HomeMy WebLinkAboutPROJECT INFORMATIONQEL-4� " Manual S Compliance Report Job: Lot3lTarpon FlatsModel... Date: Jan 29, 2016 xtsk.wt:llxoma Zone 1 By: RH DEL AIR HTG, A/C & REFRIG. INC I 531 CODISCo WAY, SANFORD, FL32771 Phone:407-333-2665 Fax:407-333-3853 Web: WWW.DELAIR.COM For: PHOENIX REALTY HOMES 3910 DUNE SIDE DRIVE, FORT PIERCE, FL34949 Design Conditions Outdoor design DB: 90.5°F Sensible gain: 35248 Btuh Entering coil DB: 78.4°F Outdoor design WB: 77.7°F Latent gain: 7841 Btuh Entering coil WB: 64.60F Indoor design DB: 75.0°F Total gain: 43088 Btuh Indoor RH: 50% Estimated airflow: 1533 cfm I Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: CH14NBO480000AO+FB4CNP048L Actual airflow: 1533 cfm Sensible capacity: 36627 Btuh 1040/6 of load Latent capacity: 9064 Btuh 1160% of load Total capacity: 45690 Btuh 106% of load SHR: 80% Design Conditions Outdoor design DB: 43.1 OF Heat loss: 33274 Btuh Entering coil DB: 68.1°F Indoor design DB: 70.0°F i Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: CH14NBO480000AO+FB4CNP048L Actual airflow: 1533 cfm Output capacity: 43114 Btuh 130% of load Capacity balance: 35 OF Supplemental heat required: 0 Btuh Economic balance: -99 OF Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1533 cfm Output capacity: 9.1 kW 93% of load Temp. rise: 56 OF Meets all requirements of ACCA Manual S. -*- wrghtsoft® 2018-May-02 16:30:26 +w-rho wa -vim Right -Suite® Universal 2018 18.0.13 RSU24011 Page 1 ...arponFlatsModelBGrtLot3lTarponFlatsModelBGr.rup Cale - MJ8 House faces: W r COPY � ::_ -� ._--- .. . m Job: Lot3lTarponFlatsModel... Manual S Compliance Report DIE-6-Al p r Date: Jan 29, 2016 ilrFaTu;aYamrrarraa Zone 2 By: RH DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM For: PHOENIX REALTY HOMES 3910 DUNE SIDE DRIVE, FORT PIERCE, FL34949 Design Conditions i Outdoor design DB: 90.5°F Sensible gain: 16133 Btuh Entering coil DB: 76.1OF Outdoor design WB: 77.7°F Latent gain: 1976 Btuh Entering coil WB: 63.1°F Indoor design DB: 75.0°F Total gain: 18110 Btuh Indoor RH: 50% Estimated airflow: 740 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: CH14NBO240000AO+FB4CNP025L Actual airflow: 740 cfm I Sensible capacity: 16516 Btuh 102% of Toad Latent capacity: 3763 Btuh 1900% of load Total capacity: 20279 Btuh 112% of load SHR: 81% Design Conditions Outdoor design DB: 43.1 OF Heat loss: 12173 Btuh Entering coil DB: 69.6°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: CH14NBO240000AO+FB4CNP025L Actual airflow: 740 cfm Output capacity: 20696 Btuh 170% of load Capacity balance: 29 OF Supplemental heat required: 0 Btuh Economic balance: -99 OF Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 740 cfm Output capacity: 2.3 kW 65% of load Temp. rise: 41 OF Meets all requirements of ACCA Manual S. -*- wrightsofk® 2018-May-02 16:30:26 xwh w,e enc.wea.,caq. y. Right-SulteO Universal 2018 18.0.13 RSU24011 Page 2 ACM ...arponFlatsModelBGALot3lTarponFlatsModelBGr.rup Calc = MJ8 House faces: W a 0p, /� Component Constructions Job: Lot3lTarpon FlatsModel... �'�A� i' Date: Jan 29, 2016 #Am 6Affidwifa Entire House By: RH DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL32771 Phone:407-333-2665 Fax:407-333.3853 Web: WWW.DELAIR.COM For: PHOENIX REALTY HOMES 3910 DUNE SIDE DRIVE, FORT PIERCE, FL34949 Location: Indoor: Heating Cooling Vero Beach Municipal AP, FL, US Indoor temperature (OF) 70 75 Elevation: 30 ft Design TD (OF) 27 16 Latitude: 280N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) -0.2 58.7 Dry bulb (OF) 43 91 Infiltration: Daily range (OF) - 16 ( L ) Method Simplified Wet bulb (OF) - 78 Construction quality Semi -tight Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions or Area U•value Insul R Htg HTM Loss Clg HTM Gain ft� BtuhRR°F ft� °F/Btuh Btuh/R= Btuh BtuhM Btuh Walls 13A-2ocs: Blk wall, stucco ext, r-2 ext bd ins, 8" thk, 1/2" gypsum n 470 0.201 0 5.41 2539 4.96 2331 board int fnsh a 275 0.201 0 5.41 1484 4.96 1362 s 415 0.201 0 5.41 2242 4.96 2058 w 250 0.201 0 5.41 1352 4.96 1241 all 1409 0.201 0 5.41 7618 4.96 6992 13A-2ocs 2:13A-2ocs 2 n 296 0.201 4.1 5.41 1600 4.96 1469 e 186 0.201 4.1 5.41 1008 4.96 925 s 312 0.201 4.1 5.41 1688 4.96 1549 w 177 0.201 4.1 5.41 956 4.96 877 all 971 0.201 4.1 5.41 5251 4.96 4820 Partitions 12C-Osw Frm wall, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud: 12C-Osw Frm wall, r-13 cav ins, 1/2" gypsum board i nt fnsh, 2"x4" wood frm, 16" o.c. stud I Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, n 1/8" thk; NFRC rated (SHGC=0.30); 50% drapes, medium; 9.58 ft overhang (5.25 ft window ht, 0.33 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, cir low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, n 1/8" thk; NFRC rated (SHGC=0.30); 50% drapes, medium; 2.25 ft overhang (2.5 ft window ht, 0.33 ft sep.); 6.67 ft head ht 2A-2omd: 2 glazing, cir low-e outr, air gas, mtl no brk frm mat, cir innr, e 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.30); 11.25 ft overhang (8 ft window ht, 0.33 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, e 1/8" thk; NFRC rated (SHGC=0.30); 2.25 ft overhang (6.3 ft window ht, e 0.33 ft sep.); 6.67 ft head ht all 2A-2ov: 2 glazing, clr low-9 outr, air gas, vnl frm mat, cir innr, 1/4" gap, e 1/8" thk; NFRC rated (SHGC=0.30); 14.42 ft overhang (6.3 ft window e ht, 0.33 ft sep.); 6.67 ft head ht all 207 0.096 13.0 2.58 533 1.70 351 14 0.360 0 9.68 136 10.1 141 6 0.360 0 9.68 61 10.1 63 144 1.020 0 27.4 3951 22.1 3182 34 0.360 0 9.68 325 28.9 972 32 0.360 0 9.68 305 28.9 911 65 0.360 0 9.68 630 28.9 1883 34 0.360 0 9.68 325 11'.9 399 32 0.360 0 9.68 305 11.9 374 65 0.360 0 9.68 630 11.9 773 =1 wrightsoft, 2018-May-0216:30:26 pw"a•roM�%•w 4�,-+, Right-Sulte® Universal2018 18.0.13 RSU24011 ice` Page 1 ...arponFlatsModelBGrlLot3lTarponFlatsModelBGr.rup Calc = MJ8 House faces: W 2A-2ov: 2 glazing, clr low-e outr, air gas, vni frm mat, cir inns, 1/4" gap, a 65 0.360 1/8" thk; NFRC rated (SHGC=0.30); 2.25 ft overhang (5.25 It window - ht, 0.33 It sep.); 6.67 ft head ht 2A-2ov: 2 glazing, cir low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, s 22 0.360 1/8" thk; NFRC rated (SHGC=0.30); 2.25 ft overhang (4.2 ft window ht, 0.33 ft sep.); 6.67 It head ht 2B-2fv: 2 glazing, cir low-e outr, air gas, vni frm mat, clr innr, 1/4" gap, s 4 0.360 1/8" thk; NFRC rated (SHGC=0.30); 2.25 It overhang (2 It window ht, 0.33 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vni