HomeMy WebLinkAboutHVAC LOADSSCANNED BY St. Lucie Curdy, Popeyes 4946 S 25th St Ft Pierce HVACI Load Analysis for Verdad IReal Estate, Inc 1211 Sout White Chapel Blvd Southl,ake, TX 76092 R.J1 TLk� ' CQMM$RG?AL, CHV)�CHVAC LOADS t IV Esc=• F' NQ-1 44649_ 1 OF Prepared By: Clark Stilwell LIS Engineering 2572 West SR 426, Suite 426 Oviedo, FL 32765 321-244-0402 Friday, December 14, 2018 FILE COPY Chvac =Full Commercial HVAC Loads.Calculation Program Etite Software Development, In . Land Investment Services, LLC Popeyes 4946 S 25th St Ft Pierce Oviedo, FL 32t765 Pa e 2 Building Summary Loads Building peaks in August at 5pm. Bldg Load Area Sen %TOt Lat Sen Net %Net Descri tions Quan Los Loss 1.77 Gain 0 Gain 2,328 Gain 2,328 Gain 0.76 Roof 2,265 2,392 Wall 3,251 7,510 5.55 0 7,554 7,554 2.47 Glass 245 5,013 3.70 0 8,443 8,443 2.77 Floor Slab 179 2,954 2.18 0 0 0 0.00 Skin Loads 17,868 13.20 0 18,325 18,325 6.00 Lighting 1,438 0 0.00 0 4,907 4,907 1.61 Equipment 9,600 0 0.00 7,680 321757 40,437 13.25 Pool Latent 0 0 0.00 0 0 0 0.00 People 50 0 0.00 10,.184 13,320 23,504 7.70 Partition 0 0 0.00 0 0 0 0.00 Cool. Pret. 0 0 0.00 0 0 0 0.00 Heat. Pret. 0 0 0.00 0 0 0 0.00 Cool. Vent. 2,625 0 0.00 78,250 28,849 107,099 35.08 Heat. Vent. 2,625 93,471 69.05 0 0 0 0.00 Cool.lnfil. 57 0 0.00 1,651 653 2,305 0.75 Heat.lnfil. 57 2,016 1.49 0 0 0 0.00 Draw-Thru Fan 0 0 0.00 0 0 0 0.00 Blow-Thru Fan 0 0 0.00 0 0 0 0.00 Reserve Cap. 0 0 0.00 0 98,080 98,080 32.13 Reheat Cap. 0 0 0.00 0 0 0 0.00 Supply Duct 0 14,675 10.84 0 7,733 7,733 2.53 Return Duct 0 7,337 5.42 0 2,905 2,905 0.95 Misc. Supply 0 0 0.00 0 0 0 0.00 Misc. Return 0 0 0.00 0 0 0 0.00 Building Totals 135,367 00.00 97,766 207,528 305,294 100.00 Building ° k Sen %dTotWat SenNet %°Net in O gjain McIN Ventilation 93,471 69.05 78,250 28,849 107,099 35.08 Infiltration 2,016 1.49 1,651 653 2,305 0.75 Pretreated Air 0 0.00 0 0 0 0.00 Room Loads 17,868 13.20 17,864 167,388 185,252 60.68 Plenum Loads 0 0.00 0 0 0 0.00 Fan/Duct/Misc Loads 22,012 16.26 0 10,638 10,638 3.48 Building Totals 135,367 100.00 97,766 207,528 305,294 100.00 Check. Fl ures Total Building Supply Air (based on a 15' TO): 10,436 CFM Total Building Vent. Air (25.15% of Supply): I 2,625 CFM Total Conditioned Air Space: 2,265 Sq.ft Supply Air Per Unit Area: 4.6075 CFM/Sq.ft Area Per Cooling Capacity: 89.0 Sq.ft/Ton \\server\redirected\clark\Documents\Elite Software\Chvac 8 Proje8ts\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM Building Summary Loads (co Cooling Capacity Per Area: Heating Capacity Per Area: Total Heating Required With Outside Air: Total Cooling Required With Outside Air: 0.0112 Tons/Sq.ft 59.76 Btuh/Sq.ft 135,367 Btuh 25.44 Tons \\server\redirected\clark\Documents\Elite Software\Chvac 8 Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM Air Handler #1 - RTU-1 - Summary Loads 1 Kitchen 800 ,195 24,377 7,212 Direct Direct 5pm August 8 ,400 3,517 0 875 875 6,400 4.25 4.40 0 875 875 Room Peak Totals: 800 ,195 24,377 7,212 Total Rooms: 1 8 ,400 3,517 0 875 875 Unique Rooms: 1 6,400 4.25 4.40 0 875 875 I� - \\server\red irected\clark\Documents\E lite Software\Chvac 8 ProjeCts\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM Chvac -Full Commercial HVAG Loads Calculation Program Elite Software Development, Inc. Popeyes 4946 S 25th St Ft Pierce Land investment Services, LLC P.a e 5 Oviedo„ F.L 32+7,65 Air Handler #1 - RTU-1 - Total Load Summary Air Handler Description: RTU-1 Constant Volume - Sum of Peaks Sensible