HomeMy WebLinkAboutFLOOR PLANREVISIONS I BY PLUMBING GENERAL NOTES 1. ALL WORK TO BE DONE IN ACCORDANCE WITH THE LOCAL PLUMBING AND BUILDING CODES. 2. BUILDING DRAINAGE SYSTEM DESIGN BASED ON 1/8'/FT MINIMUM FALL; ANY DEVIATIONS SHALL BE APPROVED BY ARCHITECT & ENGINEER. 3. CONTRACTOR TO PROVIDE 1" (MIN.) WATER PIPE CAPPED AT EVERY ELECTRICAL SWITCHGEAR ROOM OR METER ROOM TO BE USED AS GROUND. 4. ALL VALVES UNDERGROUND TO BE INSTALLED IN PRECAST CONCRETE BOXES, BROOKS OR EQUAL 5. PLUMBING CONTRACTOR TO FURNISH ALL REQUIRED FLASHINGS FOR PIPES TO ROOFING CONTRACTOR, 6. MATERIALS SHALL BE ALL NEW AND AS FOLLOWS: A) DRAINAGE PIPING - NO HUB CAST IRON STD. 30f OR PVC SCH. 40 B) WATER PIPING - SCH. 40 PVC (UNDERGROUND), COPPER TUBE TYPE L (INTERIOR) C) A/C CONDENSATE DRAIN - SCH. 40 PVC OR COPPER TYPE OC IN CEILING PLENUM. D) FLOOR AND ROOF DRAINS IF USED. JOSAM OR EQUAL E) VALVES - 125 PSI NIBCO 5COTT OR EQUAL F) HOSE BIBBS - JOSAM 7105, OR EQUAL G) A/C CONDENSATE DRAIN INSULATION - 1/2" ARMAFLEX. (') NO PVC PIPE IN COUNG SPACE R/A PLENUM, 7. PROVIDE ALL EXCAVATION BACKFlLL AND COMPACTION REQUIRED BY ALL PLUMBING WORK. 8. PERFORM THE FOLLOWING TESTS: A) WATER PIPING SHALL BE SUBJECTED TO HYDROSTATIC PRESSURE TEST OF 100 PSIG FOR A PERIOD OF TIME SUFFICIENT TO EXAMINE ENTIRE SYSTEM BUT NOT LESS THAN ONE HOUR. 8) DRAINAGE PIPING - BEFORE INSTALLATION OF ANY DRAINS, THE ENDS OF THE SYSTEM SHALL BE CAPPED AND ALL ONES FlL1.ED WITH WATER TO HIGHEST POINT AND ALLOWED TO STAND UNTIL INSPECTION is MADE AND WATER LEVEL REMAINS CONSTANT. C) CORRECT ALL DEFECTS DISCLOSED BY ABOVE TESTS. 9. STERILIZE ALL WATER LINES WITH MIXTURE OF (2) TWO POUNDS OF CHLORINATED UME TO EACH 1000 GALLONS OF WATER (50 RPM OF i AVAILABLE CHLORINE). RETAIN MIXTURE IN PIPES 24 HOURS AND Fl_U5H THOROUGHLY WITH POTABLE WATER BEFORE PLACING IN SERVICE. 10. COMPLETE SYSTEM FIXTURES AND EQUIPMENT SHALL BE GIVEN AN IN- SERVICE TEST AFTER COMPLETION OF THE INSTALLATION. 11. PLUMBING CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE THAT ALL PLUMBING WORK SHALL BE FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE, AND THAT HE WILL, AT HIS EXPENSE REPAIR AND REPLACE ALL WORK WHICH BECOMES DEFECTIVE DURING GUARANTEE PERIOD. W SANITARY PIPING ISOMETRIC ACCESSIBILITY NOTES 1. RAMPSL SHALL HAVE A MAXIMUM SLOPE OF 1:12 2. GjLL!>,tSE;A�FI SFIARSS: SHALL BE LOCATED 33" FROM AND PARALLEL TO FLOOR, MEASURED VERTICALLY TO THE TOP THE OF RAIL. SHALL HAVE A OUTSIDE DIAMETER OF 1 1/2 SHALL PROVIDE 1 1/2" OF CLEARANCE BETWEEN THE RAIL AND THE WALL . SHALL SUPPORT A LOAD OFF 250 Ibs. APPLIED AT ANY POINT DOWNWARD OR HORIZONTALLY. SHALL BE CONTINUOUSLY GRASPABLE ALONG THE ENTIRE LENGTH. 