LOAD CALCULATION 120/240VAC SINGLE PHASE
OTY,
DESCRIPTION
LOAD
1
A/C
10,000VA
1
A/C
8,000VA
1
GENERAL LIGHTING
10,239VA
1
STOVE
8,000VA
1
REFRIGERATOR
1,500VA
1
MICROWAVE
1500VA
1
SMALL APPLIANCE
3 OOOVA
1
LAUNDRY
1,500VA
1
DISHWASHER
1 TOOVA
1
DISPOSAL
1200VA
1
DRYER
5 OOOVA
1
POOL PUMP
1,500VA
TOTAL LOAD
54,539VA
A/C LOAD @ 100%
18,000VA
FIRST 8KW @ 100%
8 OOOVA
REMAINDER ® 40%
10,615VA
TOTAL CALCULATED LOAD
I 36,615VA
38 KW 120/240voc
GENERATOR
175A MCB I
EXISTING
NEW
METER
200 AMP
200 AMP
0
AUTOMATIC
TRANSFER
CIRCUIT
BREAKER
SWITCH
PANEL
2" CONDUIT
2" CONDUIT
(2) 2/0 CU STR
(2) 2/0 CU STR
(1) 1/0 CU STR
(1) 1/0 CU STR
(1) #4 CU STR GRND
-
(1) #4 CU STR GRND
2 CONDUIT
/0 CU STR
_
/(2)
1
(1) /o CU STR
(1) N4 CU STR GRND
TO UTILITY
1 f 2 3 f 4 I 5 f 6 7 1 8
uir
'10 Couffiv
I A I
I B I
NOTES:
INSTALLATION IN COMPLIANCE WITH 2O11 NEC
sT.LUCIE COUNTY
PLAN REVIEW
UrDATE:
ELE
r 5 >L 1
DATE:
PLUMB:
DATE:
MECH:_�
DATE:
D
GRADE A15
- WINTER -HAVEN ELECTRIC
7190 SE FEDERAL HWY /10
STUART. FL 34997-8693
772-283-1026
FAX: 772-283-4932
0 .pupa ISSUEO FOR REWEW
DATE FOR REVIEW E
REV. ISSM FOR REVIEW
BY SATE PRINTED: 4/w18
DESIGN A&S SCALE NONE
DRAWN BY AWS DATE 4/15/18
CH WD. BY ENGR. APPR.
BRAVING TITLE
CLEMENT GENERATOR F
12786 NW MARINER CT
AREA JDB NQ
PALM CITY, FL
DVG. ND- REV. D
CLEMENT43-1001 1/2 —0—
f9 1 10
1 2 I 3 I 4 I 5 6 7 I 8 f 9 10
0
0
E
F
86"
45"
12" TYPICAL
J
CONCRETE PAD DETAIL
12" TYPICAL
A
B
D
WINTER- HAVEN -ELECTRIC
7190 SE FEDERAL HWY /10
STUART, FL 34997-8693
772-283-1026
FAX- 772-283-4932
1%2" REBAR TYPICAL
I -
I1 1 2 3 4 5 6 8
0 •nano ISSUED FOR RENEW
d DATE FOR REVIEW E
186110 FOR CONSTRUCTION
REV. DATE PRINTED 4/16/le
DESIGN AWS SCALE NONE
DRAWN BY AWS DATE 4/15/18
CKK'D. BY ENGR. APPR.
BRAVING TITLE
CLEMENT GENERATOR F
12786 NW MARINER CT
AREA .mB NO.
PALM CITY, FL
D DV4 NO. REV.
CLEMENT—E3-1001 2/2 —0-
9 10