Popeyes 4946 S 25th St Ft Pierce
HVACI Load Analysis
for
Verdad IReal Estate, Inc
1211 Sout White Chapel Blvd
Southl,ake, TX 76092
R.J1 TLk�
' CQMM$RG?AL,
CHV)�CHVAC LOADS
t
IV Esc=•
F'
NQ-1 44649_
1
OF
Prepared By:
Clark Stilwell
LIS Engineering
2572 West SR 426, Suite 426
Oviedo, FL 32765
321-244-0402
Friday, December 14, 2018
FILE COPY
Chvac =Full Commercial HVAC Loads.Calculation Program
Etite Software Development, In .
Land Investment Services, LLC
Popeyes 4946 S 25th St Ft Pierce
Oviedo, FL 32t765
Pa e 2
Building Summary Loads
Building peaks in August at 5pm.
Bldg Load
Area
Sen
%TOt
Lat
Sen
Net
%Net
Descri tions
Quan
Los
Loss
1.77
Gain
0
Gain
2,328
Gain
2,328
Gain
0.76
Roof 2,265 2,392
Wall
3,251
7,510
5.55
0
7,554
7,554
2.47
Glass
245
5,013
3.70
0
8,443
8,443
2.77
Floor Slab
179
2,954
2.18
0
0
0
0.00
Skin Loads
17,868
13.20
0
18,325
18,325
6.00
Lighting
1,438
0
0.00
0
4,907
4,907
1.61
Equipment
9,600
0
0.00
7,680
321757
40,437
13.25
Pool Latent
0
0
0.00
0
0
0
0.00
People
50
0
0.00
10,.184
13,320
23,504
7.70
Partition
0
0
0.00
0
0
0
0.00
Cool. Pret.
0
0
0.00
0
0
0
0.00
Heat. Pret.
0
0
0.00
0
0
0
0.00
Cool. Vent.
2,625
0
0.00
78,250
28,849
107,099
35.08
Heat. Vent.
2,625
93,471
69.05
0
0
0
0.00
Cool.lnfil.
57
0
0.00
1,651
653
2,305
0.75
Heat.lnfil.
57
2,016
1.49
0
0
0
0.00
Draw-Thru Fan
0
0
0.00
0
0
0
0.00
Blow-Thru Fan
0
0
0.00
0
0
0
0.00
Reserve Cap.
0
0
0.00
0
98,080
98,080
32.13
Reheat Cap.
0
0
0.00
0
0
0
0.00
Supply Duct
0
14,675
10.84
0
7,733
7,733
2.53
Return Duct
0
7,337
5.42
0
2,905
2,905
0.95
Misc. Supply
0
0
0.00
0
0
0
0.00
Misc. Return
0
0
0.00
0
0
0
0.00
Building Totals
135,367
00.00
97,766
207,528
305,294
100.00
Building ° k
Sen
%dTotWat
SenNet
%°Net
in
O
gjain
McIN
Ventilation
93,471
69.05
78,250 28,849
107,099
35.08
Infiltration
2,016
1.49
1,651
653
2,305
0.75
Pretreated Air
0
0.00
0
0
0
0.00
Room Loads
17,868
13.20
17,864 167,388
185,252
60.68
Plenum Loads
0
0.00
0
0
0
0.00
Fan/Duct/Misc Loads
22,012
16.26
0
10,638
10,638
3.48
Building Totals
135,367
100.00
97,766 207,528
305,294
100.00
Check. Fl ures
Total Building Supply Air (based on a 15'
TO):
10,436
CFM
Total Building Vent. Air
(25.15% of Supply): I
2,625
CFM
Total Conditioned Air Space:
2,265
Sq.ft
Supply Air Per Unit Area:
4.6075
CFM/Sq.ft
Area Per Cooling Capacity:
89.0
Sq.ft/Ton
\\server\redirected\clark\Documents\Elite Software\Chvac 8 Proje8ts\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM
Building Summary Loads (co
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:
0.0112 Tons/Sq.ft
59.76 Btuh/Sq.ft
135,367 Btuh
25.44 Tons
\\server\redirected\clark\Documents\Elite Software\Chvac 8 Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM
Air Handler #1 - RTU-1 - Summary Loads
1 Kitchen
800
,195
24,377
7,212
Direct
Direct
5pm August
8
,400
3,517
0
875
875
6,400
4.25
4.40
0
875
875
Room Peak Totals:
800
,195
24,377
7,212
Total Rooms: 1
8
,400
3,517
0
875
875
Unique Rooms: 1
6,400
4.25
4.40
0
875
875
I� -
\\server\red irected\clark\Documents\E lite Software\Chvac 8 ProjeCts\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM
Chvac -Full Commercial HVAG Loads Calculation Program
Elite Software Development, Inc.
