HomeMy WebLinkAboutNOA- UNDERLAYMENT SYSTEMSSCANNED
BY
St Lucie County
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
BOARD AND CODE ADMINISTRATION DIVISION
NOTICE OF ACCEPTANCE (NOA)
Interwrap, Inc.
32923 Mission Way
Mission, BC, Canada V2V-6E4
MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208
Miami, Florida 33175-2474
T (786)315-2590 F (786) 315-2599
www.miamidade.sov/economy
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control
Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to
have this product or material tested for quality assurance purposes. If this product or material fails to perform in
the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately
revoke, modify, or suspend the use of such product or material within their jurisdiction. RER reserves the right to
revoke this acceptance, if it is determined by Miami -Dade County Product Control Section that this product or
material fails to meet the requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: itaniumO UDL-30 itanium PPSU-30 Titanium® UDL-25 PLUS / Titanium® PSU-30,
an L-MD (2 ply) / Titaniu i ® PSU-30 Underlayment System
LABELING: Each unit shall bear a permanent label:with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section
of this NOA shall be cause for termination and rem Ival of NOA.
I
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA renews and revises NOA# 13-0730.01 and consists of pages 1 through 7.
The submitted documentation was reviewed by Alex Tigera.
NOA No.: 14-0603.19
Expiration Date: 01/26/22
Approval Date: 02/02/17
Page 1 of 7
A1VTO11195
7 3379
APPROVED ® REVISE & RESt BMI-7
® APPROVEDAC~CORRECTED ❑ REJ20TED
This rev!ew'ss only for genemsl,mp
raConformance ti'�echof t''•e
project and general OUmcliance wish the informe`-cn in the corM'ct
dccmnents. Corrections or comments made on the -hop drawings duffing
this review do not re! -Sve se contractor ilom COM- "Ica s::� cie f"'i0re-
meats of the plans and specitir ations. Approval cf a speciac f+am r '0 not
ind!uda approval of an assembly of which tte fie: is ja c-r.:,ro-a. Con-
: is irresponsible for. Dimens!ons to be confi�d End cc: rr :stcd ai the
jcb site; Infc,s or to
t ra on that pa,
the so':afy io Uhe farsr aturaftruo-
the means, mAods, techniques, sequences and p
bon: coordinatim of the vvoer, of all other trades: and for performing all work _ in a safe and satisfactory manner.
DATE: ' `"� BY: -
f- w
Y
J
��tJi�ll`
MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474
BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/economy
Interwrap, Inc.
32923 Mission Way
Mission, BC, Canada V2V-6E4
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control
Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to
have this product or material tested for quality assurance purposes. If this product or material fails to perform in
the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately
revoke, modify, or suspend the use of such product or material within their jurisdiction. RER reserves the right to
revoke this acceptance, if it is determined by Miami -Dade County Product Control Section that this product or
material fails to meet the requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
i
DESCRIPTION: Titanium® UDL-30 / Titanium® PSU-30, Titanium® UDL-25 PLUS / Titanium® PSU-30,
and UDL-MD (2 ply) / Tit nium@ PSU-30 Underlayment System
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA renews and revises NOA# 13-0730.01 and consists of pages 1 through 7. ,
The submitted documentation was reviewed by Alex Tigera.
MIAMI•DADECOIJNTY qx
File COPY
ROOFING COMPONENT APPROVAL
Category Roofmg .
Sub -Category: Underlayment .
Material: Polypropylene
TRADE NAMES OF PRODUCTS MANUFACTURED BY APPLICANT
TABLE 1
Product. Dimensions
Test.
Product
Specification
Description
Titanium® UDL-25 48" x 250' rolls
ASTM D226
Woven synthetic polymer underlayment with one
PLUS
Type I & H
side coated with UV protected and slip resistant
polymer stabilized polypropylene on both sides.
Manufacturing
Location #1& #2
UDL-MD (2PIy system) 48" x 250' rolls
ASTM D226
Woven synthetic polymer underlayment with a
Type I & H
chemical slip resistant and UV protected coating on
Manufacturing
both sides.
Location #2
Titanium® UDL-30 48" x 250' rolls
ASTM D226
Woven synthetic polymer underlayment with two
Type I & II
sides coated with UV protected and slip resistant
Manufacturing
polymer stabilized polypropylene on both sides.
Location #1& #2
Titanium® PSU-30 36" x 72' rolls
TAS 103
Unreinforced polymer modified bitumen material
adhered to the underside of a polymer -coated,
Manufacturing
synthetic woven sheet. The underside is backed
Location #3
with a release film.
MANUFACTURING LOCATIONS:
1. ML1
2. ML3
3. ML4
I
MIAMMADE COUNTY I.
I
NOA No.: 14-0603.19
Expiration Date: 01/26/22
Approval Date: 02/02/17
Page 2 of 7
EVIDENCE SUBMITTED:
Test Mencv
Intertek Testing Services
Trinity I ERD
Test Identifier
#3031783
3124826-01
3119607COQ-003B
3130639COQ-002A
3124826NIID-007
314673 8COQ-003B
3146738COQ-003A
I35520.06.11
I35520.06.11
138010.08.11
I35520.08.11-1
I35520.08.11
I44970107.13-111
i
I
I
i
Test Name/Report
TAS 104
ASTM E108
ICC-ES AC48
ASTM D226
ASTM E108
ASTM D 1876/ TAS 117
ASTM D226
TAS 103 / TAS 104
TAS 103 / TAS 104
ASTM D226
TAS 114
ASTM D2523 / D1781
ASTM D226, ASTM D1876
and TAS 114(C)
Date
02/19/03
02/19/08
02/20/08
02/20/08
02/25/08
03/28/08
04/22/08
06/15/11
06/15/11
08/11/11
08/12/11
08/17/11
09/09/13
NOA No.: 14-0603.19
Miatirn�aoE�our Expiration Date: O1/26/22
Approval Date: 02/02/17
Page 3.of 7
I.
APPROVED TITANIUM UNDERLAYMENTI SYSTEM ASSEMBLIES:
Deck Type 1: ' wood
Deck Description: 19/32" or greater plywood or wood plank
System E(1): Base sheet mechanically fastened to deck, subsequent cap membrane self- adhered.
All General and System Limitations shall apply.'
Base sheet: One or more plies of Titanium® UDL-25 PLUS or Titanium® UDL-30 applied with
minimum 4" horizontal laps and minimum 6" vertical laps and mechanically fastened as
noted below.
Note: Titanium® UDL-30 shall be inverted to provide a smooth bonding surface. Primer is
not required when Titanium® UDL-30 is installed inverted (printed side facing down)
Fastening: Miami -Dade approved nails & metal/tin caps spaced 6" o.c. at the 4" horizontal laps and 8"
o.c. in a grid pattern having three, equally spaced, staggered rows in the field of the sheet.
Primer: Metal/Tin caps shall be primed with ASTM D41 primer_
Ply Sheet: (Optional) Titanium® PSU-30, self -adhered with minimum 3" horizontal laps and minimum
6" vertical laps.
Membrane: Titanium® PSU-30, self -adhered, with minimum 3" horizontal laps and minimum 6"
vertical laps. Place the first course of Titanium® PSU-30 parallel to the eave and field,
using a heavy pressure roller under safe conditions to further secure the membrane.
Surfacing: Approved for asphalt shingle, mechanically fastened roof tile, foam -on roof tile, metal
roofing, wood shakes &I shingles or slate roof assemblies.
Note: For tile roof assemblies, refer to RAS 118, 119 or 120 and the tile manufacturer's NOA. For
foam -on tile roof assemblies, approved use with ICP Adhesives Polyset AH-160 and Dow
TILE BOND Roof Tile IAdhesive.
I
NOA No.: 14-0603.19
Mwr+aoaoE cour�rnr Expiration Date: 01/26/22
Approval Date: 02/02/17
Page 4 of 7
Deck Type 1: Wood
Deck Description: 19/32" or greater plywood or wood plank -
System E (2): Base sheet mechanically fastened to deck, subsequent cap membrane self- adhered.
All General and System Limitations shall apply.
Base sheet:
One or more plies Titanium® UDL-30 applied with minimum 4" horizontal. laps and
minimum 6" vertical laps and mechanically fastened as noted below.
Fastening:
Miami -Dade approved nails & metal/tin caps spaced 6" o.c. at the 4" horizontal laps and 8"
o.c. in a grid pattern having three, equally spaced, staggered rows in the field of the sheet.
Primer:
Titanium® UDL-30 shall
be primed on the a printed side with ASTM D41 primer prior to
placement of cap sheet.
Ply Sheet:
i
(Optional) Titanium® PSU-30, self -adhered, with minimum 3" horizontal laps and minimum
6" vertical laps.
Membrane:
Titanium® PSU-30, selfladhered,
with minimum 3" horizontal laps and minimum 6"
vertical laps. Place the first
course of Titanium® PSU-30 parallel to the eave, using a heavy
pressure roller under safe conditions to further secure the membrane.
Surfacing:
Approved for asphalt shingle, mechanically fastened roof tile, foam -on roof tile, metal
roofing, wood shakes &
shingles or slate roof assemblies.1
Note:
For tile roof assemblies,
refer to RAS 118, 119 or 120 and the tile manufacturer's NOA. For
foam -on tile roof assemblies,
approved use with ICP Adhesives Polyset AH-160 and Dow
TILE BOND Roof Tile Adhesive.