Heat Ratio: 0.90 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 5pm in August. Outdoor Conditions: Clg: 89° DB, 78' WB, 128.26 grains, Htg: 420 DB H Indoor Conditions: Clg: 780 DB, 600%�inter: (avg.), Htg: 750 DB Summer: Ventilation controls outside air, ----- Ventilation controls outside air. Room Space sensible loss: 5,483 B�tuh Infiltration sensible loss: 712 Btuh 20 CFM Outside Air sensible loss: 31,157 �tuh 875 CFM Supply Duct sensible loss: 7,337 tuh Return Duct sensible loss: 3,669 Otuh Return Plenum sensible loss: 0 tuh Total System sensible loss: 48,358 Btuh Heating Supply Air: 13,532 / (.999 X 1.08 X 4) = 3,400 CFM Winter Vent Outside Air (25.7% of supply) = 875 CFM Room space sensible gain: 23,746 tuh Infiltration sensible gain: 231 Btuh Draw-thru fan sensible gain: 0 Btuh Supply duct sensible gain: 3,865 Btuh Reserve sensible gain: 30,134 tuh Total sensible gain on supply side of coil: 57,976 Btuh Cooling Supply Air: 57,976 / (.999 X 1.1 X 15) = - 3,517 CFM Summer Vent Outside Air (24.9% of supply) 875 CFM Return duct sensible gain: 1,452 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 9,616 Btuh 875 CFM Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 11,068 Btuh Total sensible gain on air handling system: 69,044 Btuh Room space latent gain: 6,080 Btuh Infiltration latent gain: 572 Btuh Outside air latent gain: 25,503 Btuh Total latent gain on air handling system: 32,155 Btuh Total system sensible and latent gain: 101,199 Btuh Cteck Fidures Total Air Handler Supply Air (based on a 150 TD): 3,517 CFM 875 CFM Total Air Handler Vent. Air (24.88% of Supply): Total Conditioned Air Space: 800 Sq.ft Supply Air Per Unit Area: 4.3961 CFM/Sq.ft Area Per Cooling Capacity: 94.9 Sq.ft/Ton Cooling Capacity Per Area: 0.0105 Tons/Sq.ft Heating Capacity Per Area: 60.45 Btuh/Sq.ft Total Heating Required With Outside Air: 48,358 Btuh \\server\redirected\clark\Documents\Elite Software\Chvac 8 Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM I I Air Handler #1 - RTU-1 - Total Load Summarvl (cont'd) I Total Cooling Required With Outside Air: 8.43 Tons \\server\redirected\clark\Documents\Elite Software\Chvac 8 Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM Chyac Fu11,Commerctal HVAC Loads Calculation Program tiEP��5.25thS`t�Ff Pie e`-1 x,- Air Handler #2 - RTU-2 - Summary Loads Front 800 6,022 24,857 7,212 Direct Direct 2 Counter/Drive Thru g 3,400 3,520 0 875 875 5pm August 7,200 4.25 4.40 0 875 875 Room Peak Totals: 800 6,022 24,857 7,212 Total Rooms: 1 8 3,400 3,520 0 875 875 Unique Rooms: 1 7,200 4.25 4.40 0 875 875 \\server\redirected\clark\Documents\Elite Software\Chvac 8 Rrojects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM Ghvac - Full Commercial HUAC Lbads Calculation Program Elite Software Development, Inc. Land LL rce OInvmt6Servie 9ie e 8 Air Handler #2 - RTU-2 - Total Load Summaryl Air Handler Description: RTU-2 Constant ' olume - Sum of Peaks Sensible Heat Ratio: 0.90 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 5pm in August. Outdoor Conditions: Clg: 89' DB, 780 WB, 128.26 grains, Htg: 420 DB Indoor Conditions: Clg: 78' DB, 60°/d RH (avg.), Htg: 750 DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: 5,310 Ptuh Infiltration sensible loss: 712 Ptuh 20 CFM Outside Air sensible loss: 311157 8tuh 875 CFM Supply Duct sensible loss: 7,337 Btuh Return Duct sensible loss: 3,669 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 48,185 Btuh Heating Supply Air: 13,359 /'(.999 X 1.08 