Popeyes 4946 S 25th St Ft Pierce
Land investment Services, LLC
P.a e 5
Oviedo„ F.L 32+7,65
Air Handler #1 - RTU-1 - Total Load Summary
Air Handler Description: RTU-1 Constant Volume - Sum of Peaks
Sensible Heat Ratio: 0.90
--- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in August.
Outdoor Conditions: Clg: 89° DB, 78'
WB,
128.26 grains, Htg: 420 DB
H
Indoor Conditions: Clg: 780 DB, 600%�inter:
(avg.), Htg: 750 DB
Summer: Ventilation controls outside air, -----
Ventilation controls outside air.
Room Space sensible loss: 5,483
B�tuh
Infiltration sensible loss: 712
Btuh
20 CFM
Outside Air sensible loss: 31,157
�tuh
875 CFM
Supply Duct sensible loss: 7,337
tuh
Return Duct sensible loss: 3,669
Otuh
Return Plenum sensible loss: 0
tuh
Total System sensible loss:
48,358 Btuh
Heating Supply Air: 13,532 / (.999 X 1.08 X 4) =
3,400 CFM
Winter Vent Outside Air (25.7% of supply) =
875 CFM
Room space sensible gain: 23,746
tuh
Infiltration sensible gain: 231
Btuh
Draw-thru fan sensible gain: 0
Btuh
Supply duct sensible gain: 3,865
Btuh
Reserve sensible gain: 30,134
tuh
Total sensible gain on supply side of coil:
57,976 Btuh
Cooling Supply Air: 57,976 / (.999 X 1.1 X 15) =
-
3,517 CFM
Summer Vent Outside Air (24.9% of supply)
875 CFM
Return duct sensible gain: 1,452
Btuh
Return plenum sensible gain: 0
Btuh
Outside air sensible gain: 9,616
Btuh
875 CFM
Blow-thru fan sensible gain: 0
Btuh
Total sensible gain on return side of coil:
11,068 Btuh
Total sensible gain on air handling system:
69,044 Btuh
Room space latent gain: 6,080
Btuh
Infiltration latent gain: 572
Btuh
Outside air latent gain: 25,503
Btuh
Total latent gain on air handling system:
32,155 Btuh
Total system sensible and latent gain:
101,199 Btuh
Cteck Fidures
Total Air Handler Supply Air (based on a 150 TD):
3,517 CFM
875 CFM
Total Air Handler Vent. Air (24.88% of Supply):
Total Conditioned Air Space:
800 Sq.ft
Supply Air Per Unit Area:
4.3961 CFM/Sq.ft
Area Per Cooling Capacity:
94.9 Sq.ft/Ton
Cooling Capacity Per Area:
0.0105 Tons/Sq.ft
Heating Capacity Per Area:
60.45 Btuh/Sq.ft
Total Heating Required With Outside Air:
48,358 Btuh
\\server\redirected\clark\Documents\Elite Software\Chvac 8 Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM
I
I Air Handler #1 - RTU-1 - Total Load Summarvl (cont'd) I
Total Cooling Required With Outside Air:
8.43 Tons
\\server\redirected\clark\Documents\Elite Software\Chvac 8 Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM
Chyac Fu11,Commerctal HVAC Loads Calculation Program tiEP��5.25thS`t�Ff Pie e`-1 x,-
Air Handler #2 - RTU-2 - Summary Loads
Front
800
6,022
24,857
7,212
Direct
Direct
2 Counter/Drive Thru
g
3,400
3,520
0
875
875
5pm August
7,200
4.25
4.40
0
875
875
Room Peak Totals:
800
6,022
24,857
7,212
Total Rooms: 1
8
3,400
3,520
0
875
875
Unique Rooms: 1
7,200
4.25
4.40
0
875
875
\\server\redirected\clark\Documents\Elite Software\Chvac 8 Rrojects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM
Ghvac - Full Commercial HUAC Lbads Calculation Program
Elite Software Development, Inc.
Land LL
rce
OInvmt6Servie
9ie
e 8
Air Handler #2 - RTU-2 - Total Load Summaryl
Air Handler Description: RTU-2 Constant
' olume - Sum of Peaks
Sensible Heat Ratio: 0.90
--- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in August.
