BED 2
192
11
BATH 2
59
12
M WIC
92
13
LIVING
316
14
COND GARAGE
627
y # Floor Type Space
1 Slab -On -Grade Edge Insulatio 2nd Floor
2 Slab -On -Grade Edge Insulatio RR KITCHEN
3Slab-On-Grade Edge Insulatio OFFICE
SPACES
Volume Kitchen. Occupants Bedro
1040 No 0
1296 Yes 1
624 No 0
936 No 0
184 No 0
744 No 0
1944 No 0 1
1648 No 0
1128 Yes 0
1536 No 0 1
472 No 0
736 No 0
2528 No 2
5016 No 0
FLOORS
Perimeter Perimeter.R--Value Area
23 it 130 ft
14.5 ft 162 ft'
11.3 ft 78 f12
oms InfilID
Finished
Cooled
Heated
1
Yes
Yes
Yes
1
Yes
Yes
Yes
1
Yes
Yes
Yes
1
Yes
Yes
Yes
1
Yes
Yes
Yes
1
Yes
Yes
Yes
1
Yes
Yes
Yes
1
Yes
Yes
Yes
1
Yes
Yes
Yes
1
Yes
Yes
Yes
1
Yes
Yes
Yes
1
Yes
Yes
Yes
1
Yes
Yes
Yes
1
Yes
Yes
Yes
Joist R-Value
Tile Wood Carl
1 0 0
1 0 0
1 0 0
8/13/2018 2.25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017), Compliant Software Page 2 of 6
FORM R405-2017
INPUT SUMMARY
CHECKLIST REPORT
FLOORS
# Floor Type
Space
rimeter Perimeter R Value
Area
Joist R-Value
Tile
Wood Carpet
4 Slab -On -Grade Edge Insulatio
ENTRY 15.9
ft
117 f12
—
1
0
0
5 Slab -On -Grade Edge Insulatio
CMD
1 ft
23 ft2
_
1
0
0
6 Slab -On -Grade Edge Insulatio
M BATH 16.1
ft
93 ft2
_
1
0
0
7 Slab -On -Grade Edge Insulatio
M BED 25.2ft
243 ft2
_
1
0
0
8 Slab -On -Grade Edge Insulatio
DINING
.8ft
206 ft2
—
1
0
0
9 Slab -On -Grade Edge Insulatio
FR KITCHEN 1
.5 ft
141 f12
_
1
0
0
10SIab-On-Grade Edge Insulatio
BED 2 3D.5
ft
192 ff?
—
1
0
0
11Slab-On-Grade Edge Insulatio
BATH 2
1 It
59 ft2
_
1
0
0
12SIab-On-Grade Edge Insulatio
M WIC
1 ft
'92 ft2
_
1
0
0
13SIab-On-Grade Edge Insulatio
LIVING
ft
316 ft2
—
1
0
0
14SIab-On-GradeEdge Insulatio
COND GARAGE 84.7
ft
627 ft2
_
1
0
0
ROOF
Roof
Gable
Roof
Rad
Solar
SA Emitt
Emitt Deck
Pitch
# Type Materials Area
Area
Color
Barr
Absor.
Tested
Tested Insul.
