HomeMy WebLinkAboutBUILDING PLANPROJECT LOG ISSUED TOR PRECON 10-18-17 ISSUED FOR PERMIT 11-17-17 1 BLDG COMMENTS 02-05-18 GENERAL NOTES 1. THIS PLANS WERE PREPARED USING THE 2014 FLORIDA BUILDING CODE 5TH EDITION 2. TYPE OF CONSTRUCTION: CLASS V. UNPROTECTED, GROUP R3 OCCUPANCY PER FLORIDA BUILDING CODE. 3. CONSTRUCTION SHALL FOLLOW THE FLORIDA BUILDING CODE AS ADAPTED BY THE COUNTY AND ALL APPLICABLE AMENDMENTS. 4. THESE PLANS, AS DRAWN AND NOTED, COMPLY WITH THE BUILDING ENVELOPE ENERGY REQUIREMENTS OF THE F.B.C. CHAPTER 13 ENERGY EFFICIENCY. 5. ALL WINDOWS AND DOORS SHALL BE CAULKED AND WEATHER STRIPPED. WINDOW UNITS SHALL DISPLAY LABELS SHOWING COMPLIANCE WITH THE F.B.C. CHAPTER 13 ENERGY EFFICIENCY SECTION. 6. REGISTERED BAITING SYSTEM FOR TERMITE TREATMENT TO BE INSTALLED AND MONITERED THIRD PARTY PRIOR TO FINAL BUILDING APPROVAL PER F.B.C. 2014 A DOD17171 ATIWIKIC ABV ABOVE AFF ABOVE FINISHED FLOOR AHU AIR HANDLER UNIT B.F. BI FOLD B.P. BI PASS BLK. BLOCK B.W. BELOW BRG. BEARING BTM. BOTTOM CLG. CEILING CMU CONCRETE MASONRY UNITS COL COLUMN CONC. CONCRETE CSMT. CASEMENT DBL. DOUBLE DIA. DIAMETER DISP. DISPOSAL DP DESIGN PRESSURE DR. DOOR DW DISH WASHER E.E. EACH END ELEC. ELECTRICAL ELEV. ELEVATION ` E.S. EACH SIDE EXT. EXTERIOR F.B.C. FLORIDA BUILDING CODE F.R. FIRE RATED FR FRENCH DOOR FIN. FINISHED FL FLOOR G.T. GIRDER TRUSS GA. GAUGE GALV. GALVANIZED GFl GROUND FAULTINTERRUPT GL BASS GWB GYPSUM WALLBOARD GYP. BD. GYPSUM WALLBOARD HGT. HEIGHT HPS. HOOPS HR HOUR HS HORIZONTAL SUDING HVHZ HIGH VELOCITY HURRICANE ZONE INS INSULATION INT. INTERIOR LG. LONG LIN, LINEN LT. LIGHT LT. LAUNDRY TUB MASONRY NOTES PLAN NOTES FRAMING NOTES ELECTRICAL NOTES 1. CONCRETE UNITS BE ASTM C 0-90. ASTM GRADES NI OR NMI. PROVIDE PRECAST LINTELS AS NECESSARY. (fm = 1500PSI) 1. PROVIDE ix2 P.T. FHORIZONTAL 0 CEILING WALL INTERSECTIONS OR 8'-0" 0/C P 1. THE TRUSS LAYOUT SHOWN ON THIS SHEET IS SCHEMATIC IN NATURE. HOWEVER, THE 1. CONTRACTOR SHALL VERIFY NTH ELECTRIC PROVIDER THE LOCATION OF SERVICE AND VENT. MAX. AND ALL OTHER LOCATIONS PER F.B.C. SECTION 716 OTHER SUPPORTING SUPERSTRUCTURE HAS BEEN DESIGNED UNDER THE ASSUMPTION THAT THE SHALL LOCATED METER & PANELS AS REQUIRED. THESE PLANS WERE PREPARED 2. MORTAR TYPE M PER ASTM C 270-92. FRAMING SCHEME SHOWN WILL CLOSELY PARALLEL FINAL TRUSS DESIGNERS LAYOUT. 2. ALL GLAZING WITHIN 24• AND PARALLEL TO A DOOR SHALL BE TEMPERED. 2. ALL WARE SHALL BE THHN COPPER. UNLESS NOTED OTHERWISE. BUILDING CODE 5th EDITION 1.. CELLS, UNTELS AND BOND BEAMS WHERE SPECIFIED SHALL BE FILLED W/ 3000 PSI PEA AU WINDOWS OR GLASS ENCLOSURES AT OR WITHIN 36" OF TUBS AND SHOWERS WITH SILLS 2• THIS FRAMING SCHEME (DIRECTION OF TRUSSES, MAJOR G.T. BEARING POINTS, ETC.) CAN USING THE 2014 FLORIDA GRAVEL CONCRETE. LE$ THAN 60" ABOVE FLOOR SHALL BE TEMPERED. ALL GLASS IN SIDELIGHTS, SLIDING GLASS BE MODIFIED ONLY AFTER OBTAINING PERMISSION FROM THE PRIME PROFESSIONAL OF 3. WHERE REQUIRED BY OTHER CODES, SERVICE AND FEEDER CONDUCTORS SHALL BE DOORS AND FRENCH DOORS SHALL BE TEMPERED. RECORD WHO MUST RENEW PROPOSED CHANGES AND AUTHORIZE STRUCTURAL REVISIONS COPPER OF EQUAL AAPACITY. 4. REINFORCING: ACCORDINGLY, 3.1EGRESS WINDOWS SHALL BE OPERABLE FROM THE INSIDE WITHOUT THE USE OF TOOLS. 