Report of Geotechnical Exploration
Proposed Two -Story Residence
Acquavista Development BLIK A Lot 1
4410 AM, St. Lucie County, Florida
�June 26, 2015
GFA Pry ject No.: 15-0786.00
For: AJT Construction Consulting, LLC
F"
Environmental - Geotechnical -
AJT Construction Consulting, LLC
Attention: Mr. Alan Tarpell
1760 N. Jog Road, Suite 140
West Palm Beach, Florida 33411
Site: Proposed Two -Story
Acquavista Develops
4410 Al A, St. Lucie
GFA Project # 15-071
Dear Mr. Tarpell:
Florida's Leading Engineering Source
Materials Testing • Threshold and Special Inspections • Plan Review & Code Compliance
ioence
BLK A Lot 1
ty, Florida
June 26, 2015
GFA International, Inc. (GFA) has completed the subsurface exploration and geotechnical
engineering evaluation for the abovei�referenced project in accordance with the geotechnical
and'engineering service agreement for this project. The scope of services was completed in .
accordance with our Geotechnical Engineering Proposal (15-0986.00) dated May 7, 2015,
planned in conjunction with and authorized by you.
EXECUTIVE SUMMARY
The purpose of'our subsurface exploration was to classify the nature of the subsurface soils and
general geomorphic conditions and evaluate their impact upon the proposed construction. This
report contains the results of our subsurface exploration at the site and our engineering
interpretations of these, with respect to the project characteristics described to us including
providing recommendations for site preparation and the design of the foundation system.
Based on conversations with the client, the project consists of, constructing a two-story
residence. The residential structure (or portion thereof) will be located east of .the Coastal
Construction Control Line (CCCL) andltherefore a pile supported foundation is required. GFA
was informed that the residence will be elevated above a lower level garage that will have walls
and ground floor slab of frangible breakaway design.
The recommendations provided herein are based upon the above considerations. If the project
description has been revised, please inform GFA International so that we may. review our
recommendations with respect to any modifications.
A total of one (1) standard penetration test (SPT) boring to a depth of approximately forty (40)
feet below ground surface (BGS) were completed for this study. Additional borings and
soundings were performed on the adjacent lots and the information is used to supplement this
report.
521 NW Enterprise Drive • Port St. Lucie, Florida 34986 - (772) 924.3575 -
THROUGHOUT FLORIDA
924.3580 (fax) - www.
Proposed Two -Story Residence Geotechnical Report
Acquavista Lot 1 (4410 AIA), St. Lucie County, FL June 26, 2016
GFA Project No. 15-0786, 00 Page 2 of 11
I
The subsurface soil conditions encountered at this site (with information from borings and
soundings performed from adjacent lots), generally consist of loose to medium sand (SP) to 4
feet, medium dense sand (SP) from 4 to 23'/z feet, and then medium dense to very dense sand
(SP) with cemented sand seams and layers the boring termination depths. Please refer to
Appendix D - Record of Test Borings for a detailed account of each boring.
GFA recommends that the proposed Iresidence be supported using a deep foundation system
consisting of angered cast -in -place (ACIP) piles. Based on our analysis, GFA has estimated
that a 14 or 16-inch-diameter ACIP pile installed to a depth of 30 feet below grade existing
grade can provide a maximum allowable axial compressive capacity of 40 tons and a maximum
tension capacity of 12 tons. i
For the ground supported frangible walls, an allowable bearing capacity of 2,500 psf may be
used for shallow footing foundation design.
The subgrade soils should be improved with compaction from the stripped grade prior to
constructing the foundation pads and footing excavations. The top 2 feet below stripped grade
should be compacted to a minimum of 95% density prior to placing fill to achieve final grade.
Fill (including stemwall backfill) should be placed in 12-inch lifts and compacted to achieve a
minimum 95% density. After excavation for footings, the subgrade to a depth of 2 feet below
bottom of footings should be compacted to achieve a minimum 95% density.
Scour elevations used in pile calculations are those provided by the Florida DEP for coastal
construction, but may not be adequate) for actual scour elevations in hurricane(s) event(s) that
exceed the DEP assumptions and cause lower scour elevations. Therefore, GFA analysis is
limited to that provided by the DEP scour elevation, and scour analysis is not included in our
scope of work.
We appreciate the opportunity to be c
continued association. Please do no
comments, or if we may further assist y
�9�g�Q1@uddAOp®d
Respecv311�tf tf,�d®''✓
GFA lower`;' ationatY,
Florid -E rtifi fAq Mion Num
w
o ;IjV,WfNr, E. ; c�
Senn, eq�chn%pl Enginfn�r
Florid'a.R i §ftVn NQ.60
ti
Copies: �2', AIA0,4pppi W`�
service to you on this project and look forward to a
hesitate to contact us if you have any questions or
i as your plans proceed.
.r 4930
ividAlker
Project Manager
GF
Proposed Two -Story Residence Geotechnical Report
Acquavista Lot 1 (4410 A1A), St. Lucie County, FL June 26, 2016
GFA Project No. 15-0786.00 Page 3 of 11
TABLE OF CONTENTS
1.0 INTRODUCTION ........................i 4
1.1
Scope of Services .................. 1......................................................................................4
1.2
Project Description..........................................................................................................4
2.0 OBSERVATIONS.................................................................................................................5
2.1
Site Inspection ......................... ..... ................................................:......................... ........5
2.2
Field Exploration ..............................................................................................................5
2.3
Laboratory Analysis..................I ......................................................................................5
2.4
Geomorphic Conditions....................................................................................................6
2.5
Hydrogeological Conditions.............................................................................................6
3.0 ENGINEERING EVALUATION AND RECOMMENDATIONS..............................................6
3.1
Foundation Recommendations 1 General.........................................................................6
3.2
Pile Foundation .............................................................................................................7
3.3
Pile Installation ..........................� 8
....................................... .
