HomeMy WebLinkAboutSLAB PLAN1. GENERAL REQUIREMENTS
1.1 DESIGN
CODE:
1.
TO THE BEST OF THE DESIGN PROFESSIONALS KNOWLEDGE, THESE
DOCUMENTS HAVE BEEN PREPARED WITH AND ARE IN COMPLIANCE WITH THE
APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS AS
DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE CHAPTERS 553 AND 633 OF THE FLORIDA
STATUES. THESE DOCUMENTS MEET OR EXCEED THE REQUIREMENTS OF:
THE FLORIDA BUILDING CODE - BUILDING, 6TH EDITION (2017)
1.2 DESIGN CRITERIA:
1.
REFERENCE STANDARDS
A. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH AMERICAN CONCRETE
INSTITUTE (ACI)318 AND 332.
B. REINFORCING STEEL SHALL BE IN ACCORDANCE WITH ACI 318
1.3 DESIGN
LOADS
1.
BUILDING RISK CATEGORY: III
2,
WIND SPEED PER ASCE 7-10: I 159 MPH - ULTIMATE DESIGN
WIND SPEED
3.
WIND SPEED PER ASCE 7 10: 1®S MPH - NOMINAL DESIGN
WIND SPEED
4.
EXPOSURE: B
1.5 GENERAL:
1,
CONTRACTOR AND SUB -CONTRACTORS SHALL STRICTLY OBSERVE ALL APPLICABLE CODES
DURING THE COURSE OF CONSTRUCTION INCLUDING ALL STATE, CITY, AND COUNTY
BUILDING, ZONING, ELECTRICAL, MECHANICAL, PLUMBING AND FIRE CODES. CONTRACTOR
SHALL VERIFY ALL CODE REQUIREMENTS PRIOR TO COMMENCEMENT OF WORK.
2.
CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD AND SHALL NOTIFY THE DESIGN
PROFESSIONAL OF RECORD OF ANY DISCREPANCY PRIOR TO CONSTRUCTION.
3.
THE ARCHITECT / ENGINEER SHALL NOT BE RESPONSIBLE FOR SAFETY PROCEDURES,
THE MEANS AND METHODS OF CONSTRUCTION, TECHNOLOGIES, OR THE FAILURE OF THE
CONTRACTOR TO CARRY OUT THE WORK IN ACCORDANCE WITH THE DRAWINGS AND
SPECIFICATIONS OR THE RELATED CODES.
4.
CONTRACTOR SHALL FULLY REVIEW ALL ITEMS CONTAINED IN THE DRAWING AND SHALL
COORDINATE ALL DIMENSIONS, LOCATE DEPRESSED SLABS, SLOPES, DRAINS, OUTLETS,
RECESSES, BOLT SETTINGS, SLEEVES, ETC.
5.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE THE ERECTION PROCEDURE
AND SEQUENCING.
6.
UNLESS OTHERWISE NOTED ON THE DRAWINGS, ALL CONSTRUCTION SHALL COMPLY WITH
THE MINIMUM REQUIREMENTS OF THE APPLICABLE FLORIDA BUILDING CODE AND LOCAL
ORDINANCES.
7.
ALL CODES, TRADE STANDARDS, AND MANUFACTURER'S INSTRUCTIONS NOTED IN THE
DOCUMENTS SHALL BE THE LATEST ADOPTED EDITION.
8.
NOTES, DETAILS, AND SECTIONS ON THE DRAWINGS ARE SHOWN AT SPECIFIC LOCATIONS
AND ARE INTENDED TO SHOW GENERAL REQUIREMENTS THROUGHOUT. DETAILS NOTED
'TYPICAL' IMPLY ALL CONDITIONS TREATED SIMILARLY. CONTRACTOR SHALL MAKE
MODIFICATIONS TO ACCOMMODATE MINOR VARIATIONS.
9,
THE CONTRACTOR SHALL MAKE NO STRUCTURAL CHANGES OR MODIFICATIONS WITHOUT
EXPRESSED WRITTEN APPROVAL OF THE DESIGN PROFESSIONAL OF RECORD.
2. SITE WORK
2.1 SOIL:
1. ALL WORK SHALL CONFORM TO THE FINAL GEOTECHNICAL REPORT AND FINAL GRADING PLAN
ACCEPTED BY THE AUTHORITY HAVING JURISDICTION.
