UES Project No.: 0310.1700251.0010
Date Typed: May 04, 2018
SCANNED
BY r
Construction Materials Testing Services F
FIELD AND LABORATORY REPORT COVER PAGE
Client: Ryan Homes RECEIVED
1450 Centrepark Blvd Suite 340 JUL 3
West Palm Beach, FL 33401 2018
Project: Oakland Lake Subdivision Lot 70 ST- WOO County, Permitting
,Fort Pierce, St. Lucie County, —FT-
As requested, Universal Engineering Sciences, Inc. (UES representatives) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No.
Date
I Type of Report
96108-1 1
04/23/2018
In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate 'needs. If you have any questions, please do not hesitate to contact
the undersigned.
Sincerely,
Universal Engineerip 'Sq ences, Inc.
Certificate of Authorization No. 00000549 .
1 4
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
I
This item has been electronically signed and sealed by
Richard E. Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verified on any electronic
copies.
I
ICC Email: cbugg@nvrinc.com; elibrihi@nvrinc.com; jomcalli@nvrinc.com; sign adn seal to ryan homes
I
i
U, s"Project No: 0310.1700251.0010
UNIVERSAL UES DOCS No:
UES Report No: 96108-1 ARC 042318
ENGINEERING SCIENCES On -Site Time (hrs): 0.50
Consultants In: GeotechnicalEngineeiing • Envir nmental Sciences Lab Time (hrs): 0.00
Geophysical Services • (Materials Testing Thr shold Inspection. Travel Time (hrs): 0.25
Building Code Administration, Compliance Inspe Lion & Plan Review Total Time (hrs): 0.75
820 Brevard Avenue, Rockledge, FL 32966 - P: 321. 38.0808 - F: 321.638.0978
Client: Ryan Homes
1450 Centrepark Blvd Suite 34C
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 7
,Fort Pierce, St. Lucie County, F
Date of Activity: Monday, 23 April, 2018
Technician: Cliff Cherrnay
As requested, a Universal Engineering Sciences Technici
earthwork testing for the House pad.
While on site, the technician observed the general condith
pad. All test(s) were performed in accordance with the AS
project compaction requirements of 95% of the maximum
n was present at the above referenced project site for the purpose of
of the areas to be tested and performed 4 density test(s) for House
I D-6938 Nuclear Gauge Method and were found to meet the
density per ASTM D-1557.
The Contractor was notified of the test results or a copy Was left for their records.
i
UNIVERSAL
NdENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Thr9shold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32956 - P: 321.638.0808 - F: 321.638.0978
Client:
Project:
Area Tested:
Type of Test:
Technician:
Requirements:
Ryan Homes 1
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Oakland Lake Subdivision Lot 70
,Fort Pierce, St. Lucie County, FL
House pad
Field: ASTM D-6938 Nuclear Gauge Method
Lab: ASTM D1557 Modified Proctor
Cliff Cherrnay
UES Project No: 0310.1700251.0010
UES DOCS No:
UES Report No: 96108-1 DT 042318
Date of Test: 04/23/2018
95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underlvino soils below the tested depths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1
N/W Test
0-1 ft
12.00
21235
113.5
12.0
98
A
2
WE Test
0-1 ft
12.00
21235
112.5
10.6
97
A
3
S/E Test
0-1 ft
I
12.00
21235
114.4
11.6
99
A
4
S/W Test
0-1 ft
12.00
21235
111.6
12.2
96
A
(1) Ref. Datum: 0 = Top of Native
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21235
116.0
10.0
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This test was performed without deviation from ASTM procedures.
I
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
-n
r
�_- V
UN'IVER
ENGINEERING SI
Consultants In: Geotechnical Engineering • Ei
Geophysical Services • Materials -Testing •
Building Code Administration, Compliance In:
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0
Construction
FIELD AND LABOI
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 70
,Fort Pierce, St. Lucie County, FL
As requested, Universal Engineering Sciences, Inc. (U
field inspection services on the above project. Testing
sheets. The contents of this package are summarized
PAL
ENCES
nmental Sciences
shold Inspection
ion & Plan Review
- F: 321.638.0978
r
UES Project No.: 0310.1700251.0010
Date Typed: May 04, 2018
rials Testing Services
RY REPORT COVER PAGE
LRECEIVED-__
JUN 2 0 2018Lucie County, Permitting
representative(s) performed construction materials testing and/or
As and/or inspection observations are reported on the attached
Scope of Work
Work Order No. I Date I iType of Report
96108-1 1 04/23/2018 In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
Sincerely,
Universal Engineering Sciences, Inc.
Certificate of Aelthorization No.- 00000549
Y , a i� . A
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
This item has been electronically signed and sealed by
Richard E. Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verifred on any electronic
copies.
ICC Email: cbugg@nvrinc.com; elibdhi@nvrinc.com; jomcalli@nvrinc.com; sign adn seal to ryan homes
0
I
UNIVER
UES Project No: 0310.1700251.0010
SAL
UES DOCS No: UES Report No: 96108- 1 ARC 042318
ENGINEERING SCIENCES On -Site Time (hrs): 0.60
Consultants In: Geotechnical Engineering • Envirpnmental Sciences Lab Time (hrs): 0.00
Geophysical Services • Materials Testing • Thrgshold Inspection Travel Time (hrs): 0.25
Building Code Administration, Compliance Inspection & Plari Review Total Time (hrs): 0.76
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Client: Ryan Homes
1450 Centrepark Blvd Suite 340I
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 7(
,Fort Pierce, St. Lucie County, FI
Date of Activity: Monday, 23 April, 2018
Technician: Cliff Cherrnay
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the House pad.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for -House
pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
r
i
i
lJ N l V� E R S A L UES DOCS Noo: 0310.1700251.0010
ENGINEERING SCIENCES UES Report No: 96108-1 DT042318
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical. Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32966 - P: 321.638.0808 - F: 321.638.0978
Client:
Project:
Area Tested:
Type of Test:
Technician:
Requirements:
Ryan Homes
1450 Centrepark Blvd Suite �340
West Palm Beach, FL 33401II
Oakland Lake Subdivision Lbt 70
,Fort Pierce, St. Lucie County, FL
House pad
Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 04/23/2018
Lab: ASTM D1557 Modifield Proctor
Cliff Cherrnay
95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underlyinq soils below the tested depths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1
NNV Test
0-1 ft
12.60
21235
113.5
12.0
98
A
2
WE Test
0-1 ft
12.00
I
1
21235
112.5
10.6
97
A
3
S/E Test
0-1 ft
12.00
21235
114.4
11.6
99
A
4
SNV Test
0-1 ft
12.00
21235
111.6
12.2
96
A
(1) Ref. Datum: 0 = Top of Native
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21235
116.0
10.0
This test was performed without deviation from ASTM procedures.
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.