3. NOT USED 4. WATER CLOSETS' SHALL COMPLY WITH THE HANDICAP CODE, SEAT HEIGHT SHALL BE AT A HEIGHT OF NO LESS THAN 17" AND NO MORE THAN 19" MEASURED VERTICALLY FROM THE FINISHED FLOOR TO THE TOP Of THE SEAT. 5. TOI_ET PAEE DISPR SHALL COMPLY WITH THE HANDICAP CODE AND BE MOUNTED 194 9 ABOVE FINISH FLOOR. 6. LAVATORIES: SHALL HAVE LEVER -OPERATED FAUCETS AND NARROW APRONS (5" MAX) WHICH, WHEN AT A MAX HEIGHT OF 34" MEASURED VERTICALLY FROM THE FLOOR TO THE TOP OF THE APRON, ALLOWS FOR THE USE OF THE LAVATORY BY A PERSON IN A WHEELCHAIR. 7. SINKS SHALL BE MOUNTED WITH THE COUNTER OR RIM NO HIGHER THAN 34" FROM THE FLOOR. EACH SINK SHALL BE A MAXIMUM OF 6 1/2" DEEP. 8. HOT WATER AND DRAIN PIPES c UNDER LAVATORIES OR SINKS SHAL BE INSULATED ` OR OTHERWISE PROTECTED. 9. MIRRORS, SHALL BE MOUNTED WITH THE BOTTOM EDGE OF THE REFLECTING SURFACE NO HIGHER THAN 40" FROM THE FLOOR. 10. TOWEL DISPENSERS• SHALL BE LOCATED ADJACENT TO ACCESSIBLE LAVATORIES & AT LEAST ONE TOWELS DISPENSER SHALL BE LOCATED WITHIN THE HANDICAPED TOILET STALL OR HANDICAP TOILET ROOM. 11. SIGNS: PROVIDE A LAMINATED PLASTIC GENDER I & HANDICAP SIGN AT ALL RESTROOMS 4" Con'1 43�0" W 41�Cb�G W 4 NE PLUMBING , IXTURES q DEMO PLUMBING ,BY LIC PLUMBERCF O I c c o 0,G 0, 0, /0/F PLUMBI!ING PLAN: � G I d ,400' 3- 5 60rS _ I L by O ,,f ° f ,_ lino I 1 - k G. 2oc9`-- I UNIT 4 3,2o s UNIT 31 G O G C 1i C C,C / v r d I pROPOS D REDET yF - T L� iT_15 M o,o..ry c'oe ti T 272 o Heooe Tyv _ Phase l Phone // - c� 5� mood PLOT PLAN: SCALE 1"=301 ft. u z_ z � 0 m � TOILET PAPER DISPENSER SCANN 6 BY St Lucie COU* copy ILE [`4 1.rIvt lo`I THESE PLANS AND ALL PROPOSED WOE AND SUBJECT AW ( REQUIRED BY FIIEELD INSPECTORS THAT MAY BE NECESSARY IN ORDER TO 1 COMPLY WITH ALL APPLICABLE CODES. 1 i NOTE: SCOPE OF WORK: A. DEMOLITION TO EXISTING BATHROOM AND THE REMOVAL OF EXISTING FIXTURES. LIC. PLUMBER SHALL TERMINATE ALL WATER AND WASTE WATER LINES. B. REMOVE EXISTING INTERIOR BATHROOM WALLS, DOORS . AND ANY ATTACHED SHELVING OR COUNTERS. C. REMOVAL OF EXISTING CONTRETE FOR NEW PLUMBING FIXTURES AS SHOWN ON FLOOR PLAN. D. INSTALL NEW FRAME WALLS FOR NEW HANDICAP BATH ROOMS. DRYWALL BOTH SIDES AND FINISH WITH TILE WALLS OR FRP PANELING. E. PROVIDE NEW 100A PANEL FOR REMODEL AND FUTURE100A PANEL FOR TENANT SEPARATION. F. NOTE: EXISTING HVAC TO REMAIN AND DUCK LAYOUT. THE BATHROOM DUCKS REMOVED FOR DEMOLITION SHALL BE RE=USED IN NEW BATHS. WORK SHALL BE DONE BY LIC. AC CONTRACTOR. NOTE: PLANS HAVE BEEN DESIGNED TO MEET FBC 2007 AND ADOPTED 2009 REVISIONS. ALL ELECTRICAL SHALL MEET 2008 NEC. THE CONTRACTOR, SUB -CONTRACTOR, SUPPLIER, ETC. SHALL VERIFY ALL DIMENSIONS, CONDITIONS AT JOBSITE, PLANS & SPECIFICATIONS ETC. 5'10" 12' MAX 54" MIN 42" MI a0 AC— z — m / VT-10 i VB— z 42" GRABIBAR 1 1 36' GRAB BAR d' 5"MIN G FLR UNTED WC� FRON1 II)Erv: CN ZINCi. 