HomeMy WebLinkAboutBUILDING PLAN PAGE 1-15THESE PLANS ARE NOT FOR CONSTRUCTION UNLESS STAMPED "Construction Set", DATED, SIGNED AND SEALED BY THE ENGINEER. ALL CONSTRUCTION SHALL BE IN COMPLIANCE WITH ALL JURISDICTIONAL PERMITS, CONDITIONS AND CONTRACT DOCUMENTS. H Ee ROOFING 0 ROOFING MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS REQUIREMENTS TO MEET THE SPECIFIED DESIGN WIND SPEED UPLIFT REQUIREMENTS. ROOF ZONE & FLOOR POSITIVE PRESSURE NEGATIVE PRESSURE Zone 1 — 2nd Floor 29.8 psf 47.4 psf Zone 2 — 2nd Floor 29.8 psf 82.4 psf Zone 3 — 2nd Floor 29.8 Psf 82.4 psf PATIO BEAM REFER TO SCHEDULE SHEET 5-4 TOP @ -O'-G" B.E.F. (23.5 N.A,V.DJ FRANGIBLE MASONRY WALL STRUCTURAL CONCRETE COLUMN BEYOND TYPICAL PILE d TRANSITION CAP - REFER TO PLANS E DETAILS FOR SPECIFICATIONS CONTRACTOR SHALL COORDINATE ALL DETAILS AND ELEVATIONS WITH ARCHITECT PRIOR TO CONSTRUCTION. COIUrPONEN TS & CLADDING EXTERIO WALL COMPONENTS SHALL BE ATTACHED PER MANUFACTURERS' SPECIFICATIONS TO MEET THE WIND PRESSURES SHOWN FIRST FLOOR ON PLAN AT RIGHT. ALL CLADDING SHALL MEET OF EXCEED THE DESIGN PRESSURES LISTED BELOW.. POSITIVE NEGATIVE WALL ZO E PRESSURE PRESSURE Zone 4 (interior zone) 51.7 psf 56.1 psf Zone 5 (end zone) 51.7 psf 69.3 psf 1st/2n� FLOOR a — 5.0' (10% of 50' least horz. dimension) 3rd FL OR a = 3.0' (10% of 30' least horz. dimension) COMPONENT/CLADDING CALCULATIONS BASED ON ASCE 7-10 with 170 Vult, EXPOSURE D ENCLOSED, 30' MEAN HEIGHT, 5:12 PITCH, ith Kd=0.85 using the ALLOWABLE STRESS DESIGN method z g V OF R TO ARCH ITECTU PAL WINGS FOR HANDRAILS GUARDRAIL DETAILS SPECIFICATIONS #4 BOTTOM STEEL @ 10" o. c. EXTEND INTO BEAM G" max. #5 BOTTOM STEEL @ 8" o.c. (2) #4'5 (G" SEPARATION) TYPICAL AT EACH TREAD REFER TO ARCHITECTURAL - #3 TIE BAR(typcal) DRAWINGS FOR TREAD AND .s RISER DETAILS c' 8 F Co TYPICAL 8"x 14" MIN. « deep CONCRETE BEAM � wl 5'S #3 STI 4 #3 STIRRUPS @ I G" o. c. n CONCRETE z- STEPS :Si s � LANDING (STRUCTU SLAB) - REFER TO I .-5 f", SECTION FOP DETP A -TYPICAL FILLED CELL....�"` COULMN (beyond) TYPIClad�ca r'x 14' MIN. deep CONCRETE BEAM Z w/ (4) #5's. $ #3 STIKFUPS @ I G" o.c. v TYPICAL FILLED CELL COULMN (beyond) TYPICAL 3" min. PROTECTION FOR ALL REINFORCEMENT STEEL N N N I G"x 1 2" deep PAD FOOTING r w/ (3) #55 (each dray) STEPS UPPER SECTION PERMIT DRAWING - PILING, CAP 4 COLUMN (typical) \Y ------ -------------- I G" square x 1 2" deep PAD FOOTING w/ (3) #5'5'(each way) - 8"x 1 2" MIN. deep CONCRETE BEAM (above) w/ (4) #55, - REFER TO SECTION FOR DETAILS ZATICSLAB A (ABOVE) STUB STEPS STEEL INTO BEAM G" max. - REFER TO—, SECTION FOR DETAILS :BEAM ABOVE (typical)-\ 1 R\\\\Y - - - - - - -- BEAM (BEYOND) - REFER TO LOWER SECTION FOR DETAILS PATIO BEAM - REFER TO SCHEDULE SHEET 5-4 TOP @ -O-G' B.F.F. (23.5 N.A.V.D.) _..__. FRANGBLLE FOOTING 12"x 12" deep CONTINUOUS FOOTING w/ (2) #5'5 cont. j 8'-0" -- ....... . .... - TYPICAL FILLED CELL COLUMNS w/ (1) #5 vert. O I I I I_ m FRANGIBLE FOOTING 2"x 12" deep CONTINUOUS FOOTING w/ (2) #5'5 cant. -� -- 1- LL I I I ro ---j O FINAL TREAD FOOTING 1 2"x20" deep CONCRETE FOOTING (1 2" below grade) REFER TO SECTION EXTERIOR STEPS FOUNDATION SCALE: I/2" = 1'-0" FRANGIBLE MASONRY WALL STRUCTURAL CONCRETE COLUMN BEYOND #5 BOTTOM STEEL @ 8" o.c. EXTEND INTO BEAM G" may. #5 BOTTOM STEEL @ 8" o,c. STRUCTURAL CONCRETE SLAo.c. E.W. (TYPICAL( � TREAD AT EACH TREAD TYPIBCAL 8'x 14? MIN-. deep "°°• , ... v.° * •- REFER TO ARCHITECTURAL CONCRETE BEAM z #3 TIE BAR (typical) DRAWINGS FOP TREAD AND w/ (4 g . ' f RISER DETAILS #3 STIRRUPS @ I G"` o.c.. r . - 1-8 TYPICAL 8"x 14" MIN. deep CONCRETE BEAM '�_�----' w/ (4) #5'5 # TYPICAL FILLED CELL �. " �' #3 STIRRUPS @ I G" o.c. COULMN (beyond) ,`°•.. a 0 0 U5 S w N11110l! Q= � kl N �v b � 0 to � 4-4 ✓ . rl U ' O 1.4 CID rz� w •� .. z eye r • • ' ' FINAL TREAD FOOTING r .. � 2500 PSl mm. CONCRETE FRANGIBLE CONTINUOUS STEPS FOOTING— _ � ' - '� • � `"° ' � 12"x20" deep CONCRETE FOOTING w/ (4) #5'5 b #3 STIRRUPS @ I G" o.c. � ,N O .� =" � O TYPICAL PILE * TRANSITION TYPICAL 3" min. 1�8 CAP BEYOND PROTECTION FOR ALL r^ _-_.REINFORCEMENTSTEEL°_.,, • � � -' -I G" G-I G20" I G"x I�daep PADF� #5 BOTTOM STEEL @ &c.cw/ (3) #5'5 (each way) EXTEND INTO BEAM G" max. EXTERIOR STEPS LOWER SECTION SCALE: 112" = -O" N � O 0 REFER TO ARCHITECTURAL DRAWINGS FOR LANDING O ,� DETAILS B SPECIFICATIONS PROJECT NO. 18-022 SHEET 5-11 C n GYP-CRETE OVER PLYWOOD 5UBFLOOR (2) 2.8 P.T. LEDGER FOR 5TRINGER5 - SECURE TO CONCRETE BEAM w, (2) 1/4" TAPCON5 @ I W o.c. •--^ TRU55 LEDGER, REFER TO + TYPICAL WALL SECTION #- PLANS FOR DETAILS TREADS < RISERS per WOOD FLOOR TRUSSES ARCHITECT - HBZ PER / BY OTHERS '- F ARCHITECT or BUILDER- V REFER TO ARCHITEC ORAL CONCRETE BEAM - REFER PLANS FOR DETAILS TO TYPICAL WALL SECTION • -a' E PLANS FOR DETAIL5 & 12 STRINGERS @ 16" o.c. MAX: 1 FINISH PER ARCHITECT or BUILDER:- REFER TO ARCHITECTURAL PLANS POP DETAILS -COORDINATE FINISH HEIGHT w/ ARCHITECTURAL DRAWINGS 2xG JOISTS @ 10 oz. MAX. _ 1 X 2xG JOIST (cleat) - 1 1 1 NOTCH STRINGER AS NECESSARY [ 11 MASONRY 5HEARWALL - REFER TO TYPICAL WALL SECTION $ PLANS FOR DETAILS a r CONCRETE BEAM -REFER TO TYFOAL WALL SECTION $ PLANS FOR DETAILS FRANGIBLE MASONRY WALL T REFER TO TYPICAL WALL SECTION $ PLANS FOR DETAILS DOUBLE 2.4 TOP PLATE - i COORDINATE HEIGHT w/ 1 1 E ACHITECTURAL DESIGN f j I 11 f I I i!E I I( 11 fl fI I 114 2x4EPARTITION I FRAMING 1 1[1 BALLOONFRAME1 I 11 € TO STRINGERS 2x4 BEARING I WALL f DOUBLE 1i 1 1 STUD 11 I 16" ox, FRAMING I 1 (bearing point) it II ii I , 2x4 F.T I• .I I, 1 1 { I iOE w/ 1/4" 1 � I TAPCO 1 12" o.c. MAX.: ! 11 II 1 i � 4" frangible SLAB @ -I I'-C" B.F.F. INTERIOR STEPS SECTION - lower SCALE: 1 /2" = 1'-0" TREADS $ RISERS per ARCHITECT - FINISH PER ARCHITECT or BUILDER - REFER ITO LS ARCHITECTURAL PLANS FOR DETAILS 2.12 5TRINGER5 @ I G" o.c. MAX. M M15H PER ARCHITECT or BUILDER - REFER TO ARCHITECTURAL PLANS FOR DETAILS - COORDINATE FINISH HEIGHT w/ ARCHITECTURAL DRAWINGS i 24 JOISTS @ I G" o.c. MAX. 2.5 LEDGER FOR STRINGERS - SECURE TO 24 LANDING FRAMING GYP-CRETE OVER CONCRETE STRUCTURAL SLAB I I CONCRETE BEAM - REFER TO TYPICAL WALL SECTION # PLANS FOR DETAILS CONSTRUCTION SET CONTRACTOR SHALL COORDINATE ALL DETAILS AND ELEVATIONS WITH ARCHITECT PRIOR TO CONSTRUCTION. 4.4 P.T. F05T TO LANDING (above) GYP CRFTE OVER PLYWOOD 5UBFLOOR - TRU55 LEDGER- REFERTO • TYPICAL WALL SECTION £ 5 FOR DETAI 5 PLAN DOUBLE STUD COLUMN \ WOOD FLOOR TRUSSES TO LANDING (above) i ° BY OTHERS CONCRETE BEAM - REFER FINISH PER ARCHITECT or LiloffR REFER TO ARCHITECTURAL TO TYPICAL WALL. SECTION PLANS FORD /�LS # PLANS POP DETAILS COORDINATE FINISH H w/� , W ARCHITECTURAL DRAWffNG5 2x6 BAND JOIST 2xG J015T5 @ I G" oA. MAX. 2x8 LEDGER FOR ----- STRINGERS -SECURE iO BEARING WALL FRAMING 2x4 BEARING WALL 16" o.c. FRAMING DOUBLE 2x4 TOP PLATE - COORDINATE HEIGHT w/ ACHITECTURAL DESIGN 2x4 P.T. SHOE w/ /4" TAPCON5 @ 2" o. c. MAX. 2x4 P,T. CLEAT5 w/J 26 P.T. JCI5T TO FOR FIRST STEP d SUPPORT LANDING 1/4" TAPCON5 into FRAMING - RIP TO APPROPRIATE DEPTH - REFER TO FRANGIBLE SLAB ACHITECURAL DRAWINGS FOR HEIGHT # FIN15H REQUIREMENTS INTERIOR STEPS SECTION - SCALE: 1/2" = 1'-0" 2xG @ G" 0.C. INTERNI DIATE I 2x8 LEDGER FOR 2x8 LEDGER FOR 5TRINGER5 5TRINGER5 _ _ _BALLOON FRAME PARTITIONN�below Stinger)_ 2x4 BEARING WALL I G" D.C. FRAMING DOUBLE STUD COLUMN 2x8 P.T. J015T TO FOR FIR5T STEP - BALLOON FRAME TO B SUPPORT LANDING FRAMING - RIP NEXT LANDING TO