4. ALL BRANCH CIRCUITS IN RACEWAY OR NON METALLIC SHEATHED CABLE. VERTICAL EGIESS WINDOWS SHALL HAVE A MINIMAL NET OPENING OF 24' HIGH, 20" VIDE, AND MIN. NET 3. FINAL SIGNED AND SEALED ENGINEERED TRUSS DESIGN MUST BE SUBMITTED TO THIS AREA OF 5.7 S.F. FOR 2nd FLOOR WINDOWS AND 5.0 S.F. FOR 1st FLOOR WINDOWS. THE OFFICE FOR RENEW. TRUSS DESIGNERS MUST PROVIDE ALL TRUSS CONNECTIONS AS PART OF 5. COORDINATE RACEWAY INSTALLATIONS WITH OTHER TRADES PRIOR TO CONSTRUCTION. A. ASTM A615-94 PER REINFORCING SECTION (GRADE 60). BOTTOM OF THE OPENING SHALL NOT BE MORE THAN 44" ABOVE THE FLOOR. THE DESIGN. 6. VERIFY ALL CONDUCTORS AND BREAKERS WITH EQUIPMENT MANUFACTURER B. WHEN A FOUNDATION DOWEL DOES NOT LINE UP WITH A VERTICAL CORE, IT SHALL NOT BE 4. TRUSS MANUFACTURER SHALL SUBMIT THREE (3) COPIES OF SHOP DRAWINGS AND SPECIFICATIONS. SLOPED MORE THAN ONE HORIZONTAL IN SIX VERTICAL ALIGNMENT, EVEN THOUGH IT IS IN AN 4.N AREAS OTHER THAN HVHZ FIXED GLASS THICKNESS SHALL COMPLY WITH SECTION 2411 ENGINEERING CALCULATIONS SIGNED AND SEALED BY A FLORIDA REGISTERED ENGINEER, OF ADJACENT CELL TO THE VERTICAL WALL REINFORCING. OFF.B.C. AS THE MINIMUM THICKNESS ALLOWED. THEIR ROOF TRUSS DESIGN FOR REVIEW INCLUDING TWO (2) COPIES FOR ARCHITECTS REVIEW 7. PROVIDE DISCONNECT SWITCH OF SIZE AS REQUIRED BY LOAD AND UNITS. C. VERTICAL REINFORCING STEEL SHALL HAVE A MINIMUM CLEARANCE OF ONE-HALF INCH FROM 5. PROVIDE A MINIMUM OF 4" CLEAR ALL AROUND AIR HANDLER UNITS. PRIOR TO FABRICATION. REVIEW OF TRUSS SHOP DRAWINGS IS A COURTESY BY THE ARCHITECT AND IN NO WAY RELIEVES THE. TRUSS MANUFACTURER OF HIS RESPONSIBILITY TO 8, PROVIDE NON -FUSIBLE GENERAL DUTY SAFETY SWITCHES AT A/C EQUIP. AND AT • THE MASONRY. PROVIDE A LAYOUT THAT FULLY INTEGRATES WITH THE ARCHITECTS SUPERSTRUCTURE. IF PUMPS NOT VISIBLE FROM CIRCUIT BREAKER PANEL AND AS PER MANUFACTURER. 6.ALL DWELLING ROOMS MUST HAVE HVAC RETURNS. RETURNS MAY BE DUCTED, JUMPERS OR THERE IS ANY CONFLICT OR ADDITIONAL STRUCTURE NEEDED, THE TRUSS COMPANY SHALL RECOMMENDATIONS. M.C. MEDICINE CABINET SMS SHEET METAL SCREWS • D. VERTICAL REINFORCING SHALL BE AS LOCATED ON THE PLAN AND AS INDICATED N THE TRMSFER GRILLES. NOTIFY THE ARCHITECT IN WRITING OF THE SPECIFIC AREAS OF CONCERN. M.R.H. MEAN ROOF HEIGHT ST. STIRRUPS COLUMN SCHEDULE. 9. PROVIDE GFl BREAKERS FOR ALL BATHROOMS, GARAGE AND EXTERIOR OUTLETS AS M.T. METAL THRESHOLD STL STEEL 7.A/C.UNITS MAY HAVE CONIC. PAD OR OTHER APPROVED MATERIAL EXTENDING ABV. 5. TRUSSES TO BE DESIGNED TO CARRY LOADS OF ATTIC AHU AND MISC. EQUIPMENT.SHOWN ON PLANS. MAX. MAXIMUM SW SWITCH E. VERTICAL REINFORCING EACH SIDE OF ANY OPENING. IF REQUIRED, SHALL BE CONTINUOUS AQI000lG GRADE OR SHALL BE SUSPENDED A MIN. OF V ABV. ADJOINING GRADE. COORDINATE LOCATIONS WITH BUILDER PRIOR TO FABRICATION AND INDICATE ON TRUSS MFR. MANUFACTURER TEMP. TEMPERED TO THE RE BEAM. PRECAST LINTELS SHALL HAVE OPENINGS TO ALLOW REINFORCING BARS TO DRAWINGS. 10. ELECTRICAL FIXTURES, TRIM AND APPUANCES SHALL BE UL APPROVED AND AS MICRO, MICROWAVE T.B. THROUGH BOLT CONTINUE UNINTERRUPTED. A,A BEAM SCHEDULE NOTES SELECTED BY BUILDER. MIN. MINIMUM T.O. THROUGH OUT 6. ALL INTERIOR LOAD BEARING PARTITIONS TO BE CONSTRUCTED NTH CLIPS, TOP AND M.O. MASONRY OPENING T.O.B.B. TOP OF MASONRY BOND BEAM HORIZONTAL: BOTTOM EACH STUD, AS PER CODE. it. PROVIDE PRE -VANED TELEPHONE OUTLETS AS SHOWN ON PLAN. MONO. MONOLITHIC LD.PL TOP OF WOOD PLATE MTL METAL T.O.T.B. TOP OF RE BEAM A. HORIZONTAL REINFORCEMENT SHALL BE PROVIDED AS SCHEDULED IN THE BEAM SCHEDULE. 