HomeMy WebLinkAboutLOAD CALCULATIONS2 mm E F 1 I 2 f 3 I 4 I 5 I 6 f 7 f 8 l 9 I 10 LOAD CALCULATION 120/240VAC SINGLE PHASE OTY, DESCRIPTION LOAD 1 A/C 10,000VA 1 A/C 8,000VA 1 GENERAL LIGHTING 10,239VA 1 STOVE 8,000VA 1 REFRIGERATOR 1,500VA 1 MICROWAVE 1500VA 1 SMALL APPLIANCE 3 OOOVA 1 LAUNDRY 1,500VA 1 DISHWASHER 1 TOOVA 1 DISPOSAL 1200VA 1 DRYER 5 OOOVA 1 POOL PUMP 1,500VA TOTAL LOAD 54,539VA A/C LOAD @ 100% 18,000VA FIRST 8KW @ 100% 8 OOOVA REMAINDER ® 40% 10,615VA TOTAL CALCULATED LOAD I 36,615VA 38 KW 120/240voc GENERATOR 175A MCB I EXISTING NEW METER 200 AMP 200 AMP 0 AUTOMATIC TRANSFER CIRCUIT BREAKER SWITCH PANEL 2" CONDUIT 2" CONDUIT (2) 2/0 CU STR (2) 2/0 CU STR (1) 1/0 CU STR (1) 1/0 CU STR (1) #4 CU STR GRND - (1) #4 CU STR GRND 2 CONDUIT /0 CU STR _ /(2) 1 (1) /o CU STR (1) N4 CU STR GRND TO UTILITY 1 f 2 3 f 4 I 5 f 6 7 1 8 uir '10 Couffiv I A I I B I NOTES: INSTALLATION IN COMPLIANCE WITH 2O11 NEC sT.LUCIE COUNTY PLAN REVIEW UrDATE: ELE r 5 >L 1 DATE: PLUMB: DATE: MECH:_� DATE: D GRADE A15 - WINTER -HAVEN ELECTRIC 7190 SE FEDERAL HWY /10 STUART. FL 34997-8693 772-283-1026 FAX: 772-283-4932 0 .pupa ISSUEO FOR REWEW DATE FOR REVIEW E REV. ISSM FOR REVIEW BY SATE PRINTED: 4/w18 DESIGN A&S SCALE NONE DRAWN BY AWS DATE 4/15/18 CH WD. BY ENGR. APPR. BRAVING TITLE CLEMENT GENERATOR F 12786 NW MARINER CT AREA JDB NQ PALM CITY, FL DVG. ND- REV. D CLEMENT43-1001 1/2 —0— f9 1 10 1 2 I 3 I 4 I 5 6 7 I 8 f 9 10 0 0 E F 86" 45" 12" TYPICAL J CONCRETE PAD DETAIL 12" TYPICAL A B D WINTER- HAVEN -ELECTRIC 7190 SE FEDERAL HWY /10 STUART, FL 34997-8693 772-283-1026 FAX- 772-283-4932 1%2" REBAR TYPICAL I - I1 1 2 3 4 5 6 8 0 •nano ISSUED FOR RENEW d DATE FOR REVIEW E 186110 FOR CONSTRUCTION REV. DATE PRINTED 4/16/le DESIGN AWS SCALE NONE DRAWN BY AWS DATE 4/15/18 CKK'D. BY ENGR. APPR. BRAVING TITLE CLEMENT GENERATOR F 12786 NW MARINER CT AREA .mB NO. PALM CITY, FL D DV4 NO. REV. CLEMENT—E3-1001 2/2 —0- 9 10