Outdoor Conditions: Clg: 89' DB, 780
WB,
128.26 grains, Htg: 420 DB
Indoor Conditions: Clg: 78' DB, 60°/d RH
(avg.), Htg: 750 DB
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Room Space sensible loss: 5,310
Ptuh
Infiltration sensible loss: 712
Ptuh
20 CFM
Outside Air sensible loss: 311157
8tuh
875 CFM
Supply Duct sensible loss: 7,337
Btuh
Return Duct sensible loss: 3,669
Btuh
Return Plenum sensible loss: 0
Btuh
Total System sensible loss:
48,185 Btuh
Heating Supply Air: 13,359 /'(.999 X 1.08 X 4) =
3,400 CFM
Winter Vent Outside Air (25.7% of supply) =
875 CFM
Room space sensible gain: 24,227
Btuh
Infiltration sensible gain: 231
Btuh
Draw-thru fan sensible gain: 0
Btuh
Supply duct sensible gain: 3,868
Btuh
Reserve sensible gain: 29,694
Btuh
Total sensible gain on supply side of coil:
58,019 Btuh
Cooling Supply Air: 58,019 / (.999 X 1.1 X 15) =
3,520 CFM
Summer Vent Outside Air (24.9% of supply,
=
875 CFM
Return duct sensible gain: 1,453
Btuh
Return plenum sensible gain: 0
Btuh
Outside air sensible gain: 9,616
Btuh
875 CFM
Blow-thru fan sensible gain: b
Btuh
Total sensible gain on return side of coil: I
11,070 Btuh
Total sensible gain on air handling system]
69,089 Btuh
Room space latent gain: 6,08i0
Btuh
Infiltration latent gain: F2
Btuh
Outside air latent gain: 25,503
Btuh
Total latent gain on air handling system:
32,155 Btuh
Total system sensible and latent gain:
101,244 Btuh
Total Air Handler Supply Air (based on a 5°
TD):
3,520 CFM
Total Air Handler Vent. Air (24.86% of Supply):
875 CFM
Total Conditioned Air Space:
800 Sq.ft
Supply Air Per Unit Area:
4.3994 CFM/Sq.ft
Area Per Cooling Capacity:
94.8 Sq.ft/Ton
Cooling Capacity Per Area:
0.0105 Tons/Sq.ft
Heating Capacity Per Area:
60.23 Btuh/Sq.ft
Total Heating Required With Outside Air:
48,185 Btuh
\\server\redirected\clark\Documents\Elite Software\Chvac 8 rcjects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM
Air Handler #2 - RTU-2 - Total Load Summary) (cont'd)
Total Cooling Required With Outside Air: I 8.44 Tons
\\server\redirected\clark\Documents\Elite Software\Chvac 8 Ijrojects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM
Air Handier #3 - RTU-3 - Summary Loads
3 ---- -- --Dining---____..
665
5pm August
46
5,985
Room Peak Totals:
665
Total Rooms: 1
46
Unique Rooms: 1
5,985
',668
24,057
7,638
Direct
Direct
,,400
3,400
0
875
875
5.11
5.11
0
875
875
',668
24,057
7,638
!,400
3,400
0
875
875
5.11
5.11
0
875
875
\\server\redirected\clark\Documents\Elite Software\Chvac 8 P
Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM
Air Handler #3 - RTU-3 - Total Load Summa
Air Handler Description: RTU-3 Constant olume - Sum of Peaks
Sensible Heat Ratio: 0.91 I --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in August.
Outdoor Conditions: Clg: 89' DB, 78' WB, 128.26 grains, Htg: 42° DB
Indoor Conditions: Clg: 78° DB, 58% RH (avg.), Htg: 75' DB
. Summer: Ventilation controls outside air, ----- inter: Ventilation controls outside air.
- Room Space sensible loss:
7,076
Btuh
Infiltration sensible loss:
592
Btuh
Outside Air sensible loss:
31,157
Btuh
Supply Duct sensible loss:
0
th
Return Duct sensible loss:
0h
Return Plenum sensible loss:
0
Btuh
Total System sensible loss:
Heating Supply Air: 7,668 / (.999 X 1.08 X 2)' _
Winter Vent Outside Air (25.7% of supply) =I
Room space sensible gain: 21,3351
Btuh
Infiltration sensible gain: 1921
Btuh
Draw-thru fan sensible gain: 0
Btuh
Supply duct sensible gain: 0
Btuh
Reserve sensible gain: 38,251
Btuh
Total sensible gain on supply side of coil:
Cooling Supply Air: 59,779 / (.999 X 1.1 X
6) _
Summer Vent Outside Air (25.7% of suppl i) _
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: Q Btuh
Outside air sensible gain: 9,61 Btuh
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
Total sensible gain on air handling system,
Room space latent gain: 5,704 Btuh
Infiltration latent gain: 568 Btuh
Outside air latent gain: 27,244 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:
17 CFM
875 CFM
3,400 CFM
875 CFM
3,400 CFM
875 CFM
875 CFM
Check�Figures
Total Air Handler Supply Air (based on a I16' TD): 3,400 CFM
Total Air Handler Vent. Air (25.74% of Supply): 875 CFM
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
38,824 Btuh
59,779 Btuh
9,616 Btuh
69,395 Btuh
33,456 Btuh
102,851 Btuh
665
Sq.ft
5.1122
CFM/Sq.ft
77.6
Sq.ft/Ton
0.0129
Tons/Sq.ft
58.38
Btuh/Sq.ft
Total Heating Required With Outside Air
38,824 Btuh
\\server\redirected\clark\Documents\Elite Software\Chvac q Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM
Air Handler #3 - RTU-3 - Total Load Sum
Total Cooling Required With Outside Air:
8.57 Tons
\\server\redirected\clark\Documents\Elite Software\Chvac 8 Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM
Room Detailed Loads (At Room Peak Times
. Roof-1-10-Susp.C-D
800
1.06
32.1
16.6
0.032
0.070
822
583
1.