X 4) = 3,400 CFM Winter Vent Outside Air (25.7% of supply) = 875 CFM Room space sensible gain: 24,227 Btuh Infiltration sensible gain: 231 Btuh Draw-thru fan sensible gain: 0 Btuh Supply duct sensible gain: 3,868 Btuh Reserve sensible gain: 29,694 Btuh Total sensible gain on supply side of coil: 58,019 Btuh Cooling Supply Air: 58,019 / (.999 X 1.1 X 15) = 3,520 CFM Summer Vent Outside Air (24.9% of supply, = 875 CFM Return duct sensible gain: 1,453 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 9,616 Btuh 875 CFM Blow-thru fan sensible gain: b Btuh Total sensible gain on return side of coil: I 11,070 Btuh Total sensible gain on air handling system] 69,089 Btuh Room space latent gain: 6,08i0 Btuh Infiltration latent gain: F2 Btuh Outside air latent gain: 25,503 Btuh Total latent gain on air handling system: 32,155 Btuh Total system sensible and latent gain: 101,244 Btuh Total Air Handler Supply Air (based on a 5° TD): 3,520 CFM Total Air Handler Vent. Air (24.86% of Supply): 875 CFM Total Conditioned Air Space: 800 Sq.ft Supply Air Per Unit Area: 4.3994 CFM/Sq.ft Area Per Cooling Capacity: 94.8 Sq.ft/Ton Cooling Capacity Per Area: 0.0105 Tons/Sq.ft Heating Capacity Per Area: 60.23 Btuh/Sq.ft Total Heating Required With Outside Air: 48,185 Btuh \\server\redirected\clark\Documents\Elite Software\Chvac 8 rcjects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM Air Handler #2 - RTU-2 - Total Load Summary) (cont'd) Total Cooling Required With Outside Air: I 8.44 Tons \\server\redirected\clark\Documents\Elite Software\Chvac 8 Ijrojects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM Air Handier #3 - RTU-3 - Summary Loads 3 ---- -- --Dining---____.. 665 5pm August 46 5,985 Room Peak Totals: 665 Total Rooms: 1 46 Unique Rooms: 1 5,985 ',668 24,057 7,638 Direct Direct ,,400 3,400 0 875 875 5.11 5.11 0 875 875 ',668 24,057 7,638 !,400 3,400 0 875 875 5.11 5.11 0 875 875 \\server\redirected\clark\Documents\Elite Software\Chvac 8 P Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM Air Handler #3 - RTU-3 - Total Load Summa Air Handler Description: RTU-3 Constant olume - Sum of Peaks Sensible Heat Ratio: 0.91 I --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 5pm in August. Outdoor Conditions: Clg: 89' DB, 78' WB, 128.26 grains, Htg: 42° DB Indoor Conditions: Clg: 78° DB, 58% RH (avg.), Htg: 75' DB . Summer: Ventilation controls outside air, ----- inter: Ventilation controls outside air. - Room Space sensible loss: 7,076 Btuh Infiltration sensible loss: 592 Btuh Outside Air sensible loss: 31,157 Btuh Supply Duct sensible loss: 0 th Return Duct sensible loss: 0h Return Plenum sensible loss: 0 Btuh Total System sensible loss: Heating Supply Air: 7,668 / (.999 X 1.08 X 2)' _ Winter Vent Outside Air (25.7% of supply) =I Room space sensible gain: 21,3351 Btuh Infiltration sensible gain: 1921 Btuh Draw-thru fan sensible gain: 0 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 38,251 Btuh Total sensible gain on supply side of coil: Cooling Supply Air: 59,779 / (.999 X 1.1 X 6) _ Summer Vent Outside Air (25.7% of suppl i) _ Return duct sensible gain: 0 Btuh Return plenum sensible gain: Q Btuh Outside air sensible gain: 9,61 Btuh Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: Total sensible gain on air handling system, Room space latent gain: 5,704 Btuh Infiltration latent gain: 568 Btuh Outside air latent gain: 27,244 Btuh Total latent gain on air handling system: Total system sensible and latent gain: 17 CFM 875 CFM 