2. ALL SITE PREPARATORY WORK REQUIRED BY THE GEOTECHNICAL REPORT SHALL BE
PRESUMED TO BE COMPLETED PRIOR TO COMMENCEMENT OF WORK.
3. IF SOT' S REPORT IS NOT AVAILABLE, SOIL BEARIN` CAPACITY IS ASSUMED TO BE A MINIMUM OF
2000.- F.
4. CONTRACTOR SHALL VERIFY COMPACTION REQUIREMENTS PRIOR TO THE EXECUTION OF
WORK. DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE DESIGN
PROFESSIONAL PRIOR TO COMMENCEMENT OF WORK,
5. FOOTTR'GS SHALL BE PLACED ON UNDISTURBED SC"' OR COMPACTED ENGINEERED FILL FREE OF
ORGF -'MATTER AND COMPACTED TO 95% OF'. _" MODIFIED PROCTOR, UNLESS OTHERWISE STATED
IN THE GEOTECHNICAL REPORT.
6. BOTTOM OF FOOTINGS SHALL BE 28 -INCHES MINIMUM BELOW FINISHED GRADE, OR AS
REQUIRED BY LOCAL REQUIREMENTS.
7. NO WOOD, VEGETATION, STUMPS, CARDBOARD, CELLULOSE CONTAINING MATERIALS, OR
TRASH SHALL BE BURIED WITHIN IT-0" OF ANY BUILDING OR PROPOSED BUILDING
8. WATER MANAGEMENT AT THE PERIMETER SHALL BE MAINTAINED AND SHALL INCLUDE;
A. CONDENSATE DRAINS AND ROOF DOWN SPOUTS SHALL DISCHARGE AT LEAST I'-0"
FROM BUILDING SIDEWALLS.
B. IRRIGATION / SPRINKLER SYSTEMS, INCLUDING ALL RISERS AND SPRAY HEAPS SHALL
NOT BE INSTALLED WITHIN V-0" OF BUILDING SIDEWALLS.
2.2 SOIL TREATMENT PER FBC 6TH EDITION (2017) SECTION 1816,1:
1. TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES
APPLIED TO WOOD OR OTHER APPROVED METHODS.
2. BOXED AREAS IN CONCRETE FLOORS FOR INSTALLATION OF TRAPS,
ETC.,SHALL BE MADE WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT FORMS SHALL BE
OF A SIZE AND DEPTH THAT WILL ELIMINATE THE DISTURBANCE OF SOIL AFTER INITIAL TREATMENT,
3. SOIL SHALL BE PROTECTED WITH MINIMUM 6 MIL VAPOR RETARDER
FOLLOWING TREATMENT.
4. AFTER COMPLETION OF WORK, ALL LOOSE WOOD AND ORGANIC
MATERIAL SHALL BE REMOVED FROM WITHIN V-0" OF THE BUILDING PERIMETER.
5. AT COMPLETION OF TERMITE TREATMENT, A CERTIFICATE OF
COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT BY A LICENSED PEST CONTROL
COMPANY BEFORE A CERTIFICATE OF OCCUPANCY WILL BE ISSUED.
THE CERTIFICATE SHALL STATE:
A. "THE BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF
SUBTERRANEAN TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND
LAWS OF THE FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES."
3. CONCRETE
3.1 CONCRETE:
1, ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE AMERICAN CONCRETE INSTITUTE
ACI 318.
2. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH AT 28-DAYS OF
2600 PSI, COMPLYING WITH ASTM C-94 UNLESS NOTED OTHERWISE IN DRAWINGS.
3. A MIX DESIGN SHALL BE SUBSTITUTED TO THE DESIGN PROFESSIONAL OF RECORD FOR ALL
CONCRETE USED PRIOR TO PLACEMENT OF ANY CONCRETE.
4, MATERIALS FOR CONCRETE SHALL CONFORM TO THE FOLLOWING:
A. PORTLAND CEMENT - ASTM C 150
B. AGGREGATES:
I. COURSE AGGREGATE - ASTM C33
II. LIGHTWEIGHT AGGREGATE - ASTM C33
III. FINE AGGREGATE - ASTM C33
5. WATER SHALL BE CLEAN, POTABLE AND FREE OF CONTAMINANTS
6. ADMIXTURES SHALL BE AS NOTED IN THE APPROVED MIX DESIGN.
3.2 TESTING AND SAMPLES
1. ALL TESTING OF CONCRETE SHALL BE DONE BY AN INDEPENDENT TESTING LABORATORY IN
ACCORDANCE WITH ASTM PROTOCOL. TEST REPORTS SHALL BE SUBMITTED TO THE DESIGN
PROFESSIONAL OF RECORD WITHINSEVEN-DAYS OF LABORATORY TESTING.