2.331010
845
1,160
Wall-1-N-G-M
W all-2-E-G-M
502
480
0.8�
0.
19.4
0.070
652
2.310
1,109
W all-3-W-G-M
480
0.:�
56.7
0.070
1,907
2.310
1,109
GIs-N-1-90-Tran
10.0
1.000
11
0.500
53
20.460
205
0%S-1-NS-Solar
10.0
0.4 0
38
0.750
114
Lights-Prof=1
480
1.0 0
1,638
Equipment-Prof=1
4,800
1.010
16,378
3,840
People-Prof=1
8.0
1.000
2,000
2,800
16.500
1,056
Floor slab
Cool.Infil.CFM/ft2
64
20
231
572
Heat. lnfil.CFM/sq.ft
20
35.608
712
Sub -total
24,377
7,212
6,195
Safety factors:
/o
---- -
+
---------
/o 0
---------
Total w/ safety factors:
24,377
7,212
6,195
0111
Kitchen 30,000 watts 23,500 Btuh 102,364 23,500
Miscellaneous-25,200 watts -5,762 watts-85,986-19,660
Equipment
_ - - — --- - - - - - - 16,378 3,840
Total
Roof- 1-10-Susp.C-D
Wall-1-E-G-M
W all-2-W-G-M
GIs-W-1-90-Tran
1 %S-1-NS-Solar
SGIs-W-1-90-Tran
1 %S-1-NS-Solar
Lights-Prof=1
Equipment-Prof=1
People-Prof=1
Floor slab
Cool. Infil.CFM/ft2
Heat. Infil.CFM/sq.ft
\\server\redirected\ciark\Documents\Elite
i° T'�'e-":-7 �Medwm_
800
1.00
32.1
0.032
822
1.056
845
320.
0.83
19.4
0.070
434
2.310
739
260
0.83
56.7
0.070
1,033
2.310
601
59.4
1.000
11
0.500
312
20.460
1,215
59.4
0.400
220
0.560
2,927
0.6
1.000
11
0.500
3
20.460
12
0.6
0.400
38
0.750
7
208
1.000
710
4,800
1.000
16,378
3,840
8.0
1.000
2,000
2,800
115
16.500
1,898
20
231
572
20
35.608
712
iftware\Chvai 8 Projects\Popeyes Ft Pierce.CH8
Friday, December 14, 2018, 02:46 PM
Detailed Loads (At Room Peak Times
Sub -total 24,857 7,212 6,022
Safety factors: +0% +0% +0%
0 /o
—
---------------- --- -
Total w/ safety factors: 24,857 7,212 6,022
Roof- 1-10-Susp.C-D
665
1.0
32.1
0.032
684
1.056
702
Wall-1=S-G-M
245
0.8
22.0
0.070
377
2.310
566
W al I-2-E-G-M
482
0.8
19.4
0.070
654
2.310
1,113
W all-3-W-G-M
482
0.83
56.7
0.070
1,914
2.310
1,113
GIs-S-1-90-Tran
75.0
1.00�0
11
0.500
394
20.460
1,535
0%S-1-NS-Solar
75.0
0.4d0
86
0.410
1,058
GIs-E-1-90-Tran
4.0
1.0 0
11
0.500
21
20.460
82
92%S-1-NS-Solar
4.0
0.460
220
0.230
81
SGIs-E-1-90-Tran
46.0
1.060
11
0.500
242
20.460
941
92%S-1-NS-Solar
46.0
0.400
38
0.750
524
GIs-W-1-90-Tran
49.5
1.090
11
0.500
260
20.460
1,013
1 %S-1-NS-Solar
49.5
0.490
220
0.560
2,439
SGIs-W-1-90-Tran
0.5
1.0p0
11
0.500
3
20.460
10
1 %S-1-NS-Solar
0.5
0.400
38
0.750
6
Lights-Prof=1
750
1.0100
2,559
People-Prof=1
46.0
1.000
12,650
7,130
Cool.lnfil.CFM/ft2
17
192
508
Heat.Infil.CFM/sq.ft
17
3-----
592
Sub -total
24,057
7,638
7,668
Safety factors:
+0%
+0%
+0%
Total w/ safety factors:
24,057
7,638
7,668
\\server\redirected\clark\Documents\Elite Software\Chvac 8 Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM