/DIVISION: 08 00 00-OPENINGS
SECTION: 08 95 43-VENTS/FOUNDATION FLOOD VENTS
i
i
REPORT HOLDER:
SMART VENT PRODUCTS, INC.
EVALUATION SUBJECT:
SMART VENT® AUTOMATIC FOUNDATION FLOOD VENTS:
MODELS #1540-520; #1540-521; #1540-510; #1540-511; #1540-570; #1540-574;
#1540-524; #1540-514
FLOOD VENT SEALING KIT #1540-526
1
1CC ICC ICC
PMG
"2014 Recipient of Prestigious Western States Seismic Policy Council
(WSSPC) Award in Excellence"
A Subsidiary of
ICC-ES Evaluation Reports are not to be construed as- representing aesthetics or any other attributes not spec jtcally
addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. : _- . _
There is no warranty.by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this
sonEc �'7uee .
report, or as to any product covered by the report. i rod ttCemnwuon Body
°yf00ti
Copyright 0 2019 ICC Evaluation Service, LLC. All rights reserved.
IMES Evaluation Report ES.R-20.74
Reissued February 2019
This report is subject to, renewal February 2021.
www-icc-es.org 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the Intemnational Code Council®
DIVISION: 08 00 00—OPENINGS
Section: 08 95 43—Vents/Foundation Flood Vents
REPORT HOLDER:
SMART VENT PRODUCTS, INC.
EVALUATION SUBJECT:
SMART VENT" AUTOMATIC FOUNDATION FLOOD ,
VENTS: MODELS #1640-620; #1540-521; #1640-610; #1540-
511; #1540-670; #1540-674;-#1640-624; #1540-614
FLOOD VENT SEALING KIT #16M-626
1.0 EVALUATION SCOPE
Compliance with the following codes:
■ 2018, 2015, 2012, 2009 and 2006 International Building
Code® (IBC)
■ 2018, 2015, 2012, 2009 and 2006 International
Residential Code® (IRC)
■ 20181nternational Energy Conservation Code® (IECC)
■ 2013 Abu Dhabi International Building Code (ADIBC)t
tThe ADIBC is based on the 2009 IBC. 2009 IBC code sections referenced
in this report are the same sections in the ADIBC.
Properties evaluated:
■ Physical operation
■ Water flow
2.0 USES
The Smart Vent® units are engineered mechanically
operated flood vents (FVs) employed to equalize
hydrostatic pressure on walls of enclosures subject to
rising or falling flood waters. Certain models also allow
natural ventilation.
3.0 DESCRIPTION
3.1 General:
When subjected .to rising water, the Smart Vent® FVs
internal floats are activated, then pivot open to allow flow in
either direction to equalize water level and hydrostatic
pressure from one side of the foundation to the other. The
FV pivoting door is normally held in the closed position by
a buoyant release device. When subjected to rising water,
the buoyant release device causes the unit to unlatch,
allowing the door to rotate out of the way and allow flow.
The water level stabilizes, equalizing the lateral forces.
Each unit is fabricated from stainless steel. Smart Vent®
Automatic Foundation Flood Vents are available in
various models and sizes as described in Table 1. The
SmartVENT® Stacking Model #1540-511 and FloodVENT®,
Stacking Model #1540-521 units each contain two
vertically arranged openings per unit.
3.2 Engineered Opening:
The FVs comply with the design principle noted in Section
2.7.2.2 and Section 2.7.3 of ASCE/SEI 24-14 [Section
2.6.2.2 of ASCE/SEI 24-05 (2012, 2009, 2006 IBC and
IRC)] for a maximum rate of rise and fall of 5.0 feet per
hour (0.423 mm/s). In order to comply with the engineered
opening requirement of ASCE/SEI 24, Smart Vent FVs
must be installed in accordance with Section 4.0. .
3.3 Ventilation:
The SmartVENT® Model #1540-51.0 and SmartVEN-14
Overhead Door Model #1540-514 both have screen covers
with 1/4-inch-by-1/4-inch (6.35 by 6.35 mm) openings,
yielding 51 square inches (32 903 mm2) of net free area to
supply natural ventilation. The SmartVENT® Stacking
Model #1540-511 consists of two Model #1540-510 units
in one assembly, and provides 102 square inches
(65 806 mm2) of net free area to supply natural ventilation.
Other FVs recognized in this report do not offer natural
ventilation.
3.4 Flood Vent Sealing Kit:
The Flood Vent Sealing Kit Model #1540-526 is used with
SmartVENT® Model- #1540-520. It is a Homasote 440
Sound Barrier® (ESR-1374) insert with 21 — 2-inch-by-2-
inch (51 mm x 51 mm).squares cut in it: See Figure 4.