frm mat, cir innr, 1/4" gap, w 34 0.360 1/8" thk; NFRC rated (SHGC=0.30); 2.25 ft overhang (6.3 ft window ht, 11.67 ft sep.); 6.67 It head ht 2A-2ov: 2 glazing, cir low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, w 34 0.360 1/8" thk; NFRC rated (SHGC=0.30); 2.25 ft overhang (6.33 ft window ht, 0.33 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, cir low-e outr, air gas, vni frm mat, cir innr, 1/4" gap, w 12 0.360 1/8" thk; NFRC rated (SHGC=0.30); 6.25 ft overhang (8 ft window ht, 0.33 It sep.); 6.67 ft head ht 2A-2ov: 2 glazing, cir low-e outr, air gas, vni frm mat, cir innr;,1/4" gap, w 14 0.360 1/8" thk; NFRC rated (SHGC=0.30); 50% drapes, medium; 2.25 ft overhang (5.25 ft window ht, 0.33 ft sep.); 6.67 It head ht w 32 0.360 1 all 46 0.360 2A-2ov: 2 glazing, cir low-e outr, air gas, vni frm mat, cir innr,11/4" gap, w 28 0.360 1/8" thk; NFRC rated (SHGC=0.30); 50% drapes, medium; 7.25 It overhang (5.25 ft window ht, 0.33 It sep.); 6.67 ft head ht Doors 11 DO: Door, wd so type w 24 0.390 n 21 0.390 all 45 0 390 Ceilings 16X19-Omd:Attic ceiling, mtl roof mat, r-20 roof ins, 1/2" gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 1959 0.408 195 0.989 0 9.68 627 27.8 1801 0 9.68 217 11.9 266 0 9.68 39 11.9 47 0 9.68 325 34.4 1156 0 9.68 327 28.9 978 0 9.68 116 20.7 249 0 9.68 136 23.6 331 0 9.68 314 23.6 765 0 9.68 449 23.6 1095 0 9.68 271 10.1 282 0 10.5 252 11.4 273 0 10.5 224 11.4 243 0 10.5 476 11.4 516 19.0 1.52 2984 1.50 2939 0 26.6 5174 0 0 wrightsoft, 2018-May-02 16:30:26 .KMrtavanaa•F4uo.vmv."< Right-Suite®Universal 2018 18.0.13 RSU24011 Page 2 ...arponFlatsModelBGrtLot3lTarponFlatsModelBGr.rup Calc = MJ8 House faces: W Component Constructions Job: Lot3lTarponFlatsModel... DLL,' Date: Jan 29, 2016 NiATIN6!itt9.f1tfilTMtiMHtp Zone 1 By: RH DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL32771 Phone:407-333-2665 Fax:'407-333-3853 Web: WWW.DELAIR.COM Project• • For: PHOENIX REALTY HOMES 3910 DUNE SIDE DRIVE, FORT PIERCE, FL34949 Location: Indoor: Heating Cooling Vero Beach Municipal AP, FL, US Indoor temperature (°F) 70 75 Elevation: 30 ft Design TD (OF) 27 16 Latitude: 280N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) -0.2 58.7 Dry bulb (°F) 43 91 Infiltration: Daily range (OF) - 16 (L ) Method Simplified Wet bulb (OF) - 78 Construction quality Semi -tight Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Cig HTM Gain fly Rtuh/FtL-F W-°F/Rtuh Rtuh/P Rhrh Rhth/K Rhrh Walls 13A-2ocs: Blk wall, stucco ext, r-2 ext bd Ins, 8" thk, 1/2" gyps m n board int ins e s w all Partitions 12C-Osw Frm wall, r-13 cav ins, 1/2" gypsum board int fnsh, 2'M" wood frm, 16" o.c. stud: 12C-Osw Frm wall, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud Windows 2A-2omd: 2 glazing, cir low-e outr, air gas, mtl no brk frm mat, clr innr, e 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.30); 11.25 It overhand (8 ft window ht, 0.33 it sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 114" gap, e 1/8" thk; NFRC rated (SHGC=0.30); 2.25 ft overhang (6.3 ft window ht, e 0.33 ft sep.); 6.67 It head ht all 2A-2ov: 2 glazing, cir low-e outr, air gas, vnl frm mat, cir innr, 1%4" gap, e 1/8" thk; NFRC rated (SHGC=0.30); 14.42 ft overhang (6.3 ft window e ht, 0.33 ft sep.); 6.67 ft head ht I all 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 114" gap, s 1/8" thk; NFRC rated (SHGC=0.30); 2.25 ft overhang (4.2 It window ht, 0.33 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, cir low-e out, air gas, vnl frm mat, Or Innr, 1/4" gap, w 1/8" thk; NFRC rated (SHGC=0.30); 2.25 ft overhang (6.3 It window ht, 11.67 ft sep.); 6.67 it head ht 2A-2ov: 2 glazing, cir low-e out, air gas, vnl frm mat, clr innr, 1/4" gap, w 1/8" thk; NFRC rated (SHGC=0.30); 2.25 It overhang (6.33 ft window ht, 0.33 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, cir low-e out, air gas, vnl frm mat, cir innr, 1/4" gap, w 1/8" thk; NFRC rated (SHGC=0.30); 6.25 ft overhang (8 ft window ht, 0.33 it sep.); 6.67 ft head ht 470 0.201 0 5.41 2539 4.96 2331 275 0.201 0 5.41 1484 4.96 1362 415 0.201 0 5.41 2242 4.96 2058 250 0.201 0 5.41 1352 4.96 1241 1409 0.201 0 5.41 7618 4.96 6992 207 0.096 13.0 2.58 533 1.70 351 144 1.020 0 27.4 3951 22.1 3182 34 0.360 0 9.68 325 28.9 972 32 0.360 0 9.68 305 28.9 911 65 0.360 0 9.68 630 28.9 1883 34 0.360 0 9.68 325 11.9 399 32 0.360 0 9.68 305 11.9 374 65 0.360 0 9.68 630 11.9 773 22 0.360 0 9.68 217 11.9 266 34 0.360 0 9.68 325 34.4 1156 34 0.360 0 9.68 327 28.9 978 12 0.360 0 9.68 116 20.7 249 .- wrighttsot 2018•May-02 16:30:26 Aw".�•re..,u.w�.....r.-,.,,, Right-Sulte® Universal 2018 18.0.13 RSU24011 Page 3 ...arponFlatsModelBGALot3lTarponFlatsModelBGr.rup Calc = MJ8 House faces: W Doors 11 DO: Door, wd so type w 24 0.390 n 21 0.390 all 45 0.390 Ceilings 16X19-Omd:Attic ceiling, mtl roof mat, r-20 roof ins, 1/2" gypsum board 1152 0.408 int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 195 0.989 ti -- wriighftsoffi� ,��.'r, xrnrteve"r.�ti�wn..gemo.,: Right -Suite® Universal 2018 18.0.13 RSU24011 ...arponFlatsModelBGrlLot3lTarponFlatsModelBGr.rup Calc ='MJ8 House faces: W 0 10.5 252 11.4 273 0 10.5 224 11.4 243 0 10.5 476 11.4 516 19.0 1.52 1755 1.50 1728 0 26.6 5174 0 0 2018-May-02 16:30:26 Page 4 Job: Lot31TarponFlatsModel... DEL -AIR Component Constructions Date: Jan 29, 2016 'IItEAi1N8.'AIBI�tl�Illitptpl Zone 2 By: RH DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL32771 Phone:407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Project• • For: PHOENIX REALTY HOMES 3910 DUNE SIDE DRIVE, FORT PIERCE, FL34949 Location: ! Indoor: Heating Cooling Vero Beach Municipal AP, FL, US Indoor temperature (OF) 70 75 Elevation: 30 ft Design TD (OF) 27 16 Latitude: 280N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) -0.2 58.7 Dry bulb (OF) 43 j 91 Infiltration: Daily range (OF) - 16 (L ) Method Simplified Wet bulb (OF) - 78 Construction quality Semi -tight Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain fF BtuhM °F ftMF/Btuh Btuh/ft' Btuh Btuh/t2 Btu Walls 13A-2ocs 2: 13A-2ocs 2 i n 296 0.201 4.1 5.41 1600 4.96 1469 e 186 0.201 4.1 5.41 1008 4.96 925 s 312 0.201 4.1 5.41 1688 4.96 1549 w 177 0.201 4.1 5.41 956 4.96 877 all 971 0.201 4.1 5.41 5251 4.96 4820 Partitions (none) Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, n 1/8" thk; NFRC rated (SHGC=0.30); 50% drapes, medium; 9.58 it overhang (5.25 ft window ht, 0.33 