9
MIAMfDADE COUNTY
NOA No.: 14-0603.19
Expiration Date: 01/26/22
Approval Date: 02/02/17
Page 5 of 7
Deck Type 1: Wood
Deck Description: 19/32" or greater plywood or wood plank
System E(3): Base sheet mechanically fastened to deck, subsequent cap membrane self- adhered.
All General and System Limitations shall apply.
Base sheet: One or more plies of UDL-MD (2Ply system) applied with minimum 4" horizontal laps and
minimum 6" vertical laps and mechanically fastened as noted below.
Fastening: Miami -Dade approved nails & metal/tin caps spaced 6" o.c. at the 4" horizontal laps and 8"
o.c. in a grid pattern having three, equally spaced, staggered rows in the field of the sheet.
Ply Sheet: (Optional) Titanium® PSU-30, self -adhered with minimum 3" horizontal laps and minimum
6" vertical laps.
Membrane: Titanium® PSU-30, self -adhered, with minimum 3" horizontal laps and minimum 6"
vertical laps. Place the first course of Titanium® PSU-30 parallel to the eave and field,
using a heavy pressure roller under safe conditions to further secure the membrane.
Surfacing: Approved for asphalt shingle, mechanically fastened roof tile, foam -on roof tile, metal
roofing, wood shakes & shingles or slate roof assemblies.
Note: For tile roof assemblies, refer to RAS 118, 119 or 120 and the tile manufacturer's NOA. For
foam -on tile roof assemblies, approved use with ICP Adhesives Polyset AH-160 and Dow
TILE BOND Roof Tile Adhesive.
NOA No.: 14-0603.19
Expiration Date: O1/26/22
Approval Date: 02/02/17
Page 6 of 7
Application for building permit shall beaccompanied by copies of the following:
1. This Notice of Acceptance.
2. Any other documents required by the' Building Official or applicable building code in order to properly
evaluate the installation of this material.
LIMITATIONS
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing'Materials Directory for
fire ratings of this product.
2. This acceptance is for prepared roofing applications. Minimum deck requirements shall be in compliance with
applicable building code.
3. Titanium Synthetic Underlayments shall be applied to , a smooth, clean and dry surface with deck free of
irregularities. All nails in the deck shall be carefully checked for protruding heads. Re -fasten any loose decking
panels. Sweep the deck thoroughly to remove any dust and debris prior to application.
4. Titanium® UDL-25 PLUS / Titanium® PSU-30, Titanium® UDL-30 / Titanium® PSU-30,'UDL-MD (2Ply
system) / Titanium® PSU-30 two-ply underlayment system, may be used in asphalt shingle, mechanically
fastened roof tile, foam -on roof tile, metal roofing, wood shakes & shingles or slate roof assemblies.
5. The standard Maximum roof pitch for the Titanium® UDL-25 PLUS / Titanium® PSU-30, Titanium® UDL-30
/ Titanium® PSU-30, UDL-MD (2Ply system) / Titanium® PSU-30 two-ply underlayment system shall be 5:12
for flat tiles and 6:12 on profiled tiles with lugs. For, flat tile applications at slopes exceeding 5:12, flat tiles
shall be staged 2 base tiles perpendicular to slope behind a mechanically attached batten or toe board with
maximum 7 tiles high on the slope atop base tiles (Total of stack not to exceed 9 tiles). At roof slopes greater
than the above limitations, the use of loading battens or toe boards are required to load the roof tile.
6. Titanium Synthetic Underlayments shall not be applied over an existing roof membrane as a recover system.
7. Titanium® UDL-30 / Titanium® PSU-30, Titanium® UDL-25 PLUS / Titanium® PSU-30, UDL-MD (2Ply
system) /Titanium® PSU-30 two-ply underlayment system shall not be left exposed as a temporary roof for
longer than 90 days of application.
8. Titanium Synthetic Underlayments are components used in roof system assemblies. Roof system assemblies are
approved under a specific Notice of Acceptance. Refer to Prepared Roofing System Product Control Notice of
Acceptance for listed approval of this product with specific prepared roofing products.
9. Titanium Synthetic Underlayments may be used with any approved roof covering Notice of Acceptance listing
Titanium Synthetic Underlayments as a component part of an assembly in the Notice of Acceptance. If
Titanium Synthetic Underlayments are not listed, a request may be made to the Authority Having Jurisdiction
(AHJ) or the Miami -Dade County Product Control Department for approval provided that appropriate
documentation is provided to detail compatibility of the products, wind uplift resistance, and fire testing results.
10. All membranes or packaging shall bear thel imprint or identifiable marking of the manufacturer's name or logo
and the following statement: "Miami -Dade County Product Control Approved" or the Miami -Dade County
Product Control Seal as shown below. j
MAMI•DADE COUNTY
END OF THIS ACCEPTANCE
i
MAMfDADECOUNTY
,...•
nuj
NOA No.: 14-0603.19
Expiration Date: 01/26/22
Approval Date: 02/02/17
Page 7 of 7