1. ALL COMPOSITE UNTEL (MART( "L') TOP BARS SHALL BE CONTINUOUS UNLESS OTHERWISE NOIED 7. STRUCTURAL WOOD AND TIMBER FRAMING SHALL CONFORM TO THE "TIMBER CONSTRUCTION 12. PROVIDE PRE- WIRED T.V. OUTLETS FOR CABLE AS SHOWN ON PLANS. O.H.D. OVER HEAD DOOR TYP. TYPICAL O/C ON CENTER U.N.O. UNLESS NOTED OTHERWISE 5. GENERAL: RILL BOND BEAMS (MARK 'BB") REINFORCING SHALL BE CONTINUOUS THROUGH BOND MANUAL" AS PUBLISHED BY THE AMERICAN INSTITUTE OF TIMBER CONSTRUCTION. 13. DEDICATED CIRCUITS SHALL HAVE NO MORE THEN 6 DUPLEX RECEPTACLES. P.L.F. POUNDS PER LINEAR FOOT UL UNDERWRITERS LABORATORIES V.I.F. VERIFY IN FIELD A. STRUCTURAL DESIGN IS IN ACCORDANCE WITH A.C.I. 530-05/ A.S.C.E. BKMS ONLY. ALL SPLICES TO BE A MINIMUM OF 48 BAR DIAMETERS. 8. ALL WOOD IN CONTACT NTH MASONRY OR CONCRETE SHALL BE PRESSURE TREATED. 14. IN KITCHENS, DINING ROOMS AND BATHROOMS, RECEPTACLE OUTLETS FOR COUNTER P.S.F. POUNDS PER SQUARE FOOT W.A. WEDGE ANCHORS 7-10/T.M.S. 402-05, BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND THE PROVIDE AN APPROVED MOISTURE VAPOR BARRIER BETWEEN THE CONCRETE OR OTHER SPACES SHALL BE GFCI PROTECTED ACCORDING TO NEC 210-8(D). P.S.I. - POUNDS PER SQUARE INCH COMMENTARY ON BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES. 3. IOND BEAM SCHEDULE DEPTHS ARE MINIMUM AND MAY BE INCREASED 8" TO FIT BLOCK CEMENTITOUS MATERIALS AND THE WOOD AS PER CODE. P.T. PRESSURE TREATED WC WATER CLOSET PARTN. PARTITION B. CONSTRUCTION SHALL BE IN ACCORDANCE WITH A.C.I. 530.1-05/ASC.E 7-10/LM.S 602- WvK 9. CARPENTER SHALL BE RESPONSIBLE FOR PROVIDING ADEQUATE BRACING AND BRIDGING USED 15, ALL CLOSET UGHTING SHELL COMPLY NTH NEC SEC. 410.8. PKT. POCKET WD. WOOD 05, SPECIFICATIONS FOR MASONRY STRUCTURES AND THE COMMENTARY ON SPECIFICATIONS 4:REFER TO CONCRETE NOTES FOR INFORMATION ON CONCRETE AND STEEL SPECIFICATIONS DURING ERECTION OF TRUSSES TO PREVENT COLLAPSE OR DAMAGE. 16. SMOKE DETECTORS SHALL BE CONNECTED TO KITCHEN OR BATH LIGHTING CIRCUITS PKT, PLYWOOD R.O. ROUGH OPENING FOR MASONRY STRUCTURES. 10. HEADERS FOR FRAMED OPENINGS GREATER THAN 6'-0" MUST BE ENGINEERED AND AHEAD OF SWITCH AND HAVE SELF CONTAINED BATTERY BACK-UP. DETECTORS SHALL BE S.C.SOLID CORE 6. VERTICAL CELLS FOR MASONRY TO BE GROUTED SHALL HAVE VERTICAL ALIGNMENT (ONCRETE NOTES STAMPED BY THE TRUSS MANUFACTURER. (UNLESS NOTED OTHERWISE) TANDEM CURED SO ALL DETECTORS SOUND SIMULTANEOUSLY. S.G.D. SUDING GLASS DOOR SUFFICIENT TO MAINTAIN A CLEAR, UNOBSTRUCTED CONT. CELL 17. PRENRE FOR GARAGE DOOR OPENER SENSOR. SF SQUARE FOOT it. ALL HEADERS OVER DOORS AND WINDOWS TO BE (2) OR (3) 2X72'S UNLESS OTHERWISE SH SINGLE HUNG 7. CLEANOUT OPENINGS SHALL BE PROVIDED AT THE BOTTOM OF GROUTED CELLS AT EACH 1•CONCRETE SHALL CONFORM TO ASTM C94-94 AND SHALL HAVE STRENGTH IN 28 DAYS AS NOTED. (FOR WOOD FRAME CONSTRUCTION DEPENDING ON ALL WALL THICKNESS). IS. ARC FAULT -INTERRUPTER PROTECTION PER NEC 210.12. REQUIRED FOR ALL LIFT OVER 4'-0" HIGH CLEANOUTS SHALL BE SEALED AFTER CLEANING AND INSPECTION, AID SECFED IN THE FOUNDATION AND MASONRY NOTES (UNLESS NOTED OTHERWISE) ALL 120-VOLT, ST. LUCIE COUNTY PRODUCT APPROVAL OPENING SCHEDULE: VERHEAD DOORS, SLIDING DOORS, FIXED GLASS, WINDOWS & SKYLIGHTS GLASS ATTACH. METHOD TYPE, SIZE, SPACING BUILDING DESIGN PRODUCT DESIGN OPEN ID PRODUCT I MODEL # MANUF. DESCRIPTION AND EMBED. FILL ALL MANUF. HOLES PRESSURE PRESSURE A FL-9174.10 111 1100 OHD 16080 WAYNE DALTON N/A W/ 1-1/a" WASHER & 2-3/4' MIN. EMBED. D.P.