it sep.); 6.67 it head ht 2B-2fv: 2 glazing, cir low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, n 1/8" thk; NFRC rated (SHGC=0.30); 50% drapes, medium; 2.25 ft overhang (2.5 ft window ht, 0.33 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr,11/4" gap, e 1/8" thk; NFRC rated (SHGC=0.30); 2.25 ft overhang (5.25 ft window ht, 0.33 It sep.); 6.67 ft head ht 2B-2fv: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, s 1/8" thk; NFRC rated (SHGC=0.30); 2.25 It overhang (2 ft window ht, 0.33 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, w 1/8" thk; NFRC rated (SHGC=0.30); 50% drapes, medium; 2.25 ft overhang (5.25 It window ht, 0.33 ft sep.); 6.67 It head ht w all 2A-2ov: 2 glazing, Or low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, w 1/8" thk; NFRC rated (SHGC=0.30); 50% drapes, medium; 7.25 ft overhang (5.25 ft window ht, 0.33 ft sep.); 6.67 It head ht 14 0.360 0 9.68 136 10.1 141 6 0.360 0 9.68 61 10.1 63 65 0.360 0 9.68 627 27.8 1801 4 0.360 0 9.68 39 11.9 47 14 0.360 0 9.68 136 23.6 331 32 0.360 0 9.68 314 23.6 765 46 0.360 0 9.68 449 23.6 1095 28 0.360 0 9.68 271 10.1 282 Aa- wtrightsoft- 2018-May-0216:30:26 Right-Suite® Universal 2018 18.0.13 RSU24011 Page 5 ...arponFlatsModelBGrlLot3lTarponFlatsModelBGr.rup Calc = MJ8 House faces: W Doors (none) Ceilings 16X19-Omd:Attic ceiling, mtl roof mat, r-20 roof ins, 1/2" gypsum board 807 0.408 19.0 1.52 1229 1.50 1211 i nt fns h Floors (none) 1: "0114' wrightsoft, 2018-May-02 16:30:26 +-A RwRight-Sulte® Universal 2018 18.0.13 RSU24011 Page 6 ...arponFlatsModelBGr%Lot3lTarponFlatsModeISGr.rup Calc = MJ8 House faces: W Project Summar Pro Job: Lot3lTarpon FlatsModel... DEL-AihZ j y Date: Jan 29, 2016 xtl�•w+caa+�trl�l+rrz- Entire House By: RH DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Project• • For: PHOENIX REALTY HOMES 3910 DUNE SIDE DRIVE, FORT PIERCE, FL34949 Notes: RVSD 10/20/2016 by FJF LS 5/2118 JA Design Information Weather: Winter Design Conditions Outside db 43 OF Inside db 70 OF Design TD 27 OF Heating Summary Structure 33364 Btuh Ducts 10369 Btuh Central vent (58 cfm) 1714 Btuh Humidification Piping Equipment load Infiltration Method Construction quality Fireplaces 0 Btuh 0 Btuh 45447 Btuh Vero Beach Municipal AP, FL, US Simplified Semi -tight 0 Heating Cooling Area (ft2 2632 2632 Volume (ft3) 25724 25724 Air changes/hour 0.28 0.15 Equiv. AVF (cfm) 120 64 Heating Equipment Summary Make n/a Trade n/a Model n/a AHRI ref n/a Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat n/a Summer Design Conditions Outside db 91 OF Inside db 75 OF Design TD 16 OF Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Sensible Cooling Equipment Load Sizing Structure 34339 Btuh Ducts 15563 Btuh Central vent (58 cfm) 988 Btuh Blower 0 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Equipment sensible load 50890 Btuh Latent Cooling Equipment Load Sizing Structure 3364 Btuh Ducts 4140 Btuh Central vent (58 cfm) 2313 Btuh Equipment latent load 7504 Btuh Equipment Total Load (Sen+Lat) 58394 Btuh Req. total capacity at 0.70 SHR 6.1 ton Cooling Equipment Summary Make n/a Trade rVa Cond n/a Coil n/a AHRI ref rVa n/a Efficiency n/a Sensible cooling 0 Btuh 0 Btuh Latent cooling 0 Btuh 0 OF Total cooling 0 Btuh 0 cfm Actual air flow 0 cfm 0 cfm/Btuh Air flow factor 0 cfm/Btuh 0 in H2O Static pressure 0 in H2O Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsofC- 2018-May-02 16:30:26 .~ �,rt.•+° ^— Right -Suite® Universal 2018 18.0.13 RSU24011 Page 1 A...arponFlatsModelBGr\Lot3lTarponFlatsModelBGr.rup Calc = MJB House faces: W Job: Lot3lTarpon FlatsModel... DEL -Ally. Project Summary Date: Jan 29, 2016 Ilt)RIINt."WCdNhrtlt)KIM Zone 1 By: RH DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM For: PHOENIX REALTY HOMES 3910 DUNE SIDE DRIVE, FORT PIERCE, FL34949 Notes: RVSD 10/20/2016 by FJF LS 5/2118 JA Weather: Vero Beach Municipal AP, FL, US Winter Design Conditions Outside db 43 OF Inside db 70 OF Design TD 27 OF Heating Summary Structure 23934 Btuh Ducts 7626 Btuh Central vent (58 cfm) 1714 Btuh Outside air Humidification 0 Btuh Piping 0 Btuh Equipment load 33274 Btuh Infiltration Method Simplified Construction quality Serr tight Fireplaces 0 i Heatingg Coolingg Area (ft2 1919 1919 Volume (ft3) 18219 18219 Air changes/hour 0.24 0.13 Equiv. AVF (cfm) 74 40 Heating Equipment Summary Make Carrier Trade Model CH14NB0480000A0 AHRI ref 9162789 Efficiency 8.2 HSPF Heating input Heating output 45500 Btuh @ 47OF Temperature rise 27 OF Actual air flow 1533 cfm Air flow factor 0.049 cfm/Btuh Static pressure 0.30 in H2O Space thermostat Capacity balance point = 35 OF Backup: Input = 9 kW, Output = 30981 Btuh, 100 AFUE Summer Design Conditions Outside db 91 OF Inside db 75 OF Design TD 16 OF Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Sensible Cooling Equipment Load Sizing Structure 99997 Btuh Ducts 11963 Btuh Central vent (58 cfm) 988 Btuh Outside air Blower 0 Btuh Use manufacturer's data y Rate/swing multiplier 1.00 Equipmei sensible load 35248 Btuh Latent Cooling Equipment Load Sizing Structure 2376 Btuh Ducts 3152 Btuh Central vent (58 cfm) 2313 Btuh Outside air Equipment latent load 7841 Btuh Equipment Total Load (Sen+Lat) 43088 Btuh Req. total capacity at 0.75 SHR 3.9 ton Cooling Equipment Summary Make Carrier Trade Cond CH14NB0480000A0 Coil FB4CNP048L AHRI ref 9162789 Efficiency 11.5 EER, 14 SEER Sensible cooling 34500 Btuh Latent cooling 11500 Btuh Total cooling 46000 Btuh Actual air flow 1533 cfm Air flow factor 0.045 cfm/Btuh Static pressure 0.30 in H2O Load sensible heat ratio 0.82 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. �. writsoft 2018-May-0216:30:26 Right -Suite® Universal 2018 18.0.13 PSU24011 Page 2 ...arponFlatsModelBGrlLot3lTarponFlatsModelBGr.rup Calc = MJ8 House faces: W w Job: Lot31Tarpon FlatsModel... DE6Alt Project Summary Date: Jan29,2016 ';. fo:GilNW•AtA:CdHtiWR' Zo/%@ 2 By: RH DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM For: PHOENIX REALTY HOMES 3910 DUNE SIDE DRIVE, FORT PIERCE, FL34949 Notes: RVSD 10/20/2016 by FJF LS 5/2118 JA Design Information Weather: Vero Beach Municipal AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 43 OF Outside db 91 OF Inside db 70 OF Inside db 75 OF Design TD 27 OF Design TD 16 OF Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 9430 Btuh Structure 12380 Btuh Ducts 2743 Btuh Ducts 3754 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 