3,400 CFM 875 CFM 3,400 CFM 875 CFM 875 CFM Check�Figures Total Air Handler Supply Air (based on a I16' TD): 3,400 CFM Total Air Handler Vent. Air (25.74% of Supply): 875 CFM Total Conditioned Air Space: Supply Air Per Unit Area: Area Per Cooling Capacity: Cooling Capacity Per Area: Heating Capacity Per Area: 38,824 Btuh 59,779 Btuh 9,616 Btuh 69,395 Btuh 33,456 Btuh 102,851 Btuh 665 Sq.ft 5.1122 CFM/Sq.ft 77.6 Sq.ft/Ton 0.0129 Tons/Sq.ft 58.38 Btuh/Sq.ft Total Heating Required With Outside Air 38,824 Btuh \\server\redirected\clark\Documents\Elite Software\Chvac q Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM Air Handler #3 - RTU-3 - Total Load Sum Total Cooling Required With Outside Air: 8.57 Tons \\server\redirected\clark\Documents\Elite Software\Chvac 8 Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM Room Detailed Loads (At Room Peak Times . Roof-1-10-Susp.C-D 800 1.06 32.1 16.6 0.032 0.070 822 583 1. 2.331010 845 1,160 Wall-1-N-G-M W all-2-E-G-M 502 480 0.8� 0. 19.4 0.070 652 2.310 1,109 W all-3-W-G-M 480 0.:� 56.7 0.070 1,907 2.310 1,109 GIs-N-1-90-Tran 10.0 1.000 11 0.500 53 20.460 205 0%S-1-NS-Solar 10.0 0.4 0 38 0.750 114 Lights-Prof=1 480 1.0 0 1,638 Equipment-Prof=1 4,800 1.010 16,378 3,840 People-Prof=1 8.0 1.000 2,000 2,800 16.500 1,056 Floor slab Cool.Infil.CFM/ft2 64 20 231 572 Heat. lnfil.CFM/sq.ft 20 35.608 712 Sub -total 24,377 7,212 6,195 Safety factors: /o ---- - + --------- /o 0 --------- Total w/ safety factors: 24,377 7,212 6,195 0111 Kitchen 30,000 watts 23,500 Btuh 102,364 23,500 Miscellaneous-25,200 watts -5,762 watts-85,986-19,660 Equipment _ - - — --- - - - - - - 16,378 3,840 Total Roof- 1-10-Susp.C-D Wall-1-E-G-M W all-2-W-G-M GIs-W-1-90-Tran 1 %S-1-NS-Solar SGIs-W-1-90-Tran 1 %S-1-NS-Solar Lights-Prof=1 Equipment-Prof=1 People-Prof=1 Floor slab Cool. Infil.CFM/ft2 Heat. Infil.CFM/sq.ft \\server\redirected\ciark\Documents\Elite i° T'�'e-":-7 �Medwm_ 800 1.00 32.1 0.032 822 1.056 845 320. 0.83 19.4 0.070 434 2.310 739 260 0.83 56.7 0.070 1,033 2.310 601 59.4 1.000 11 0.500 312 20.460 1,215 59.4 0.400 220 0.560 2,927 0.6 1.000 11 0.500 3 20.460 12 0.6 0.400 38 0.750 7 208 1.000 710 4,800 1.000 16,378 3,840 8.0 1.000 2,000 2,800 115 16.500 1,898 20 231 572 20 35.608 712 iftware\Chvai 8 Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM Detailed Loads (At Room Peak Times Sub -total 24,857 7,212 6,022 Safety factors: +0% +0% +0% 0 /o — ---------------- --- - Total w/ safety factors: 24,857 7,212 6,022 Roof- 1-10-Susp.C-D 665 1.0 32.1 0.032 684 1.056 702 Wall-1=S-G-M 245 0.8 22.0 0.070 377 2.310 566 W al I-2-E-G-M 482 0.8 19.4 0.070 654 2.310 1,113 W all-3-W-G-M 482 0.83 56.7 0.070 1,914 2.310 1,113 GIs-S-1-90-Tran 75.0 1.00�0 11 0.500 394 20.460 1,535 0%S-1-NS-Solar 75.0 0.4d0 86 0.410 1,058 GIs-E-1-90-Tran 4.0 1.0 0 11 0.500 21 20.460 82 92%S-1-NS-Solar 4.0 0.460 220 0.230 81 SGIs-E-1-90-Tran 46.0 1.060 11 0.500 242 20.460 941 92%S-1-NS-Solar 46.0 0.400 38 0.750 524 GIs-W-1-90-Tran 49.5 1.090 11 0.500 260 20.460 1,013 1 %S-1-NS-Solar 49.5 0.490 220 0.560 2,439 SGIs-W-1-90-Tran 0.5 1.0p0 11 0.500 3 20.460 10 1 %S-1-NS-Solar 0.5 0.400 38 0.750 6 Lights-Prof=1 750 1.0100 2,559 People-Prof=1 46.0 1.000 12,650 7,130 Cool.lnfil.CFM/ft2 17 192 508 Heat.Infil.CFM/sq.ft 17 3----- 592 Sub -total 24,057 7,638 7,668 Safety factors: +0% +0% +0% Total w/ safety factors: 24,057 7,638 7,668 \\server\redirected\clark\Documents\Elite Software\Chvac 8 Projects\Popeyes Ft Pierce.CH8 Friday, December 14, 2018, 02:46 PM