4.0 DESIGN AND INSTALLATION
4.1 SmartVENT 0 and FloodVENT®:
SmartVENT® and FloodVENTO are designed to be
installed into walls or overhead doors of existing or new
construction from the exterior side. Installation of the
vents must be in accordance with the manufacturer's
instructions, the applicable code and this report.
Installation clips allow mounting in masonry and concrete
walls 'of any thickness:. In order to comply with the
engineered opening design principle noted in Section
2.7.2.2�,and 2.7.3 of ASCE/SEI 24-14 [Section 2.6.2.2 of
ASCE/SEI 24-05 (2012, 2009, 2006 IBC and IRC)], the
Smart Vent® FVs must be installed as follows:
■ With a minimum of two openings on different sides of
each enclosed area.
■ With a minimum of one FV for every 200 square
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as 1�1L t
to atty finding or other matter in this report, or as to any product covered by the report
Copyright 0 2019 ICC Evaluation Service, LLC. All rights reserved. Page 1 of.5
ESR-2074 1 Most Widely Accepted and Trusted
Page 2 of 5
feet (18.6 m2) of enclosed area, except that the
6.2
The Smart Vent® FVs must not be used in the place
SmartVENT Stacking Model #1540-511 I and
of "breakaway walls" in coastal high hazard areas, but
FloodVENT'2) Stacking Model #1540-521 must be
are permitted for use in conjunction with breakaway
installed with a minimum of one FV for !every
walls in other areas.
400 square feet (37.2 mz) of enclosed area. l
. ,
6.0
EVIDENCE SUBMITTED
:i
■ Below the base flood elevation.
' 6.1
Data in accordance with the ICC-ES Acceptance
■ With the bottom of the FV • located a maximum of
Criteria for Mechanically Operated Flood Vents
12 inches (305.4 mm) above the higher of they .final
(AC364); dated August 2015 (editorially revised
grade or floor and finished exterior grade immediately
October 2017):
under each opening.
6.2
Test report on air infiltration in accordance with ASTM
4.2 Flood Vent Sealing Kit
E283.
The Flood Vent Sealing Kit Model 1540-526 is used in
7.0
IDENTIFICATION
conjunction with FloodVENT Model #1540-520. When
7.1
The Smart VENT' models and the Flood Vent Sealing
installed and tested in accordance with ASTM E283, the
Kit recognized in this report must be identified by a
FV and Flood Vent Sealing Kit assembly have an air
leakage rate of less than 0.2 cubic feet minute
label bearing the manufacturer's name (Smarivent
per per
lineal foot (18.56 I/min per lineal meter) at.a pressure
Products, Inc.), the model number, and the evaluation
differential of 1 pound per square foot (50 Pa) based on
report number (ESR-2074).
12.58 lineal feet (3.8 lineal meters) contained by the Flood
7.2
The report holder's contact information is the
Vent Sealing Kit.
following:
5.0 CONDITIONS OF USE
SMART VENT PRODUCTS, INC.
®
The Smart Vent FVs described in this report comply,with,
430 ANDBRO DRIVE, UNIT 1
or are suitable alternatives to what is specified in, those
PITMAN, NEW JERSEY 08071
(877) 441-8368
codes listed in Section 1.0 of this report, subject to the :
following conditions:
www.smartvent.com
infoOsmartvent.com
5.1 The Smart Vent® FVs must be installed in accordance
with this report, the, applicable code and
the
manufacturer's installation instructions. In the event
of
a conflict, the instructions in.this report'govern.
TABLE 1—MODEL SIZES
MODEL NAME
MODEL NUMBER,
MODEL SIZE (in.)
COVERAGE (sq. ft.)
FloodVEN
1540-520
153/4" X 73/4"
200
SmartVENT®
1540-510
153/4' X 73/4"
200
FloodVENT' Overhead Door
1540-524 '
153/4' X 73/4"
200
SmartVENTO Overhead Door
1540-514
153/4' X 73/4"
200
Wood Wall FloodVENT®
1540-570
14" X 83/4' '
200
Wood Wall FloodVENT® Overhead Door
1540-574
14" X 83/4'
200
SmartVENT® Stacker
154.0-511
16" X 16"
400
FloodVent® Stacker
1540-521
16" X 16"
400
For SI: 1 inch = 25.4 mm; 1 square foot = 61'
FIGURE 1—SMART VENT: MODEL 1540-510
ESR-2074 I Most Widely Accepted and Trusted Page 3 of 5
FIGURE 2—SMART VENT MODEL 1540-520
FIGURE 3—SMART VENT: SHOWN WITH FLOOD DOOR PIVOTED OPEN
FIGURE 4—FLOOD VENT SEALING KIT
IMES Evaluation
ESR-2074 CBC and CRC Supplement
Reissued February 2019
This report is subject to, renewal February 2021.
wwmicc-es.org 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the International Code Council®
DIVISION: 08 00 00—OPENINGS
Section: 08 95 43—Vents/Foundation Flood Vents
REPORT HOLDER:
SMART VENT PRODUCTS, INC.
EVALUATION SUBJECT:
SMART VENT® AUTOMATIC FOUNDATION FLOOD:
570; #1540-674; #1540-624; 91640.614
FLOOD VENT SEALING KIT #1540-626
1.0 REPORT PURPOSE AND SCOPE
: MODELS #1540-620; #1540-521; #1.540-610; #1540-511; #1540-
Purpose:
i
The purpose of this evaluation report supplement is to indicate! that Smart Vent® Automatic Foundation Flood Vents,
recognized in ICC-ES master evaluation report ESR-2I 74, have also been evaluated for compliance with codes noted
below.
Applicable code edition:
■ 2016 California Building Code (CBC)
■ 2016 California Residential Code (CRC) i
2.0 CONCLUSIONS
2.1 CBC:
The Smart Vent® Automatic Foundation Flood Vents, described in Sections 2.0 through 7.0 of the master evaluation report
ESR-2074, comply with' 2016 CBC Chapter 12, provided the design and installation are in accordance with the 2015
International Building Code . (IBC) provisions noted in tl%e master report and the additional requirements of CBC Chapters
12, 16 and 16A, as applicable.
The products recognized in this supplement have not been evaluated under CBC Chapter 7A for use in the exterior design
and construction of new buildings located in any Fire I Hazard Severity Zone within State Responsibility Areas or any
Wildland-Urban Interface Fire Area. I
2.2 CRC:
The Smart Vent® Automatic Foundation Flood Vents, described in Sections 2.0 through 7.0 of the master evaluation report
ESR-2074, comp with the 2016 CRC, provided the design and installation are in accordance with the 2015 International
Residential Code (IRC) provisions noted in the master report.
The products recognized in this supplement have noti,been evaluated under 2016 CRC Chapter R337, for use in the
exterior design and construction of new buildings located in any Fire Hazard Severity Zone within State Responsibility Areas
or any Wildland-Urban Interface Fire Area.
The products recognized in this supplement have not been evaluated for compliance with the International Wildland=Urban
Interface Code®. I -
This supplement expires concurrently with the master report! reissued February 2019.
I '
1 ,
ICC-ES Evaluation Repairs are not to be construed as representing aesthetics or any otherattributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as :ice
to anyfinding or other matter in this report, or as to any product covered by the repori ��¢ ^-
Copyright © 2019 ]CC Evaluation Service, LLC. All rights reserved. I Page 4 of 5
0
IMES Evaluation Report ESR-2074 FBC Supplement
Reissued February 2019
This report is subject to renewal February 2021.
www.icc-es.ora (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council°
DIVISION: 08 00 00—OPENINGS
Section: 08 95 43—Vents/Foundation Flood Vents
REPORT HOLDER:
SMART VENT PRODUCTS, INC.
EVALUATION SUBJECT:
SMART VENT' AUTOMATIC FOUNDATION FLOOD VENTS: MODELS #1540.620; #1540-621; #1540-610; #1540-611;
#1640.670; #1540-574; #1540-624; #1540-614
FLOOD VENT SEALING KIT #1640-626,
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that Smart Vent® Automatic Foundation Flood Vents, recognized
in ICC-ES master report ESR-2074, have also been evaluated for compliance with the codes noted below.
Applicable code editions:
■ 2017 Florida Building Code —Building
■ 2017 Florida Building Code —Residential
2.0 CONCLUSIONS
The Smart Vent® Automatic Foundation Flood Vents, described in Sections 2.0 through 7.0 of the master evaluation report
ESR-2074, comply with the Florida Building Code —Building and the FRC, provided the design and installation are in
accordance with the 2015 International Building Code® provisions noted in the master report.
Use of the Smart Vent® Automatic Foundation Flood Vents has also been found to be in compliance with the High -Velocity
Hurricane Zone provisions of the Florida Building Code —Building and the Florida Building Code —Residential.
For products falling under Florida Rule 9N-3, verification that the report holder's quality assurance program is audited by a
quality assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the
responsibility of an approved validation entity (or the code official when the report holder does not, possess an approval by
the Commission).
This supplement expires concurrently with the master report, reissued February 2019.
IqC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its fuse. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report. .11, MIA
�.
Copyright © 2019 ICC Evaluation Service, LLC. All rights reserved. Page 6 of 5