APPROPRIATE DEPTH - REFER TO ACHITECURAL DRAWINGS FOR HEIGHT FINISH REQUIREMENTS INTERIOR STEPS FRAMING -lower SCALE: 1/2" = -0' 2xG @ I G" o.c. 44AX. INTERMEDIATE L NDING v g o z IL Q_ 0 N z N 0 N 5TRUCTURAL 5LA LANDING - REFER 10 LOWER BEAM PLA (2) 2x8 P.T. LEDGER -ATTACH TO MASONRY 511EARWALL w/ (2) I /W TAPCON5 @ I G" o.c. MAX. MASONRY 5HEARWALL - REFER TO TYPICAL WALL, SECTION PLANS FOR DETAIL5 (2) 2x8 P.T. LEDGER -. ATTACH TO MASONRY 51-1 W/ (2) 1/4" TAPCON5 @ I Or o.c. MAX. MASONRY 5HEARWALL - REFER TO TYPICAL WALL SECTION 8 PLANS FOR DETAILS 4x4 P.T. P05T 5UPPORT FOR NEXT LANDING CONCRETE BEAM - REFER TO TYPICAL WALL SECTION PLAN5 FOR DETAILS (2) 2x8 P.T. LEDGER FOR STRINGERS - SECURE TO CONCRETE BEAM W/ (2) 1/4" TAPCON5 @ I G" ox. THESE INTERIOR STAIRS DETAILS ARE INTENDED TO DEMONSTRATE STRUCTURAL ASPECTS OF CONSTRUCTION. THE CONTRACTOR SHALL COORDINATE WITH THE ARCHITECT WITH REGARD TO FINISH MATERIALS AND ADJUST HEIGHTS AND DEPTHS ACCORDINGLY. GYP-CRETE OVER PLYWOOD 5UBFLOOR WOOD FLOOR ( " TRUSSES BY OTHERS 11 CONCRETE BEAM - REFEP� TO TYPICAL WALL SECTION $ PLANS FOR DETAILS MAEONRY.5HEARWALL - REFER TO TYPICAL WALL SECTION E� _ PLANS FOR DETAILS 2xG JOISTS @ 16 o c MAX (2) 2x8 P.T. LEDGER - ATTACH TO MA50NKY 5HEAKWALL M (2) 1 /4" TAPCON5 @ I G" o. c. MAX. 2x8 P.T, LEDGER SECURE TO CONCRETE w/ (2) 1/4"TAPCONS@ 12'o.c. PADOUTLANDING w/ (2) 2,1 L TREADS $ RISERS per ARCHITECT FINISH I'ER. ARCHITECT o. BUILDER REFER TO ARCHITFCTURAL PAN! FOR DETAILS 2x 12 STRINGERS @ I G" o.c. MAX. (2) 2x8 DOUBLE STUD COLUMN (frorn landing below) 2xG BAND LOOT (treat) - NOTCH STRINGER AS NECESSARY TREADS # RISERS per ARCHITECT - FINISH PER ARCHITECT or BUILDER - REFER, TO ARCHITECTURAL PLANS FOR DETAIIS 2.12 5TRINGER5 @ 10 FINISH PER ARCHITECT or BUILDER - REFER TO ARCHITECTURAL PLANE FOR DETAILS COORDINATE FINISH HEIGHT ARCHITECTURAL DRAWINGS 5 TYPICAL MA50NRY WALL REFER TC TYPICAL WALL SECTION # PLANS FOR 2xG JOISTS @ I G" o.c. MAX. DETAILS (2) 2x8 P.T. LEDGEK - ATTACH TO MASONRY 5HEARWALL/ (2) 1/4' L TAFCON5 @ I G" o,c. MAX. (2) 4x,5 P.J. LEDGER - A ACH O TYPICAL MASONR WAL w/ (2) 114" TAPCC 5 @ 1 " o.c. MAX. THESE PLANS ARE NOT FOR CONSTRUCTION UNLESS STAMPED "Construction Set", DATED, SIGNED AND SEALED BY THE ENGINEER. ALL CONSTRUCTION SHALL BE IN COMPLIANCE WITH ALL JURISDICTIONAL PERMITS, CONDITIONS AND CONTRACT DOCUMENTS. STRUCTURAL SLAB (front balcony) CONCRETE STRUCTURAL SLAB - refer to plans C detatle y.. CONCRETE BEAM - REFER TO TYPICAL WALL SECTION # PLANS FOR DETAILS `—FRANGIBLE MASONRY WALL REFER TO TYPICAL WALL SECTION $ PLANS FOR DETAILS —2xG LEDGER FOR STRINGERS - 5ECURETO 2x0 LANDING FRAMING 2x 125TANGER5 @ I G' o.c. MAX. 2x F T. FIRST R15ER - RIP TO REQUIRED DEPTH 2a4 P.T, CLEAT - SECURE TO 5RUCT'URAL SIRS w/ 1 /4" TAPCON5 @ I Z o,c. CONCRETE BEAM - PETER TO TYPICAL WALL SECTION t PLANS FOR DETAILS CONCRETE 5TP.UCTURAL SLAB refer to plans # UetJI15 t—_ J a.-O SIMPEON GA2 (or CONCRETE BEAM - REFER egaail w/ (4) SIDE TO TYPICAL WALL SECTION SCREWS- TYPICAL $ PLANS FOR DETAILS AT EACH .STRINGER INTERIOR, STEPS SECTION - upper SCALE: 1/2" = I'-0' FINISH PCR ARCHITECT or BUILDER - REFER. TO ARCHITECTURAL. PLANS FOR DETAILS - COORDINATE `nU5N HEIGHT w/ ARCHITECTURAL DRAWINGS 2xG BAND JOIST ........... 2.8 LEDGER FOR STRINGERS - 5ECUR,E TO BEARING WALL FRAMING DOUBLE STUD COLUMN (from landing below) GYP-CRETE OVER PLYWOOD 5UBFLOOP TRU55 LEDGER - REFER TO— • a TYPICAL WALL SECTION # PLANS FOR DETAILS WOOD FLOOR TRUSSES + BY OTHERS R CONCRETE BEAM - REFER TO TYPICAL WALL SECTION # PLANS FOR DETAILS (2) 2x8 LEDGER 4x4 F.T. COST (from land ng oelow) INTERIOR 5TEP5 SECTION -upper SCALE: 1 /2" = -O" IV 2xG.@ 16 o.c. MAX. 2x 12 5TRINGER5 @ I G"o.c. MAX. INTERMEDIATE LANDING 2xG LEDGER FOR ' STRINGERS i (1 —2x4 CRIPPLE WALL I i, I Or S.C. FRAMING 2x 1.2 RINGERS 2x4 P.T, SHOE @.I G .c. MAX. . 5TRUCTURAL5LAB- '. LANDING - REFER TO LOWER BEAM PLAN. .. .. CONCRETE BEAM - - REFER TO TYPICAL WALL SECTION B PLAN5 FOR DETAILS INTERIOR STEPS FRAMING - u I'.. s(-,Al F: 1121 = 1 T-O-I EXTEND LEDGER # ATTACH STRINGER DOUBLE STUD COLUMN - from landing below 2xG BAND J015T over (2) 2x8 LEDGER 51MPS0N GA2 FRAMING ANGLE AT EACH STRINGER BUILT-UP LANDING REFER TO SECTION DETAIL CONCRETE BEAM - REFER TO TYPICAL WALL SECTION I$ PLAN5 FOR DETAILS � (2) 2x8 P.T. LEDGER - ATTACH TO MASONRY 5HEARWALL W/ (2) 1/4" TAPCON5 @ I G" ox. MAX. DING �4x4 P.T. POST - from landing below i o I 0 0) I N O N 0 �P- Z En N O Q O Ld K 4 z 00 N W f O C) a W 4 W W N Y Q O M ONe N Z n CL 0 a o 00 Z � W � U J 0 0 1 U o U N D%: 001 bOq n N U M yS W CM E—j 4 O v �c r A. OQ�� C/� W wz �-LR W LT,o L, z 4, as < H� w w a w o �oU n 'a1 V z 1i I H U p 00 RI J 0. 0 114 z i.l Q W i vl 4-1 � �4 w O x o U O V.5 � a � PROJECT NO. 18-022 SHEET S-12 11B3 IBRIEW L MQ)H93 ABV. ABOVE ACOUS. ACOUSTICAL ADJ. ADJUSTABLE AL. ALUMINUM APPROX. APPROXIMATE BD. BOARD BLDG. BUILDING 4 BLK. BLOCK ' BOT. BOTTOM • CAB. CABINET '& CER. CERAMIC C.I. CASTIRON CLR. CLEAR COL. COLUMN CONC. CONCRETE CONN. CONNECTION CONT. CONTINUOUS CTSK. COUNTERSUNK DECOR. DECORATIVE DET. DETAIL D.F. DOUGLAS FIR DIA. DIAMETER DIM. DIMENSION ON. DOWN D.S. DOWN SPOUT DWG. DRAWING EA. EACH EL. ELEVATION ELEV. ELEVATOR ELEC. ELECTRICAL EQ. EQUAL EXH. EXHAUST EXP. EXPANSION EXT. EXTERIOR EXIST. EXISTING F.F. FINISH FLOOR FLASH. FLASHING FLUOR. FLUORESCENT FT. FOOT/FEET FTG. FOOTING GA. GAUGE GALV. GALVANIZED GL. GLASS GR. GRADE GYP. GYPSUM H.B. HOSE BIBB H.C. HOLLOW CORE R.O. ROUGH OPENING HDWD. HARDWOOD RWD. REDWOOD HDWE. HARDWARE R.W.L. RAIN WATER LEADER HGT. HEIGHT S.C. SOLID CORE HORIZ. HORIZONTAL SCHED. SCHEDULE I.D. INSIDE DIAMETER SHT. SHEET INCAND. INCANDESCENT SIM. SIMILAR INSUL. INSULATION SQ. SQUARE INT. INTERIOR SST. STAINLESS STEEL JT. JOINT STD. STANDARD LAM. LAMINATE STL. STEEL LAV. LAVATORY STOR. STORAGE LOC. LOCATION STRUCT. STRUCTURAL MAX. MAXIMUM SUSP. SUSPENDED MECH. MECHANICAL SYM. SYMMETRICAL MET. METAL T.C. TOP OF CURB MFR. MANUFACTURER TEL. TELEPHONE MIN. MINIMUM T&G TONGUEANDGROOVE MISC. MISCELLANEOUS THK. THICK M.O. MASONRY OPENING T.O.C. TOP OF CHIMNEY MTD. MOUNTED T.O FR. TOP OF FRAMING MUL. MULLION T.O.L. TOP OF LEDGER N.I.C. NOT IN CONTRACT T.O.P. TOP OF PLATE NO NUMBER T.O PL. TOP OF PLATE N.T.S. NOT TO SCALE TYP. TYPICAL O.A. OVERALL U.O.N. UNLESS OTHERWISE OBS. OBSCURE NOTED O.C. ON CENTER VERT. VERTICAL O.D. OUTSIDE DIAMETER VEST. VESTIBULE OFF. OFFICE V.G.D.F. VERTICAL GRAIN OPNG. OPENING W/ WITH OPP. OPPOSITE W/O WITHOUT PL. PLATE W.C. WATER CLOSET PLAS. PLASTER WD. WOOD PLYWD. PLYWOOD WOW. WINDOW PR. PAIR W.H. WATER HEATER PRCST. PRECAST WSCT. WAINSCOT P.T. PRESSURE TREATED WT. WEIGHT PTN. PARTITION SYMB. SYMBOLS Q.T. QUARRY TILE AND RAD. RADIUS ANGLE REINF. REINFORCE @ AT REQ. REQUIRED CENTER LINE RM. ROOM DIAMETER OR ROUND # POUND OR NUMBER PROJECT TEAM ARCHITECT: RANDALL STOFFT ARCHITECTS 42 NORTH SWINTON AVE., SUITE 1 DELRAY BEACH, FL. 33444 561-243-0799(T) CONTACT: GARY STOFFT EMAIL: gary@stofft.com STRUCTURAL ENGINEER KNIGHT, McGUIRE & ASSOCIATES, INC 80 ROYAL PALM POINTE, SUITE 401 VERO BEACH, FL 32960 ` TEL: 772-56M505,FAX: 772-569-1455 CONTACT: David Knight, P.E. EMAIL: david@knightmcguire.com u up yr/ (K quz Awnovl� DBU # ,�,H �11 I DD931012D PIMIHD4DDD BUILDING CLASSIFICATION: CODE EDITIONS: TWO STORY SINGLE FAMILY RESIDENCE Florida Building Code (FBC) 2017 FBC 2017 CHAPTER 3, GROUP R.3 OCCUPANCY National Electrical Code (NEC) 2014 TABLE 503 CONSTRUCTION TYPE V-B WIND LOADS AS PER FBC 2017 EDITION AND ANSI/ASCE 7-10 THE FOLLOWING DESIGN PARAMETERS ARE REPEATED FROM THE STRUCTURAL DRAWINGS (SEE STRUCTURAL PLANS FOR ADDITIONAL STRUCTURAL NOTES/DESIGN PARAMETERS) CODE EDITION: FLORIDA BUILDING CODE 2017 BUILDING DESIGNED AS: ENCLOSED, RIGID WIND EXPOSURE CLASSIFICATION: D WIND SPEED DESIGN: 160 mph Vult INTERNAL PRESSURE COEFFICIENT +-0.18 Kd 0.85 a MEAN ROOF HEIGHT BUILDING CATAGORY II L. n ROOF LIVE LOAD: 30 PSF TOP CHORD DEAD LOAD: 15 PSF BOT CHORD DEAD LOAD: 10 PSF FLOOR LIVE LOAD: 40 PSF FLOOR DEAD LOAD: SUPERIMPOSED 25 PSF MIN. SOIL BEARING. PRESSURE: 2,500 PSF -, SHUTTERS: NO IMPACT RESISTANT ASSEMBLY: YES •,i a IS A CONT. LOAD PATH PROVIDED YES .. .