= +28.5 PSF +39.2 PSF -43.7 PSF 2-3 4" MIN. EDGE DISTANCE 6" FROM END -32.2 PSF B R 17499.E SH 35 W/ MI WINDOWS &DRS NON IMPACT 3/16• TAPCONS W/ 1-1/4' MIN EMBED D.P: +31.9 PSF +55.0 PSF -55.0 PSF FL 15349.1 F.G. ABV. 0 10" O/C MAX. SPACING & 2" FROM EDGE -34.8 PSF +60.0 PSF -60.0 PSF C FL 17499,E SH H33 MI WINDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4' MIN EMBED D.P.= +33.5 PSF +55.0 PSF -55.0 PSF 0 10' 0/C MAX. SPACING & 2' FROM EDGE -36.3 PSF D FL 17499.6 SH 35 MI WINDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4- MIN EMBED D.P.= +31.9 PSF +55.0 PSF -55.0 PSF 0 10 O/C MAX. SPACING & 2" FROM EDGE -34.8 PSF E FL 17499.6 SH 35 MI WINDOWS & DRS NON IMPACT 3/16' TAPOONS W/ 1-1/4• MIN EMBED D.P: +31.9 PSF +55.0 PSF -55.0 PSF 0 10" O/C MAX. SPACING & 2" FROM EDGE -34.8 PSF "F FL 17499.E SH H33 MI WINDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4' MN EMBED D.P: +33.5 PSF +55.0 PSF -55.0 PSF 0 10 O/C MAX. SPACING & 2" FROM EDGE -34.8 PSF G FL-7630.1 2680 SGL CITE DR THERMA TRU NON IMPACT 1/4' TAPCONS W/ 1-1/4" MIN. EMBED CORNERS 0 D.P: +31.9 PSF +50.0 PSF -50.0 PSF 6' & 14" O/C MAX. SPACING. -34.8 PSF H FL 17499.6 (2) SH 26 MI WINDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4" MIN EMBED D.P: +29.9 PSF - +55.0 PSF 55.0 PSF 0 10' O/C MAX. SPACING & 2" FROM EDGE -32.7 PSF FL 15349.1 6414 TRANSOM MI WINDOWS & DRS NON IMPACT 3/16" TAPCONS W/ 1-1/4' MIN EMBED D.P: +33.5 PSF +60.0 PSF -60.0 PSF EQUAL SPACING & 3' FROM EDGE -36.3 PSF J FL 17499.6 SH 36 MI WINDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4" MIN EMBED D.P: +31.9 PSF +55.0 PSF -55.0 PSF 0 10 O/C MAX. SPACING & 2" FROM EDGE -34.8 PSF K FL 15349.1 4614 TRANSOM MI WINDOWS & DRS NON IMPACT 3/W TAPCONS W/ 1-1/4' MIN EMBED D.P: +33.5 PSF +60.0 PSF -60.0 PSF EQUAL SPACING & 3" FROM EDGE -36.3 PSF L FL 22401.3 12080 SGD MI WINDOWS & DRS NON IMPACT 3/16" TAPCONS W/ 7-1/4' MIN EMBED D.P: +28.5 PSF +35.0 PSF -35.0 PSF 012'"O/C MAX. SPACING -31.3 PSF M FL 15349.1 12014 TRANSOM MI WINDOWS & DRS NON IMPACT 3/16" TAPCONS W/ 1-1/4' MIN EMBED D.P: +31.9 PSF +60.0 PSF -60.0 PSF EQUAL SPACING & 3" FROM EDGE -34.8 PSF N FL-7630.1 2880 SGL LITE DR THERMA TRU NON IMPACT 1/4' TAPCONS W/ 1-1/4' MIN. EMBED CORNERS 0 D.P: +31.9 PSF +50.0 PSF -50.0 PSF 6' & 14' O/C MAX. SPACING. -41.7 PSF 0 FL 17499.6 (2) SH 35 MI WINDOWS & DRS NON IMPACT 3/16" TAPCONS W/ 1-1/4' MIN EMBED D.P: +29.9 PSF +55.0 PSF -55.0 PSF 0 10' O/C MAX. SPACING & 2" FROM EDGE -33.6 PSF p FL 17499.6 SH H33 MI WINDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4' MIN EMBED D.P: +33.5 PSF +55.0 PSF -55.0 PSF 010 O/C MAX SPACING & 0 FROM EDGE -36.3 PSF Q FL 15349.1 8020 TRANSOM MI WINDOWS &DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4" MIN EMBED D.P: +33.5 PSF +60.0 PSF -60.0 PSF EQUAL SPACING & 3" FROM EDGE -36.3 PSF R FL 17499.6 SH 35 MI WINDOWS & DRS NON IMPACT 3/16' TAPOONS W/ 1-1/4' MIN EMBED D.P: +31.9 PSF +55.0 PSF -55.0 PSF 010 0/0 MAX. SPACING & 2" FROM EDGE -34.8 PSF S FL 17499.6 SH 15 MI WINDOWS & DRS NON IMPACT 3/16" TAPCONS W/ 1-1/4' MIN EMBED D.P: +33.5 PSF +55.0 PSF -55.0 PSF FL 15349.1 W/ F.G. ABV. 0 10 O/C MAX SPACING & 2" FROM EDGE -36.3 PSF +60.0 PSF -60.0 PSF T FL-15037.4 PR 3080 DRS THERMA TRU N/A 1/4' TAPCONS W/ 1-1/4'-MIN. EMBED CORNERS 0 D.P: +29.9 PSF +50.0 PSF -50.0 PSF 6" & 14. O/C MAX. SPACING. -327 PSF U FL 15349.1 6428 TRANSOM MI WINDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4• MIN EMBED D.P: +33.5 PSF -36.3 PSF +60.0 PSF -80.0 PSF EQUAL SPACING & 3' FROM EDGE V FL 17499.6 SH 15 MI WINDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4" MIN EMBED D.P: +33.5 PSF +55.0 PSF -55.0 PSF PSF -60.0 PSF FL 15349.1 W/ F.G. ABV. 0 10" O/C MAX. SPACING & 2" FROM EDGE -36.3 PSF +60.0 W FL 17499.6 (2) SH 25 MI WINDOWS & DRS NON IMPACT 3/16" TAPOONS W/ 1-1/4' MIN EMBED D.P.