(deg)
1 Hip Composition shingles 2613f12
0 ft2
Light
N
0.5
No 0.9
No 0
18.4
ATTIC
V # Type
Ventilation
Vent
Ratio (1 in)
Area
RBS
IRCC
1 Full attic
Vented
300
2479 ft2
N
N
CEILING
# Ceiling Type
Space
R Value
Ins Type
Area
Framing Frac
Truss Type
1 Under Attic (Vented)
2nd Floor
30
Blown
130 fie
0.11
Wood
2 Under Attic (Vented)
RR KITCHEM
30
Blown
162 ft2
0.11
Wood
3 Under Attic (Vented)
OFFICE
30
Blown
78 112
0.11
Wood
4 UnderAttic(Vented)
ENTRY
30
Blown
117ft2
0.11
Wood
5 Under Attic (Vented)
CMD
30
Blown
23 ft2
0.11
Wood
6 Under Attic (Vented)
M BATH
30
Blown
93 ft2
0.11
Wood
7 Under Attic (Vented)
M BED
30
Blown
243 W
0.11
Wood
8 Under Attic (Vented)
DINING
30
Blown
206 ft2
0.11
Wood
9 Under Attic (Vented)
FR KrrCHE
4
30
Blown
141 ft2
0.11
Wood
10 Under Attic (Vented)
BED 2
30
Blown
192 ft2
0.11
Wood
11 UnderAttic (Vented)
BATH 2
30
Blown
59 ft2
0.11
Wood
12 Under Attic (Vented)
M WIC
30
Blown
92 ft2
0.11
Wood
13 Under Attic (Vented)
LIVING
30
Blown
316 ft2
0.11
Wood
14 Under Attic (Vented)
COND GARAGE
30
Blown
627 ft2
0.11
Wood
8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) T FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 3 of 6
,
IN
IN
IN
IN
IN
IN
IN
li
I�
li
li
li
li
I�
li
li
li
I
I
I
I
I
I
I
I
I
G`iJ
�'
O
N
w
v+
A
W
IV
Z
�!
W
N
i
#
C
C
UP
m
Z
cn
m
cn
In
Z
m
Z
cn
m
z
I
cn
II
cn
II
I
cn
II
co
*
II
m
II
0
m
m
m
O
U1
m
z
V
V
V
V
y
V
V
V
V
V
V
y
V
V
V
can
m
m
m
m
o
cn
m
CO
m*
cyn
cn
cn
m
z
to
m
m
(n
m
m
z
m
m
m
Z
o
to
w
z
z
Z
Z
0
0
a
i
w
co
0
cn
cm
-•
C
G
m
11
7.
7.
o,
Q.
7.
7.
7.
Q.
7.
7.
7.
Q.
v
O•
v
Q.
7.
O.
7.
7.
v 01
>=
v
1
�
7.
o
Q.
0
Q.
0
0
7.
0
0
7.
0
0
0
0
0
0
0
0
0
0
0
0
v
0
0
0
0
0
m
y
y
d
=j
d
^I
=j
O
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
CD
a3
>
�'
>
a
>
>
>
>
>
>
>
0
>
>
>
>
>
>
>
>
>.
m.
>
>
>
>
>
r
O
r
Q
r
O
r
O
r
O
r
O
o
N
N
O
fD
N
fD
N
�
fD
fa
N
N
N
N
fD
fa
W
N
o
�
0
0
C
A
N
C
C
C
y
C
O
N
N
ET
fD
lD
N
fD
W
N
N
iD
ED
ar
tD
N
ar
fD
TI
N
-1
T
ID
N
N
E'D
iD
m
m
m
m
m
o
d
�+
W
m
m
W
0o
W
m
o0
177
m
oo
aw
m
oo
ao
m
w
3
a)@
3
is
9
m
m
aw
w
Z
0
0
0
0
0
0
0
0
fD
0
m
o
�
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
o
i
c
�'
0
m
R.
RL
RL
RL
RL
RL
RL
R-
RL
RL
6P
RL
9
9
x
RLRL
&
N
a
CD
Q
Eo
Q
<D
N
Q
fD
O.
I
i
1
1
1
1
i
1
1
i
1
1
1
1
1
1
1
1
1
1
1
1
1
C
a
O
O
w
O
w
�
>
NQ
>
a
o
�
>
>
>
>
>
_
�
>
_
>
N
>
>
>
�
a
06
N
CD
0
N
N
N
rn
H
N
N
N
rn
N
N
N
°
z
mo
m
Z
v
z
v
cn
�o
z
v
z
v
z
v
z
v
r'
W
my
m
m
m
m
0
Z
0
Z
O
O
O
v@+
ego�°
n
y
y
m
m
m
m
D
D
—0t7
G�
O�O
z
N
N
N
�
z
O
z
O
m
v
m
v
m
v
m
v
�
-C
O
n
n
o
0
p
12
m
m
m
m
m
o
o
�f7
m
o
0
0
0
0
J
Qi
0
%i
�i
0
-
i
-
i
-
—
-
-
i
i
-
i
-
i
J
J
-►
'�
J
i
i
i
i
A
�
h
i
A
i
1 03i
C
ci
a
z
O
�
ca
rn
11 o
o
Cl)
V O
0
4
TI
O
l'A
O
E.W
O
G1
O
CW
O
f+1
O
G1
=
In
n
'w
Y,
A
00
p
p
�
N
N
w
A
N
01
N
i
t„n
w
w
p
w
01
OI
,..