2. THREE (3) TEST CYLINDERS SHALL BE MADE FOR EACH DAY'S POUR, FOR APPROXIMATELY 50
YARDS OF CONCRETE PLACED.
3. SLUMP TEST SHALL BE MADE ON EACH BATCH TESTED IN ACCORDANCE WITH ASTM C143.
4. ONE CYLINDER SHALL BE BROKEN AT 7-DAYS AND ONE AT 28-DAYS. IF NO FURTHER TEST IS
NEEDED, THE RESERVE CYLINDER MAY BE DISCARDED AFTER SIXTY DAYS,
CURRENT RELEASE v3.0 171214
K:\EnvirssafeVLot Jobs\St. L"Ce CC OPEC AllO5OIS Ob55-U)ADwy S , :t _,o d ni a-FI P4, Date i i 'day, M,fcli 1,18, 2018,5'.IS 49 PM; Plotted By: S eveR
3.4 REINFORCING
1. REINFORCING SHALL HAVE GRADE IDENTIFI TION MARKS AND SHALL T CI) CONFORM 0 ASTM
A615 GRADE 40 OR 60.
REINFORCING STEEL MIN
MUM REQUIREMENTS
40 KSI
60 KSI
BAR
SIZE
MINIMUM
LAP
MINIMUM MINIMUM
BEND DIA. ACI HOOK
I
S
AR MINIMUM
ZE LAP
I MINIMUM MINIMUM
BEND DIA. ACI HOOK
# 4
# 5
20"
3"
101,
4
24"
3" 101,
I 3-3/4" 101,
4-1/2" 11"
1 5-1/4" 13"
25"
3-3/4"
101,
5
30"
# 6
34"
4-1/2"
12"
6
3611
# 7
42"
5-1/4
14"
7
42"
2.
REINFORCING SHALL BE FREE OF RUST, SCALE
OR OTHER BOND -REDUCING COATINGS.
3.
REINFORCING SHALL BE PLACED IN CONCRETE
TO PROVIDE MINIMUM COVERAGE IN
ACCORDANCE WITH ACI 318, OR AS INDICATE
HEREIN:
A. CONCRETE CAST AGAINST AND PERMANI
NTLY EXPOSED TO EARTH - 3-INCHES.
B. CONCRETE EXPOSED TO EARTH OR WEATHER
- i 1/2-INCHES.
C. CONCRETE NOT EXPOSED TO WEATHER
OR IN CONTACT WITH GROUND - 3/4-INCHES
4.
ACCURATELY PLACE AND SUPPORT REINFORCI
G WITH CHAIRS, BAR SUPPORTS, SPACERS,
OR HANGERS AS RECOMMENDED BY ACI DETA
LING MANUAL.
5.
PLACE ONE (1) ACI STANDARD LAP SPLICE BAR,
OF THE SAME SIZE AS FOUNDATION
OUTSIDE BA
REINFORCING LOCATED AT THE OUTS.
OF FOUNDATION CORNER S
6.
WELDED WIRE MESH, IF USED, SHALL BE IN ACCORDANCE
WITH ASTM A82 AND SHALL BE
6x6xW1.4xW1.4, UNLESS NOTED OTHERWISE
ON DRAWINGS.
A. INSTALL WELDED WIRE MESH IN THE MI
DUE OF THE SLAB AND SUPPORT WITH
APPROVED MATERIALS OR SUPPORTS A
SPACING NOT TO EXCEED3 FEET ON CENTER
OR IN ACCORDANCE WITH THE MANUF
RERS SPECIFICATIONS.
B. LAP ALL JOINTS IN WELDED WIRE MESH
"
7.
FIBER MESH, IF USED, SHALL BE IN LIEU OF W
HUDED WIRE MESH AND AS SPECIFIED IN THE
CONCRETE DESIGN MIX.
3.5 PLACEMENT AND FINISHING
1.