- +29.9 PSF +55.0 PSF -W.0 PSF FL 15349.1 W/ F.G. ABV. 010. O/C MAX. SPACING & 2" FROM EDGE -327 PSF +60.0 PSF -60.0 PSF BEFORE GROUTING. CINCREIE WORK SHALL BE IN ACCORDANCE WTH ACI 318-11 AND ACI 301-05, ALL 12. DIMENSIONAL LUMBER SHALL BE SOUTHERN PINE. NO. 2 OR BETTER AND SHALL PROVIDE SINGLE PHASE 15 AND 20 AMP BRANCH CIRCUITS SUPPLYING OUTLETS DWELLING UNITS. CNCREIE MASONRY WORK SHALL BE N ACCORDANCE NTH ACI 530-11. ALLOWABLE STRESS VALUES OF 1200 PSI IN BENDING FOR A SINGLE MEMBER USES. 90 PSI 19. CARBON MONOXIDE DETECTORS REQUIRED WITHIN 10' OF ANY SLEEPING ROOM. FOUNDATION NOTES 2•1MfOUM CONCRETE COVER OVER REINFORCING SHALL BE: SLABS ON VAPOR BARRIER - IN HORIZONTAL SHEAR AND SHALL HAVE A MODULES ELASTICITY OF 1600 KSI OR BETTER, AS DETERMINED BY AN APPROVED LUMBER GRADING AGENCY. 3/:' BEAMS AND COLUMNS - 1 IIT FORMED CONCRETE BELOW GRADE-0 UNFORMED 1. FLOOR SLAB TO BE 4" THICK POURED CONCRETE SLAB NTH FIBERMESH ONORETE BELOW GRADE-3" 13. NON -BEARING INTERIOR PARTITIONS MAY BE CONSTRUCTED OF 2x4 0 24" D.C. PLUMBING NOTES ON 0.00E NSQUEEN (OR EQUAL) ON CLEAN WELL COMPACTED FILL aREIMFORCING STEEL: GRADE 60 (F16ODDO) ASTM A615-94. STUDS, NTH 1/2' GYPSUM BUGLE HEAD DRYWALL SCREWS ATL12EACH 0/CSMAX.ATTACH DRYWALL NTH 1' LONG 1, ALL PLUMBING FIXTURES SHALL BE INSTALLED IN ACCORDANCE NTH SECTION 405, F.B.C. 2, ALL REINFORCING STEEL TO BE GRADE 60. 4. DETAIL OF CONCRETE REINFORCEMENT SHALL BE IN ACCORDANCE NTH "THE MANUAL OF 14. METAL LATH OVER SHEATHING SHALL BE 3/8' V-GROVE OR DIMPLED. FASTEN TO 2. ALL PLUMBING FIXTURES SHALL MEET THE REQUIREMENTS OF TABLE 604.3, F.B.C. STANDARD PRACTICE FOR REINFORCED CONCRETE CONSTRUCTION' AS PUBLISHED BY THE SUBSTRATE AT 4" O/C AS FOLLOWS; 3. COLUMN AND WALL CENTERLINES SHALL COINCIDE WIN FOOTING CENTERUNES UNLESS 04CRETE REINFORCING STEEL INSTITUTE IRISS NOTED OTHERWISE CONCRETE: 3 4 LOG STUB NAILS W1 3 8 HEAD. HORIZONTAL AND VERTICAL WOOD 3. DISPOSITION OF RAIN WATER SHALL COMPLY NTH F.B.C. PLUMBING CODE CHAPTER 11. OTHERWISE NOTED. 5 ADEQUATE VERTICAL AND HORIZONTAL SHORING SAFELY SUPPO SHALL BE PROVIDED TO SAFE )FIT 4. FOOTING DESIGN BASED ON ASSUMED SOIL BEARING CAPACITY OF 2500 P.S.F., ALL GOADS DURING CONSTRUCTION. FRAMING MEMBERS W/ NAILS OR STAPLES TO PROVIDE AT LEAST 1-3/4" PENETRATION INTO HORIZONTAL WOOD FRAMING MEMBERS, AND 3/4' PENETRATION INTO VERTICAL WOOD 4. ALL PLUMBING PENETRATIONS MUST BE A MINIMUM 10'-0' FROM ROOF JACKS. FRAMING MEMBERS. ON VERTICAL WOOD FRAMING MEMBERS, COMMON NAILS SHALL BE 5. FILL PLACED WITHIN 5'-C" OF THE CONSTRUCTION PERIMETER SHALL CONSIST OF CLEAN 6. CONCRETE BEAM SIZES MAY INCREASED (8" MAX.) AS REQUIRED FOR ARCHITECTURAL BENT OVER TO ENGAGE AT LEAST THREE STRANDS OF LATH, OR BE BENT OVER A RIB 5. CONDENSATE DRAINS MUST BE A MINIMUM OF 12" OFF THE BUILDING. WELL GRADED SAND COMPACTED TO ACHIEVE A DETAILS OR FIT BLOCK COURSING, DROP BOTTOM OF TIE BEAM AS REQUIRED AT WINDOW AND WHEN RIB LATH IS INSTALLED. SHEATHING: 14 GAUGE STAPLES 1" LEG, 7/16" CROWN