12173 Btuh Use manufacturer's data y Rate/swingq multipplier 1.00 Infiltration I Equipmenfsensible load 16133 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Semi -tight Fireplaces 0 Structure 988 Btuh Ducts 988 Btuh Central vent (0 cfm) 0 Btuh Heatingg Coolingg (none) Area (ft2) 713 713 Equipment latent load 1976 Btuh Volume (ft3) 7505 7505 Air changes/hour 0.37 0.20 Equipment Total Load (Sen+Lat) 18110 Btuh Equiv. AVF (cfm) 46 25 Req. total capacity at 0.75 SHR 1.8 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade Trade Model CH14NB0240000A0 Cond CH14NB0240000A0 AHRI ref 9162301 Coil FB4CNP025L AHRI ref 9162301 Efficiency 8.2 HSPF Efficiency 11.5 EER, 14.5 SEER Heating input Sensible cooling 16650 Btuh Heating output 22200 Btuh @ 47OF Latent cooling 5550 Btuh Temperature rise 27 OF Total cooling 22200 Btuh Actual air flow 740 cfm Actual air flow 740 cfm Air flow factor 0.061 cfm/Btuh Air flow factor 0.046 cfm/Btuh Static pressure 0.30 in H2O Static pressure 0.30 in H2O Space thermostat Load sensible heat ratio 0.89 Capacity balance point = 29 OF Backup: Input = 2 kW, Output = 7934 Btuh, 100 AFUE Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. .�. - wrghtsoft` 2018-May-02 16:30:26 .'��. •�^+ r^--+ Right -Suite® Universal 2018 18.0.13 RSU24011 Page 3 ...arponFlatsModelBGALot3lTarponFlatsModelBGr.rup Calc = MJ8 House faces: W QDEL AIR Right-J® Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 GODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot3l Tarpon FlatsModel BG r Date: Jan 29, 2016 By: RH Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. .!- wrlghtsoft 2018-May-0216:30:26 AaFA Right -Suite@ Universal 2018 18.0.13 RSU24011 Page 1 ...arponFlatsModelBGrlLot3lTarponFlatsModelBGr.rup Calc = MJ8 House faces: W DEL �►IR Right-J® Worksheet mra":a�ea�rnormro Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot3l Tarpon FlatsModel BG r Date: Jan 29, 2016 By: RH Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. t- wrlgF�irsofto 2018-May-02 16:30:26 r ""^"°"" " ^� ^� Right -Suite® Universal 2018 18.0.13 RSU24011 Page 2 arponFlatsModeISGr%Lot3lTarponFlatsModelBGr.rup Cale = MJ8 House faces: W DE"IR Right-J® Worksheet Zone 1 DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL32771 Phone:407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot3l Tarpon FlatsModelBG r Date: Jan 29, 2016 By: RH 1 Room name Zone 1 Mstr Bath 2 Exposed wall 194.5 ft 31.5 ft 3 Room height 9.3 ft d 9.3 it heat/cool 4 Room dimensions 1.0 x 198.0 ft 5 Room area 1959.0 ft2 198.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ftz°F) (Btu 2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool s W .13$-2oes. -.._ :.0.20# -..n _ 5.41 4:6(l 470 25392ii�% ° 1�2 = #12 fiO3 54 1A-2ocs 2 0.201 n 0.00 0.00 0 0 0 0 0 0 0 0 2'A ov 0.360 n 0.00 0.00 0 0 0 0 0 0 0 0 2B-2fv 0.360 n 0.00 0.00 0 0 0 0 0 0 0 0 11 13A 2ocs: ! 0201 .. ,i fYNi e'- n ` 5:4i' .2. •77 dA. 496 � �M�tn a 549 � .....` 1A:1 �"` '275 .. 1AA ° i484 •.gar4 1962 -.71G9 6 < . A 0 . A 0777-7-76 » •:t '*_ A ..: n 13A-2DCs 2 0.201 a 0.00 0.00 0 0 0 0 0 0 0 0 2A 2ov 0 360 e 0 00 0 00 0 0 0 0 0 0 0 0 13A 2acsx 0.201 s ;` 4 5.41: 4 96 -. : : 437 4152 r58 33 33 : °. 16 :,° 16P o 0.360...s.� ".�:�-iffi 1L$Z = ` '='22 afZ 266 _0 0 0 0 13A-20cs 2 0.201 s 0.00 0.00 0 0 0 0 0 0 0 0 2B 2fv 0.360 s 0 00, 0.00 0 0 0 0 0 0 0 0 _ 13A-2ocs U-20i =� w 5W � 4.96 � . �. _ 250 7 _� W . ,'1241 � 149 ; � 115 _- 8� �5I1. 2A 2ov 0 360 wr 9 68 34 41 34 0 325 1156 0 0 0 0 2A 2ov -' 1)360 w,` 9 68 28 95 , 34 8 327 978 34 8 327 978 26 2fv ° 0 360 w,e 9:88 20,73 12 7 116 249 0 0 0 0 11A0 0390 w 70:49 -- _.11,39 -. •:?4 ... 24 a252 _, _. 273 0 0 13A-2ocs 2 0.201 w 0.00 0.00 0 0 0 0 0 0 0 0 2A-2ov 0.360 w 0.00 0.00 0 0 0 0 0 0 0 0 2A-2ov 0.360 w 0.00 ' 0.00 0 0 0 0 0 0 0 0 2A 2ov 0.360 w 0.00 0.00 0, 0 0 0 0 0 0 0 _ ilno Wfrm 4a3gDn is....22$'�2o��y ,77 351 - o oo �o i RXl4rlmfl nAnR w1049i696 1 C;q i rn 11r9 11 F9 17Fg; 243 179R _o-.,-o.�0. 10A 10n An7 0. 907 1=010000 0 E E� 6 c) AED excursion 0 460 Envelope loss/gain 21753 18074 2868 3021 12 a) Infiltration 2181 673 353 109 b) Room ventilation 0 0 0 0 13 Intemal gains: Occupants @ 230 4 920 0 0 Appliances/other 2630 0 Subtotal (lines 6 to 13) 23934 222971 3221 3130 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 23934 22297 3221 3130 15 Duct loads 32% 549/6 7626 11963 320/6 54% 1026 1 16110 Total room load 31560 34260 4248 4810 Air required (cfm) 1533 1533 206 215 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. w rlghtst" Yof2018-Ma -02 16:30:26 �^ ^ ; Right -Suite® Universal 2018 18.0.13 RSU24011 Page 3 ...arponFlatsModelBGALot3lTarponFlatsModelBGr.rup Calc = MJ8 House faces: W DEL a1R Right-J® Wolrksheet Zone 1 DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot31TarponF1ats1V1ode1BGr Date: Jan 29, 2016 By: RH 1 Room name Mstr We Dining 2 Exposed wall 6.0 ft 13.0 ft 3 Room height 9.3 ft heat/cool 9.3 It heal/cool 4 Room dimensions 10.0 x 6.0 ft 13.0 x 12.5 ft 5 Room area 60.0 ftz 162.5 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftq Load number (Btuh/ft2°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cod Gross N/P/S Heat Cool r13A-2ocs 2 0.201 n 0.00 0.00 0 0 0 0 0 0 0 0 2A-2ov 0.360 n 0.00 0.00 0 0 0 0 0 0 0 0 2B-2fv 0.360 n 0.00 1 0.00 0 0 0 0 0 0 0 0 �1 '' 13A=2ocs 0 201 =-e7 5.41 � : 7 -4 � 0 77b 77. -` b 7777776- 0 , '70�7767777776 2A2ov °= 0360 ens 968 eo x t 1187 u ° 00 -° -v .. u -0 v 0 v 0 V 0 V 00 v 26 2fv M360 e 9168, ' 28 92 _' -Q 0 `' 0 0 O z 0 0 ;` 0 2B-ztV D 350 .� ' 9 68. 11.87.:i 9- 13A-2ocs 2 0.201 a 0.00 1 0.00 0 0 0 0 0 0 0 0 2A 2ov 0 360 e 0 00 0 00 0 0 0 0 0 0 0 0 Y3A2ocs< 0201 s 541 _4.96: 0 8 fl _-.." ..0t_�-,`..0 "" 0 0 0 2A.2oV 0D 0 ._.,......0 13A-2ocs 2 0.201 s 0.00 ' 0.00 0 0 0 0 0 0 0 0 28 2fv 0.360 s 0.00 0.00 0 0 0 0 0 0 0 0 13A 2ocs0 201 w,; 5 41 _ 4 96 0 0 0 0 74 41 221 202 2A2oV�� 0.3603441,, °p 04s0 0 34 0 925 11-56 7A2ov 0.360 wr 9.68 [ , `28s5.0. 0 0 0 ,0 A 0 2B 2fv .� 0.360 w: 9.68 2Q73 2° 0, 0 0 0 0 0 0 0 � W, L..JO._49 Liz"�_0 L _ 9 L. 13A-2ocs 2 0.201 w 0.00 0.00 0 0 0 0 0 0 0 0 2A-2ov 0.3' w 0.00 0.00 0 0 0 0 0 0 0 0 2A-20v 0.360 w 0.00 0.00 0 0 0 0 0 0 0 0 2A 2ov 0 360 w 0.00 0.00 0 0 0 0 0 0 0 0 12C Osw arm wa11, r Q 6 : 2 58 170 `� 0 0 Q 0 - 79 ; `.' 79 s 204 134. 1iD0 .'e � ..�..:0.390 _"n� i0.49 11:39 °` LI -r0 �., D 0 �_c .-_m___.0 z` °.�;.