HomeMy WebLinkAboutTO BE REVIEW-REVIEW COMMENTS�ttfit� �flttt2� ~�
OO �
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue.
Fort Pierce, FL. 34982
Phone:(772)462-2172 Fax:(772)462.6443
SCANNED
BY
St Lucie COUI
REVIEW COMMENTS
Page 1
PROPERTY INFORMATION
Address: 7601 S Ocean Dr Wastewater Plant Owner(s):
St Lucie County
City / State / Zip: Jensen Beach, FI 34957
- Parcel #: 3522-312-0003-000/1 Jurisdiction: SAINT LUCIE COUNTY
Zoning: U Lot#: Block:
APPLICATION INFORMATION
Permit Number: 1805-0116 Stories: Automatic Sprinkler System? No
i
Permit Type: GAS PIPING COMMERCIAL (INCLUD GENERATORS
CONTRACTOR INFORMATION
t
Contractor Name: Curtis L Evans �� \ Fax Number: 352-241-9753
I
Business Name: Envirosafe Enterprises Inc W�
I Business Addr: 1789 East County Rd 48 f� Email: Curtis@ Envirosafetanks.Com
City / State / Zip: Bushnell, FI 33513
REVIEWS AND COMMENTS
Review Type Status Reviewed B Date Started Date Completed Date Released
FIRE DEPARTMENT REVIEW PENDING Tony Jergerl
Comment:
FRONT COUNTER REVIEW COMPLETE Deanna Givens 18 5/3/2018 5/3/2018
I
Comment:
' PLANS EXINER ELECT 1C PE DING �til(fa'(ter Pn`de y
-
Comment: '' C
PLANS EXAMINER REVIEW INCOMPLETE Joe Cicio I /4/2018
I
5/4/2018 Comment: WIND SPEED AND EXPOSURE NOT LEGIBLE ON PLANS * ENGINEER TO DESIGN TO 175 M.P.H. WIND
SPEED [ RISK III ] AND EXPOSURE DI* FBC 1609 AND 1609.4.3
Comment: ENGINEER TO REMOVE ALL UN -NECESSARY NOTES UNDER [ GENERAL REQUIREMENTS ] FROM PLANS
AND CERTIFY THE EXISTING SLAB / FOOTING THAT THIS TANK IS BEING PLACED UPON *** ENGINEER TO
5/4/2018 DESIGN THE TANK TO THE FFPC 66.211.3.4 * WHERE A TANK IS SUBJECT TO FLOODING PROVISIONS
SHALL BE TAKEN TO PREVENT TANKS EITHER FULL OR EMPTY FROM FLOATING DURING A RISE IN
WATER LEVEL UP TO THE ESTABLISHED MINIMUM FLOOD STAGE OR DESIGN FOR ABOVE THE DFE
I
5/4/2018 Comment: SUBMIT [ 3 ] ST LUCIE COUNTY " CERTIFICATION FOR DESIGN LOAD COMPLIANCE " SHEETS WITH
ORIGINAL SIGNATURE, SEAL AND DATE FROM ENGINEER
5/4/2018 Comment: SUBMIT IN TRIPLICATE THE MANUFACTURERS SPECIFICATIONS FOR THE FUEL TANK AND DISPENSORS
FOR REVIEW [ HOW MANY DISPENSORS ] SIZE OF TANK ETC
5/4/2018 Comment: SUBMIT AN ORIGINAL FLOOD ELEVATION CERTIFICATE TO DETERMINE THE FLOOD ZONE AND REQUIRED
ELEVATION OF TANK SYSTEM *
5/4/2018 Comment: ENGINEER TO ALSO DESIGN FOR IMPACT AND FATIGUE ON THE STRUCTURE * SEE FBC 1607.7.4 AND
1607.7.4.1
5/4/2018 Comment: DESIGN FOR VEHICLE IMPACT LOADS PER FBC 1607.9
I