N
N
W
O
Y,
S
0) CO)
r
m
z
z
z
c
N
..
G
>
>
>
w
G
V
O
O
O
O
T
O
w
W
C
w
y
wwwwwwwwwwwwwwwwwwww�Dwwwww
rn
iv
V
W
0
V
C71
p
=
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
�
O.
M
OD
A
W
A
i+.
N
C71
-�
O
-•
w
O
m
OOo
co
?
O~1
w
?
C
:1
v
V
V
i4
Eat
G
W
Op
0
C
J4
p
N
v
O
'J
v
C
O
O
O
C
O
V
W
W
O
7
7
O
i
A
7
7
7
N
O.
m
W
W
.+
(/)
O
CD
O
CDW
O
O
Q y
Q.
�
O
O
O
O
O
0
N to
N
CD
y
>
>
>
>
>
>
C
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
N
O
7
47
T1
K
co
w
Co
T
~�
O
O
O
O
O
CD
O
CD
O
O
O
O
O
O
O
O
N
O
O
N
O
N
O
CD
O
O
{U
a
Z
Z
Z
Z
Z
Z
f0
Wcil
7
m
7
m
7
cD
7
cD
7
m
7
m
a
�
r.
cin
CD
o
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
o
p
o
0
0
0
0
0
d
b�
b�
it
ct
b�
it
b�
bo
bo
b�
in
b�
0
0
it
0)
m
En
m
m
m
m
0
En
b�
�
CD
0
_
N
00
N
A
N
A
a
,
w
N
N
N
fD
fD
fD
�
O
0
O
0
0
0
O
0
0
O
0
O
O
O
0
O
0
0
0
0
0
0
O
0
0
0
e
FORM R405-2017
INPUT SUMMARY
CHECKLIST REPORT
WINDOWS
Orientation shown is the entered orientation
=> changed
to As Built rotated 270 degrees).
Wall
Overhang
# Omt ID
Frame
Panes
NFRC
U-Factor SHGC
Imp
Area
Depth
Separation
Int Shade
Screening
7 S=>E 10
TIM
Low-E Double
Yes
0.75 0.3
Y
4.7 ft2
7ft 7 in
0 ft 0 in
None
None
8 W=>S 11
TIM
Low-E Double
Yes
0.75 0.3
Y
9A ft2
4 ft 0 in
0 ft 0 in
None
None
9 W=>S 11
TIM
Low-E Double
Yes
0.75 0.3
Y
4.9 ft2
4.ft 0 in
0 ft 0 in
None
None
10 N=>W 12
TIM
Low-E Double
Yes
0.45 0.3
Y
47.3 ft'
3 ft 5 in
0 It 0 in
None
None
11 NW=>SW17
TIM
Low-E Double
Yes
0.76 0.3
Y
38.0 ft2
1 ft 6 in
oft 0 in
None
None
12 NW=>SW17
TIM
Low-E-Double
Yes
0.76 0.3
Y
19.5 ft2
1 ft 6 in
0 ft 0 in
None
None
13 NW=>SW17
TIM
Low-E Double
Yes
0.45 0.3
Y
72.0 ftZ
3 It 5 in
0 ft 0 in
None
None
14 NW=>SW18
TIM
Low-E Double
Yes
0.45 0.3
Y
72.0 ft?