Vibration
3.4
Monitoring ................ 8
3.5
Design of Footings (Ground Level Frangible Walls).........................................................9
3.6
Ground Floor Slab (Frangible)....I......................................................................................9
3.7
Site Preparation...............................................................................................................9
4.0 REPORT LIMITATIONS.................1...................................................................................11
5.0 BASIS FOR RECOMMENDATIONS..................................................................................11
Appendix A - Vicinity Map
Appendix B - Test Location Plan
Appendix C - Notes Related to Borings
Appendix D - Record of Test Borings
Appendix E - Discussion of Soil Groups
GFH
i
i
I
Proposed Two -Story Residence Geotechnicat Report
Acquavista Lot 1 (4410 A1A), St. Lucie County, FL June 26, 2016
GFA Project No. 15-0786.00 Page 4 of 11
1.0 INTRODUCTION
1.1 Scope of Services
The objective of our geotechnical services was to collect subsurface data for the subject project,
summarize the test results, and discuss any apparent site conditions that may have
geotechnical significance for building construction. The following scope of services are provided
within this report: I
1. Prepare records of the soil boring logs depicting the subsurface soil conditions encountered
during our field exploration.
2. Conduct a review of each soil sample obtained during our field exploration for classification
and additional testing if necessary. I
3. Analyze the existing soil conditions found during our exploration with respect to foundation
support for the proposed structure.
4. Provide recommendations with
allowable soil -bearing capacity,
5. Provide criteria and site
construction.
1.2 Project Description
t to foundation support of the structure, including
elevations, and foundation design parameters.
n procedures to prepare the site for the proposed
Based on conversations with the client, the project consists of constructing a two-story
residence. The residential structure (or portion thereof) will be located east of the Coastal
Construction Control Line (CCCL) and therefore a pile supported foundation is required. GFA
was informed that the residence will be elevated above a lower level garage that will have walls
and ground floor slab of frangible breakaway design.
Based on a site visit and elevations f�om topographic data from GoogleEarth website, the
current grade at the location of the proposed residence varies from about +8 on the west side
and slopes upwards to the east to +11 feet NGVD. Assuming the proposed house will have a
ground level garage grade about +9 feet NGVD, about 0 to 2 feet of fill will be required to
achieve final grade.
We assume the residence will have typical construction, and be supported on columns
terminating on pile caps slightly below the ground floor elevation. We assume that fill will be
placed to achieve final (or near final) grade before installing the pile foundations, and top of piles
(bottom of pile caps) would be about +8 feet NGVD.
We have not received any information regarding structural loads. For the foundation
recommendations presented in this report we assumed the maximum column load will be 80
kips and the maximum wall loading will be'l 4 kips per linear foot.
GF
y a Proposed Two -Story Residence I Geotechnica! Report
Acquavista Lot 1 (4410 A1A), St. Lucie County, FL June 26, 2016
GFA Project No. 15-0786.00 I Page 5 of 11
The recommendations provided herei are based upon the above considerations. If the project
description has been revised, please inform GFA International so that we may review our
recommendations with respect to any modifications.
OBSERVATIONS
2.1 Site Inspection
The project site was generally grassylwith some palm trees and bushes. The site was about
even with the adjacent road on the west side and sloped upwards to the east, and at the end of
the east side of the lot the grade variedlwith dunes and vegetation. The Atlantic Ocean bordered
the east side of the property on the east side of the dunes.
2.2 Field Exploration
A total of one (1) standard penetration (test (SPT) boring to a depth of approximately forty (40)
feet below ground surface (BGS) were completed for this study. Additional borings and
soundings were performed on the adjacent lots and'the information is used to supplement this
report. The locations of the boring per ormed for this lot is illustrated in Appendix B: "Test
Location Plan". The Standard Penetration Test (SPT) method was used as the investigative
tools within the borings. SPT tests were performed in substantial accordance with ASTM
Procedure D-1586, "Penetration Test land Split -Barrel Sampling of Soils". The SPT test
procedure consists of driving a 1.4-inch I.D. split -tube sampler into the soil profile using a 140-
pound hammer falling 30 inches. The number of blows per foot, for the second and third 6-inch
increment, is an indication of soil strength.
The soil samples recovered from the soil boring were visually classified and their stratification is
illustrated in Appendix D: 'Record of Test Borings". It should be noted that soil conditions might
vary between the strata interfaces, which are shown. The soil boring data reflect information
from a specific test location only. Site Ispecific survey staking for the test locations was not
provided for our field exploration. The indicated depth and location of each test was
approximated based upon existing grade and estimated distances and relationships to obvious
landmarks. The boring depths were confined to the zone of soil likely to be stressed by the
proposed construction and knowledge of vicinity soils.
2.3 Laboratory Analysis
Soil samples recovered from our field exploration were returned to our laboratory where they
were visually examined in general accordance with ASTM D-2488. Samples were evaluated to
obtain an accurate understanding of the soil properties and site geomorphic conditions. After a
thorough visual examination of the recovered site soils, no laboratory testing was deemed.
necessary. Bag samples of the soil encountered during our field exploration will be held in our
laboratory for your inspection for 30 days and then discarded unless we are notified otherwise in
writing.