4i„ 5,0„ 4_2 L 10 0 a[[7ei 100A PANEL EXISTS -a a �3 3 I WW �U a ��z H w H U H x Iw F EXISTING OFFICES X I W 3068DR EXIST c a 43'0" 5110" 6' 5'10" e_ wC sty 3068D AC 30 8DR l V AC I Illllllllll III NEW 100A PANEL io r� 3068DR� 10 i I---lvll i I� II II lUDEM II DEMO BATHORM. BATH RM. I PROPOSED: CONFERENCE OR CLASS RM- COUNTER OR TABLE (ADA) FLOOR PLAN: SCALE 1/4" = 1 FT. EXISTING CBS WALLS INTERIOR WALLS DEMO. NEW INTERIOR WALLS EXISTING INTERIOR WALLS 1313" r3068DR 'E){asT 058DR EXIST >YP. BOARD WALL TALL TILE OR FRP TOWEL DISPENSED LOCATE CONTROL VALVE ON WIDE SIDE OF TOILET PER A.D.A. 36' LONG GRAB BAR, 42" LONG GRAB BAR PAPER HOLDER 4" VINYL COVE BASE — U a O u W 0 z o� =w > U :d —z H y = E+ to r M W � I � Po N 2 AM 00 >— J_ o r LU O n ~ LL LU W LL 0 w 2cc J1- N 'n y 0 N m (L C WN V Uj O � a� J A y W O m 1• � 0 W i W a .. O W W t!1 O Q-I a as ® we Date PAUL WELCH INC. MECHANICAL * ELECTRICAL " CIVIL ENGINEERING Scale 1 984 S.W. BILTMORE ST. - SUITE #1 14 0 PORT ST. LUCIE, FL 34984 Drawn / PHONE E-MAIL FAx Job (772) 785.988B PWELCHINCPAOL.COM (772) 7BS-9933 Sheet OCT Q 1 2009 Of 2 Sheets REVI£ r- 120/240VAC 1phase 3wire PANEL UNIT- 4 Ckt Pole Tri Remarks emarks Tri Pole Clot 1 1 20 Lighting 4iiecepta tin 15 1 2 3 1 15 Receptacles cles 20 1 4 5 1 20 Receptacles Receptacles 20 1 6 7 2 60 A.H.U. COMP 30 2 8 9 A.H.U. COMP 110 ll 1 12 Phase 1 Total hase 2 Total 28000 24000 PANEL UNIT_ 120/240VAC 1phase 31xire Ckt Pole Trip Remarks Remarks Trip Pole Ckt 1 1 20 Ligting Lighting 20 1 21 3 1 20 Lighting Receptacles 20 1 4 5 1 20 Rece tacles Receptacles 20 1 16 '7 2 60 A.H.U. COMP 30 2 8 g 1A.H.Tj. COMP 10 11 12 'Phase 1 Total iPhase 2 Total 25000 i22000 VYISTING DRYWALL CEILING NOTE: 2x4 WD STUD WALL INTERIOR W/ 2x6 BETWEEN BATHS. (5/8"TYP X DRYWALL TO BE USED) OPT> STEEL STUDS NOTE: 1/2 DRYWALL MAYBE USED FOR INTERIOR WALLS (EXCEPT BETWEEN BATHROOMS TYP-X 5/8" REO.I 2x4 PT PLATE W/1/4" TAPCONS 16"OC MIN. 3" EMBEDMENT \ i STUDA @ 24"OC MIN. NOTE EXISTIIG CIONC SLAB (TYP) WALL SECTION: ELECTRICAL LOAD CAL'S. UNIT- 3 LIGHTING: 780 SQUARE FEF,'T @ l .l WATT/SQ. FT. = 858.OV/A l EXTERIOR LIGHT @ 60V/A = 60 V/A I- SIGN @ 120 V/A = 120 V/A SUB TOTAL....................................1038.0 V/A OUTLETS; 14 OUTLETS @ 180 V/A EACH = 2520.0 EACH @ 100% = 2520.0 SUB- TOTAL....................................2520.0 V/A H.V.A.C.: I- HEAT STRIP @ IOKW = 10,000 V/A SUB TONAL .......... ....................... 