� X COMPONENT & CLADDING YES r e � I y h: c ° ° wm,%V DD7nDD HQTIRg OCR DIFDOLD��ODD CaD1D DDDD D DDDDDDDDDD4D ARCHITECT'S STATUS: EARTH WORK: TRUSSES ROUGH CARPENTRY: TIMBER A. PERFORM ALL WORK IN CONFORMANCE WITH THE FINAL SOILS, COMPACTION AND A. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR AND WILL NOT HAVE CONTROL OR GEOLOGICAL REPORTS. A. THE TRUSS L AYOUT SHOWN ON CONSTRUCTION DOCUMENTS IS SCHEMATIC IN A. ALL BEAMS INSTALLED WITH CROWN UP UNLESS OTHERWISE NOTED. CANTILEVERED A. STRUCTURAL TIMBER TO BE SOUTHERN PINE #2 (MIN.) STRESS GRADE LUMBER OR ' CHARGE OF CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR NATURE. HOWE JER, THE SUPPORTING SUPERSTRUCTURE HAS BEEN DESIGNED UNDER BEAMS SHALL BE INSTALLED WITH CROWN DOWN. APPROVED EQUAL. THE MIN. ALLOWANCE PROPERTIES ARE AS FOLLOWS: PROCEDURES, OR FOR THE SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH B. FOUNDATIONS SHALL BE MONOLITHIC OR SPREAD FOOTINGS BASED ON A SOIL THE ASSUMPTICN THAT THE FRAMING SCHEME SHOWN WILL CLOSELY PARALLEL THE ' FB = 1,150 PSI FV = 90 PSI E = 1,600,000 PSI AND PRESSURE TREATED FOR USE AGAINST THE WORK, AND HE OR SHE WILL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S FAILURE BEARING CAPACITY OF 2500 PSF. FINAL WRITTEN VERIFICATION SHALL BE SENT TO THE FINAL TRUSS M . LAYOUT. THIS FRAMING SCHEME (DIRECTION OF TRUSSES, MAJOR G.T. B. 3" MINIMUM BEARING BY BEAMS AND GIRDERS ON MASONRY OR CONCRETE. CONCRETE AND MASONRY. TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THE OWNER AND ARCHITECT PRIOR TO THE START OF CONSTRUCTION. BEARING POINTS, CAN BE MODIFIED ONLY AFTER OBTAINING PERMISSION FROM ARCHITECT SHALL NOT BE RESPONSIBLE OR HAVE CONTROL OR CHARGE OVER THE ACTS O AFTER STANDARD CLEANING AND GRUBBING HAS BEEN COMPLETED AND APPROVED, THE PRIME PRC FESSIONAL OF RECORD WHO MUST REVIEW PROPOSED CHANGES AND C. PROVIDE 4"X4" POSTS OR (2) 2"X4" STUDS MINIMUM UNDER ALL BEAMS AND HEADERS B. ALL TIMBER AND TIMBER CONSTRUCTION SHALL COMPLY WITH SPECIFICATIONS AND OR OMISSIONS OF THE CONTRACTOR, SUBCONTRACTORS OR ANY OF THEIR AGENTS OR APPLY VIBRATORY COMPACTOR WITH A MINIMUM OF FOUR PASSES. MAKE STRUCTUI ZAL REVISIONS ACCORDINGLY. FINAL SIGNED AND SEALED ENGINEERING UNLESS OTHERWISE NOTED. CODES AS SPECIFIED BELOW: EMPLOYEES, OR ANY OTHER PERSONS PERFORMING ANY OF THE WORK. TRUSS DRAWIN S MUST BE SUBMITTED TO THE ARCHITECT FOR REVIEW PRIOR TO AMERICAN INSTITUTE OF TIMBER CONSTRUCTION, TIMBER CONSTRUCTION MANUAL; ,. D, SOIL SHALL BE COMPACTED TO 95% MODIFIED PROCTOR (ASTM D1557) TO A DISTANCE POURING OF FO JNDATION. D. ALL SUB -SILLS, OVER 8'4" IN LENGTH SHALL BE DOUBLE 2"X4"s. NATIONAL FOREST PRODUCTS ASSOCIATION, NATIONAL DESIGN SPECIFICATION FOR CODES. OF 5 FEET BEYOND ALL BUILDING EDGES. AT LEAST ONE FIELD DENSITY TEST SHALL BE WOOD CONSTRUCTION; AMERICAN PLYWOOD ASSOCIATION, PLYWOOD DESIGN f PERFORMED FOR EACH 2500 SQUARE FEET OF AREA. DENSITY TESTS ARE TO BE MADE 12 B. WOOD ROOF TRUSSES ARE TO BE DESIGNED FOR THE WOOD FABRICATOR BY A E. DOUBLE 2"X4"s, SPIKED TOGETHER w/ 16d'S @ 5" O/C STAGGERED MAY BE USED IN LIEU SPECIFICATION; AMERICAN WOOD PRESERVERS ASSOCIATION STANDARDS; NATIONAL A. ALL CODES HAVING JURISDICTION SHALL BE OBSERVED STRICTLY IN THE INCHES BELOW THE COMPACTED SURFACES. RESULTS OF PROCTOR TEST(S) AND FIELD PROFESSIONAL PECIALTY ENGINEER REGISTERED IN THE STATE OF FLORIDA. TRUSS OF 4"X4" POSTS WHERE CONTAINED WITHIN WALLS UNLESS SPECIFICALLY NOTED LUMBER MANUFACTURERS ASSOCIATION, NATIONAL DESIGN SPECIFICATION FOR STRESS e CONSTRUCTION OF THE PROJECT, INCLUDING ALL APPLICABLE STATE, CITY AND COUNTY DENSITY TESTIS) SHALL BE FURNISHED TO THE ARCHITECT/ENGINEER. FABRICATOR TO PROVIDE PRE -FABRICATED HANGERS AS REQUIRED. OTHERWISE ON PLANS. GRADE LUMBER AND ITS FASTENINGS. BUILDING, ZONING, ELECTRICAL, PLUMBING, LIFE SAFETY AND FIRE CODES. CONTRACTOR E FILL SHALL BE CLEAN, WELL GRADED SAND, CLASSIFICATION SW PER ASTM D2487-69 C. DESIGN, FAB (CATION, AND INSTALLATION OF WOOD TRUSSES AND SHEET METAL F. ALL LUMBER IN DIRECT CONTACT WITH STEEL OR CONCRETE SHALL BE PRESSURE C. ALL TIMBER CONNECTIONS ARE TO BE MADE USING PREFABRICATED CONNECTORS. SHALL VERIFY ALL CODE REQUIREMENTS AND BRING ANY DISCREPANCY BETWEEN THE (75) WITH LESS THAN 12% PASSING 200 SIEVE. FILL MATERIAL SHALL BE PLACED IN LIFTS CONNECTORS S ALL BE IN ACCORDANCE WITH THE FOLLOWING STANDARDS. TREATED, HAVE AN APPROVED SEPARATING MATERIAL OR HAVE A GALVANIZED ANCHOR TOE NAILING WILL NOT BE PERMITTED. SUBMIT MANUFACTURER'S DATE FOR APPROVAL. CODES AND THE CONSTRUCTION DOCUMENTS TO THE ATTENTION OF THE ARCHITECT. OF NOT MORE THAN 12" AND COMPACTED AS ABOVE. SEAT. FASTENERS TO BE AS MANUFACTURED BY USP OR SIMPSON. D. DESIGN SPECIFICATIONS FOR METAL PLATE CONNECTED WOOD ROOF TRUSSES PER T ADESIGNED I ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS THE PROJECT WAS N F, TERMITE PROTECTION SHALL BE IN ACCORDANCE WITH SECTION 1816 OF THE FL TPI 1-2014; DESIGN SPECIFICATIONS FOR METAL PLATE CONNECTED PARALLEL CHORD G. BUILDING PAPER: FEDERAL SPECIFICATIONS UU-B-790. INSTALL UNDER ROOFING AND D. LUMBER USED FOR LOAD SUPPORTING SHALL HAVE GRADE MARKS COMPLYING WITH FOR REINFORCED CONCRETE (ACI 318-14 EDITION). (AMERICAN INSTITUTE OF STEEL BUILDING CODE 2017. TRUSSES PER P T 80; HANDLING, INSTALLATING, RESTRAINING AND BRACING OF METAL TRIM AND CAREFULLY APPLY SO AS TO FORM A WATERTIGHT MEMBRANE. EACH COURSE AND PROCEDURES AND AGENCIES APPROVED BY US PROCEDURE PS 20-94. CONSTRUCTION) AISC ASD/13th EDITION. BUILDING CODE REQUIREMENTS AND PLATE CONNEC ED WOOD TRUSSES PER BCSI 2013 EDITION OF PAPER SHALL OVERLAP THE COURSE BENEATH IT 6" MINIMUM. WHERE PAPER MEETS SPECIFICATIONS FOR MASONRY STRUCTURES (ACI 530-13/ASCE 5-13/TMS 402-13). BUILDING CONCRETE: ANY OPENING, THE PAPER SHALL BE CAREFULLY LAPPED OVER THE FRAME TO PREVENT E. PLYWOOD: PRODUCT STANDARD PS-1-73 AND RULES FOR DFPA GRADE TRADEMARKS CODE REQUIREMENTS AND NATIONAL DESIGN SPECIFICATIONS FOR WOOD A. GENERAL: ALL CONCRETE WORK SHALL CONFORM TO ALL RECOMMENDATIONS AND THE PASSAGE OF WATER BEHIND THE FRAME. INSTALL SILKA KRAFT PAPER AT EXTERIOR OF AMERICAN PLYWOOD ASSOCIATION. CONSTRUCTION (ANSI/NFOPA NDS-2015). REQUIREMENTS OF ACI. 318-14. CONCRET UNIT MASONRY: DOORS AND WINDOW FRAMES. B. THESE PLANS AS DRAWN AND NOTED COMPLY WITH THE BUILDING ENVELOPE ENERGY 8. PORTLAND CEMENT: ASTM C-150 TYPES I OR B. LOW ALKALI, SILL TESTED AND CERTIFIE H. ALL BEARING PARTITIONS SHALL BE SECURED TO ADJACENT PARTITIONS, AND SHALL F. MARKING: WOOD AND LUMBER SHALL BE MARKED WITH ITS GRADE AND PLYWOOD WITH ITS GRADE TRADEMARK IN ACCORDANCE WITH THE REFERENCED STANDARDS. A REQUIREMENTS OF THE FLORIDA MODEL ENERGY CODE. CONTRACTOR SHALL USE TYPE V CEMENT FOR SOIL CONTAINING