3 ft 5 in
0 ft 0 in
None
None
15 NE=>NW19
TIM
Low-E Double
Yes
0.76 0.3
Y
49.3 ft2
1 ft 6 in
0 tt 0 in
None
None
16 NE=>NW 1
TIM
Low-E Double
Yes
0.75 0.3
Y
20.6 ft2
3 ft 11 in
0 ft 0 in
None
None
INFILTRATION
# Scope
Method
SLA
C�M
50 ELA EgLA
ACH ACH 50
1 Wholehouse
Proposed ACH(50)
.000254
1152.7
90.73 170.63
.0881 5
HATING
SYSTEM
#
System Type
Subtype
Eitidency
Capacity Block Ducts
1
Electric Heat Pump/
Split
HSPF:9
46.5 kBtu/hr 1 sys#1
2
PTHP/
None
COP:5.8
11.5 kBtu/hr 2 Ductless
C60LING
SYSTEM
# System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit/ Split SEER:16 46.5 kBtu/hr 1550 cfm 0.,8 1 sys#1
2 PTAC and Room Unit/ Through the Wall Single) SEER: 11 12 kBtu/hr 370 ctrn 0.8 2 Ductless
HOT WATER SYSTEM
# System Type SubType Location JEF Cap Use SetPnt Conservation
1 Electric None 2nd Floor 0.95 40�gal 60.9 gal 120 deg None
SOLAR HOT WATER SYSTEM
i
FSEC Collector Storage
Cert # Company Name m Model # Collector Model # Area Volume FEF
None None ft2,
8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 5 of 6
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
DUCTS
— Supply
—
—
Return
—
Air
CFM 25
CFM25
HVAC #
# Location R Value Area
Location
Area
Leakage Type
Handler
TOT
OUT QN' RLF
Heat Cool
1 Attic 6
739 IF
Attic 739
IF
Prop. Leak Free
2nd Floor
— cfm
55.6 cfm 0.03
0.50
1 1
�17MPERATURES
Programable Thermostat Y
Ceil
Fans:
Coolin an Feb
Heat HJan Feb
Mar
Mar
A r
r
Apr
a
a
Jun Jul
Jun Jul
AugSe
Auge
Oct
Oct
Nov
Nov
Dec
HDec
Venting Jan Feb
Mar
ay
Jun Jul
Aug
Sep
Oct
Nov
Dec
Thermostat Schedule: HERS 2006 Reference
Hours
Schedule Type
1
2
3
4
5 6
7
8
9 10
11
12
Cooling (WD) AM
78
78
78
78
78 78
78
78
80 80
80
80
PM
80
80
78
78
78 78
78
78
78 78
78
78
Cooling (WEH) AM
78
78
78
78
78 78
78
78
78 78
78
78
PM
78
78
78
78
78 78
78
78
78 78
78
78
Heating(WD) AM
66
66
66
66
66 68
68
68
68 68
68
68
PM
68
68
68
68
68 68
68
68
68 68
66
66
Heating (WEH) AM
66
66
66
66
66 68
68
68
68 68
68
68
PM
68
68
68
68
68 68
68
68
68 68
66
66
MASS
Mass Type
Area
Thickness
Furniture Fraction
Space
Default(8 Ibs/sq.fL
0 ftZ
Oft
0.3
2nd floor
Default(8 Ibs/sgA
ft'
ft
0.3
RR KITCHEN
Default(8 Ibs/sq.fL
ft2
ft
0.3
OFFICE
Default(8 lbs/sq.ft.
ftz
ft
0.3
ENTRY
Default(8 lbs/sq.fL
ftZ
ft
0.3
CMD
Default(8 ibs/sq.f .
ftZ
It
0.3
M BATH
Default(8 Ibs/sq.fL
ftZ
ft
0.3
M BED
Default(8 Ibs/sq.fL
ftZ
ft
0.3
DINING
DefauH(8 Ibs/sq.ft.
ftZ
It
0.3
FR KITCHEN
Default(8 Ibs/sq.ft.
ftZ
ft
0.3
BED 2
Default(8 Ibs/sq.ft.
ftZ
ft
0.3
BATH 2
Default(8 lbs/sq.ft.
ftZ
ft
0.3
M WIC
Default(8 Ibs/sq.ft.
ftZ
It
0.3
LIVING
Defhn1 8 Ibs/s .ft.
ftZ
It
0.3
COND GARAGE
8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) -1 FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 6 of 6
Florida Building Code,
atory Reauirements for Re
ergy Conservation, 6th Edition (2017)
Intial' Performance, Prescriptive and ERI Methods
IADDRESS: 5 Port each A a u, 34952 I Permit Number. I
.MANDATORY REQUIREMENTS See
SECTI
code sections for full details.