60
Proposed Two -Story Residence I Geotechnical Report
Acquavista Lot 1 (4410 A1A), St. Lucie County, FL June 26, 2016
GFA Proiect No, 15-0786, 00 Page 6 of 11
The recovered samples were not xamined, either visually or analytically, for chemical
composition or environmental hazards GFA would be pleased to perform these services for an
additional fee, if required. 1
2.4 Geomorphic Conditions
The geology of the .site as mapped orb the USDA Soil Survey website consists ofPalm Beach
fine sand, 0 to 5 percent slopes (27). These are sandy soils and organic soils are not
indicated. It should be noted that the oil Survey generally extends to a maximum depth of 80
inches (approximately 63/ feet) . belo .. ground surface and is not indicative of deeper soil
conditions. I
Boring logs derived from our field exp
Borings". The boring logs depict the ob
Test borings indicate the penetration
sampling activities. The classifications
upon visual characterizations of the re
been depicted and classified in general
modified as necessary to describe ,typi
Soil Groups", for a detailed description c
gyration are presented in Appendix D: 'Record of Test
erved soils in graphic detail. The Standard Penetration
.sistance, or N-values logged during the drilling and
nd descriptions shown on the logs are generally based
overed soil samples. All soil samples reviewed have
accordance with the Unified Soil Classification System,
al Florida conditions. See Appendix E: "Discussion of
various soil groups.
The subsurface soil conditions encountered at this site (with information from borings and
soundings performed from adjacent lots), generally consist of loose to medium sand (SP) to 4
feet, medium dense sand (SP) from 4 tol23'/Z feet, and then medium dense to very dense sand
(SP) with cemented sand seams and layers the boring termination depths. Please refer to
Appendix D - Record of Test Borings for � detailed account of each boring.
2.5 Hydrogeoiogicai Conditions
On the .dates of our field exploration, the groundwater table was encountered at a depth of
approximately 8 feet below the existing ground surface. The groundwater table will fluctuate
seasonally depending upon local rainfall end other site specific and/or local influences including
the water level in the nearby Atlantic Oc an with tidal influences. Brief ponding of stormwater
may occur across the site after heavy rains.
No additional investigation was included lin our scope of work in relation to the wet seasonal
high groundwater table or any existing well fields in the vicinity. Well fields may influence water
table levels and cause significant fluctuations. If a more comprehensive water table analysis is
necessary, please contact our office for additional guidance.
3.0 ENGINEERING EVALUATION AND RECOMMENDATIONS
3.1 Foundation Recommendations -
The residential structure will be located e
and therefore a pile supported foundation
level walls may be pile supported ,or si
regulations (to be determined by others),
of the Coastal Construction Control Line (CCCL)
required. Frangible ground floor slabs and ground
,orted on footings in accordance with rules and
GF�
Proposed Two -Story Residence
Acquavista Lot 1 (4410 A1A), St. Lucie County, FL
GFA Project No. 15-0786.00
3.2 Pile Foundation
The following is design parameters GFA used for pile recommendations:
➢ For CCCL construction, the FD'I
lowest structural member) of
structures within St. Lucie Coun
➢ For CCCL construction, the FC
(design scour elevation) of +2.7
➢ A loss of soil support between i
elevation (+2.7 feet NGVD)
capacity analyses.
➢ We assume the residence will
terminating on pile caps slightly
be placed to achieve final (or ni
top of piles (bottom of pile caps
Geotechnical Report
June 26, 2016
Page 7 of 11
:P has established a 100-year storm elevation (bottom of
+17.0 to +17.9 feet NGVD (depends on location) for
At this time, GFA recommends the de
(ACIP). Additional lateral capacity may
the piles will have a minimum of 1% st
procedures should be performed in e
edition of the Deep Foundations Instii
capacity and pile top deflection were
software. A summary of pile capacitie
following table.
EP has established a 100-year storm erosion elevation
feet NGVD for all of St. Lucie County.
ie bottom of lowest structural member and design scour
ras included in compressive, tensile, and lateral pile
re typical construction, and be supported on columns
low the ground floor elevation. We assume that fill will
final) grade before installing the pile foundations, and
)uld be about +8 feet NGVD.
:) foundation to consist of augered cast -in -place piles
e attained by utilizing inclined piles. We assumed that
;I reinforcement for the analyses. ACIP pile installation
;ordance with the guidelines presented in the latest
`e's Augered Cast -In -Place Pile Manual. The lateral
slculated using the commercially available L-pile 4.0
for a 14-inch diameter ACIP piles is presented in the
Pile Recommendations For All Pile Supported Structures
1,
Maximum
Nominal
Pile Top
Recommended
Pile
Pile
Pile
Pile Lateral
Pile
Elevation
Pile Tip
Lengths
Compression
Tension
Capacity
Recommended
Diameter
(NGVD)*
Elevation
(ft)**
Capacity
Ca aci
(Tons)***
Grout Strength
f
0.5 Tons
(Free Head)
14" or
1.25 Tons
16"
Unknown
Unknown
30
40 Tons
12 Tons
Fixed Head
5000 psi
*Pile top elevation assumed at, or more than,+6 feet NGVD for analyses.