SULFATE CONCENTRATIONS OF MORE THAN 0. A. THIS PROJEC IS DESIGNED AS ENGINEERED UNIT MASONRY. STRUCTURAL DESIGN HAVE AT LEAST A DOUBLE STUD POST AT ALL ENDS, CORNERS AND EACH SIDE OF ALL PIECE WITH DEFECTS SHALL NOT BE USED REGARDLESS OF GRADING. FAMILIARIZE HIMSELF WITH THE GOVERNING CODE IN IT'S ENTIRETY AND BUILD IN PERCENT. SHALL BE IN AC ORDANCE WITH ACI 530-13/ASCE 5-13/TMS 402-13, BUILDING CODE WINDOW AND DOOR OPENINGS. ACCORDANCE WITH ALL PROVISIONS OF THIS CODE. REQUIREMENTS OR MASONRY STRUCTURES AND THE COMMENTARY ON BUILDING CODE G. EXTERIOR PLYWOOD SHEATHING SHALL BE GROUP I STANDARD (C-D) EXT-DFPA, (C-C). C. WATER: FROM DOMESTIC SOURCES, CLEAN, POTABLE, AND FREE FROM ALL ORGANIC O REQUIREMENTS =OR MASONRY STRUCTURES. I. ROOF SHEATHING: 19/32" THICK STANDARD PLYWOOD SHEATHING, EXTERIOR GLUE, C-D EXT-DFPA, STRUCTURAL I (C-D) EXT-DFPA OR STRUCTURAL I (C-C) EXT-DFPA. PERMITS: OTHER DELETERIOUS MATERIALS. GRADE, 4 PLY, INDES 24/0, APA GRADE TRADEMARKED, APPLY WITH FACE GRAIN B. REINFORCING STEEL: LAP REINFORCING NOT LESS THAN 48 BAR DIAMETERS AT SPLICE PERPENDICULAR TO SUPPORTS AND STAGGER JOINTS DOORS AND WINDOWS: D, AGGREGATES: ASTM C-33 FOR SLABS ON GRADE. IN WALL REINFO CING. LAP HORIZONTAL REINFORCING A MINIMUM OF 18" AROUND A. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL REQUIRED BUILDING AND TRADE PERMITS AND FOR THEIR RESPECTIVE COSTS E, SAND: ASTM C-33 FOR SLABS ON GRADE. CORNERS. HOR ZONTAL BARS SHALL BE TIED TO VERTICAL BARS AS. THE WORK J. HANGERS, FRAMING ANCHORS AND FASTENERSSTAMPED AMD FABRICATED STEEL OF A. DOOR OPENINGS BETWEEN THE GARAGE AND DWELLING TO BE SOLID CORE NOT LESS PROGRESSES At FORCING IN D SHALL BE EMBEDDED IN GROUT. PLACING OF HORIZONTAL JOINTS OR MORTAR WILL NOT BE PERMITTED EXCEPT FOR WIRE JOINT THE TYPE INDICATED, NAILS TO BE THOSE FURNISHED OR RECOMMENDED BY THAN a �� THICK OR BE IN COMPLIANCE WITH FBC WITH A FIRE PROTECTION RATING JOB CONDITIONS: F, FOUNDATIONS: INSTALL AS PER THE STRUCTURAL DWG'S, OR AS AMENDED BY THE FINAL ,[��[J SYY1NFORCING. MANUFACTURER FOR THIS SPECIFIC USE. NAILS SHALL BE FULLY DRIVEN IN ALL HOLES IN r-LOSING NOT LESS THAN 20 MINUTES. DOORS SHALL BE SELF CLOSING AND SELF LATCHING. S SELF REPORT. THE ANCHOR, ALL HANGERS AND ANCHORS SHALL BE GALVANIZED. A. THE CONTRACTOR SHALL VISIT THE PROJECT SITE PRIOR TO SUBMITTAL OF BID AND / VAPOR B RRIE B EAT SLA S TO E 6 IL. P LYE YL E. C. FOUNDATION DOWELS: SHALL NOT BE SLOPED MORE THAN ONE HORIZONTAL TO 6 K. DRAFT -STOPPING: IN FLOOR AND CEILING ASSEMBLIES NOT TO EXCEED 1,000 S/F. IN B. DOORS CONTAINING GLAZING MATERIAL NOT GREATER THAN 9 SQUARE FEET IN SURFACE AREA SHALL BE CLASSIFIED AS CATEGORY I AND SHALL BE CAPABLE OR CONTRACT NEGOTIATIONS. AND HE SHALL VERIFY EXISTING CONDITIONS WITH THE VERTICAL TO AL GN WITH BLOCK CORE. ATTICS FOR AREAS. OVER 3,000 S/F OF WITHSTANDING A 150 FOOT-POUND IMPACT TEST. CONSTRUCTION DOCUMENTS, DISCREPANCIES BETWEEN CONSTRUCTION DOCUMENTS N. STRUCTURAL CONCRETE SHALL CONFORM TO ACI 301 SPECIFICATIONS AND SHALL 1 .SHALL BE BROUGHT TO THE ARCHITECTS ATTENTION IN WRITING FOR CLARIFICATION. DEVELOP THE FOLLOWING MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS: D. CLEAN OUT CC PENINGS SHALL BE PROVIDED AT BOTTOM OF GROUTED CELLS. SEAL L. FIRE -BLOCKING: INSTALL IN CONCEALED SPACES BOTH VERTICAL AND HORIZONTAL, C. DOORS &SHOWER ENCLOSURES, AND SLIDING GLASS DOORS CONTAINING BIDS SHALL NOT BE SUBMITTED OR CONSTRUCTION CONTRACTS NEGOTIATED BY THE SPREAD AND WALL FOOTINGS 3000 PSI AFTER CLEANIN AND INSPECTION. .SUCH AS BUT NOT LIMITED TO, STUD WALLS, FURRED SPACES, SOFFITS, DROP CEILINGS, ,BATH GLAZING MATERIAL GREATER THAN 9 SQUARE FEET IN SURFACE AREA SHALL BE CONTRACTOR PRIOR TO CLARIFICATION OF THE INTENT OF THE CONSTRUCTION COLUMNS AND WALLS 3000 PSI COVES, STAIR STRINGERS (TOP AND BOTTOM) OPENINGS FOR VENTS, PIPES, DUCTS, CLASSIFIED AS CATEGORY II AND SHALL BE CAPABLE OF WITHSTANDING A 400 DOCUMENTS WHERE SUCH INTENT IS IN DOUBT. BACK CHARGES WILL NOT BE ACCEPTED. BEAMS AND SLABS 3000 PSI E. MASONRY U TS SHALL BE ASTM C-90 TYPE II WITH MINIMUM COMPRESSIVE STRENGTH CHIMNEYS, FLOOR JOISTS OR TRUSSES. FOOT-POUND IMPACT TEST OF 1900 PSI ON ET AREA OF INDIVIDUAL UNITS. ALL CMU SHALL BE LAID IN A FULL BED OF B. DIMENSIONS AND NOTES SHALL TAKE PRECEDENCE OVER SCALE AND GRAPHICS. DO USE REGULAR WEIGHT CONCRETE. MORTAR IN RUN JING BOND U.N.O. ALL REINFORCING STEEL SHALL BE MANUFACTURED SHOP DRAWINGS. NGING D. THE GLAZING IN SLIDING AND SWINGING DOORS AND IN SHOWER OR TUB ENCLOSURES, NOT SCALE DRAWINGS. FROM HIGH STIRNGTH BILLET STEEL CONFORMING TO ASTM DESIGNATION A-615 GRADE I, STRUCTURAL CONCRETE SHALL CONFORM TO ACI 301 AND HAVE THE FOLLOWING 60. INCLUDING ANY GLAZING WITHIN 60 OF THE FINISHED FLOOR IN WALLS C. IF WORK IS BEING PERFORMED IN AN EXISTING BUILDING AND / OR AS AN ADDITION OR SLUMPS & AGGREGATE REQUIREMENTS: A. THE CONTRACTOR SHALL SUBMIT THREE COPIES OF ALL SHOP DRAWINGS, ALL SURROUNDING TUB & SHOWER ENCLOSURES SHALL BE SAFETY GLAZED FOR CATEGORY II ALTERATION(S) TO AN EXISTING BUILDING, THE CONTRACTOR SHALL VERIFY ALL EXISTIN LOCATION SLUMP MAX. AGGREGATE F. ALL MORTAR HALL BE TYPE S IN ACCORDANCE WITH ASTM SPECIFICATION C-270 WITH FABRICATED ITEMS AND EQUIPMENT FOR ARCHITECT'S REVIEW PRIOR TO FABRICATION GLAZING PRODUCTS. • CONDITIONS WITH REFERENCE TO ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND FOOTINGS 4"ti" ASTM #57 A MINIMUM COM RESSIVE STRENGTH OF 1800 PSI AT 28 DAYS. NO TESTING FOR MORTAR AND COMMENCEMENT OF THE WORK. - ELECTRICAL SYSTEMS. ANY DISCREPANCIES BETWEEN THE EXISTING CONDITIONS AND COLUMNS 5"t1" ASTM #57 STRENGTH IS REQUIRED FOR THIS PROJECT. E. GLASS OR MIRRORS IMMEDIATELY SURROUNDING A BATHTUB OR SHOWER ENCLOSURE CONSTRUCTION DOCUMENTS SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION IN BEAMS AND SLABS 5"t1" ASTM #57 B. CABINET SUPPLIER SHALL PROVIDE SHOP DRAWINGS. SHALL BE SAFETY GLAZING WHERE THE GLASS OR MIRRORS ARE LESS THAN 60" ABOVE WRITING PRIOR TO THE SUBMISSION OF BIDS OR CONTRACT NEGOTIATIONS. THE FILLED CELLS 8"31" ASTM#8 PEAROCK TIE BMS & TIE COL'S 5"t1" ASTM #BPEAROCK G. GROUT SHAL BE A HIGH SLUMP MIX 8"- WITH 11 IN ACCORDANCE H ASTM ( ) THE FLOOR OF THE TUB OR SHOWER. • CONTRACTOR SHALL COORDINATE AND SCHEDULE WORK BY TRADES, SUPPLIERS, PILES 8"t1" ASTM #8 PEAROCK SPECIFICATION HAVING A MINIMUM COMPRESSIVE STRENGTH OF 3,000 PSI. NO C. WINDOW AND DOOR SUPPLIER SHALL PROVIDE SHOP DRAWINGS. F. EGRESS WINDOWS SHALL BE OPERABLE FROM THE INSIDE WITHOUT THE USE OF SUBCONTRACTORS AND OTHER PROVIDERS TO INSURE THAT THE WORK, WHEN CONSTRUCTION TESTING FOR G OUT OUT STRENGTH IS REQUIRED FOR THIS PROJECT. SECTION AND DETAILS TOOLS. THEY SHALL PROVIDE A CLEAR OPENING OF NOT LESS 20" WIDE, 24" HIGH AND 5.7 '- COMPLETED WILL BE IN ACCORDANCE WITH THE INTENT OF THE DOCUMENTS. A. ALL WORK SHALL COMPLY WITH THE REQUIREMENTS SET FORTH IN. THE "MANUAL OF H. PROVIDE 9 G UGE HORIZONTAL JOINT REINFORCEMENT (LADDER TYPE ONLY) AT SQUARE FEET MINIMUM AREA. THE BOTTOM OF OPENING SHALL NOT BE MORE THAN 44' STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES" PUBLISHED EVERY SECOND OURSE FOR ALL EXTERIOR WALLS.. ALL DETAILS, SECTIONS AND NOTES SHOWN ON THE DRAWINGS ARE INTENDED TO BE ABOVE FLOOR AND LATCH AT 54" ABOVE FLOOR (MAX). D. CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATE BRACING OF STRUCTURAL AND BY THE AMERICAN CONCRETE INSTITUTE, EXCEPT WHERE MORE EXACTING TYPICAL AND SHALL APPLY TO SIMILAR SITUATIONS ELSEWHERE U.N.O. G. WINDOW UNITS SHALL DISP. LABELS SHOWING COMPLIANCE WITH THE FL ENERGY NON-STRUCTURAL MEMBERS DURING CONSTRUCTION. REQUIREMENTS ARE SPECIFIED IN THE CONTRACT DOCUMENTS. I. ALL CONCRET MASONRY BEARING AND SHEAR WALLS MUST BE INSPECTED BY A • QUALIFIED ENG( 4EER JUST PRIOR TO POURING OF THE FOUNDATION 1ST & 2ND FLOOR TIE CODE. B, MINIMUM CONCRETE COVERAGE OF REINFORCING STEEL. BEAMS. CONSTF UCTION SHALL BE IN ACCORDANCE WITH THE "SPECIFICATION FOR THE PLUMBING FIXTURES: WORK NECESSARY TO COMPLETE CONSTRUCTION: • SLAB ON VAPOR BARRIER 2" (ELEVATED 1 Ys") DESIGN AND CO ISTRUCTION OF LOAD BEARING CONCRETE MASONRY" PUBLISHED BY THE H. ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES, TRI-PLEXES, CONDOMINIUMS AND ' BEAMS AND COLUMNS 1 1/2 " NATIONAL CONIC RETE MASONRY ASSOCIATION. TOWNHOUSES SHALL PROVIDE AT LEAST ONE BATHROOM, LOCATED WITH MAX. POSSIBLE . FORMED CONCRETE BELOW GRADE 2" A. ALL SHOWER HEADS SHALL HAVE ANTI -SCALDING PROTECTION PRIVACY, WHERE BATHROOMS ARE PROVIDED ON HABITABLE GRADE LEVELS, WITH A A. IT IS THE PURPOSE OF THESE PLANS AND SPECIFICATIONS TO DESCRIBE A COMPLETE "N.I.C" ' UNFORMED BELOW GRADE 3" STRUCTURAL STEEL: DOOR THAT HAS A MIN. 29" CLEAR OPENING. AND FINISHED PROJECT OTHER THAN ITEMS MARKED (NOT IN CONTRACT) ' FOOTING 3"CLEAR AT BOTTOM & SIDES 2"CLEAR OF TOP . WALLS 2" CLEAR OUTSIDE FACE, 1 1/2" CLEAR INSIDE THERMAL MOISTURE PROTECTION: .. CLEAN UP /REPAIR: • SLABS 3/4" CLEAR AT TOP (INTERIOR), i y" CLEAR AT TOP (EXTERIOR) A. WORKMANS IP: WORK SHALL COMPLY WITH A.I.S.C. LRFD 13TH EDITION, UNLESS MORE ' BEAMS 1 112" CLEAR TO STIRRUPS EXACTING REQUIREMENTS ARE SPECIFIED IN THE CONTRACT DOCUMENTS. ' COLUMNS 1 1/2" CLEAR TO TIES A. INSULATION: INSULATION SHALL BE PROVIDED AND INSTALLED PER FBC 2017 A. THE CONTRACTOR SHALL MAINTAIN THE PREMISE CLEAN AND FREE OF ALL TRASH, B. ALL STRUCTL RAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH ENERGY CONSERVATION CODE. PRESCRIPTIVE REQUIREMENTS INCLUDE: a DEBRIS, AND SHALL PROTECT ALL ADJACENT WORK FROM DAMAGE, SOILING, PAINT C. REINFORCING MESH: ON -GRADE BUILDING SLABS SHALL BE ACI-318 ELECTRICALLY THE LATEST AISC CODE. STRUCTURAL STEEL SHALL CONFORM TO ASTM SPECIFICATION MINIMUM OF R-30 CLG INSULIN CLIMATE ZONE 1, R-38 CLG INSULIN CLIMATE ZONE 2. ' OVER -SPRAY, ETC. ALL FIXTURES, EQUIPMENT, GLAZING FLOORS, ETC. SHALL. BE LEFT WELDED WIRE FABRIC, SIZES AND GAUGES AS SHOWN ON THE DRAWINGS. A36. ALL STEEL ruBING & PIPE SHALL CONFORM TO ASTM SPECIFICATION A-500 GRADE B MASONRY WALLS A MINIMUM OF R-41N CLIMATE ZONE 1, R-61N CLIMATE ZONE 2. CLEAN AND READY FOR OCCUPANCY UPON. COMPLETION OF THE PROJECT. (FY=46KSI). ALL ;TEEL TO HAVE A SHOP COAT OF RUST INHIBITIVE PAINT, ALL SHOP AND FRAME WALLS A MINIMUM OF R-131N BOTH CLIMATE ZONE 1 & 2. 0, GENERAL BEAM NOTES: FIELD WELDING HALL BE PERFORMED BY WELDERS QUALIFIED, AS DESCRIBED IN VERIFY REQUIRED INSULATION VALUES TO BE INSTALLED AGAINST FBC ENERGY a ai> S. THE CONTRACTOR SHALL REPAIR AND / OR REPLACE ALL ITEMS DAMAGED BY THE 1) SCHEDULE HOOPS OR STIRRUPS SHALL BE PLACED AT EACH END OF BEAM U.N.O. "AMERICAN WEL ANG SOCIETY'S STANDARD QUALIFICATION PROCEDURE" (ASW D1.1), TO CONSERVATION ENERGY CALCULATIONS AS SUBMITTED. PROCESS OF CONSTRUCTION AND SHALL FINISH ALL PATCHWORKS AND REPAIRS TO 2) BUNDLE ALL STIR. BEAM TOP BARS IN PAIRS OVER SUPPORT WI TOP BARS FROM ADJ. PERFORM THE PE OF WORK REQUIRED. ALL STEEL WELDING RODS SHALL BE E70XX MATCH ADJACENT AREAS AND SURFACES. 11EAMS. ELECTRODES. B. ROOF / TILE: TILE SHALL BE AS SHOWN ON DRAWINGS AND AS SELECTED BY 3) ALL TIE BEAM REINFORCING SHALL EXTEND INTO SPAN OF ANY ADJ. STR. BEAM PER ARCHITECT/DESIGNER. INSTALLATION SHALL BE PER MANUFACTURER'S CLIMATE & GEOGRAPHIC DESIGN CRITERIA: STANDARD ASTM BENDING DIAGRAM. RECOMMENDATIONS AND FLORIDA BUILDING CODE 2017. AT THE COMPLETION OF THE 4) TIE BEAM DEPTHS ARE MIN. AND MAY BE INCREASED (8" MAX.) TO FIT BLOCK WORK AND WORK, THE CONTRACTOR SHALL FURNISH ROOFERS WRITTEN GUARANTEE A. PER 2017 FBC-RESIDENTIAL, TABLE R301.2(1), 'SUBJECT TO DAMAGE FROM' WINDOW AND DOOR HEADS. g) DROP BOTTOM OF TIE BEAMS, AS REQUIRED, AT WINDOW & DOOR HEADS (28" MAX. BEAM COVERING WORKMANSHIP. MATERIAL MANUFACTURERS FACTURERS GUARANTEE FOR REPLACEMENT WEATHERING IS CLASSIFIED AS'NEGLIGIBLE'. TERMITE DAMAGE IS CLASSIFIED AS VERY DEPTH) &ADD 2 BOTTOM, IF DROP EXCEEDS 8" U.N.O. ON PLANS. OF THE SAME AT NO COST TO THE OWNER WITHIN WARRANTEE PERIOD. HEAVY'. SEE ADDITIONAL NOTES UNDER EARTHWORK. N 8) ALL ADDED LONGITUDINAL BEAM REINFORCING TO EXTEND 6" MIN. INTO SUPPORT U.N.O. THE PROJECT WAS DESIGNED IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318-14, 315-11, LRFD). (AMERICAN INSTITUTE OF STEEL CONSTRUCTION) AISC _RFD 13th EDITION. BUILDING CODE REQUIREMENTS AND SPEC'S FOR MASONRY STRUCTURES (ACI 530-1 VASCE 5-05/TMS 402-11). BUILDING CODE REQUIREMENTS AND NATIONAL DESIGN SPECIFICATIONS FOR WOOD CONSTRUCTION (ANSI/NFOPA NDS-2012, ASD, AF&PA). RESIDENTIAL CODE INFORMATION ALL RESIDENTIAL CONSTRUCTION SHALL COMPLY WITH SEVEN VOLUMES OF THE FLORIDA BUILDING CODE 2017 EDITION. THE CODE IS COMPILED WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE ADOPTED BY REFERENCE. THE NATIONAL ELECTRICAL CODE IS REFERENCED STANDARD NFPA-70. RESIDENTIAL POOL SAFETY ACT - CHAPTER 45 OF THE 2017 FBC RESIDENTIAL ALL DOORS AND WINDOWS PROVIDING DIRECT ACCESS FROM THE HOME TO THE POOL SHALL MEET THE REQUIREMENTS OF RESIDENTIAL POOL SAFETY ACT SECTION R4501.17.1.9. THE G.C. IS TO VERIFY THAT ALL ACCESS TO THE POOL AREA MEET THE SWIMMING POOL SAFETY ACT. DRAWING INDEX co .N O C N N E O F U N c IY CO Ui w 0- A001 COVER SHEET N/A - SITE PLAN BY ENGINEER A200 GARAGE LEVEL FLOOR PLAN A201 1 ST FLOOR PLAN A202 2ND FLOOR PLAN A210 ARCHITECTURAL 1ST FLOOR FRAMING PLAN A211 ARCH. 2ND FL FRAMING PLAN & UPPER ROOF A301 FRONT & REAR ELEVATIONS A302 SIDE ELEVATIONS A303 BUILDING SECTIONS & PLUMBING RISER A601 GARAGE & 1ST FLOOR REFLECTED CEILING PLAN A602 2ND FLOOR REFLECTED CEILING PLAN A801 TYPICAL WALL SECTIONS & DETAILS A802 TRUSS END/DASCIA DETAIL A901 DOOR/WINDOW DETAILS A902 TYPICAL DETAILS E101 ELECTRIC PANELS & RISER E201 GARAGE LEVEL& 1 ST FLOOR ELECTRIC PLAN E202 2ND FLOOR ELECTRIC PLAN S1-S? STRUCTURAL PLANS FIL REVISIONS B) Q IBO GI ® QI ENG REVS G, N A' 1st Bldg Comments G, I Job No.18020 MAR 0 4 201! FL-0011105 FIRM-) GARAGE LEVEL DOOR SCHEDULE MARK 1 SIZE WD S-0' 16'-0" Y4" - e 3'-0" 3 —0" 2 6 21-8" 5'-0" 2'—B" TYPE HGT 8'-0 FRENCH 8'-0" OVERHEAD GARAGE DR 8'-0" FRENCH T-0" EXT SWING 7'-0" E_XT SWING 8'-0" _FRENCH 8'-0" INT SWING (SC) MIN 8'-0" INT SWING_ SC 8'-0" _ INT SWING DBL SC 8'-0" INT SWING (SC)-- NOTES -- __- -- -- PVC JAMB__..____ PVC JAMB -- 1 3/8" THK, SELF CLOSER -- 2 _ 3 4 5 _ 6 7 9 10 11 2'-8" 2'-8°' 2'-8" 2'-8" 2'-8" 8'-0" 8'-0" 8'-0" 8'-0" 8'-0" INT SWING SC -- 12 INT SWING (SC) MIN 1 3P" THK, SELF CLOSER___- 13 INT SWING (SC) MIN 1 3 8 THK, SELF CLOSER 14 INT SWING _ 15 INT SWING SC -- 16 2'-0" 8'-0" Pocket Door -- GARAGE LEVEL WINDOW SCHEDULE I HEAD T MARK TYPE NOTES WD HGT ELEV 1 21 11" 8-01 " i SIDELIGHT 9-0" 2 4 11 I 8 —0 _ SIDEUGHT 9 0� — w FIXED GLASS BELOW _...__ 3 4'-ON 5-6" CSMNT DBL 8'—O" 4�-0 5 6 CSMNT DBL 8-0" w FIXED GLASS BELOW _4 6 __ 5_0" 5'-6" CSMNT DDUBLE _ 8'-0" -- 7 4'-0" 4- FIXED DOUBLE I 8 -O -- !t! I_\ v N y 0 m 0 001 2 4'-0" 3 4 Y So 002 31I HB 003 0 in enm GARAGE 12'-10" Clg 49'4' x 38'-10" 0 . 1 fS ••� !7 _ ,,:a r:;°.