R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (MiIndatory)3 he building official shag require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate -and cored before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statutes) requires the EPL displa� card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contai s information indicating the energy performance level and efficiencies of components
installed in a dwelling unit The building official shag verify th t the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compfian for the building. A copy of the EPL display card can be found in Appendix RD.
R402.4 Air leakage (Mandatory). The building thermal envelope shag be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancie$ and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
R402.4.1 Building thermal enveldjw- building therma envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.
The sealing methods between dissimilar materials shag allow for differential expansion and contraction.
R402A.1.1 lnstallation.The components of the buildino thermal envelope as listed in Table R402.4.1.1 shall.be installed in accordance
with the manufacturer's instructions and the criteria listeo in Table R402A.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
r
R402-4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNETACC 380 and reported ai a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i) or
an approved third party, A written report of the results oflthe test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions,
buildings in which the new construction is less than 85
During testing:
1. Exterior windows and doors, fireplace and stove door
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, back
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall
4. Exterior doors for continuous ventilation systems and
5. Heating and cooling systems, if installed at the time c
6. Supply and return registers, if installed at the time of
renovations, or repairs, of the building thermal envelope of existing
the building thermal envelope.
be dosed, but not sealed, beyond the intended weatherstripping or
and flue dampers shall be dosed, but not sealed beyond intended
open.
at recovery ventilators shag be dosed and sealed.
ie test, shall be turned off.
test, shall be fully open.
R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on.fadory-built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces,lthe doors shall be listed and labeled in accordance with UL 907.
11402:4.3 fenestration air leakagdlYndows, skylights and sliding glass doors shall have amairinfiltration rate of no more than 0.3 ctm per
square foot (1.5 Us/m2), and swinging doors no more than 0.5 fin per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101A.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (C
R402.4.4 Rooms containing fuel -burning appliances. In C11mate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in,a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall met not less than the basement wall R value requirement The door into the room shall be
fully gasketed and any water fines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake anq exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Se on R402.4.2 and Section R1006 of the Florida Building Code, Residential.
R402A.5 Recessed lighting. Recessed luminaires installed i� the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed lu maires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the h using and the interior wall or ceiling covering.
R403.1 controls. SECT ON R403 SYSTEMS
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat op ration when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All duds, air handlers, liter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered duds o plenum chambers, shall be constructed and sealed in accordance with Section
C4032.9.2 of the Commercial Provisions of this code and shall be shown to meet dud tightness criteria below.
Duct -tightness shall be verified by testing in accordan with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(1), (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
n R403.3.2.1 Sealed air handler. Air handlers shalt' have a manufacturer's designation for an air leakage of no more than 2 percent
JJ of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1, Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the
manufacturer's air handler enclosure if in talled at the time of the test. All registers shall be taped or otherwise sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the
entire system, including the manufacture air handler enclosure. Registers shall be taped or otherwise sealed during the
test.
Exceptions:
1. A duct air leakage test shall not be wired where the duds and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buil ings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
❑ R403.3.5 Building cavities (Mandatory). Building framing cavr Ies shall not be used as duds or plenums.
R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105'F (41 °C)
or below 55'F (13°C) shall be insulated to a minimum of R-3.
❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory)Heated water circulation systems shall be in
accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return
❑ pipe shall be a dedicated return pipe or cold water supply pipe. Gravity and thernosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the
occupancy. The controls shall automatically turd off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
R403.5.1.2 Heat trace systems. Electric heat ttrace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems
shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water is used in thq occupancy.
8/1312018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps (Mandatory). Storage water heateml not equipped with integral heat traps and having vertical pipe risers shall have
' heat traps installed on both the inlets and outlets. External hat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3'h inches (89 mm) n the hot waterdistribution line and cold water line located as close as possible
to the storage tank.
a R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1.1 Automatic controls. Service wate -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acre;table temperature settings for the intended use. The minimum temperature
setting range shall be from 100"F to 140OF (380C 13 600C).