**From ground surface existing at time of drilling.
***For calculated pile top deflection of/z inches at top of pile elevation.
GFA assumed that the piles will have a minimum of 1 % steel reinforcement for the analyses.
Augercast piles should be reinforced over their entire length for tension capacity. The
reinforcement shall be as designed by the Structural Engineer.
If piles of lesser or greater capacities than those mentioned in the table above are required,
GFA would be pleased to provide further recommendations upon request.
The following additional notes are applicable to the pile design:
GF�
Proposed Two -Story Residence
Acquavista Lot 1 (44 10 A1A), St. Lucie
GFA Project No. 15-0786.00
Structural stresses in
design capacity; theret
the selected pile sectio
Geotechnica! Report
FL June 26, 2016
Page 8 of 11
piles may impose a more severe limitation on the
we recommend the allowable stresses be verified for
The pile reinforcement is sufficiently embedded in the pile cap so as to afford a
fixed end connection if reauired.
3.3 Pile Installation
Pile design and installation shall be in accordance with the applicable sections of the Florida
Building Code and other applicable federal, state and local requirements. In addition, piles
should be installed in accordance with the following:
Pile Length: The proposed 14-inch-diameter piles should be installed as determined by
the inspecting Geotechnical Engineer.
2. Spacing - Piles installed in groups should be spaced at a center -to -center distance of not
less than 3 pile diameters.
3. Plan Location - The center of the top of any pile at cut-off should be displaced laterally
no more than 3 inches from the position shown on the plans. This applies to both. single
piles and piles installed in groups.
4. Vertical Alignment - The vertical alignment of the piling should not deviate from the
plumb by more than 1/4 inch per foot of length.
5. Reinforcing Cage Positioning -The top of the reinforcing cages installed in the piling
should not be more than 6 inched above and no more than 3 inches below the positions
shown in the plans. The reinforcinlg cages should be positioned concentrically within the
grouted pile shaft. The grout cover over longitudinal reinforcing bars should not be less
than 3 inches. Reinforcing centralizers shall be placed at maximum spacing of 15 feet at
the lower portion of the pile and atl5 feet from the cage's top.
6. Adiacent Piles - A minimum time period of 12 hours should be specified for the
installation of piles located within 51feet, center -to -center, of each other.
Grout Factor - The minimum acceptable grout factor (i.e. actual grout volume divided by
theoretical grout volume) should bey 1.1.
3.4 Vibration Monitoring
The proposed construction will be within close proximity to residential structures and roadways -
that maybe susceptible to damage from vibration generated at the site. We recommend that
during all aspects of construction, the bordering landmarks be monitored using a seismograph
to determine the. extent of vibration absorption that these features will be subject to. The
seismograph used to monitor at this site should have the capability to measure ground velocities
along vertical, transverse, and longitudinal axes. The project structural engineer should
60
I
Proposed Two -Story Residence
Acquavista Lot 1 (4410 A1A), St. Lucie Clounty, FL
GFA Project No. 15-0786.00
establish allowable ground velocities) that the
any damage.
Geotechnica! Report
June 26, 2016
Page 9 of 11
bordering facilities can safely withstand without
3.5 Design of Footings (Ground Level Frangible Walls)
Footings may be designed using and allowable soil bearing pressure of 2,500 psf. Shallow
foundations should be embedded a minimum of 12 inches below final grade. This embedment
shall be measured from the lowest adjacent grade. Isolated column footings should be at least
24 inches in width and continuous strip footings should have a width of at least 16 inches
regardless of contact pressure.
Once site preparation has been perfori
in this report, the soil should readily,
foundation system. Settlements have
differential. All footings and columns
they will be loaded differently and at
designed.
3.6 Ground Floor Slab (Frangible)
ied in accordance with the recommendations described
support the proposed structure resting on a shallow
been projected to be less than 1-inch total and 1/2-inch
should be structurally separated from the floor slab, as
different times, unless a monolithic mat foundation is
The ground floor slabs may be supported directly on the existing grade or on granular fill
following the foundation site preparatioh and fill placement procedures outlined in this report.
For purposes of design, a coefficient of subgrade modulus 150 pounds per cubic inch may be
used. The ground floor slab should be structurally separated from all walls and columns to
allow for differential vertical movement.
Water vapor is likely to rise through the granular fill and condense beneath the base of the floor
slab. If moisture entry into the floor slab 'is not desirable, an impermeable membrane should be
installed at the slab bottom - subgrade interface.
3.7 Site Preparation
GFA recommends the following compaction requirements for this project:
➢ Proof Roll .................................... I...............................95% of a Modified Proctor
➢ Building Pad Fill ................ ........................................... 95% of a Modified Proctor
➢ Footings I..................95% of a Modified Proctor
The compaction percentages presented 'above are based upon the maximum dry density as
determined by a "modified proctor" test. (ASTM D-1557). All density tests should be
performed to a depth of 2 feet below stripped surface and 2 feet below bottom of
footings. All density tests should be performed using the nuclear method (ASTM D-2922), the
sand cone method (ASTM D-1556), or Hand Cone Penetrometer (HCP) tests.
Our recommendations for preparation of� the site are presented below. This approach to
improving and maintaining the site soils has been found to be successful on projects with similar
soil conditions.