10,000.0 V/A MISC: ( PROVISIONAL WATER HEATER= 7200.0 V/A SUB -TOTALS: 20,758 V/A 20,758 / 240- 1 0 = 86.49 AMPS. NEW MIN. 100A PANEL INSTALLED (RISER EXISTS) EXISTING HVAC W/ DISC. SW ELECTRICAL LOAD CAL'S. UNIT- 4 LIGHTING: 780 SQUARE FEET @ 1.1 WATT/SQ. FT. = 858.OV/A 1 EXTERIOR LIGHT @ 60V/A= 60 V/A 1- SIGN @ 120 V/A = 120 V/A SUB TOTAL....................................1038.0 V/A OUTLETS; 12 OUTLETS @ 180 V/A EACH = 2160.0 V/A EACH @ 100% = 2160.0 V/A SUB- TOTAL....................................2160.0 V/A H.V.A.C.: 1- HEAT STRIP @ IOKW = 10,000 V/A SUB TOTAL.................................10,000.0 V/A III I SC: ( PROVISIONAL WATER HEATER= 7200.0 V/A SUB- TOTALS: 2%338 VIA 20,398 / 240- 1 0 = 84.99 AMPS. NEW MIN. 100A PANEL INSTALLED (RISER EXISTS) EXISTING HVAC W/DISC SW. ELECTRICAL PLANE SCALE 1/4" = 1 FT. ELECTWCAL NOTES: 1 — ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL LOCAL CODES AND ORDINANCES. INSTALLATION SHALL COMPLY WITH THE NATIONAL ELECTRICAL. CODE AND OSHA REGULATIONS. 2 — CONTRACTOR SHALL GUARANTEE THE ENTIRE ELECTRICAL WOR, INCLUDING PARTS AND LABOR, FOR A PERIOD OF ONE (1) YEAR AFTER FINAL WRMTT-EN ACCEPTANCE BY OWNER. 3 — GLITTERS, WIREWAYS, PULLBOXES, ETC. SHALL BE SIZED PER NATIONAL ELECTRICAL CODE. 4 — THIS CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTION, TESTS, FINES, ETC., AS REQUIRED. 5 — ALL WORK SHALL BE PERFORMED BY A UCENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS MANNER AND SHALL BE COMPLETED AND FULLY OPERATNE TO THE ACCEPTANCE OF THE OWNER AND ENGINEER. 6 — VISIT PROJECT SITE FOR FAMILIARIZATION AND VERIFY EXACT LOCATION OF POWER AND TELEPHONE SERVICES WITH UTILITY COMPANY REPRESENTATIVES. NOTIFY ENGINEER OF ANY CONFLICTS. 7 — THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHER TRADES AS WELL AS PROVIDING TEMPORARY POWER AT PROJECT SITE FOR ALL TRADES. 8 — ALL MATERIALS SHALL BE NEW OF AMERICAN MANUFACTURE AND BEAR THE UNDERWRITERS LABORATORY AND UNION LABELS AS APPLICABLE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE DELIVERY SCHEDULE OF MATERIALS. 9 — ALL EQUIPMENT INSTALLED SHALL BE OF MANUFACTURE AND TYPE SPECIFIED: ANY OTHERS SHALL HAVE THE ENGINEER'S PRIOR APPROVAL PROVIDE SIX SETS OF SHOP DRAWINGS. 10 — VERIFY EXACT LOCATION OF ALL OUTLETS WITH ARCHITECTURAL DRAWINGS AND WITH'THE OWNER. 