❑ 11403.5.6.1.2Shut-down. A separate switch or early,marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be tamed off. A separa a valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water -heating systems to be turned oil
R403.5.6.2 Water -heating equipment. Water-hgafing equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building ode, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall i neet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy facto of a -system shall be determined from the Florida Solar Energy Center Directory of.
Certified Solar Systems. Solar collectors shi ill be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic of Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a till angle between 1 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation (Mandatory). The bui ding shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Cc ide, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outc oor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy require ents of Table R403.6.1.
Exception: Where whole -house mechanical entilaflon fans are integral to tested and listed HVAC equipment, they shall be
powered by an electronically commutated motor.
R403.6.2 Ventilation air. Residential buildings desf
fined to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums r residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system male -up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or�utdoor spaces adjacent to swimming pools or spas.
If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceili i �ig shall be insulated to a,minimum of R-19, space permitting, or RA 0
otherwise.
R403.7 Heating and cooling equipment (Mandatory).
R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with �CCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and
indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1. This Code does no# allow designer safety factors, provisions for future expansion or other factors that
affect equipment sizing. System sizing calculatiops shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TAB4E R403.6.1
WHOLE-F[OUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMU
(CFM)
Range hoods
Any I
2.8 cfm/wat
Any
In4ine fan
Any
2.8 ckn/wat
Any
Bathroom, utility room
10
1.4 chn/wat
<90
Bathroom, utilityroom
90
2.8 cfin/wat
Any
For SI: 1 cfm = 28.3 Umin. a.
8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev.
en tested in accordance with HVI Standard 916
1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software
Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
,❑R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.7, or the closest available size provided by the v rianufacturer's product lines. The corresponding latent capacity of the
i equipment shall not -be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rabng-test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling my equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water tern rature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance w� good design practice.
R403.7.1.2 Heating equipment capacity.
❑ 11403.7.1.2.1 Heat pumps. Heat pump,sizinj 1 shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacit shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than tha design Cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Eled ric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
- ❑ R403.7.1.2.3 Fossil fuel heating equipment The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in a . Man ce with Section R403.7.1.
'r— I R403.7.1.3 Extra capacity required for special occas�ons. Residences requiring excess cooling or heating equipment capacity on an
LJ intermittent basis, such as anticipated additional load caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within tht space by or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the IECC--Commercial Provisions in Iir u of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) now- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off a system when the pavement temperature is above 50'F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric powe to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the I eater thermostat Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other Co ritroll methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors thathave built in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-h
2. Pumps that operate solar- and waste-heat-i
3. Where pumps are powered exclusively from
R403.10.3 Covers. Outdoor heated swimming pool
❑ the water surface or a liquid cover or other means p
Exception: Where more than 70 percen
energy, such as from a heat pump or sola
R403.10.4 Gas- and oil -fired pool and spa heaters.
❑ efficiency of 82 percent for heaters manufactured on c
heaters fired by natural or LP gas shall not have contii
ur pump operation.
icovery pool heating systems.
on -site renewable generation.
and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
Dvento reduce heat loss.
of the energy for heating, computed over an operation season, is from site -recovered
energy source, covers or other vapor -retardant means shall not be required.
All gas- and oil -fired pool and spa heaters shall have a minimum thermal
after April 16, 2013, when test4idAccordance with ANSI Z 21.56. Pool
uously burning pilot lights.
8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1)1- FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 4 of 5
r
R403.10.5 Heat pump pool heaters. Heat pump
with AHRI 1160, Table 2, Standard Rating Conditions
required to verify procedure compliance. Geothermal
• 0 R403.11 Portable spas (Mandatol%e energy consumption i
requirements of APSP-14.
ELECTRICAL POWER AND LIGHTING SN
R404.1 Lighting equipment (Mandatory). Not less thi
high -efficacy lamps or not less than 75 percent of the permar
Exception: Low -voltage fighting.
R404.1.1 Lighting equipment (Mandatory)Fuel
ool heaters shall have a minimum COP of 4.0 when tested in accordance
ow Air Temperature. A test report from an independent laboratory is
rimming pool heat pumps are not required to meet this standard.
electric -powered portable spas shall be controlled by the
R404
75 percent of the lamps in permanently installed lighting fixtures shall be
ntly installed lighting fodures shall contain only high -efficacy lamps.
lighting systems shall not have continuously burning pilot lights.