ALL CONCRETE PLACED UNDER ROOF PROTEC11ON
SHALL BE PLACED OVER
16 MIL POLYETHYLENE VAPOR BARRIER, LAPPED
6" MINIMUM WITH ALL SEAMS TAPED, UNLESS
NOTED OTHERWISE
2.
PLACE ALL EMBEDDED ITEMS (ANCHOR BOLTS
DOWELS, ETC.) IMMEDIATELY PRIOR TO
PLACEMENT OF CONCRETE OR DURING CONCRETING
OPERATIONS.
3.
PROTECT ALL CONCRETE FROM DAMAGE AFTER
PLACEMENT.
4.
CONCRETE SHALL BE PLACED WITHIN 90 MIN
TES OF BATCHING.
5.
CONCRETE SHALL BE PLACED WITHIN THE SLUMP
LIMITS SPECIFIED IN THE DESIGN MIX.
6.
WATER ADDED AT THE SITE SHALL BE KEPT TO
A MINIMUM AND WITHIN THE SPECIFIED SLUMP.
RUN MIXER FOR 30 REVOLUTIONS AT EIGHT 70
TWELVE RPM FOLLOWING THE ADDITION OF
WATER AT THE SITE.
7.
CONCRETE SHALL NOT BE PLACED DURING RA
N. FOLLOWING PLACEMENT OF CONCRETE,
PROTECT FROM RAIN PRIOR TO INITIAL SET.
8.
PLACEMENT SHALL BE CONTINUOUS UNTIL ALI.
WORK IS COMPLETED„
9.
DO NOT USE CONTAMINATED, DETERIORATED
OR RE -TEMPERED CONCRETE.
10.
THOROUGHLY WORK CONCRETE AROUND REINFORCING
BARS.
11.
PLACE CONCRETE TO GRADES AND ELEVATIONS
REQUIRED FOR PROJECT
12.
REMOVE ALL GRADE STAKES AFTER PLACEMENT
OF CONCRETE.
13.
CONTRACTOR SHALL INSTALL SAW -CUT CONTROL
JOINTS IN CONCRETE SLABS PER ACI 224.3R AS
FOLLOWS:
A. PROVIDE SAW -CUT FOLLOWING FINISHIN
AS SOON AS CUT EDGES WILL NOT RAVEL
B, SAW CUTS SHALL BE A MINIMUM OF 1/8" 1
VIDE
C. CUTS SHALL BE 1/4 OF SLAB DEPTH NO LESS
THAN 1", WHICHEVER IS GREATER. FOR
STEEL -FIBER -REINFORCED SLABS 1/3 THE
SLAB DEPTH.
D. SAW CUTS SHALL NOTt., :EED 12 FEET IN
ANY DIRECTION
E. LOCATE SAW CUT JOINTS:
1. MAKE PANELS AS SQUARE AS POSSIB1
E
2. JOINT LOCATIONS `''TALL NOT EXCEED
i
1.5 TO 1 RATIO
3. PANELS SHALL NO'1-HAVE "T" OR "L"
HAPE
4. NO RE-ENTRANT CORNERS SHALL BE
kLLOWED
14.
PROVIDE SURFACE FINISH REQUIRED FOR INTENDED
FINAL APPLICATION.
15.
SILL PLATE ANCHORS SHALL BE AS SPECIFIED
IN SECTION 6.
16.
CONSOLIDATE CONCRETE DURING PLACEMENT
OPERATIONS.
4. METALS
4.1 MATERIALS
1.
ALL STRUCTURAL PLATES, CHANNELS, AND MISCELLANEOUS
METALS SHALL BE IN
ACCORDANCE WITH ASTM A36.
2.
ALL STRUCTURAL STEEL SHALL BE IN ACCOR
ANCE WITH ASTM A992.
3.
ALL ANCHOR BOLTS AND THREADED RODS SHALL
BE A MINIMUM GRADE A307STEEL.
4.
ALL STEEL EXPOSED TO WEATHER SHALL BE GALVANIZED.
4.2 EXECUTION
1.
INSTALL METALS AS DETAILED ON DRAWINGS
2.
STEEL WORK SHALL CONFORM TO THE LATE
EDITION OF THE DESIGN, FABRICATION AND
ERECTION OF STRUCTURAL STEEL FOR BUILDING
AS ADOPTED BY THE A.I.S.C.