METAL 6. INSTALL CHASE PIPE FOR HVAC. MINIMUM OF 95% MODIFIED PROCTOR ASTM D 1557. DOOR BEAMS (28' MAX.) AND ADD 2-#5 BARS BOTTOM IF DROP EXCEEDS 8'. MTL. FRAMING: SELF TAPING SCREWS #12 x 1/2" WASHER HEAD STAPLES SHALL NOT BE 6. ALL MONOLITHIC FOOTINGS HAVE BEEN CHECKED TO PREVENT THE USE OF TRANSFER USED FOR SOFFITS OR CEILINGS REINFORCEMENT AT PERIMETER. RATIONAL ANALYSIS SHALL BE SUBMITTED, BUT ONLY IF 7. DOWELS COLUMN AND WALL REINFORCING TO FOOTING NTH SAME SIZE AND NUMBER OF THE DOWELS AS VERTICAL BARS ABOVE. 15. PNEUMATIC FASTENERS SYSTEM TO BE HILTI 12G -COIL NAIL PROGRAM. TYPE TO BE CRF 1 MECHANICAL NOTES REQUESTED BY BUILDING OFFICIAL 1-1/2" LONG AND .120" DIAMETER D.N.D. 7. CONCRETE FOR FOUNDATIONS AND FOOTINGS STALL BE 2500 PSI MIN. B. REINFORCING STEEL SHALL BE LAPPED 48 BAR DIA. MIN. WHERE SPLICED AND SHALL BE WIRED TOGETHER. PROVIDE CORNER BARS SAME SIZE AND NUMBER AS HOfRIZ. BEAM 16. TRUSS MANUFACTURER SHALL DESIGN TRUSSES M COMPLY WITH ALL SUPERIMPOSED 1. ALL HEATING, AIR CONDITIONING, REFRIGERATION AND VENTILATION EQUIPMENT SHALL 8. DAMAGE PROBABILITIES FROM TERMITE INFESTATION IS VERY HEAVY PER TABLE R301.2(1). REINFORCING AT EACH FACE. LAP 48 BAR DIA. MIN. WIND LOADS PER F.B.C. 2014 5TH EDITION & ASCE 7-10. CONFORM TO THE REQUIREMENTS SET FORTH IN THE 'FLORIDA BUILDING CODE MECHANICAL" AND CHAPTER 28 OF THE FLORIDA BUILDING CODE. 9. PLACING DRAWINGS ON BAR LISTS SHALL CONFORM TO ACI'S "MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE CONSTRUCTION AS PUBUSHED BY THE STEEL NOTES GA GARAGE NOTES CONCRETE REINFORCING STEEL INSTITUTE UNLESS NOTED OTHERWSE. 10. DAMAGE PROBABILITIES FROM WEATHERING IS NEGLIGIBLE PER FBC TABLE R301.2(1). 1. STRUCTURAL STEEL SHALL CONFORM TO THE AISC 'SPECIFICATION FOR THE DESIGN, t. OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE EQUIPPED NTH SOLID WOOD - FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS" 2005 EDITION MATERIALS DOORS NOT LESS THAN' (35 MM) THICK SOLID OR HONEYCOMB CORE STEEL DOORS NOT ATTACHMENT METHOD BUILDING DESIGN PRODUCT DESIGN PRODUCT MODEL # MANUF. TYPE, SIZE, SPACING, EMBED., STIFFENERS, ETC PRESSURE PRESSURE MULLIONS MAX. 104-1 4" HORIZ. MI WINDOWS & DOORS 1/4' TAPCONS W/ 1-1/4• MIN EMBED (4) FASTENERS PER CUP TOP & BTM. 377 PSF' `. ,. 6;4.0 PSF -54.0 PSF -. FL 15353.4 a.,. 3" (2) 10d RING SHANK NAILS -83.4 psf -172 psf. ROOFING NOA NO. 16-0314-.06 EAGLE ROOFING BEL-AIR CONCRETE TILE PRODUCTS ROOFING NOA N0. 17-D614-.22 POLYGASS USA MEMBRANE: POLYSIICK TU MAX SELF ADHERED 1 OR MORE PLIES NAILS AND TIN CAPS 12" GRID, 6' O.C. AT A MIN. 4' N/A N/A UNDERLAYMENT PEEL & STICK SBS UNDERLAYMENT INC. A HEAD LAP SIDING STUCCO N/A N/A N/A N/A 2 RING SHANK ATTACHED TO UNDERSIDE OF TRUSS N/A SOFFIT STUCCO N/A SPACED 0 EVERY HI RIB (4" 0%C). W/ 1-3/4" EMBED. N/A PER NAIL HURRICANE PANELS FL 16293.1 HURRICANE STORM 1/4" -20 z 3/4" S.S. 37.7 PSF +49.0 PSF -56.0 PS 120" MAX SPAN GALV STEEL PANEL PANEL KNURLED STUDS 12-1/2' O.C. TOP AND BTM MANUFACTURING, INC TERMITE TREATMENT ALL MANUFACTURES LABLES SHOWING U FACTORS AND SHGC COMPLIANCE WITH FEIC ENERGY CODE MUST REMAIN ON ALL DOORS AND WINDOWS UNTIL INSPECTIONS ARE APPROVED " THESE PLANS AND ALL PROPOSED WORK 11RE SUBJECT TO ANY CORRECTIONS G EOUIPED MY FIELD INSPECTORS THAT . A.Y BE NECESSARY IN ONDER TO �ptdulY WITH ALL APPLICABLE CODES• SEALED FASTENERS OR ATTACHMENTS ARE THE RESPONSIBILITY OF THE CONTRACTOR OF RECORD to w 0 1 Bi" SH 15 M.O. 20 1/e" PROPOSED SINGLE FATLY RESIDENCE BY: 0 TAOMA L0-170 MEADWOOD COPYIT 2017 TYPICAL "MI" WINDOWS ■ SH 25 M.O. 38" K, 2x, OR 5/4 BOARD P.T. WOOD BUCK 38" El 25j" SHALL CONFORM TO THE APPLICABLE ASTM SPECIFICATION AS FOLLOWS: SHAPES, PLATES A-3t LESS THAN J' (35 MM) THICK, OR 20-MINUTE FIRE -RATED DOORS. BOLTS - A 307-00 TUBULAR - A500-01D GRADE B (42 KSQ 2. DUCTS IN GARAGE AND DUCTS PENETRATING THE WALLS OR CEILINGS SEPARATING THE 2. WELDED CONSTRUCTION SHALL CONFORM TO THE AMERICAN WELDING SOCIETY "STRUCTURAL DWEWNG FROM THE GARAGE SHALL BE CONSTRUCTED OF A MINIMUM NO, 26 GAGE (0.48 MM) WELDING .CODE'. ELECTRODES FOR FIELD AND SHOP WELDS SHALL BE A.W.S. A5.1 E70XX. SHEET STEEL OR OTHER APPROVED MATERIAL AND SHALL HAVE NO OPENINGS INTO THE GARAGE. _ 3. THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND ITS ATTIC AREA BY NOT LOAD SCHEDULE I LESS THAN (12.7 MM) GYPSUM BOARD APPLIED TO THE GARAGE SIDE. LOCATION Uff. DEAD E&rli TOTAL GROUND FLOOR 40 50 10 100 SECOND FLOOR 40 15 10 65 ROOF 30 18 0 48 ATTIC 20 10 0 30 ANLTL ULITIMATE WIND SPEED = 160 m.p.h. BUILDING RISK CATEGORY = II BUILDING DESIGN AS ENCLOSED EXPOSURE = C ROOF DEAD LOAD FOR WIND DESIGN TAKEN AT 10 p.s.f. NOTE: THIS STRUCTURE IS DESIGNED IN ACCORDANCE NTH CHAPTER 16 OF THE FLORIDA BUILDING CODE AND ASCE 7-10. DESIGN PRESSURES FOR EXTERIOR DOORS AND WINDOWS ARE NOTED ON THE ELEVATIONS. WINDOW AND DOOR MANUFACTURERS SHALL MULTIPLY THE GIVEN DESIGN PRESSURES BY THE APPROPRIATE FACTORS TO OBTAIN TEST PRESSURES. THERMA TRU EXTERIOR DOORS ICI \ \ \ \ 2x P.T. WOOD BUCK SHOWN TYP. Ell M.O. 35 1/4" W M.O. 37 1/4" W M.D. 41 1/4" W M.O. 55 1/2' W M.O. 77 1/2" W X 98 1/2' H X 98 1/2" H X 98 1/2" H X 98 1/2- H X 98 3/4" H- P.T. WOOD BUCK _ EDGE OF SLAB EDGE OF SLAB EDGE OF SLAB EDGE OF SLAB 70" 38" • ® • ® 8 ■ SH 35 SH 35 i H35 M.0.541/8' .271/21 1x 2x, OR 5/4 BOARD TYP. BAY WINDOW , 1 r`N\J EDGE OF SLAB 2680 EXT DR 2880 EXT DR 3080 EXT DR 3080 EXT DR W/ 14" SIDELITE PR 3080 DR (OUT SWING) (OUT SWING) (OUT SWING) (OUT SWING) (OUT SWING) DOOR INSTALLATION NOTE DOOR BUCKS USED MAY BE 24, 5/4" BOARD OR 1x6. CONCRETE SCREWS USED TO SECURE THE DOOR FRAMES TO THE OPENINGS MAY BE ANGLED SUGHTLY WITHOUT APPRECIABLE LOSS IN RESISTANCE. ALL FASTENERS SHALL BE OF THE SIZE, LENGTH AND SPACIN® AS REQUIRED IN THE PRODUCT APPROVAL INSTALLATION PROCEDURES. SYMBOLS LEGEND # DETAIL SCALE rf DETAIL owc SCALE SECTION oWG. SCALE SECTION owc SCALE INTERIOR ELEV. SCALE B 1 BEAM LABEL QREVISION NORTH ARROW DRAWING INDEX C-1 COVER SHEET A-1 FOUNDATION PLAN A-2 FLOOR PLAN A-3 ELEVATIONS A-4 SECTIONS A-5 STRUCTURAL PUN A-6 TRUSS PLAN E-1 ELECTRICAL PLAN M-1 MECHANICAL PLAN 1 Ca INTERIOR 4 owc. 2 ELEVATION €3Y st Lucie >v0UC1t� 3 C# COLUMN LABEL F# FOOTING LABEL POT SHELF HEIGHT AS NOTED DROPPED SOFFIT HEIGHT AS NOTED ARCHED OPENING SEE PLAN OR ELEV. MASONRY CONSTRUCTION TYPICAL GROUT FILLED CELL SEE FOUNDATION PLAN NON -BEARING FRAME CONSTRUCTION BEARING FRAME CONSTRUCTION BREAK LINE ELEV BEAM HEIGHT CHANGE U Y Y r SCALE; 1 GRAPHIC SCALE �0'-0" FlN. FL. SLAB FLOOR ELEVATION UJ v O W W J W 2 e M M m a J LU LU 2 0 N L'i U J LL ❑ z 0 Q J Q 0 a19 ❑ Z O L a O C O O n C a OM O v J E O O O '� Ln On a CID c a _� `- L`ni vI i -0fo U 5 0 _ O } v coo o E a a�i o = cro aM E E o 2 o O E iv 0 -o d U 0 O N U E (n GT C C O = LJJ v O (7 p Z a CL cn y= '0 N- V E y 0L oe 6. C Q C _ LU 2 � 0 r O J r LN" a 7: 0 �N T 1" .V