8/13/2018 2:25 PM EnergyGauge® USA 6.0.02 (Rev. 1) - FlaRes2917 FBC 6th Edition (2017) Compliant Software Page 5 of 5
2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
ABLE 402.4.1.1
AIR BARRIER AND INSULA1i`ION INSPECTION COMPONENT CRITERIA
Project Name: Yancy Residence EG
Builder Name:
Street: 581 Beach Avenue
Permit Office:
City, -State, Zip: Port St Lucie, FL, 34952
Permit Number.
Y
w
Owner. Yancy Residence
Jurisdiction: St. Luse County
=
Design Location: FL, ST LUCIE CO INTL
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be instal
in the building envelope.
Air -permeable insulation shall
The exteriorthernal envelope containtb,e
continuous air barrier
not be used as a sealing material.
requirements
Breaks or joints in the air barrier shall
sealed.
Ceiling/attic
The air barrier in any dropped ceiling1si
M shall be aligned with
The insulation in any dropped ceiling/soffit
the insulation and any gaps in the air b
irrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or I
nee wall doors to
unconditioned attic spaces shall be se
led.
Walls
The junction of the foundation and sill 1
late shall'be sealed.
Cavities within comers and headers of frame walls
The junction of the top plate and the top
of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/door jambs
and framing, and
and -doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any
axposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spa
s shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overtappirig
joints taped.
shall be permanently attached to the crawlspace
Shafts, penetrations
'Dud shafts, ufifity penetrations, and flub
exterior or unconditioned space shall be
shafts opening to
sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between
a garage and conditioned spac
3s.
Recessed lighting
Recessed light fixtures installed in the
¢uilding thermal envelope
Recessed fight fixtures installed in the building
shall be sealed to the drywall.
thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
extend behind piping and wiring,
Shower/tub
The air barrier installed at exteriorwal4
adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the shovers
and tubs.
be insulated.
Electrical/phone'box or
The air barrier shall be installed behindl
electrical or communication
exteriorwalls
boxes or air -sealed boxes shall be instilled.
HVAC:register boots
HVAC register boots that penetrate building
thermal envelope shall
be sealed to the sub -floor or drywall.
Concealed
When required to be seated, concealed
fife sprinklers shall only be
sprinklers
sealed in a manner that is recommended
by the manufacturer.
Caulking or other adhesive sealants shall
between fire sprinkler cover and
not used to fill voids
6alls or ceilindk- '
I
a. In aoginon, mspecuon or tog waus snau be in accoraance witty the pmvrsions otac:c:-auu.
8/13/2018 225 PM EnergyGauge® USA 6.0.02 (Rev. 1) flaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction: St. Lucie County
Permit #:
}
'lA
aa. fi.«3`s�,'r'Sptlfiirrf''y��
�`p.� ''ilh+; t.� Via;..,"p �'�•Cf h 9 rx';{y'2l C tai4xagP'��s ""+� 5 ` r:.;
r,(srk7,,�'4n,y
n•,*. ..t&,7.F,.