•.....V _ e .e. �.... vt:.. .,.,.,,. his...... I 1 1 "l 1 oil N= toll «m 1 11 1 • - • / i 214 BONUS STORAGE ROOM 14 (BELOW 9, C WINDOW) 33'-6" x 4'- 10" 0 0 33'-6" NOTE: Q INTERIOR FRAMED WALLS ON THIS LEVEL TO BE CONSTRUCTED PER D3 ON SHEET A801 FOR BREAKAWAY CONSTRUCTION 1S'-9" oi- c 69'-4" i;ORAGE 9' Clg 014 4'-2„ c - �^ POOL STORAGE 9' Clg a 015 Al 16'-0" 16-0" / 1- T-8" ABLE AREA BELOW ELEVATED DECK POO EQ�UI�P I � 1 NOTE: A IP. TO BE ELEVATED ON El IESTALS/STANDS ABOVE DFE (DESIGN FLOOD ELEVATION) OF NAVD 16.4 005 POOL ABOVE LIVING AREA CALCULATION 1) 1ST FLOOR LIVING 2585 SF 2) 2ND FLOOR LIVING 1263 SF 3) LOBBY 390 SF 4238 SF DETAIL AREA CALCULATION 1) 1ST FLOOR LIVING 2585 SF 2) 2ND FLOOR LIVING 1263 SF 3) LOBBY 390 SF BALCONY 1 82 SF BALCONY 2 200 SF BONUS STORAGE 699 SF COVERED ENTRY 68 SF GARAGE 1877 SF OUTDOOR LIVING 356 SF 7520 SF 200 SERIES KEYNOTES 200 - MIRROR 201 - BUILT-IN CABINETRY 202-OPEN SHELVES 203 - CUSTOM CLOSET INTERIOR 204 - TEMPERED GLASS SHOWER ENCLOSURE 205 - CURB FOR SHOWER 206 - TROUGH FOR POOL INFINITY EDGE 207 - DRAPERY POCKET 208 - .. 209 - ADJACENT WALLS TO HAVE MIN R-11 INSUL & MIN 1/2" GYP BD ON GARAGE SIDE FOR GARAGE SEPARATION 210 - MIN 5/8" TYPE'X' GYP BD FOR GARAGE CLG BELOW HABITABLE ROOMS 211 - T.S. COLUMN IN WALL 212 - T.S. COLUMN IN DECORATIVE COL/POST 213 - 42" HIGH CMU WALL 214 - 8"x16" ENGINEERED SMART FLOOD VENT I bI2 2; 215 F - MI R-2 SP Y A PLI11 D O EN CELL D FOAM INSULATION AT GARAGE CEILING 1 216 - 16"x8" WALL LOUVER FOR FLOOD VENTING THRU INTERIOR SPACES BOT OF VENT 0 8" REVISIONS --- BY DATE Irm _ Q, IBO GS 4.17.2018 ® ENG REV'S GS 8.6,2018 N A.1st Bldg Comments GS 3.12019 r M NOTE: DESIGN FLOOD ELEVATION IS AT 16.4 NAVD. PER FBC R322.1.8 BUILDING MATERIALS AND INSTALLATION METHODS USED FOR FLOORING & INTERIOR AND EXTERIOR WALLS AND WALL COVERINGS BELOW THE DESIGN FLOOD ELEVATION (DFE) SHALL BE FLOOD DAMAGE RESISTANT MATERIALS THAT CONFORM TO THE PROVISIONS OF FEMA TB-2. MECHANICAL, ELECTRICAL, & PLUMBING SYSTEMS BELOW DFE ARE TO BE DESIGNED & INSTALLED TO PREVENT WATER FROM ENTERING OR ACCUMULATING WITHIN THE COMPONENTS AND TO RESIST HYDROSTATIC AND HYDRODYNAMIC LOADS Q AND STRESSES PER FBC R322.1.6 PER ASCE 24-05 ELEVATOR COMPONENTS LOCATED BELOW THE DFE SHOULD BE CONSTRUCTED OF FLOOD DAMAGE -RESISTANT MATERIALS AND DESIGNED TO RESIST PHYSICAL DAMAGE DURII• FLOODING. IF AN ELEVATOR CAB PROVIDES ACCESS TO AREAS BELOW THE DFE IT MUST BE EQUIPPED WITH CONTROLS THAT PREVENT THE CAB FROM DESCENDING INTO FLOODWATERS L FLOOD VENT CALCULATION 8"xl6" ENGINEERED FLOOD VENTS THAT PROVIDE 200 SF OF FLOOD COVERAGE ( GARAGE 1877 SF/200 = 9.3 = 10 VENTS LOBBY & STORAGE AREAS 1089 SF/200 = 5.4 = 6 VENTS BELOW POOL DECK AREA 1066 SF/200 = 5.3. = 6 VENTS THE DESIGN OF THE FLOOD VENT OPENINGS WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD FORCES ON EXTERIOR WALLS BY ALLOWING FOR THE AUTOMATIC ENTRY AND EXIT OF FLOODWATERS AS SPECIFIED IN SECTION 2.7.2.2 OF ASCE 24. PER FBC o R322.2.2 FOOT NOTE 2.1 v THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN 1 FOOT ABOVE THE HIGHER OF THE FINAL INTERIOR FLOOR AND THE FINISHED EXTERIOR GRADE IMMEDIATELY BELOW THE OPENING GARAGE LEVEL PLAN SCALE: 1 /4" = 1'-01. ;J w F-M Sai $ U r ry T .8..2 � r COO 0 Cd r-, 1 v .Ha < z Job No.1802011 MAR 08 2019 F'L-0011105 FIRM-AA003379 200 FII_�' C�DV 1ST FLOOR DOOR SCHEDULE MARK SIZE WD HGT TYPE NOTES 101 11'-0" SLD GLASS OXX — 102 _9'-0 15'-Y 10 -0 SLD GLASS OXX POCKET SOD 103 6'-0" 10'-0 SLD GLASS -- 104 2O'-0 10 -0 SLD GLASS OXXO -- 105 12 0" 10'-0 SLD GLASS OXX Pocket Door -- 106 1 2'4 8 -0 -- -- 107 108 _ 109_ 110 111 112 113 114 115 116 117 2'-8 2 -6" 2'-8" 2'-8" 2'-8" 2 8" 5 0" 2 8" 2'-6" 2'-6" 2'-8" 8 0 8�-0" 8 -0" 8'-0" 8'10" _ 8' 0" 8 0" 8' 0" 8'-0" -8'-0" 6 0" INT SWING (SO) _ Pocket Door INT SWING SC INT SWING SO INT SWING SC INT SWING SC INT SWING DBL SC _ INT SWING SC INT SWING SC INT SWING (SC)-- INT SWING (SC) -- -- -- -- -- -- -- -- 1ST FLOOR WINDOW SCHEDULE MARK WD I' 4 0" 4 0" _ 2 6" 2 0" 2 0" 2' 81 2'-8" 2 -8 HGT ZE 1' 6" _1' 611 5' 0" 5' 0" 5' 0" 6'- 0" 6'-0" 6'-0" TYPE FIXED FIXED CSMNT CSMNT _ CSMNT CSMNT FIXED CSMNT HEAD ELEV T NOTES _4'-6" BETWEEN CAB'S, VERIFY HT. 4'-6" BETWEEN CAB'S, VERIFY HT. _ 9r0" -- 9 0 -- 9 -0�_ -- -- 101 _ 102 103 104 105 106 T--0" EGRESS,-w/ FIXED GLASS BELOW 107 9 0 w/ FIXED GLASS BELOW 9 0 EGRESS, w/ _FIXED GLASS BELOW 9 0' --_ 9 -0 -- 9 -0 -- 9 -0 -- 10 -0 w FIXED GLASS ABV 108 109 2'-0" 5'-0" CSMNT 110 2 -0 5'-0" CSMNT 111 2'-0" _ 5'-0" CSMNT 112 - - 113 5'-4"__6'-0" 2'-8"1 CSMNT DBL 5'-0" CSMNT G1 rn GUARD T-4" STAIR RAIL UP 101 P-O" 13'-8" LIBRARY 11' Clg 1416" x 12'-6" 14'-0" UPPER STAIR DETAILS 13'-0" FLOOR TO FLOOR 22 RISERS @ 7.09" EACH 11" TREADS W/ 1" BULLN( /OPEN TO- / BELOW A101 BALCONY GUARD 20'-5" C� 109 a 201 - ODO (0 C WENS COOKTOP H 21'-8" HOOD ABV I � Q IC I i L--J Cotter (Ag 11'/11'-4" 11'-0" 4'-8" 2 r4'"x 12r6" DINING 11' Clg 16'-8" x 11' 16'-8" IIIIIIIIII IIII OUTDOOR LIVING 102 c - 11' Clg — 15-10" x 23' BALCONY -- __--- -�- - GUARD -- a o _ 103 24'-10" l f GREAT ROOM 704 Coffer C1g 111/11'-4" N 25' x 23'-6" Oj f 20'-6" 112 " — -- — — - � I z 4'- 20'-6" ELEVATOR, 0 T-O" 14'-0" 4'-8" MASTER BEDROOM 105 Coffer c1 10'-6°/lr ITTING Co C 19'-10' x 17'-0" 11' Clg 4'-0" ih OUTSIDE STAIR DETAILS 18 RISERS @ +-7 1/4" VERIFY HEIGHT OF GRAC TO ELEVATED DECK FOR RISER HEIGHT 12" TREADS w/ 1" BULLNC SUN SHELF 8 INFINITY EDGE OPTIONAL POOL/SPA LIVING AREA CALCULATION 1) 1ST FLOOR LIVING 2585 SF 2) 2ND FLOOR LIVING 1263 SF 3) LOBBY 390 SF 4238 SF DETAIL AREA CALCULATION 3'-8" 1) 1ST FLOOR LIVING 2585 SF IL 2) 2ND FLOOR LIVING 1263 SF 3) LOBBY 390 SF BALCONY 1 82 SF BALCONY 2 200 SF BONUS STORAGE 699 SF COVERED ENTRY 68 SF GARAGE 1877 SF OUTDOOR LIVING 356 SF 7520 SF !al 200 SERIES KEYNOTES 200 - MIRROR 201 - BUILT-IN CABINETRY 202-OPEN SHELVES 203 - CUSTOM CLOSET INTERIOR 204 - TEMPERED GLASS SHOWER ENCLOSURE 205 - CURB FOR SHOWER 206 - TROUGH FOR POOL INFINITY EDGE 207 - DRAPERY POCKET 208 - .. 209 - ADJACENT WALLS TO HAVE MIN R-11 INSUL & MIN 1/2" GYP BD ON GARAGE SIDE FOR GARAGE SEPARATION 210 - MIN 5/8" TYPE'X' GYP BD FOR GARAGE CLG BELOW HABITABLE ROOMS 211 - T.S. COLUMN IN WALL 212 - T.S. COLUMN IN DECORATIVE COL/POST 213 - 42" HIGH CMU WALL 214 - 8' x16" ENGINEERED SMART FLOOD VENT I F 215 - MI R-2 SP Y APPLI D OPEN CELL D FOAM INSULATION AT GARAGE CEILING 1 216 - 16"l WALL LOUVER FOR FLOOD VENTING THRU INTERIOR SPACES BOT OF VENT @ 8" F. REVISIONS - r 0 160 O Q} ENG REVS tV s 9st Bldg Comments t M BY DATE GS ', 4.17.2018 GS 8.6.2018 GS 3.1.2019 tz- u. .r Q u ti CJ ri w &.a o all r> Z 43 u Q %a = p v Job NG.1802011 wllR Q $ 2019 i F°L--0011105 FfRWAA00.33.379 A201 2ND FLOOR DOOR SCHEDULE SIZE MARK TYPE NOTES WD HGT 201 8'-0" SLID 8'-0 202 8'-0" 8-0 SLD GLASS_ -- 203 2'-6 8'-0" INT SWING SC 204 __ 2'-6" 8'-0" INT SWING SC 205 2'-8" 8'-0" 'INT SWING Sc -- 266 2'-8" 8'-0"__ INT SWING SC) -- 207 - __ 2'-8" 8'-0 INT SWING Sc 208 2-8" 8'-0" 1 INT SWING SC) -- 209 2'-6" 8'-0" INT SWING SC -- 210 2 -6" 8'-0" INT SWING SC -- 211 2 -8" 8'-0" INT SWING (SC) -- 212 - 2 -6" 8'-0" Pocket Door -- 213 2'-6" 8'-0" INT SWING (SC)-- 2ND FLOOR WINDOW SCHEDULE SIZE HEAD HT MARK TYPE NOTES WD HGT ELEV 201 2'-8' 5'-O" CSMNT 0 EGRESS, FIXED GLASS BELOW 202 2'-8" 5 0°_ 8 -O w FIXED GLASS BELOW 203 2'-8" 5'-0" -_FIXED CSMNT 8'-0 EGRESS FIXED GLASS BELOW 204 3'-0" 8 -0 FIXED 8`-0 -- 205 3'-0" 8 -0 FIXED 8 -0" -- 206 3'-0" _ 8 0 _ FIXED-- 207 2'-0" 4 -6 FIXED8`-0 -- 208 5' 0" 5 -0 _ CSMNT DBL EGRESS 209 2'-0" 5'-0" CSMNT _8 8`--0" -- 210 4' 0" 5' 0" RED 8 -0 -- 211 2'-0" 5-0" CSMNT- M 2' 0" 3' 0" FIXED 8'-0� 213 3' 0" 3'-O" HOR SLIDE 8'-0 _ 214 3'-0" 3'-0" HOR SLIDE -- if A (V v N M 0 F 10' Clg 14' x 12'-8" 4'-0" I - 1-- _'-4� T-10" 4'-4" I I I I b B b 110 Ii1 . 