�.._0 �* .e ' D. 1RX1 Q-r1mr1 n 4m - i F9 I 1 Fn An Rn Qi an n n n n 6 c) AED excursion -22 422 Envelope loss/gain 553 345 1347 2146 12 a) Infiltration 67 21 146 45 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 1 230 Appliances/other 01 0 Subtotal (lines 6 to 13) 620 366 1493 2421 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 620 366 1493 2421 15 DuctlOads 32% 549/6 1 198 196 321/o 540/61 476 1299 Total mom load 818 .5621 1969 3720 Air required (cfm) 40 251 96 i66 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. I iurirlghtt scxrt-z 2018-May-02 16:30:26 ABARight-Suite® Universal 2018 18.0.13 RSU24011 Page 4 ...arponFlatsModelBGr\LotSITarponFlatsModelBGr.mp Cale = MJ8 House faces: W DE"IR Right-J® Worksheet rranra pm ealtort�rmta Zone 1 DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL32771 Phone:407-333-2665 Fax: 467-333-3853 Web: WWW.DELAIR.COM Job: Lot3l Tarpon FlatsModelBG r Date: Jan 29, 2016 By: RH 1 Room name Great Kitchen 2 Exposed wall 45.0 ft 42.5 ft 3 Room height 9.3 ft heat/cool 9.3 ft heat/cool 4 5 Room dimensions Room area 1.0 x 644.5 ft 644.5 ft2 1.0 x 384.0 ft 384.0 ft2 Ty Construction number U-value (Btuh/ft2°F) Or HTM I (Btuftz) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) I or perimeter (ft) Load (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 -W V)/ L-_CG' VAS 1.3°1.2ocs z � 13A-2ocs 2 2A-2ov 2B-2fv 13�C=2ocs�;9 � Q,201. 0.201 0.360 0 360 �,,.�8.201 -E n n _ n �j7777a. ......8 0.00 0.00 0.00 4 4 3& 0.00 0.00 �.0.00 _ 4.9sf 0 0 0 0 ..W 251' i� 0 0 0 f& .-. , =0 0 0 0 „ 7-81J — = 0 0 0 0 _53'2":""`a` . ` ._tl 0 0 0 ei"ae _ _ .0 0 0 0 �� ����,.84 , _ 17 � W. 0 0 0 �..: _45s _ f 0 0 0 .._, .:ITS 13A-2ocs 2 2A-2ov i3A gods. i' 2A2av 13A-2ocs 2 2B-2fV 13A-2ocs_-;' 51 2A 2ov 2A 2ov 28-2fv > 13A-2ocs 2 2A-2ov 2A-2ov 2A-2ov 12C-0sw 11DO�.d.>•# 16X19-0md 0.201 e 0.3p -0 e 0.360 '-s' 0.201 s 0390 1N.w.- E- AG- 9. `' g=1i:39L - 24 0.201 w 0.00 0.00 0 0.360 w 0.00 0.00 0 0.360 w 0.00 0.00 0 0.360 w 0.00 0.00 0 0<096 "� 2 59 170 Q 0:390 ti- n erw - 199 1 rn an 0 0 ft 0 0 0 0 0 0 0 0 0 61 c) AED excursion 1-325 -271 Envelope loss/gain 6851 4609 4588 3204 12 a) Infiltration 504 156 476 147 b) Room ventilation 0 0 0 0 13 1ntemal gains: Occupants @ 230 2 460 0 0 Appliances/other 230 1200 Subtotal (lines 6 to 13) 7356 54541 1 5064 4551 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 7356 5454 5064 4551 15 Duct loads 32% 54% 2344 2926 329% 549/6 16141 2442 Total room load 9700 8381 6678 6993 Air required (cfm) 471 375 324 313 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. we �aA'r - 2018-May-02 16:30:26 Aft k Right -Suite® Universal 2018 18.0.13 RSU24011 Page 5 ...arponFlatsModeiSGrlLot3lTarponFlatsMadelBGr.rup Cale = MJ8 House faces: W i `" DEL lR; Right-J® Worksheet Zone 1 DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot3l Tarpon FlatsModelBG r Date: Jan 29, 2016 By: RH 1 Room name Mstr Bdrm Mstr Wic 2 Exposed wall 46.5 ft 10.0 ft 3 Room height 9.3 ft heat/cool 9.3 ft heat/cool 4 Room dimensions 16.0 x 17.5 ft 11.0 x 10.0 ft 5 Room area 280.0 ft2 110.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/ftz°F) (BtutUftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cod Gross N/P/S Heat Cool 6 VV .13A:2+aCS� ,��_ .;�0,201. :r.ct� ....5:9ti 4.96 .'Cp °'�`�n'-•�63 �:�BtiO �.»:�,. �� d06 �:«.�.83 �._.....::�._..33 zH��...�t13 �2 yl 13A-2ocs 2 0.201 n 0.00 0.00 0 0 0 0 0 0 0 0 IF-G 2A-2ov 0.350 n 0.00 0.00 0 0 0 0 0 0 0 0 11 1 ' <` 2B-2fv 13A 2oc 0.360 v 0.201 n ,.67 0.00 5 Ai 0.00 :. _,t A 96 0 =� 349 0 ",_� . ,84 0 . , . 453 0 � a.. 415 0 0 0 .. :.. 0 0 3.9 0 0 77776 13A-2ocs 2 2A-20v 12w-2ocs 2A-2ov 13A-2ocs 2 13A-2ocs 2 2A-20v 2A-20v 0,201 a 0.00 0.360 e 0,00 4.201 s : 5.41'. D.360 68 0.201 s _ 0.00 NY u.uu NY 0.00 w 0.00 w 0.00 77 2,"W 1.52 0 0 0 0 0 0 0 0 0 0 0 0 0 0, 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .0 0- 0 p. 0 0 0 0 0 L eU 0 mm 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 61 c) AED excursion 1-180 -37 Envelope loss/gain 4280 3946 936 589 12 a) Infiltration 521 161 112 35 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 1 230 0 0 Appliances/other 600 0 Subtotal (lines 6 to 13) 4802 4937 1 1049 624 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 4802 4937 1049 624 Duct loads 1320/o 549/6 1530 2649 32% 54% 334 335 r Total room load 6331 7586 1383 959 Air required (cfm) 308 339 67 q3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrlglEsaft� 2018-Ma -02 16:30:26 c o ""`'"""' ^` "" Right -Suite® Universal 2018 18.0.13 RSU24011 y Page 6 ...arponFlatsMode]SGALot31Tarpon Flats ModelBGr.rup Calc = MJ8 House faces: W DEL AIR Right-J® Worksheet aemta ��a Zone 1 DEL AIR HTG, A/C & REFRIG. INC i 531 CODISCO WAY, SANFORD, FL32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot3l TarponFlatsModelBG r Date: Jan 29, 2016 By: RH 1 Room name Powder Utility 2 Exposed wall 0 ft 0 ft 3 Room height 9.3 ft heat/cool 9.3 ft heat/cool 4 Room dimensions 8.0 x 10.0 ft 8.0 x 5.0 It 5 Room area 80.0 ft2 40.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2 °F) (Btuh/ftq, or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 .W... 1.3A.2oCs� 0 =n-a _ZW--T 4.96' R,.......7 .:10 `'.0 =0 yl 13A-20cs 2 0.201 n 0.00 0.00 0 0 0 0 0 m 0 0 0 2A 2ov 0.360 n 0.00 0.00 0 0 0 0 0 0 0 0 2B 2fv 0.360 n 0.00 0.00 0 0 0 0 0 0 0 0 11 13A=2ocs� 0201 a 541 4�` WO D'+ D�mm0�0 0 0 %0 2A 2Drnd a e U a o 0 2A 2ov 0.360 a 9.68 2892 0 0 40 0 0 0 0 0 2A 2ov 0 360 e, ° 9:68` 11187 0 0 0 : 0 0 4 0 0 0' 2B2ty� 036U d 9sfl r'28.92 t) 0 D 0 _. r0360....�9.88' i1.8Z 0 t w.w_ 0 V11 13A-2ocs 2 0.201 a 0.00 10.00 0 0 0 _ .._0 0 0 0 0 L-C 2A 2ov 0.3 e 0.00 1 0.00 0 0 0 0 0 0 0 0 13A 2ocs Q 201 s77,5741 ',_ 7' '.7`M(1777 "."". '0 -� ;-x, 6 �D „2A 2ov 0.360 s 9:fi8 a 1t 87 vF nO a0 0 13A-2ocs 2 0.201 s 0.00 0.00 0 0 0 0 0 0 0 0 t-C 2B-2tv 0.360 s 0.00 0.00 0 0 0 0 0 0 0 0 13A 2pc5 0 201 w �5 41; 4 96 0 6 0 0 0 0" " 0 gip. 2A2ov 0360 .w 9.68 344i P �0 0 0,0' a360 w s 9;6f3 2$ 95 0 U 0 0 0 0 x 0 Q 26 2fv -' 0 360 w 9.68 20 73 0 0 0 Q 0 0 0 0 0 0a9a w: , .,aa9 y139 13A-2ocs z 0.20w 0.00 0.00 0 0 0 0 0 0 0 0 2A-2ov 0.360 w 0.00 0.00 0 0 0 0 0 0 0 0 2A-2ov 0.360 w 0.00 0.00 0 0 0 0 0 0 0 0 2A-2ov 0.360 w 0.00 '0.00 0 0 0 0 0 0 0 0 P 12p Asw rrn watt ► i 096 2 58 170 =6 70 7 � �a 6 777776 14 74 192 12` �D ftDD 0.390 _rig.,10.99 _.�t 39 = _� f} 0 0 �0 _� D O _0 _ 0 C 16X19-0md 0.408 1.52 11.50 50 50 76 75 40 40 61 60 F., w ,22A tpl R 989777728 fi(1 : 4 Af? ' ar ttn q 0 0 - 4Q i ,..