Gfi�
Proposed Two -Story Residence I Geotechnical Report
Acquavista Lot 1 (4410 A1A), St. Lucie County, FL June 26, 2016
GFA Project No. 15-0786, 00 I Page 10 of 11
Initial site preparation should consist of performing stripping (removing surface vegetation,
near surface roots, and other deleterious matter) and clearing operations. This should be
done within, and to a distance of five (5) feet beyond, the perimeter of the proposed building
footprint (including exterior isolated columns). Foundations and any below grade remains of
any structures that are within the footprint of the new construction should be removed, and
utility lines should be removed or properly abandoned so as to not affect structures. If the
demolished residence had a pile foundation, GFA must be notified as the recommendations
may change. i
2. Following site stripping and prior the placement of any fill, areas of surficial sand (not
exposed limestone) should be compacted ("proof rolled") and tested. We recommend using
a steel drum vibratory roller with sufficient static weight and vibratory impact energy to
achieve the required compaction. (Density tests should be performed on the proof rolled
surface at a frequency of not less than one test per 2,500 square feet, or a minimum of three
(3) tests, whichever is greater. Areas of exposed intact limestone shall be visually confirmed
by the project geotechnical engineer prior to fill placement, in lieu of proof rolling.
3. Fill material may then be placed in the building pad as required. The fill material should be
inorganic (classified as SP, SW, GP,I GW, SP-SM, SW-SM, GW-GP, GP -GM) containing not
more than 5 percent (by weight) organic materials. Fill materials with silt/clay-size soil
fines in excess of 12% should notlbe used. Fill should be placed in lifts with a maximum
_lift thickness not exceeding 12-inches. Each lift should -be compacted and tested prior to the
placement of the next lift. Density tests should be performed within the fill at a frequency of
not less than one test per 2,500 square feet per lift in the building areas, or a minimum of
three (3) tests per lift, whichever is greater.
4. For any footings bearing on a limest ine formation, the bottom of all footing excavation shall
be examined by the engineer / geologist or his representative to determine the condition of
the -limestone. The limestone shall be probed for voids and loose pockets of sand. Such
areas shall be cleaned to depth of 3 times the greatest horizontal dimension and backfilled
with lean concrete.
i
5. For footings placed on structural fill for compacted native granular soils, the bottom of all
footings shall be tested for compaction and examined by the engineer / geologist or his
representative to determine if the soil is free of organic and/or deleterious material. Density
tests should be performed at a frequency of not less than one (1) density test per each
isolated column footing and one (1)11 test per each seventy five (75) lineal feet of wall
footings.
6. Upon completion of production pile installation and pile cap construction, the Pile caps
should be backfilled in 6 to 8 inch thick lifts and compacted to at least 95% of the modified
Proctor maximum dry density (ASTM D,1557).
7. The contractor should take into account the final contours and grades as established by the
plan when executing his backfilling and ',compaction operations.
Using vibratory compaction equipment at this site may disturb adjacent structures. We
recommend that you monitor nearby structures before and during proof -compaction operations.
19
Proposed Two -Story Residence I Geotechnical Report
Acquavista Lot 1 (4410 A1A), St. Lucie County, FL June 26, 2016
GFA Project No. 15-0786.00 Page 11 of 11
A representative of GFA International can monitor the vibration disturbance of 'adjacent
structures. A proposal for vibration monitoring during compaction operations can be supplied
upon request.
4.0 REPORT LIMITATIONS
This consulting report has been prepan
other members of the design team for tl
Lot 1, 4410 A1A, St. Lucie County, Flo
generally accepted local geotechnical i
implied. The evaluation submitted in tt
a field exploration, however, the nah
profile may not become evident until th
it may be necessary to reevaluate inf
report. In the event changes are ma
structure, the evaluation and opinions
unless the changes are reviewed ar
International.
for the exclusive use of the current project owners and
s Proposed Two -Story Residence located at Acquavista
Ja. This report has been prepared in accordance with
igineering practices; no other warranty is expressed or
report, is based in part upon the data collected during
and extent of variations throughout the subsurface
time of construction. If variations then appear evident,
•mation and professional opinions as provided in this
e in the nature, design, or locations of the proposed
.ontained in this report shall not be considered valid,
conclusions modified or verified in writing by GFA
Scour elevations used in pile calculatio s are those provided by the Florida DEP for coastal
construction, but may not be adequate for actual scour elevations in hurricane(s) event(s) that
exceed the DEP assumptions and cause lower scour elevations. Therefore, GFA analysis is
limited to that provided by the DEP scour elevation, and scour analysis is not included in our
scope of work.
5.0 BASIS
The analysis and recommendations sub
from the tests performed at the locations
report does not reflect any variations, whi
representative of the subsurface conditic
reaches, local variations characteristic of
may be encountered. The delineation be
and the description represents our interpi
boring locations on the particular date dril
RECOMMENDATIONS
itted in this report are based on the data obtained
idicated on the attached figure in Appendix B. This
i may occur between borings. While the borings are
s at their respective locations and for their vertical
ie subsurface soils of the region are anticipated and
,een soil types shown on the soil logs is approximate
ration of the subsurface conditions at the designated
Any third party reliance of our geotechnical report or parts thereof is strictly prohibited without
the expressed written consent of GFA International. The applicable SPT methodology (ASTM
D-1586), CPT methodology (ASTM 13-3441), and Auger Boring methodology (ASTM D-1452)
used in performing our borings and sounding, and for determining penetration and cone
resistance is specific to the sampling tools lutilized and does not reflect the ease or difficulty to
advance other tools or materials.
19
Appendix A - Vicinity Map
Gfi�
Appendix�B - Test Location Plan
GF�
Test Location Plan: Proposed Two -Story Residence Ac uavista Development BLK A Lot 1 4410 Al St. Lucie Count FL
..:.. P Y Q p Y,
�a C1CF l\ \"{1311' Fi41'.1'i`F_5 LE's< 1! Df 1( REIi{ IU\ \ 7T ll 1l',i
. t -s.a.• ..I s�M ,x:c;i`a,la'� n.. ii a ..... m......
l_4\i, t\!'lI'lStt �,' t.A A>p»•S YY •, �,.a•. > f M l � }
( m ��;, I Jv... M.II 's'r3J1*rl: Xa:! _' M1t•t .. r i V W'la4 "EIS Hi'Kf''V]}lair',,^tt.4� •Fd
f � m,� •m ` , � � 1 `i�p�ll� \.i 1 ` a t a a 01 N IY.fY1R.9T
:\�. Y " 'ti\ i '\ �� \_.1 i >•. a u \..vr..xa CaFnIP
4 "s `,•,i.a..,r..��AM,`t x•, ua>•� r 3c Ira • ix Haaway
\.•+ 'to`i��*l l nai
l Tln 1 IS0.� r� \:JV. i}
Y,VbI )IM\' (M1 ��{ fti Uv[, r'•'
fmn;_az: i,!•. �.il.
(rUP ADMAn. ` N1 Y1t ` +� J A..-rn_.i L, [, I:F IY.v: 1. t?a tir! a,n..:,N•iltw
,�„ \ ,�� nr } �� •; +°.� 3 �� ti � i. ` i � G? S, r,t,.�ta2s r..:.: n.s�•xr }. rc? w>mxx..x�\,:xr.u�s.a-n•.,. ..
iCCi Y�: ` .•l 4 1- v. 't .�...,�\ '..,.� _ .,7_. .�V !w. unto
1 �\ � `• � t XM1 H •f Ui\M1NI J47ri'i A W 377A'•li Ai' } (IAh1 M.. I'iM 1(LhW rlLt (i 1
` l '{ 1 •'t ; .ii as \ �`'h pia/
f tCt?TiD \[)ti t t }q•I lb\ , ii i\ ,� � ii � � i r,•..it,.,. r:;,., is «iy iari acic ..
fw»t,rxxr.�smA .¢` t ; \' t .yl i5g t 5 ( t � r-Iwu --r - •rt,::a.: '•... �..
YUE WMR:t41i111E.y ;t 1. t'„ � "�• 1 a i
r// r a, t 5\• .-• 1 � � .. v. 1 i. SroY l Y � Y,v,�>, 4 at Y : YA,^. rt�rt11 •'�.r CCi
fi f i ' ` ` �� •..Ir t }ram � i •:. a , , >.. .>.,..a.. ay..r. 3 � a sr0 . .:rr„ �r V.! C.�
PW
Wu . , .A \•t tom. ; % ,vi '� �, i f , ,t^� r' f=� ';�,� ' V ( rae .-x ' • -.'. / Lw�,{ La ,:Y$'" 5 i'i Fl+-�•��, V L {`�\\'�A _ �`\t'-.>:-ii -'- ila-���1�```as�,'• ,, s_— __.y — — .�. �• f
-f --- -- ------ -- - - , ' ! :r 'i..•A" ,, .y • .t * ` ttt i ,:. [('''^`�-'-�-'�� t'iii,;l3�i) -ac u::. <,.:. f *��• � s �
[[C1tt---••iii� __ fi i:� S: a. • 1'•. `•::'. t �'\ `ramj 1'HftiF.RI'ii r iC�
ti 11Y yt�!
/ % i {\ it \ wo <5 onnr h•15s <.w > �3
;_,�- ~1!•`••�..�— -_ i -` t\ A�
\
`�---.—J \ 1 '• i t t t — t + -' � J� ; .� n,:ttrr t• . r,.�..a � ,� �
• j \ r.ca..f t:ytl user N , 1' m ' � ��., � '1 . i �', a t , +. �_ � �t.a, o.t>.....,,,r _ ..,,.. -' is1 `3
lhS.kmG••51l.s asm�.am f'.tu,rf6•y.,17 \} 1'S'" ,!•'^�`• r'� i• }+.easA.,m: Yr 14 }Efll. iY:ri W.]m�`. i.,,' o( j ; •` Y' '
1Uf'1"At6 ( / r,' \ \ 4` ,';' i t i i \ 1: (, : r,: }i:..•..✓:W`r `M1, t i '
M.
11, .. tsra.>L�
R?:."•"` , i •:t �� t 4 h 5 i -i- .•'. _ ti "n, 1 f' t I?F , P
e7..1t175-1..,:,..«.- ._�. •l'`i�,{^ . --- - +;, i i` r�la •i j �;
`� '•t� i•i: ,T F .. tt � i � `tt �t �`• _
( uay. txiul: rl•,snxu \` f )� `:i ".'..', 1Swr ,.1.. �,• P $. '. 1 ( 1 `t ` 7 1 �.-..i 4�-..'.!'�tiii4 SK}' _ _
�J
i f t
.+nn.r '^ W,• ( 'i ��t'oa:Ni%' \:73'G\C.P.TRO{:nut }�.•�...-.__rr_
A o n.ls� tty j
_�_••� }.�• i / ytt .'^i .• :` i i:�:. `�.. Pnxx..,
....._........` i t � ei •tr..,+..i:e...,:.. �xrs.