11 — CORRECTION OF ANY DEFECTS, REPAIR OF DAMAGE DURING CONSTRUCTION AS WELL A5 ANY MINOR CHANGES IN OUTLET LOCATIONS SHALL BE MADE WITHOUT ADDITIONAL COST. 12 — VERIFY EQUIPMENT SIZES, VOLTAGE AND CURRENT CHARACTERISTICS, ETC., BEFORE ORDERING ANY EQUIPMENT AND BEFORE ROUGHING —IN FOR EQUIPMENT TO BE SUPPLED BY OTHERS. NOTIFY ENGINEER OF ANY CONFI-ICTS, 13 — CIRCUITS INDICATED ON PLANS ARE DIAGRAMATIC; ROUTE AND COMBINE FOR BEST CONCEALMENT AND VERIFY EXACT WALL CONSTRUCTION AND STRUCTURE BEFORE INSTALLATION. 14 — UNLESS OTHERWISE NOTED, MINIMUM BRANCH CIRCUIT WIRE SHALL BE NO. 12 AWG; NO. 10 AWG AND SMALLER SHALL BE SOLD COPPER WITH TW OR THWN INSULATION; NO. 8 AWG AND LARGER SHALL BE STRANDED COPPER WITH THW OR THWN INSULATION. GROUNDING SHALL. BE PER N.E.C. ART. 250. 15 — ALL WIRING SHALL BE IN RACEWAY, AS- FOLLOWS-. A) UNDERGROUND OR IN GROUND FLOOK SLAB OR CAST IN CONCRETE ABOVE GROUND PVC SCH. 40 WITH GREEN BOND WIRE; OR, ASPHALT —COATED RIGID GALV. STEEL. B) INTERIOR WORK -- EMT. C) EXPOSED OUTSIDE — RIGID GALVANIZED STEEL D) CONNEC— TIONS TO EQUIPMENT — FLEXIBLE CONDUIT, LIQUID —TIGHT IN WET LOCATIONS. 16 — PROVIDE NO. 16 AWG PULL WIRES IN ALL EMPTY CONDUITS FOR FUTURE USE. 17 — FURNISH AND INSTALL HEAVY—DUTY DISCONNECT SWITCHES AND MOTOR STARTERS AS, SHOWN AND AS REQUIRED FOR EQUIPMENT FURNISHED BY OTHERS. FUSES SHALL BE DUAL ELEMENT, TIME DELAY. 18 -- PROVIDE ACCURATELY TYPED PANEL DIRECTORIES. PROVIDE AND INSTAL_ PLASTIC TAPE LABELS FOR ALL ELECTRICAL DISTRIBUTION DEVICES SUCH AS PANELS, DISCONNECT SWITCHES, GUTTERS„ ETC.; INDICATING DEVICE NAME, VOLTAGE, PHASE, ETC. 19 — ALL TELEPHONE OUTLETS SHALL BE CONNECTED WITH MINIMUM OF 3/4" RACEWAY. 20 — WIRING DEVICE PLATES IN FINISHED AREAS SHALL BE OF PHENOLIC COMPOUND WITH POLISHED FINISH. WIRING DEVICE PLATES IN UNFINISHED AREAS SHALL BE GALVANIZED STEEL WITH ROUNDED CORNERS FOR SURFACE MOUNTED BOXES. 21 — ALL BALLASTS SHALL BE INDIVIDUALLY FUSED. ALL FLUORESCENT RALIASTS ARID LAMPS SHALL BE ENERGY —SAVING TYPE. PLANS AND ALL PROPOSED WORK SUBJECT TO ANY CORRECTIONS UIRED BY FIELD INSPECTORS THAT kY BE NECESSARY IN ORDER TO PLY WITH ALL APPLICABLE CODES. d d o i� I0.074.0' ?O. 0' 24I0 t5 < � Bldg, Hgf 10 o,...--- !�-O� T P ca l If , 1w NOTE: PLANS HAVE BEEN DESIGNED TO MEET FBC 2007 AND ADOPTED 2009 REVISIONS. ALL ELECTRICAL SHALL MEET 2008 NEC. THE CONTRACTOR, SUB -CONTRACTOR, SUPPLIER, ETC. SHALL VERIFY ALL DIMENSIONS, CONDITIONS AT JOBSITE, PLANS & SPECIFICATIONS ETC. PAUL WELCH INC. MECHANICAL * ELECTRICAL * CIVIL ENGINEERING 1 984 S.W. BILTMORE ST. - SUITE #1 14 PORT ST. LUCIE, FL 34984 PHONE E-MAIL FAX (772) 785-9886 PWELCHINCPAOL COM (772) 7195-9933 OCT 01 2009