3.
ALL STEEL SHALL BE PAINTED WITH ONE COAT
OF RED OXIDE PRIMER. TOUCH UP ALL FIELD
WELDS AND DAMAGED AREAS.
READ AND UNDERSTAND ALL NOTES PRIOR TO CONSTRUCTION. IF YOU HAVE
ANY QUESTIONS, CONTACT THE DESIGN ENGINEER,
1 ALL CONSTRUCTION SHALL CONFORM TO THE STANDARD, STATE, AND
LvCAL COUNTY BUILDING CODES LATEST EDITIONS.
2) CONTRACTOR IS TO VERIFY ALL LOCATIONS, ELEVATIONS, AND DIMENSIONS.
IN THE FIELD AND REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO
THE START OF CONSTRUCTION.
3) IT IS THE RESPONSIBILITY OF THE CONTRACTOR OR OWNER TO NOTIFY ALL
REVIEW AGENCIES 48 HOURS PRIOR TO THE START OF CONSTRUCTION.
41 ANY DEVIATIONS FROM THE APPROVED CONSTRUCTION PLANS WILL HAVE TO
BE APPROVED BY THE DESIGN ENGINEER AND ALL APPROPRIATE REVIEW AGENCIES.
IA
Ll
1
s
,,e
s
- a
CORCRE
ROAD
ENGINEERING FIRM POLLUTANT STORAGE CONTRACTOR
POLLUTANT STORAGE SYSTEMK CONTRACTOR, PU -E50
r ARCHITECTURE+ENGINEERING CURTIS EVANS - GENERAL MANAGER
MEMCO, INC_ IDEA ENVIROSAFE FIJEL SYSTEMS
FOREFRONT �°�^ ^�"�° 1-99 CR. 48
Sella Beyantlpeslpn P. BPBb� FPAE 0.") BUSHNELL, FLORIDA 33513
SITE INFORMATION:
ST. LUCIE COUNTY UTILITIES COMMISSION
7501 S. OCEAN DR. ST. LUCIE FLORIDA 34957
vi*�T
,0
p�
/� . o �'A I C3��1
A �+1 col
RE-- �
t
a
a y
t
1 4
t
P q,
,
Xi �.
#17057 2s
OWNER 101 00
T P -M RPNS RC IER L
9-88 SDE Y HAY ES L.
3 I N P,L.
ORLANDO FLORIDA 32824
ri
T
-
NOTES
W
ENGINEERS SEAL ON THIS PLAN ARE
1.
COND. TO DISPENSER SHOULD TERMINATE
W
FOR STRUCTURAL ELEMENTS ONLY.
IN DISP. JUNCTION BOX & REQUIRE SEAL
o
OTHER ITEMS SHOWN ON THIS PLAN
2.
OFF ON BOTH ENDS.
CONDUIT SHOULD TERMINATE 18" ABV.
z
g
ARE FOR REFERENCE ONLY.
SLAB, INSIDE SENTRY.
0
3.
CONDUIT INSIDE SENTRY SHOULD FIT INTO
y
AN 8"x8" PATTERN.
4.
ALL CONDUIT NEEDS TO BE AT LEAST 3/4"
Z
ED
AND NEEDS PULL LINE IN CONDUIT & ONE
W�
CAP JOINT FOR EASE OF PULLING. SHOULD
BE RIGID CONDUIT.
+
5.
DISPENSERS MUST HAVE A 10:1 DRY REED
PULSER, OR IF ELECTRONIC. THEY WILL
LU
A,
NEED A 10:1 PULSE OUTPUT:
N
Y�
6J
(V
a
y��
U
W
,D
v
Il
Q
f R
APR b 5 26%
ONTRACTOR SHALL FIELD `.ERIFY ALL CONSTRUCTION PRIOR
0 BIDDING. THIS PLAN M,i NOT REFLECT ALL CONSTRUCTION
)BSTACALES, ACCESS, DEWATERING, LOCAL PERMITTING, ETC.
HAT MAY BE REQUIRED.
XANNED
BY
St Lurie COurjjv
CALL 72 HOURS
BEFORE YOU DIG
It's the Law!
811
SUNSHINE STATE ONE CALL yr rwni�n, nv�.