113 114 115 A8�1 STAIR RAIL BELOW 10'-10" - MECH 10' g AHU 3 '-6" I. =_ T-1 _N— 43'-4" 9 rn BALCONY GUARD F WIC = 208 SITTING 10' clg bj 211 214 BEDROOM 3 10' Clg 13'-4" x 13'-8" LOFT 10' Clg 13'-8" x 10'-6" 205 o toy v BATH 2 . 6-2" 10' ag 9'-10" BEDROOM 2 10' Clg 18'-8" x 13' T-O" I N I I I 212 --- 213 M M U 200 SERIES KEYNOTES 200 - MIRROR 201 - BUILT-IN CABINETRY 202 - OPEN SHELVES 203 - CUSTOM CLOSET INTERIOR 204 - TEMPERED GLASS SHOWER ENCLOSURE 205 - CURB FOR SHOWER 206 - TROUGH FOR POOL INFINITY EDGE 207 - DRAPERY POCKET 208 - .. 209 - ADJACENT WALLS TO HAVE MIN R-11 INSUL & MIN 1/2" GYP BD ON GARAGE SIDE FOR GARAGE SEPARATION 210 - MIN 5/8" TYPE'X' GYP BD FOR GARAGE CLG BELOW HABITABLE ROOMS 211 - T.S. COLUMN IN WALL 212 - T.S. COLUMN IN DECORATIVE COUPOST 213 - 42" HIGH CMU WALL 214 - 8"x16" ENGINEERED SMART FLOOD VENT F V 2 5- IN -20SP Y PP IED OF N ELLED FOAM INSULATION AT GARAGE CEILING 1 , FLOOR PLAN '� a 0) REVISIONS BY DATE r Q IBO GS 4,172018 ® 0} ENG REV'S GS 8.6.2018 N Qi 1st Bldg Comments GS 3.1.2019 M I r e a LL s r! W ti �v//+^J,, nu 4 r WEll 1 a Ell 4 C. a� > I(} u 43i q _ ir,ANNONaw ' d a WNW oa 0 Ili IJob No.1802011 1 g MAR 0 4 2019 e 00 r � N O r THIS PLAN IS FOR INTENT OF DESIGN AND REFERENCE SEE STRUCTURAL PLANS FOR FINAL DESIGN INCLUDING STRUCTURAL BEAMS (CONCRETE AND STEEL), STRUCTURAL COLUMNS (CONCRETE AND STEEL), TRUSSES, TRUSS STRAPPPING, WIND PRESSURES, ETC. 1 st FLOOR FRAMING PLAN SCALE: 3116" = V-0" REVOONS BY DATE IBO GS 4.17.2018 -ENG REVS GSA 8.6,2018 &m4 cooC3 e 0 y i gywq+• 4rvee«[ Job No. 1802011 13-2018 mwl m I E { /f €€ € €€ € a 9' CLG L_ BEAM „ NN 9' CLG NOTE: THIS PLAN IS FOR INTENT OF DESIGN AND REFERENCE SEE STRUCTURAL PLANS FOR FINAL DESIGN INCLUDING STRUCTURAL BEAMS (CONCRETE AND STEEL), STRUCTURAL COLUMNS (CONCRETE AND STEEL), TRUSSES, TRUSS STRAPPPING, WIND PRESSURES, ETC. UPPER ROOF PLAN SCALE: 3/16" _: 1,-0,, NOTE: THIS PLAN IS FOR INTENT OF DESIGN AND REFERENCE SEE STRUCTURAL PLANS FOR FINAL DESIGN INCLUDING STRUCTURAL BEAMS (CONCRETE AND STEEL), STRUCTURAL COLUMNS (CONCRETE AND STEEL), TRUSSES, TRUSS STRAPPPING, WIND PRESSURES, ETC. 2nd FLOOR FRAMING & LOWER ROOF PLAN SCALE: 3/16" = V-0" 00 f O� N N O REVISIONS BY I DATE 1130 GS 4.17.2018 ENG REV'S GS 8.6.2018 Job No. 1802011 �I�►v11 � 2oi8 FL-0011105 I A21 1 TOP OF BEAM @ +23'-0" A.F.F. C!I�JI 2ND FLOOR @ +13'-W A.F.F. TOP OF BEAM @ +11'-4" A.F,F. 1ST FLOOR ELEV 0'-0" NAVD 24.0 4_BELOW ELEVATED DECK NAVD 12.5 LM ID I f ¶II if _LE L ,214112 300 AM LL- - -- — 0 ILM nl� ���irillw 12 1� - It lip �rilu EAST ELEVATION (rear) SCALE: 1 /4" = T-0" TOP OF BEAM @ +23'-0" A.F.F. 2ND FLOOR @ +13'-0" A.F.F. TOP OF BEAM Jill @ +11'-4" A.F.F. 1ST FLOOR ELEV NAVD 24.0 GARAGE (ci? -14'-10" NAVD 9.17 300 SERIES KEYNOTES 300 - STANDING SEAM METAL ROOF (MILL FINISH) 301 - SMOOTH STUCCO FINISH (TYP.) 302 - RAISED SMOOTH STUCCO BAND/SILL 303 - CORAL STONE WALL CLADDING 304 - PORCELAIN TILE 305 - ALUMINUM RAIL (TO REJECT 4" SPHERE) 306 - IMPACT WINDOWS/DOORS (ALUMINUM) 307 - EDEN COAST GARAGE DOOR STAINED, LOUVERED 308 - WALL MOUNTED LIGHT FIXTURE 309. KNIFED POOL EDGE w/ GLASS PANEL 310. DECORATIVE OUTRIGGER w/ SMOOTH STUCCO FINISH 311 - INFINITY EDGE POOL & TROUGH REVISIONS BY DATE 4f— A' {BO GS 4.17.201 O Q. ENG REV'S GS 8.6.201 N Q 1st Bldg Comments i GS 2.7.201 N U O O I� 7, 0 � w w r� O � U U O QW � bob No.1802011 �AAR n 4 2019 01u05 IRM-AA003 LA301 •� — � I I I �I I I I a P OF BEAM @ +23'-0" A.F.F. TO 2ND FLOOR @ +13'-0" A.F.F. TOP OF BEAM @ ♦11'_4 A.F.F. 1ST FLOOR ELEV 0'-0" ITT NAVD 24.0 10 1ST FLOOR ELEV 0'-0" IF NAVD 24.0 n x,x-vrrnrrrrrni TOP OF BEAM ' @ +11'-4" A.F.F. IF ,III F7 �J 0 A. 0 ro 12 �4 1/2 `# lit s "t >J31 v,tf Jj1 v ti{ f bY{{-;�}>},{sk,]H �p R A +Wi� $ L•w£ '9Cy i.�flt11 E t t .fit.ii}t#k�44b. it ##i" ifi4Gh }.a k 14� 4' { Su f� #�z• �j} 411 f rstk sta 7'12 i30 Slot }yq1�°}(13 t'L7 o �7 ' 1 _' px" Q ° �Jf �,tt xt'm r �,Y.` 5 }.1.31lrGjr 110 ±'�§+ ..�J`a` 12 14 1/2 q i � I I Ll DFE (D ELEVA NORTH ELEVATION (left) SCALE: 1 /4" = V-0" TOP OF BEAM @ +23'-0" A.F.F. 2ND FLOOR @ +13'-0" A.F.F. TOP OF BEAM +11'-4"A.F.F. N FLOOD ) @ 16.4 NAVD SOUTH ELEVATION (right) SCALE: 1/4" = V-0" 1 1 — J TOP OF BEAM @ +23'-0- A.F.F. 4AW2 2ND FLOOR @ +13'-0' A.F.F. TOP OF BEAM @+11'-4"A.EF. 1 ST FLOOR ELEV 0'-0" NAVD 24.0 300 SERIES KEYNOTES 300 - STANDING SEAM METAL ROOF (MILL FINISH) 301 - SMOOTH STUCCO FINISH (TYP.) 302 - RAISED SMOOTH STUCCO BAND/SILL 303 - CORAL STONE WALL CLADDING 304 - PORCELAIN TILE 305 - ALUMINUM RAIL (TO REJECT 4" SPHERE) 306 - IMPACT WINDOWS/DOORS (ALUMINUM) 307 - EDEN COAST GARAGE DOOR STAINED, LOUVERED 308 - WALL MOUNTED LIGHT FIXTURE 309 - KNIFED POOL EDGE w/ GLASS PANEL 310 - DECORATIVE OUTRIGGER w/ SMOOTH STUCCO FINISH 311 - INFINITY EDGE POOL & TROUGH 00 r � O� N N 0 � REVISIONS FY DATE IBO GS 4.17.2018 ENG REV'S GS 8.6.2018 Job No. 1802011 13 2018 HRM-A,A i3379 A302 TOP OF BEAM @ +23'-O" A.F.F. TOP OF BEAM @ +12'-8" A.F.F. o 1ST FLOOR ELEV 0'-0" NAVD 24.0 DFE (DESIGN FLOOD —,NORMAL ELEVATION) @ 16.4 NAVID MATERIALS FLOOD PROOF (CLASS 4 OR 5 LOBBY LEVEL a-11'-0" TECHNICAL BU NAVD 13.0 N 2" VTR J; L I SHIN CO LAV WC 2" 3 2'VTR 2" VTR J; L J;L I I 3" SHR AV 3. CO WC CO 3' 2 LAV TUB W° 2ND FLOOR 3" VTR J L 2' STUDOR VENT 2 i 2 VTR LAV "V7 KIT SINK CO 1ST FLOOR 4 WC CO 2" 3" 3" TUB WM 2 4" LAV LAV 2�� SHR 3" 3 CO CO 2"STUDOR VENT WC WC LAV �! 2 LT WC CO 3" <710 2" WC SHR PLUMBING RISER N.T.S. 00 Irm N N O V REVISIONS 1B0 ENG REV'S BY DATE GS 4,17,2018 GS 8.6,2018 Email 12 �aYry PRE-ENG MIN R-20 SPRAY ON Hill ROOF TRUSSES A802 FOAM INSUL. (TYP.) a @ 24" O/C MAX SEE TYP. WALL SECTION — — TIE BEAM TYP. J (SEE STRUCTURAL w PLANS FOR DETAILS) 3 B ig COO A801 A801 0 LGYPCRETE ON PLYWOOD ON FLOOR TRUSSES (SEE IL4 TYPICAL WALL SECTION) n "I Qto 2ND FLOOR " 1 @ +13'-0" A.F.F. LE All >� 7, Am LGYPCRETE ON PLYWOOD ELEVATED POO _ ON FLOOR TRUSSES (SEE � DECK L TYPICAL WALL SECTION) INFINITY EDGE _ .. ,. ,. , . . • . I � :Sob No. 1802011 1,77 INFINITY EDGE R TROUGH It onq 3 20% Y A801 SEE STRUCTURAL _ - PLANS FOR SLAB AND CONNECTION DETAILS I I I I I I I I I I kT N - HABITABLE BEl VATD D I CK N HABITA OW LE +� VD 12.5 .._ --.....I I.__-. __I ril -__. --_' .__. ! .___ .__�..- _. ._._ ._! _ -. i::__i :..- i::_.:: iI :_ � __IIi .. __ -._:I ...--! -_ .r ;_-: :- •.. I I I 1 1— IIL._.1=1 1II._III-_, e i ! i I I —— --- I � I- III _t I I:-1 I I, I I 1= -1-_III it—�— LL—LiI-1II II_ I_ -- I II=1_ III-1 . III III —III Iil IIIIIglililnll�Inl1:_ — -_.-- __ _ L1,-III ILI III- I I I I ° : �• , °-. III III —III III 1l. II _III III II I II � 1-1, 11 III „1�1--:�!I I — � III I I Ill- III III —III III-t -.III II' tl!L,} II1;11 III III —III III II 1 111=III ill II i! ,II III IIIIII III III III 11 I!I_II-.,III�ni�,l,303 FOUNDATION SHOWN FOR ILLUSTRATIVE I I PURPOSES -SEE STRUCTURAL PLANS � � �J FOR ALL FOUNDATION DETAILS INCLUDING BLDG SECTION A -A PILING, GRADE BEAMS, FLOOR SLABS, ETC SCALE: 1 /4" = V-0" I VFSMLG ° Q BATH 6 — to' cIg E BALCONY PANTRY 10' Qg CF PWDR 10' CF Q 10' CLG F Q TSOFFIT 9' CLG VP° II-4 CF KI N CF f 1 11'/tl 4" Coffer iel Coffu 4440'-6"/ I1 7 10' CLG ° Q H 0 y a DINING I1*1 a'2 °L1 °L1 n / ® °L1 °L1 OUTDOOR LIVING 11, Clg °L1 °L1 / °L1 °L1 .;,',.. ® °- GREAT ROOM ® Coffer Clg I1'/ll'-4" qe} 13 17 ° ° ° II- / MA "U-DO�K C I0' 1Ell i . 