=f
rf
it ` i i — — -• `" — 3" v,
EOC L7 it)\ ,11tLP •.
T.tMM,al:w!It'rt liL: : �� �' t , ♦ ff �:•, nx>
<i•uM•,:>x.%u.r1Yr' l 5 l �+t'. Y-Is. 1 n Al
iYA nn,J MIT ll\' 'i i i S �ir•�•r w.;, '••. :-••�
\t . � t l M••us.a..;..y:rl, * i. •• A ;.-'.zi
_ t w.^ E..:.. a �.. r.,...
t'dCA.A`f ;t Z .1 1 i.1tta 2.i
AA}\I\ ; it(MI)11. — t � — t AU
i_i\Y, 1'.<1; fttf t1 `. ,l ++.MM......-•..r} ...�
SPT @ Lot I, ,;u .r...-,i �t t vOopment
plan
>_(! air Hr li IUY
LN" I4AR:\60111, (A 1\ihl.
\• i16fIL>>(
--Approximate Standard Penetration Test (SPT) Boring Location
Appendix C - Notes Related to Borings
ma
I
,I
�I
I
I
I
INOTES RELATED TO
CORDS OF TEST BORING AND
RALIZED SUBSURFACE PROFILE
1. Groundwater level was encountered and lrecorded (if shown) following the completion of the soil test boring on
the date indicated. Fluctuations in groundwater levels are common; consult report text for a discussion.
2. The boring location was identified in the field by offsetting from existing reference marks and using a cloth tape
and survey wheel.
3. The borehole was backfilled to site grade
when pavement was encountered,
4. The Record of Test Boring represents our
the soil samples.
5. The Record of Test Boring is subject to thi
text.
boring completion, and patched with asphalt cold patch mix
of field conditions based on engineering examination of
limitntions, conclusions and recommendations presented in the Report
6. "Field Test Data" shown on the Record of Test Boring indicated as 11/6 refers to the Standard Penetration Test
(SPT) and means 1 I hanuner blows drove the sampler 6 inches. SPT uses a 140-pound hammer falling 30 inches.
7. The N-value from the SPT is the sum of tile, hanuncr blows required to drive the sampler the second and third 6-
inch increments.
S. The soil/rock strata interfaces shown on thel Records of Test Boring are approximate and may vary from those
shown. The soil/rock conditions shown oil the Records of Test Boring refer to conditions at the specific location
tested; sail/rock conditions may vary between test locations.
i
9. Relative density for sands!gravels and consistency for silts/clays are described as follows:
SPT
CPT
SANDS/GRAVELS
SPT
CPT
SILTS/CLAYS
BLOWS/FOOT
KG/CM-
RELATIVE DENSITY
BLOWSIFOOT
KG/CM-
CONSISTENCY
0-4
0-16
Very loose 1
0-1
0-3
Very soft
5-10
17-40
Loose
2-4
4-6
Soft
11-30
41-120
Medium Dense
5-8
7-12
Finn
31-50
121-200
Dense
9-15
13-25
Stiff
504-
over 200
1 Very Dense I
16-30
25-50
Very stiff
>30
>50
Hard
10. Grain size descriptions areas follows: 11
NAME
SIZE LIMITS
Boulder
12 Inches or more
Cobbles
3 to 12 Inches
Coarse Gravel
'/ to 3 Inches
Fine Gravel
No. 4 sieve to Y4 inch
Coarse Sand i
No. 10 to No. 4 sieve
Medium Sand
No. 40 to No. 10 sieve
Fine Sand.
No. 200 to No. 40 sieve
Fines
Smaller than No. 200 sieve
11. Definitions related to adjectives used in soil/rock descriptions:
PROPORTION
ADJECTIVE
APPROXIMATE ROOT DIAMETER
ADJECTIVE
<5%
Trace
Less than 1/32"
Fine roots
5%to 12%
Little
1/32" to VV
Small roots
12% to 30%
Some
%" to 1"
Medium roots
30% to 50%
And
Greater than V
Large roots
Organic Soils: Soils containing vegetable tissue in various stages of decomposition that has a fibrous to amorphous texture,
usually a dark brown to black color, and an organic odor.
Organic Content <25%: Slightly to Highly Organic; 25% to 75%: Muck; >75%: Peat
Gfi�
Appendix D - Record of Test Borings
I
I
I�
GF
GFA INTERNATIONAL
521 N.W. ENTERPRISE DRIVE, PORT ST. LuclE, FLORID 34986
PHONE: (772) 924-3575 - FAX: (772) 924-3580
STANDARD PENETRATION TEST BORING (ASTM D-1586)
Client: AJT Construction Consulting, LLC Project No.: 15-0986.00
Lab No.:
Project: Proposed Two -Story Residence - Aequavista Development BLK A Lot 1 Page: 1 of 1
4410 AIA, St. Lucie County, FL Date: 6/2/2015
Elevation: Existing Grade Drill Rig: Simco-24
Water Level: 8 feet after 0 hours Drilling Fluid commenced at depth of 10 feet Field Party: WN/JB
TEST LOCATION SPT @ Lot 1 N27.51474° W1 80.307840
Laboratory
Tests
Depth
Blows/
N
Sample
Layer:
USCS
I Description
Passing
Moisture
Organic
(feet)
6 in.
Value
No.
From/to
No. 200
Content
Content
.............
1
0-2
SP
Brown fine sand
1
--
2
4
1
3
...