0 0
E
UN
CO 0
0 Lu BU
N Q M
U C
•_ O
LI; w
In 0
� � o
a0'0
C1 00
`m00
oa
d
Y
O
0
M
N
r
F_
f`
O
J
z
z
,J
Z
W
O
m
U
a
Q
U
Q
J
J
W
U
CCS
I
ANY DISCREPANCY OR ERROR IN
DIMENSIONS OR NOTES SHALL BE
BROUGHT TO THE ATTENTION OF
THE DESIGN PROFESSIONAL FOR
CLARIFICATION PRIOR TO
COMMENCEMENT OF CONSTRUCTION.
-_ SOOT
I N. <.'PYI F THIS DJt MENi AfIC OR THE DESIGN CONCEPT WITHOUT THE WRITTEN CISENT R ,.. ARE RESERVED. ANY REPROD_� . I (. NG, OR USE 0 H . .0 / S NT Of FOREFRONT ARCHITECTURE &ENGINEERING LLV I STRICTLY PROHIBITED AND PROTE..TEU BY UNITED ST.,TES AND IN fERNATIONAL LAW. IF PRINTED ON 11Y11 LEI HALF THE SIZE NOTED
rl, � efREFRONi 4R, m :_�,.: _ c i,. I :Lt R, v,. � I � I ', v _ . e "< ,� �,h i „rJ i �z ,:F 5 T � i ELIII �a � ilt PROPERTY OF CORER. ]NT ARCHITECTURE & ENGINEERING I AND ALL RIGHTS OF OWNERSHIP, INCLUDING COPYRIGHT OF INTELLECTUAL PROPERTY, I 5 SFR CTL 0 A SCALE 5 5 ,
LULA I OK MAP
EXISTING CONCRETE SLAB
5E61i'li
2
5EG7ION:
1
TANK LEG ANCHORAGE DETAIL
EXISTING CONCRETE SLAB
r ,
n
K:AE"Nmsaf"1Lot 7oU515t. Lucie County 1rll05]\18-06E5400ADwgs\Sheets\Stmctural\5]Ol ; PI"[ Dale Tnms4y, Mann 08, L018,5'.10:50 PM; Pk�Sied By: Stave{: IC, F _ RE RC„I
TANK LEG W/ 1/2"x 6" GALV.
EXPANSION BOLTS (2 PER LEG 1 EA
SIDE) EMBED 4" MIN.
Ce17fOr
3/4"=V-0"
BF02
15'-1"
E:VTCTTAI!` V1 AD
LAB AREA TO
ELD VERIFY SIZE.
L BE CENTERED ON
L0
W
Z J
H
Z J LJJ
0
®
Q Q
� U �
N
IM
AY DISCREPANCY OR ERROR IN
DENSIONS OR NOTES SHALL ED
BRO
H
UGHT TO THE ATTENTION OF
TE DESIGN PROFESSIONAL FOR
CLARIFICATION PRIOR TO
COMMENCEMENT OF CONSTRUCTION.
EDGE DETAIL F'le Nave. 18
a7 3/4"=V-0" SCALE: 1/2"=V-0" DATE: S1O1
MFOS
E & ENGINEERING I I. 4inl1, P ,n>, :, E -F � 6 - TIP. , „. OF INTELLECTUAL PROPERTY, ARE RESERVER ANY REPRODUCTIONc UJPYIN[ '2.ISE 2F THI 'If Lf T AM ".: I LONE , 'dl F, _ .- 5i POL, Dj „t - � IN - I - S o.- __ _ ---
.. d�L+i ,Nqt✓'ll,_i_I ,16N..ONU, �n.RL �. i.eEl �i�.L HI RW _2 ,, .,R. WJl .�IIIEOURE&ENGINEERING LLC AND RIGHTS OFOWNERSHIP, INCLUDING ,I C�i URt__ALI]��.fIEeR.NG LIA.I»,IUCILI PROHIBITED AND IROTELIN BY UNTIED STATESAND INTERNATIONAL LAW. IF PRINTED ON II%1J SCALE I5HALF l'HE SIZE NOTED.
N
IM
AY DISCREPANCY OR ERROR IN
DENSIONS OR NOTES SHALL ED
BRO
H
UGHT TO THE ATTENTION OF
TE DESIGN PROFESSIONAL FOR
CLARIFICATION PRIOR TO
COMMENCEMENT OF CONSTRUCTION.