�,._._ � � �� � ' " ,ate- � a•�'""_" s�-�" 6 c) AED excursion -4 -44 Envelope loss/gain 76 71 253 142 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 01 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 600 Subtotal (lines 6 to 13) 76 71 253 742 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 76 71 253 742 15 Duct loads 32% 54% 24 38 3216 549/6 81 398 Total room load 100 109 334 1141 Air required (cfm) 5 5 16 51 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -yj& vwrl9htisafe®+ 2018-Ma -02 16:30:26 Right -Suite® Universal 2018 18.0.13 RSU24011 y Page 7 ...arponFlatsModelBGrlLot3lTarponFlatsModelBGr.rup Cale = MJ8 House faces: W i s DEL AIR Right-J® Worksheet �a�a Zone 2 DEL AIR HTG, A/Ci & REFRIG. INC 531 COD ISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot3l Tarpon FlatsModelBG r Date: Jan 29, 2016 By: RH 1 Room name Zone 2 Bdrm 3 2 Exposed wall 122.0 ft 11.5 ft 3 Room height 9.3 ft d 9.3 ft heat/coal 4 5 Room dimensions Room area 807.0 ft2 11.5 x 13.0 ft 149.5 ft2 Ty Construction U-value Or HTM', Area (ft2) Load Area (ft2) Load number (Btuh/ftz°F) (BtuWft?) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W _ .13A 2t>& - __,Q 201 n =W. aa0 m" it t) ' ;y o G a V)I 13A-2ocs 2 0.201 n 5.41 4.96 316 296 1600 1469 0 0 0 0 2A-2ov 0.360 n 9.68 10.07 14 0 136 141 0 0 0 0 11 - 2B-2fv 13A=2ocs'te :: 0.360 7U.201 n a :z 9.68 , Ub 10. 0 07 '. =` ;#.,,0-D01 6 -,- ° : o7777761, 0 61 ,, .'.:V :"r 0 63 6 0 , a 6 0 , ...... 0 0 n 0 , 13A-2ocs 2 0.201 a 5.41 4.96 251 2A 2ov 0.360 e 9.68 27.82 65 -1 2ocs' - 0'.96 s ; o tl0 `Q 13A-2ocs 2 0.201 s 5.41 4.96 316 2B-2fv 0.360 s 9.68 11.87 4 13A 2o� to M w ,� ' O.DO 0 00 4,0 2A 2ov _.; 0360 " w''; $ :0,00 = ;o 2B 2fv 0360 w ` o oo 0 ao ;, o L,._. M �00L� 251 13A-2ocs 2 0.201 w 5.41 4.96 2A-20v 0.360 w 9.68 23.62 14 2A-2ov 0.360 w 9.68 23.62 32 2A-2ov 0.360 w 9.68 10.07 28 12G 0sw, Frm wall r 77' 096 00) 0 11 0,390 Lin 0.00. °n- ` Mtn A 16X19-0md 0.408 1.52 1.50 807 956 877 0 136 331 0 314 765 0 403 370 314 901- _�0 0 0 0 0 0 4 ; 0 o: 0 o '0 0 0 0 0 61 c) AED excursion 1697 -36 Envelope loss/gain 6063 10158 944 1459 12 a) Infiltration 1368 422 129 40 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 1800 300 Subtotal (lines 6 to 13) 94301 12380 1073 1798 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 9430 12380 1073 1798 15 Duct loads 29°/, 301/6 2743 3754 29% 309/6 312 545 Total room load 12173 16133 1386 2344 Air required (cfm) 740 740 84 108 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. �. '!�I� wrlgfilt olC� 2018-May-0216:30:26 Right-Sulte® Universal 2018 18.0.13 RSU24011 Page 8 ...arponFlatsModelBGrlLot3lTarponFlatsModelBGr.rup Calc - MJ8 House faces: W .DEL pIJR Right-J® Worksheet ImmG`Mcammr m Zone 2 DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL32771 Phone:407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot3l Tarpon FlatsModelBG r Date: Jan 29, 2016 By: RH Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. A_��„! �9ti�a1" 2018-May-02 16:30:26 i Right -Suite® Universal 2018 18.0.13 RSU24011 Page 9 ... arponFlatsModelBGrNLot31Tarpon FlatsModelBGr.rup Cale = MJ8 House faces: W g DEL -AIR Right-J® Worksheet '?Cxrarna•uaearmmoraxa Zone 2 DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM Job: Lot3l Tarpon FlatsModelBG r Date: Jan 29, 2016 By: RH 1 Room name Lounge Shared Bthrm 2 Exposed wall 55.0 it 13.5 It 3 Room height 9.3 it heat/cool 9.3 it heat/cool 4 Room dimensions 1.0 x 339.0 It 5.5 x 13.5 it 5 Room area 339.0 ft2 74.3 ftz Ty Construction U-value Or HTM I Area 0t2) Load Area (ft2) Load number (Btuh/ftz°F) (Btuhlftz) 1 or perimeter (it) (Btuh) or perimeter (ft) (Btuh) Heat I Cool, Gross N/P/S Heat Cod Gross N/P/S Heat Cool 6 .W :AW., °020i 0. O.QO. 0.00�' 0 00 0 y/ 13A-2ocs 2 0201 n 5.41 4.96 270 263 1424 1308 0 0 0 0 I�---(C 2A-2ov 0 360 n 9.68 10.07 0 0 0 0 0 0 0 0 26-2fv 0.360 n 9.68 10.07 6 0 61 63 0 0 0 0 11 13A-2oc '0201 a � CFOO ;0,00 y77;0 77 ` 2A-2omdt' Q 020 ' e 0.00' O.OQ ' :0 0 0 0 - 0 0 0 0. 2A 2ov 0 360 e• 0 00 0 00 0 0 0 0 0 0 0 0 2A 2ov g 360 e 0 00 0 00 , R 0 i) 0 0 0 0 0 0 282fv D350 a 0001 0.00.; ;0 0 �,0 F 0 0 0 0 0 `0 360 a� 0 00 :.,�.QO- ' .0 I 0 Vy 13A-2ocs 2 0.201 a 5.41 4.96, 93 61 328 301 0 0 0 0 �G 2A 20v 0.360 e 9 68 27.82 : 32 9 314 901 0 0 0 0 13A 2ocs': 777 2M ss ; ''""0 00- `, 0 00 . 0 0 0 6 0 0 0 0 0 �0 ,,�..:._.0 tyl 13A 2ocs 2 0.201 s 5.41 4.96 19 19 101 92 126 122 657 603 I-i 28 2fv 0.360 s 9.68 11.87 0 0 0 0 4 4 39 47 �" 13A2ocs A201 w. 000 000 00 0 1.0 0 -. 0 0 '0` 2A 2ov 0 360 w ° 0.00 -, 0 DD 8 0 D 0 0 1) 0, 0 0 2A 2ov 0.360 w .: 0.00 0 DD 0 0 0 0 0 0 0 0 26 2fv z 0.360 w 0 00 0 00 ) 0, _p 0 0 0 0 0 0 13A-2ocs 2 0.201 w 5.41 4.96 1 130 88 477 438 0 0 0 0 2A-2ov 0.360 w 9.68 23.62 14 4 136 331 0 0 0 0 2A 2ov 0.360 w 9.68 23.62 0 0 0 0 0 0 0 0 2A 2ov 0.360 w 9.68 10.07 26 28 271 282 0 0 0 0 Px 12f:-Osw(=rmwail r DA96 000lz 000 ft'0 77777707 0 0 = 0 6 0 0 _iiDO 0.390 ri 0.00 0 0 0 ti0 0. C 16X19-0md 0.408 152 150 339 339 516 509 w 74 74 113 ill 22A tpl- . -. , 0..00 ,.,,_,_0 00, ' 0;00 N �"«�V 0 ._._ "� 77 ._ .-.-�.,,.- r-.�; s--�H-•--a--r-�-,--�----,�.�..�-,....--.--.m. € -R i m -. -� F -° - =-5 -1 _. - ..?..e:..:,:.....--'��.�., � :r 6 c) AED excursion 285 -31 Envelope loss/gain 3627 4508 809 731 12 a) Infiltration 617 190 151 47 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 1200 0 Subtotal (lines 6 to 13) 4243 5898 960 778 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 4243 5898 960 778 15 Duct loads 29% 30% 1234 1788 29% 30% 279 236 Total room toad 5478 7687 1240 1014 Airrequired(cfm) 333 353 75 47 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -�'�+ w�rlglitiso' Right-S2018-May-0216:30:26uite® Universal 2018 18.0.13 RSU24011 Page 10 ...arponFlatsModelBGrlLot3lTarponFlatsModelBGr.rup Calc = MJ8 House faces: W II Duct System Summary Job: Lot3lTarponFlatsModel... Date: Jan 29, 2016 NEAitNB.