Job iafarntatton r 4a«
t
f �3
j M
rmx:"i'.A. "N �._Z.,. .rc✓�. �c''.`�� ,^h''t3��� 1,�s�,.�.. wc"+�.x'a_
y
d��5v �J
����4,�t•. 1'd `�.�v'R.�Z ..fns�'; �F�!„r5.. �l;a�xl' i�i...2� ry�6C.. i, .C'9xXt^:_
Builder: Community:
Lot: NA
Address: 581 Beach Avenue
City: Port St. Lucie
State: FL Zip: 34952
.,�' .. r.. s ,'.r'" `r .r,:a v:3�eia;,. z Nil' 'i"z:Tic�t•k::,.. F ksr§x5�,��
A>Ir Leakage tat esc ttst "'Passg�rtgv result
4C y� S'.'kktY4`� ;r s .. ., fft'k3Yly+3 J' i y fi .,,r
it us 'meet erther fate e'er orrrlance i'fes npt�v or €Rl Method
;F
,
4.J" FL
ilk
vv
u�, pRESCRIt�TNE METHO�T�e budding'�oi+dwetlm�urfshalfb��teste�ancCwenfiect,asxhavrtig
a'� ieakag� rate of;notexceedmg 7 air
as
W `
-� changes per hour at4a presstirQft} 2 mch w g58 Pascals)
in+Climate Zones 1 and.2 f a
..t .1m'.R$ �:�.fi .�.? i. ?".:�:wta s�'•;l.r'.'.-:�:,a��. �:�.i�.:kM
l:.�'-. >kut: �.x.t .�s'aiAa 3+�Ni�„=dz.: _,t,a t,.1.�1�( '.Trv,`s, A a.+s ..,- wE.'�`.y;'- ,
Te�dmg
f :�.{'r Fr.' .✓'' 'It .r
O
hale fne tested and raieof
y0s ; PERFQRMA(�CE orF(ERI METN+�D ofr
ellmg urf 0,00 �avmg an aarteakage noteceetlulg
ihef5elected"AC t.(50) va7ue� as shown bn l ortn Rot)5 201
Pe farmar iej orR406-2077 (ERl), secGorrtabeteS as;inflftff nyaub sgctionPACH50.'
_
< "yACI 1(50) specrfied on dorm F40r20
.. '.eY.rn) ,C ti 3 e� r h
7 FriergyCatc((�erFcrrrdnce}�rR40fr2017 (ER!) 5.000
x 60 _ 19832 —
Method for calculating building volume:
CFM(50) Building Volume ACH(50)
0 Retrieved from architectural plans
1-1 PASS
•Code software calculated
When ACH(50) is less than 3,'Mechanical
ventilation installation O Field measured and calculated
must be verified by building department
R402.4.1.2 Testing. Testing shall be conducted in accordance
with ANSURESNETACC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals).
Testing shall be conducted by either individuals as defined in
Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f) (g), or () or an approved third party. A written
report of the results of the test shall be signed by the party conducting the test and
provided to thecode offrciaL Testing shall be performed at any
time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors sh
ill be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft
and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open_
4. Exterior doors for continuous ventilation systems and heat
recovery ventilators shall be dosed and sealed.
5. Heating and cooling systems, if installed at the time of theltest,
shall be tamed off.
6. Supply and return registers, if installed at the time of the test,
shall be fully open.
- '� i ,°c't'1 t 1 pad £y;''ur�„ ! l.fr.r' fl"w'�T3,�?«�{ t %`it'��� :�
�ryry�ai'L "�rt�f A'�'i ye �✓3 _.i?_ �}wl•�� r}'� fx'u H','g�'�'(fr�r� °n. ,L �v"%fi /.,,f ¢`°�t :! `�3R `�:` f p:.�?
Company Name:
Phone:
1 hereby verify that the above Air Leakage results area
in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance
method selected above,
Signature of Tester.
Date of Test:
Printed Name of Tester:
License/Certification #:
Issuing Authority:
8/13/2018 2:25:50 PM EnergyGauge® USA 60.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1
E
Duct LeAage Test Report
I
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Cade, Energy Conservation, 6th Edition
Jurisdiction: St Lucie County
Permit #--
IMP,
Builder: Community: Lot: NA
Address: 581 Beach Avenue
City: Port St. Lucie State: FL Zip: 34952
System 1
cfm25
System 2
cfm25
System 3
cfm25
Sum of any
cfm25
Total of all
cfm25
+ 2479
Total -of all Total Conditioned
systems Square Footage
PASS FAll Proposed Leak Free 0.03
L-1
Duct tightness shall be verified by testing in accordance with ANSURESNETI[CC380 by either individuals as defined in Section
553.993(5) or (7), Florida Statutes, or individuals licen' sed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes.
W,
d
Company Name: Phone:
I hereby verify that the above duct leakage testing.1'esufts are in accordance with the Florida Building Code requirements with the
selected compliance path as stated above, either the Prescriptive Method or Performance Method.
Signature of Tester. I Date of Test
Printed Name of Tester:
License/Certification #: Issuing Authority:
8/13/2018 225:57 PM EnergyGauge@ USA 6.0.02 (Rev. 1) - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1