2 _ 7
SP
Brown fine sand, trace silt
2-
3
3_
3
6
2
-- 4
... ..........
---
6
5
7
��
---
7
14
3
6
g
---
-
---
g-
7
..10 .........
T- 10
SP
Light brown fine sand, trace shell
11
21
4
8
1-
---
8
-
10
9
---
--i2-
__
22
5
to
-11.
---
11
12
----
....
---
...
13
-------
------
14
_6_
. -
13%2 - 15
SP
Gra i fine sand, trace silt, little shell
--
8
15...
9
........
17
.
6
16
----
---
I
--- 17
..............
I
-_ 18
..............
19
- 6
--.-_
18'/z - 20
SP
Light brown fine sand, some shell
__
7
14
7
I
GFA j INTERNATIONAL
521 N.W. ENTERPRISE DRIVE, PORT ST. LUCIE, FLORIDA 34986
PHONE: (772) 924-3575 - FAX: (772) 924-3580
STANDARD PENETRATION TEST BORING (ASTM D-1586)
Client: AJT Construction Consulting, LLC I
Project No.: 15-0986.00
Lab No.:
Project: Proposed Two -Story Residence - Acgnavista Development BLK A Lot 1
Page: 2 of 2
4410 AIA, St. Lucie County, FL
Date: 6/2/2015
Elevation: Existing Grade
Drill Rig: Simeo-24
Water Level: 8 feet after 0 hours Drilling Fluid commenced at depth of 10 feet
Field Party: WN/JB
TEST LOCATION SPT rr Lot 1 N27.514740 W80.307840
Laboratory Tests
Depth
Blows/
N
Sample
Layer:
USCS
I Description
Passing
Moisture
Organic
(feet)
6 in.
Value
No.
From/to
No. 200
Content
Content
20
--------------
21
----
22
---
---
23
..............
35
23%2 - 25
SP
Light gray fine sand, some shell, little cemented
24
-
50/5"
_ --
sand
-- _
2n_
........--.
�r
50/5
8
26
..............
27
---
--
- -- 78
..............
28%2 - 30
SP
Gray fine sand, trace silt and shell
-
_.25 _
. _ .
29-30
34
63
9
i
31
..............
33
•...
---
33%2 - 35
SP
Light gray fine sand, trace silt, some
34
--10
13
-- -
cemented sand
35
16
--..
29
...
10
36
..............
37
---
---
38
----
---
i
5
38%2 - 40
SP,SP-SM
Brown fine sand, trace/little silt and clay
39
l'
L
-- 7�
.._..
2
9
11
Boring terminated at 40 feet
I
I
Appendix E it Discussion of Soil Groups
60
DISCUSSION OF SOIL GROUPS
COARSE GRAINED SOILS
GW and SW GROUPS. These groups comprise well -graded gravelly and sandy
soils having little or no plastic fines (less than percent passing the No. 200 sieve).
The presence of the fines must not noticeably change the strength characteristics
of the coarse -grained friction and must not interface with it's free -draining
characteristics.
i
GP and SP GROUPS. Poorly graded gravels and sands containing little of no
plastic fines (less than 5 percent passing the No. 200 sieve) are classed in GP
and SP groups. The materials may be called uniform gravels, uniform sands or
non -uniform mixtures of very coarse materials and very fine sand, with
intermediate sizes lacking (sometimes called skip -graded, gap graded or step -
graded). This last group often results from borrow pit excavation in which gravel
and sand layers are mixed.
GM and SM GROUPS. In general, ithe GM and SM groups comprise gravels or
sands with fines (more than 12 perrcent the No. 200 sieve) having low or no
plasticity. The plasticity index and liquid limit of soils in the group should plot
below the "A" line on the plasticity chart. The gradation of the material is not
considered significant and both well and poorly graded materials are included.
GC and -SC GROUPS. In general, the GC and SC groups comprise gravelly or
sandy soils with fines (more than 12',percent passing the No, 200 sieve) which
have a fairly high plasticity. The liquidl limit and plasticity index should plat above
the "A" line on the plasticity chart.
FINE GRAINED SOILS
ML and MH GROUPS. In these groups, the symbol M has been used to
designate predominantly silty material. ;The symbols L and H represent low and
high liquid limits, respectively, and an arbitrary dividing line between the two set
at a liquid limit of 50. The soils in the ML and MH groups are sandy silts, clayey
silts or inorganic silts with relatively low`; plasticity. Also included are loose type
soils and rock flours.
CL and CH GROUPS. In these groups the symbol C stands for clay, with L and
H denoting low or high liquid limits, with the dividing line again set at a liquid of
50. The soils are primarily organic clays,. Low plasticity clays are classified as
CL and are usually lean clays, sandy clays or silty clays. The medium and high
plasticity clays are classified as CH. These include the fat clays, gumbo clays
and some volcanic clays.
9-
OL and OH GROUPS. The soil in the OL and OH groups are characterized by
the presence of organic odor or color, hence the symbol O. Organic silts and
clays are classified in these groups. The materials have a plasticity range that
corresponds with the ML and MH groups.
HIGHLY ORGANIC SOILS
i
The highly organic soils are usually very soft and compressible and have
undesirable construction characteristics. Particles of leaves, grasses, branches,
or other fibrous vegetable matter are common components of these soils. They
are not subdivided and are classified into one group with the symbol PT. Peat
humus and swamp soils with a highly organic texture are typical soils of the
group.