931 0 m 0 I I' C1g L2 1 st FLOOR ZEFLECTED CEILING PLAN SCALE: 3/16" = 1'-0" 00 TR 0 N N O I REVISIONS BY DATE IBG GS 4.172018 ENG REVS GS 8.6.2018 Job Na 1802011 iand r �2018_ A601 00 REVISIONS BY DATE r e Q iBo GS 4.17.2018 O r ENG REV'S GS 8.6.2018 N � _ C r 1 2nd FLOOR REFLECTED CEILING PLAN SCALE: 3/16" = V-0" w tx 9 EMM4 0 1 M Qom .tea>H:A,=tt=: AMIN vvm Job No, 1802011 114 em �� ill A602 I NOTE: PICKET SPACING TO REJECT 4" DIA. SHERE 0 En NOTE: ALL FASTENERS FOR RAIL ATTACHMENTS TO BE STAINLESS STEEL 08 (ALUMINUM GUARD DETAIL Al 4" MIN EDGE DISTANCE TOP CAP ON 2"x2y" TUBE %" DIA SOLID ALUM ROD (TYP.) e e 2"x2"SO ° PICKET e o e M 2"x2 PICKET RAILING POST (REFER TO SHOP DRAWINGS FOR SIZE & LOCATIONS) MIN POST EMBEDMENT = 4" 3 1/4" DIA x 4" DEEP HOLE INTO CONCRETE, FILL HOLE w/ EPDXY BONDING/GROUTING ADHESIVE (SIKADUR 32 HI -MOD) d a Q < d d d Q d a d Qa d a d 07 1 EXTERIOR RAILING ATTACHMENT RECOMMENDED WATERPROOFING BE PROVIDE AT THE COLD JOINT BETWEEN THE DECK AND THE CMS TO PREVENT WATER INTRUSION. RECOMMEND WATERPROOFING BE PROVIDED 1" BEYOND THE SLIDING GLASS DOOR PERIMETER SEALANT TOWARD THE INTERIOR; 1" ON THE DECK OUT FROM THE RETURN; 2" OUT AWAY FROM THE CMU; AND SIX TO EIGHT INCHES UP THE EXTERIOR FACE OF THE WALL RECOMMENDED 3/4" X 3/4" SILICONE CANT PRIMER. IF REQUIRED CANT BEAD TO BE PROVIDED AFTER STUCCO AT THE JUNCTION OF THE CONCRETE SLAB AND THE EXTERIOR FACE. CANT BEAD TO TIE INTO THE SLIDING GLASS DOOR PERIMETER SEALANT, 1" BEYOND SLIDING GLASS DOOR PERIMETER SEAL CONCRETE BLOCK STUCCO --,,. SLIDING FRAME SG LASS DOOR .��rL TOF CAP ON- 2" "TUBE 2"x2" SO VERTICAL (TYP.) 14"x14" SO PICKET (TYP.) TANDEMICAP @ NEWEL PIOST 2x4 NAILED TO FLOOR TRUSSES ((2) 16d each truss) No. 6 x 1" GALV SCREWS - @ 32" O/C TO TOP RUNNER No. 5 x 1" GALV SCREWS @ 32" O/C TO BOT PLATE 3/4" = 1'- " P.T. 2x4 w/ 1/4" x 3"- CORROSION RESISTANT TAPCONS @ 16" O/C HARDWO D BALUSTERS SPACEDTO REJECT 4" DIAMETER SPHERE POST NTS 03 WOOD BALCONY RAILING DETAIL 3/4" = 1'-0' GRASPABLE TOP RAIL PE N.F.P.A. 101 5-2.2.4.5 (C) R 311.5.6 HANDRA LS SHALL BE PROVIDED ON AT LEAST 1 SillE OF EACH STAIRS & SHALL BE CONTINUOUS FOR THE FULL LENGTH OF THE FLIGHT �4HAIR WOOD BALUSTERS 'PDREJECT I METOR SPHERE CANT BEAD) WOOD STAIRS 1J1 HARDWOOD MEMBRANE WATERPROOFING i i RECESS DECORATIVE RISERS % �$/4" HARDWOOD SKIRTBOARD VULKEM TRAFFIC COATING TO BEJ USED ON BALCONY SURFACES UPPER STAIR - RISE=7.09", RUN=11" LOWER STAIR - RISE=6.95", RUN=11" 06 WATERPROOFING @ BALCONY NTS 02 STAIR RAIL DETAIL 3/4°° = 1'-0" NON-SKID FLOORING ON EPDXY BASED SETTING MATERIAL & GROUT OVER TRAFFIC COATING 3%" METAL RUNNER (NO PHOSPHATE BASED MORTAR) FOR FIRE RATED & ADJACENT WALLS:TRA CKS (25 ga) TOP & BOT TOP & BOT RUNNERS TO BE FASTENED TO TRAFFIC COATING CEILING & FLOOR @ MAX 24" O/C w/ 5/8 EMBED NAILS OR SELF TAPPING SHEET BULLNOSE METAL SCREWS FOR METAL TO METAL EDGE 3% METAL STUDS a I (25 a) @ 24" O/C d a d WATER DRIP— GROOVE SMOOTH STUCCO FINISHED BALCONY 05 1 BALCONY EDGE DETAIL METAL RUNNER CKS (25 ga) TOP & BOT ____�3%" METAL STUDS (25 ga) @ 16" O/C NORMAL MATERIALS DESIGN FLOOD ELEVATION (DFE) SEE PLANS FLOOD PROOF MATERIALS (CLASS 4 OR 5 PER FEMA TECHNICAL BULLETIN #2) THIS DESIGN ALLOWS THE METAL FRAMED WALL TO BREAKAWAY FROM THE PERMANENT TOP & BOT 2x4 RUNNERS WITHIN THE 10-20 PSF LOADIN( RANGE WITHOUT HARM TO THE ELEVATED PORTI OF THE BUILDING OR SUPPORTING FOUNDATION INTERIOR NON -BEARING _ D3 BREAKAWAY WALL CONSTRUCTION 1 1/2„ — 1 -0„ STANDING SEAM METAL ROOF (.032 ALUM 5V CRIMP) OVER VERSASHIELD ON PEEL & STICK MEMBRANE OVER 30# FELT TIN TAGGED TO APA 40/20 19/32" EXPOSURE 1 PLYWOOD SEE ANCHOR SCHEDULE ON STRUCTURAL PLANS FOR ROOF TIE DOWNS n TOP OF BEAM @+11' 4" A.F.F. EA80)2 SEE SHEET A802 FORD TRUSS END DETAILS TOP OF BEAM & 1ST FLOOR ELEV 0'-0" 8"x16" BOND BEAM (SEE STRUCTURAL PLANS) FILLED CELLS w/ VERT. DOWELS (SEE STRUCTURAL PLANS FOR SIZES & LOCATIONS) 3/4" RECESS GARAGE/LOBBY 0. v ELEV-14'-10"/-1 T-0" GRADE VARIES MIN R-20 1/2 lb. PER CUBIC FOOT SPRAY APPLIED OPEN CELLED FOAM INSULATION THAT PASSES ACC 377 APPENDIX'XWITHOUT A COATING 12 / 14 1/2 A MT PIT IN 0 IN ■ NOM NO I OWN Sim ■ ■�I IN 9 III\ • :•• ••■ • •- 5/8" GYP BOARD w/ A I'1 sly ¥ LEVEL p; 4 FINISH OR u 5/8" DUROCK @ WET AREAS ,I, NOTE: 1 BATT INSULATION FOR WALLS P.T. 2x4 FRAMING AROUND Q; BETWEEN CONDITIONED and ALL SHOWER OPENINGS (, UNCON I, ITIONED SPACES, AT 1, OPT. LO ATIONS FOR SOUNq= GENERAL NOTE SPECIFICATIONS: SEE PLANS -ALL CONCRETE SHALL BE OCEAN MIX -ALL NAILS SHALL BE GALVANIZED -ALL FASTENERS SHALL BE STAINLESS STEEL NTS 01 INTERIOR FRAME WALL (NON BEARING) 1 1/2" = 1'-011 D1 TYPICAL 2-STORY WALL SECTION v METAL FRAMING @ 5UFFI I b P.T. 1x3 FIRESTOP CONT. 5/8" GYP BOARD OVER R4.1 FI-FOIL INSULATION STAPLED TO P.T. 1x2 FURRING @ 24" O/C P.T. 1x4 CONT, fI i a I—III—III=1 1, I =1 1° ® 1 a ° SEE STRUCTURAL PLANS FOR PILING, GRADE BEAMS, I , ' < I' FOUNDATION DETAILS 1 4.1 'LIED ;ES INTERIOR WALL & CEILING FINISH NOTES: 1. ALL INTERIOR WALL & CEILING FINISHES TO COMPLY w/ FBC 2017 R302.9 FOR FLAME SPREAD & SMOKE DEVELOPED INDEX, 2. FLAME SPREAD INDEX NOT TO EXCEED 200. 3. SMOKE DEVELOPED INDEX NOT TO EXCEED 450. INSULATION NOTES: 1. ALL INSULATION TO COMPLY w/ FBC 2017 R302.10 FOR FLAME SPREAD & SMOKE DEVELOPED INDEX. 2. FLAME SPREAD INDEX NOT TO EXCEED 25. 3. SMOKE DEVELOPED INDEX NOT TO EXCEED 450. STANDING SEAM METAL ROOF (.032 ALUM 5V CRIMP) OVER VERSASHIELD ON PEEL & STICK MEMBRANE OVER 30# FELT TIN TAGGED TO APA 40120 19/32" EXPOSURE 1 PLYWOOD SEE ANCHOR SCHEDULE ON STRUCTURAL PLANS FOR ROOF TIE DOWNS isLOPBEAM BEAM @ +2F3'-0" A.F.F. F1 SEESHEETA802FOR— A802 TRUSS END DETAILS n TOP OF BEAM & 2ND FLOOR @ +13'-0" A.F.F. 8"x16" BOND BEAM (SEE STRUCTURAL PLANS) n TOP OF BEAM & 1 ST FLOOR ELEV 0'-0" 8"x16" BOND BEAM (SEE STRUCTURAL PLANS) FILLED CELLS w/ VERT. DOWELS (SEE STRUCTURAL PLANS FOR SIZES & LOCATIONS) 3/4" RECESS GARAGE/LOBBY @ v ELEV-14'-10"/-11'-0" GRADE VARIES GENERAL NOTE SPECIFICATIONS: -ALL CONCRETE SHALL BE OCEAN MIX -ALL NAILS SHALL BE GALVANIZED -ALL FASTENERS SHALL BE STAINLESS STEEL MIN R-20 1/2 lb. PER CUBIC FOOT SPRAY APPLIED OPEN CELLED FOAM INSULATION THAT PASSES ACC 377 APPENDIX'X' WITHOUT A COATING 12 14 1/2 ��� • :• •-■ • 111 NE Iml • • • �■ : • ■ A _DT 1vA ( nK17 ■ ■ son IN E r ■ • 1 � 11 1*4 ■ - • • :Ise _ i • IN ■ m ■ 1�� 1 . _ • • .. . . IN 1 ■II\ • • •-■ • •• METAL FRAMING @ SOFFITS P.T. 10 FIRESTOP CONT. 1�g6g E OR •• IN IN 0 01��1� ... • • ■ ■�I _ 3/4" = 1'-0" I D2 I TYPICAL 3-STORY WALL SECTION METAL FRAMING @ SOFFITS P.T. 1x3 FIRESTOP CONT. 5/8" GYP BOARD OVER R4.1 FI-FOIL INSULATION STAPLED TO P.T. 1x2 FURRING @ 24" O/C P.T. 1x4 CONT. •1 1 4I II „III II II I I 1 . II ° III SEE STRUCTURAL PLANS I^ 1= FOR PILING, GRADE BEAMS, I' FOUNDATION DETAILS I° J 6— --A REVISION_ S BY DATI ISO GS 4.1720 ENG REVS GS 8.6.20' tst Bldg Comments GS 3.1.20' r_ k U LIED .ES INNN4 z3 Sw ra Q 'LIED ` P ;ES 3 ' lob No. 1802011 �� o 2019 FL-0011105 FI.RWAA(033? 12 4 1/21 STANDING SEAM METAL ROOF (TYP.) # 1:-r..= GALV METAL DRIP OVER P.T. 1x2 ON 2x6 CYPRESS FASCIAw/ (2) 16d TO EACH TRUSS MIN %" SMOOTH STUC' ON SELF FURRING MEl LATH SOFT 00 REVISIONS BY DATE Q1B0 GS 4.17.2018 O ENG REVS GS 8.6.2018 N N O ki 4t O H U I I Jab No, 1802011 Fl,-00W05 AA003379 A802