• AIR COHtlfrl8fAN0 Zone 1 By: RH DEL AIR HTG, A/C & REFRIG. INC ' 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: WWW.DELAIR.COM For: PHOENIX REALTY HOMES 3910 DUNE SIDE DRIVE, FORT PIERCE, FL34949 Heating Cooling External static pressure 0.30 in H2O 0.30 in H2O Pressure losses 0.06 in H2O 0.06 in H2O Available static pressure 0.24 in H2O 0.24 in H2O Supply / return available pressure 0.120 / 0.120 in H2O 0.120 / 0.120 in H2O Lowest friction rate 0.199 in/100ft 0.199 in/100ft Actual air flow 1533 cfm 1533 cfm Total effective length (TEL) 121 ft Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Dining C 3720 96 166 0.261 7.0 Ox0 VIFx 21.8 70.0 Great h 4850 236 187 0.272 8.0 Ox 0 VIFX 18.2 70.0 Great -A h 4850 236 187 0.296 8.0 Ox 0 VIFx 11.2 70.0 Kitchen- h 3339 162 156 0.201 7.0 Ox0 VIFX 34.6 85.0 sti Kitchen -A h 3339 162 156 0.203 7.0 Ox0 VIFx 33.1 85.0 sti Mstr Bath C 4810 206 215 0.299 8.0 Ox 0 VIFX 10.3 70.0 Mstr Bdrm C 3793 154 170 0.272 8.0 Ox 0 VIFx 18.2 70.0 Mstr Bdrm-A c 3793 154 170 0.284 8.0 Ox 0 VIFx 14.5 70.0 Mstr We h 818 40 25 0.304 4.0 Ox 0 VIFx 9.0 70.0 Mstr Wic h 1383 67 43 0.293 5.0 Ox 0 VIFX 11.9 70.0 Powder C 100 5 5 0.319 4.0 Ox0 VIFX 5.2 70.0 Utility C 1141 16 51 0.199 4.0 Ox0 VIFX 35.5 85.0 sti Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk st1 Peak AVF 341 364 0.199 463 12.0 0 x 0 VinlFlx -I'fi- wrightsoft- 2018-May-02 16:30:28 ti:. nNrt•�• e.w way �wr Right -Suite® Universal 2018 18.0.13 RSU24011 Page 1 ACCK ...arponFlatsModelBGr\Lot3lTarponFlatsModelBGr.rup Cale = MJ8 House faces: W Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb2 Ox 0 1533 1533 0 0 0 0 Ox 0 VIFx wrightsoft® 2018-May-02 16:30:28 1Right-Suite® Universal 2018 18.0.13 RSU24011 Page 2 ADM ...arponFlatsModelBGALot3lTarponFlatsModelBGr.rup Cale = MJ8 House faces: W DEL -AIR Duct System Summary ' "°� • 164 Zone 2 DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407r333-3853 Web: WWW.DELAIR.COM For: PHOENIX REALTY HOMES 3910 DUNE SIDE DRIVE, FORT PIERCE, FL34949 External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 % 0.120 in H2O 0.290 in/100ft 740 cfm Job: Lot3lTarpon FlatsModel... Date: Jan 29, 2016 By: RH Cooling 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 / 0.120 in H2O 0.290 in/100ft 740 cfm 83 ft Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR', Diam (in) H x W (in) Duct Mail Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Bdrm 3 c 2344 84 108 0.326 6.0 Ox 0 VIFx 5.0 70.0 Bdrm 3 WIC h 933 57 34 0.290 5.0 Ox 0 VIFx 12.7 70.0 Bdrm 4 c 4347 191 199 0.299, 8.0 Ox 0 VIFx 10.3 70.0 Lounge C 3843 166 176 0.3091 8.0 Ox 0 VIFx 7.8 70.0 Lounge -A C 3843 166 176 0.295 8.0 Ox 0 VIFx 11.4 70.0 Shared Bthrm h 1240 75 47 0.297 5.0 Ox 0 VIFx 10.8 70.0 Name Grille Size (in) Htg (cfm) Cig (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rbi Ox0 740 740 0 0 0 0 Ox 0 VIFx wrightsoft® 2018-May-02 16:30:28 =�: ���•v.,, Right -Suite® Universal2018 18.0.13 RSU24011 Page 3 CICK ...arponFlatsModelBGALot3lTarponFlatsModelBGr.rup Cale = MJ8 House faces: W I I 2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot31TarponFlatsModelBGr I Builder Name: PHOENIX REALTY HOMES Street: 3910 DUNE SIDE DRIVE ` Permit Office: City, State, Zip: FORT PIERCE, FL, } Permit Number: Owner: ` Jurisdiction: 661000 Design Location: FL, Fort Pierce COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. Breaks or joints in the air barrier shall be sealed. not be used as a sealing material. The air barrier in any dropped ceiling/soffit shall be aligned with Ceiling/attic the insulation and any gaps in the air barrier shall be sealed. The insulation in any dropped ceiling/soffit Access openings, drop down stairs or knee wall doors to shall be aligned with the air barrier. unconditioned attic spaces shall be sealed. � Walls The junction of the foundation and sill plate shall be sealed. Cavities within comers and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity with sealed. J a material having a thermal resistance of R-3 per inch Knee walls shall be sealed. minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped, shall be permanently attached to the crawlspace walls Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the drywall. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -floor or drywall. Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover nintes and walls or cemleng§_ a. in aaaition, inspection of log wails snap be in accordance witn the provisions of ICC-400. 5/2/2018 3:45 PM EnergyGauge® USA-.FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 FORM R405-2017 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Simulated Perform= Applications for compliance with the 20171 residential Simulated Performance Method ❑ This checklist fsiness and Professional Regulation Alternative (Performance) Method a Building Code, Energy Conservation via the include: ❑ A Form R405 report that documents that the Proposed Design complies with Section R405.3 of the Florida Energy Code. This form shall include a summary page indicating home address, a -ratio and the pass or fail status along with summary areas and types of components, whether the home was simulated as a worst -case orientation, name and version of the compliance software tool, name of individual completing the compliance report (one page), and an input summary checklist that can be used for field verification (usually four pages/may be greater). ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 4 ❑ Mandatory Requirements (five pages) Required prior to CO for the Performance Method: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed Envelope Leakage Test Report (usually one page) ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed Form R405 Duct Leakage Test Report (usually one page) EnergyGauge® - USRCSB v6.0 5/2/2018 3:45:12 PM Page 1 of 1 FORM R405-2017 Envelope Leakage Test Report Performance FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Envelope Leakage Test Report Performance Method i, Project Name: Lot3l Tarpon FlatsModel BGr I Builder Name: PHOENIX REALTY HOMES Street: 3910 DUNE SIDE DRIVE Permit Office: City, State, Zip: FORT PIERCE, FL, I Permit Number: Design Location: FL, Fort Pierce I Jurisdiction: 661000 Cond. Floor Area:: 2632 sq.ft. Cond. Volume: 24478 cu ft. Envelope Leakage Test Results Regression Data: C: n: R: Single or Multi Point Test Data HOUSE PRESSURE FLOW. ` 1 Pa cfm 2 Pa cfm 3 Pa I cfm 4 Pa 1cfm 5 Pa cfm 6 Pa cfm Leakage Characteristics Required ACH(50) from FORM R405-2017 : Tested ACH(50) * : *Tested leakage must be less than or equal to the required ACH(50) shown on Form R405-2017 for this building. If the tested ACH(50) is less than 3 the building must have a mechanical ventilation system. R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes per hour in Climate Zones 1 and 2 ... Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g. (50 Pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes or individuals licensed as set forth in Section 489.105(3)(0, (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures; 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures; 3. Interior doors, if installed at the time of the test, shall be open; 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed; 5. Heating and cooling systems, if installed at the time of the test, shall be turned off, and 6. Supply and return registers, if installed at the time of the test, shall be fully open. I hereby certify that the above envelope leakage performance results demonstrate compliance with Florida Energy Code requirements in accordance with Section R402.4.1.2. SIGNATURE: PRINTED NAME: DATE: Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes or individuals licensed as set forth in Section 489.105(3)(0, (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the third party conducting the test and provided to the code official. BUILDING OFFICIAL: DATE: 5/2/2018 3:45 PM EnergyGauge® USA - FlaRes2017 - Section R405.4.1 Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 6th Edition (2017) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 3910 DUNE SIDE DRIVE Permit Number: FORT PIERCE, FL, MANDATORY REQUIREMENTS See individual code sections for full details. 1 i SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mar datory).The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card containslinformation indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for, the building. A copy of the EPL display card can be found in Appendix RD. R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. R402.4.1.1 InstallationThe components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. i R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. ,l Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. R402.4.2 Fireplaces. New woad-buming fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. R402.4.3 Fenestration air leakagdIVindows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfrn per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 5/2/2018 3:45 PM EnergyGauge® USA - FlaRes2017 - FBC 6th Edition (2017) Complia Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. I Exceptions: Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. SECTION R403 SYSTEMS R403.1 Controls. R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be 'substantially leak free' in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturers designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the', time of the test. All registers shall be taped or otherwise sealed during the test. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler'enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying'by Section 405 of this code. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41 °C) or below 55°F (13°C) shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory)Heated water circulation systems shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 5/2/2018 3:45 PM EnergyGauge® USA - FlaRes2017 - FBC 6th Edition (2017) Complian Page 2 of 5 . MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'Y2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to',60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to, be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of'a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that dose when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where whole -house mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. No ventilation or air-conditioning system make-up air shall b&provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment (Mandatory). R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfrnhvatt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 Umin. a. When tested in accordance with HVI Standard 916 5/2/2018 3:45 PM EnergyGauge® USA - FlaRes2017 - FBC 6th Edition (2017) Complia Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section 403.7, or the closest available size provided by the manufacturers product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only 'equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than�80 percent of that load. 2. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design , requirements calculated according to the procedure selected in Section R403.7.1. R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403. R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. 5/2/2018 3:45 PM EnergyGauge® USA - FlaRes2017 - FBC 6th Edition (2017) Complia Page 4 of 5 R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test reportfrom an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. R403.11 Portable spas (Mandatoryirie energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be high -efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high -efficacy lamps. Exception: Low -voltage lighting. 1 R404.1.1 Lighting equipment (Mandatory)Fuel gas lighting systems shall not have continuously burning pilot lights. 5/2/2018 3:45 PM EnergyGauge® USA - FlaRes2017 - FBC 6th Edition (2017) Complia Page 5 of 5 MASTER ,-7--. "`m i 14x8I J" loath auct to roof cap w/fan Nutone 696RNB e 4561 ds duct Pbath roof cap fan-llght tone 763RLNB roof cap an one 696RNB IBS l.cd I 14�x'8 Ircd � J >z' 7' rraK 12.6 I.cd 1.cd Tron�er ducWorili- slid In conpliance With Florida ResWentinl BWldtrg Cody - NI6024 0 TDN Y/8KV B24DV 1PI1 µJ_"—'""� Balanced Return AU, excePibrs f-3 I Bultler dust provitle unrestricted 1 Yid, 24x16 rad IBx16 pled l undrrv+t an dour to ho6iioblr roods. ANU WUIGING IN ATTIC _ i tale �v8'-r0' ti HONEY WELL Y8150 FRESH AIR VENTILATION SYSTEM 6' SNAPLOCIC, FLEXABLE WTAL PIPE, OR FLEX r L = 1 L` — J T't r, oAnAaBi 'u .r. I I I INSULATE V/ L5 IN e/aKI DUCT WW WALL CAP cT l 150 FRESH AM DAMPER OUTSIDE AIR DETAIL TO SOFFIT OR VALL CAP av 4' drver duct to 42X42 A/C SLAB BY BLDR MIN 2' EOM WALL Must hove a nlnlnun clearance of 4 Inches around the air handler per the State Energy code. All duct has an r=6 Insulation value. Ss" �� NVCN g �C5Nco v � m z� -o , F CU 0 N Ij t\ w LJ W J Q L, X m — z w Z J O J OAF' tOI.J 2Ej0 Q IL f J 1-- z O j- N m W > z Q H m H Q 5 J 0 0 0 w O]O_.JIn00 a BUILDER: PLAN LOT SUBDIVISION DATE: DRAWN BY: MANOR IF:i rP. III I� I g—�` -I rod I PH❑ENIX REALTY HOMES MODEL B LOT 31 TARPON FLATS 1-16-14 J,MILLER REVISIONS Pet Alr DATE BY Hoa nq, Air Cmditlonlnq & Pefrlgerz 07.28.16 EIR R 109 Commerce Street 5/2/18 JA 5u& 1101 Lake Mary FI, 32746-6206 phone, 401-631-2665