l7/z- /a ST. LUCIE COUNTY UI LD C D IR k�VIEWED FOR C L CE REVIEWED Y DATE PLANS AND PE?RMI MUS BE PT GR No P.N'SPECTION WILL BE NLLDE. J c L'' O � V-� Z_ Q o O LU O ??: O U J LU OJ Ln 1/4" = 1'-0" U,N.O. COVER SHEET M11�=�i� JOB PROJECT LOG ISSUED FOR PRECON 10-18-17 ISSUED FOR PERMIT 11-17-17 GENERAL NOTES I. THIS PLANS WERE PREPARED USING THE 2014 FLORIDA BUILDING CODE 5TH EDITION 2. TYPE OF CONSTRUCTION: CLASS V, UNPROTECTED, GROUP R3 OCCUPANCY PER FLORIDA BUILDING CODE. 3. CONSTRUCTION SHALL FOLLOW THE FLORIDA BUILDING CODE AS ADAPTED BY THE COUNTY AND ALL APPLICABLE AMENDMENTS. 4. THESE PLANS, AS DRAWN AND NOTED, COMPLY WITH THE BUILDING ENVELOPE ENERGY REQUIREMENTS R THE F.B.C. CHAPTER 13 ENERGY EFFICIENCY. 5. ALL WINDOWS AND DOORS SHALL BE CAULKED AND WEATHER STRIPPED. WNDOW UNITS SHALL DISPLAY LABELS SHOWING COMPLIANCE WITH THE F.B.C. CHAPTER 13 ENERGY EFFICIENCY SECTION. 6. REGISTERED BAITING SYSTEM FOR TERMITE TREATMENT TO BE INSTALLED AND MONITERED THIRD PARTY PRIOR TO FINAL BUILDING APPROVAL. PER F.B.C. 2014 ABBREVIATIONS ABV ABOVE EXT. EXTERIOR AFF ABOVE FINISHED FLOOR F.B.C. FLORIDA BUILDING CODE AHU AIR HANDLER UNIT F.R. FIRE RATED B.F. BI FOLD FR FRENCH DOOR B.P. BI PASS FIN. FINISHED BLK. BLOCK FL FLOOR BLW. BELOW G.T. GIRDER TRUSS BRG. BEARING GA. GAUGE BTM. BOTTOM GALV. GALVANIZED CLG. CEILING GFl ROUND FAULT INTERRUPT CMU CONCRETE MASONRY UNITS GL. GLASS COL COLUMN GINS GYPSUM WALLBOARD CONC. CONCRETE GYP. BD. GYPSUM WALLBOARD CSMT. CASEMENT HGT. HEIGHT DEL. DOUBLE HPS. HOOPS DIA. DIAMETER HR HOUR DISP. DISPOSAL HS HORIZONTAL SUDING DP DESIGN PRESSURE HVHZ HIGH VELOCITY HURRICANE ZONE DR. DOOR INS. INSULATION DW DISH WASHER INT. INTERIOR E.E. EACH END LG. LONG ELEC. ELECTRICAL UN. LINEN ELEV. ELEVATION LT. LIGHT E.S. EACH SIDE L.T. LAUNDRY TUB MASONRY NOTES PLAN NOTES FRAMING NOTES ELECTRICAL NOTES 1. CONCRETE UNITS R BE ASTM C 90-90. ASTM GRADES NI OR NIL. PRONE PRECAST LINTELS AS NECESSARY. (I'm = 1500 PSI) 1. PROVIDE tx2 P.T. FOTHERP HORIZONTAL 0 CEILING WALL INTERSECTIONS OR 8'-0' 0/C 1. THE TRUSS LAYOUT SHOWN ON THIS SHEET IS SCHEMATIC IN NATURE. HOWEVER, THE 1. CONTRACTOR SHALL VERIFY WITH ELECTRIC PROVIDER THE LOCATION OF SERVICE AND MAX. AND ALL OTHER LOCATIONS PER F.B.C. SECTION 718 C SUPPORTING SUPERSTRUCTURE HAS BEEN DESIGNED UNDER THE ASSUMPTION THAT THE SHALL LOCATED METER & PANELS AS REQUIRED. THESE PLANS WERE PREPARED 2. MORTAR TYPE M PER ASTM C 270-92. FRAMING SCHEME SHOWN WLL CLOSELY PARALLEL FINAL TRUSS DESIGNERS LAYOUT. 2. Al GLAZING WITHIN 24' AND PARALLEL TO A DOOR SHALL BE TEMPERED. 2. AL 2. ALL NONE SHALL BE THHN COPPER. UNLESS NOTED OTHERWISE. 5th EDITION 3. CELLS, UNTELS AND BOND BEAMS WHERE SPECIFIED SHALL BE FILLED W/ 3000 PSI PEA ALLMNDOWS OR GLASS ENCLOSURES AT OR WITHIN 36' OF TUBS AND SHOWERS WITH SILLS 2. THIS FRAMING SCHEME (DIRECTION OF TRUSSES, MAJOR G.T. BEARING POINTS, ETC.) CAN USING THE 2014 FLORIDA BUILDING CODE GRAVEL CONCRETE. LESS THAN 60' ABOVE FLOOR SHALL BE TEMPERED. ALL GLASS IN SIDEUGHTS, SUDING GLASS BE MODIFIED ONLY AFTER OBTAINING PERMISSION FROM THE PRIME PROFESSIONAL OF 3. WHERE REWIRED BY OTHER CODES, SERVICE AND FEEDER CONDUCTORS SHALL BE D0013 AND FRENCH DOORS SHALL BE TEMPERED. RECORD WHO MUST RENEW PROPOSED CHANGES AND AUTHORIZE STRUCTURAL REVISIONS COPPER OF EQUAL AAPACITY. 4. REINFORCING: ACCORDINGLY. 3. DRESS WINDOWS SHALL BE OPERABLE FROM THE INSIDE WTHOUT THE USE R TOOLS. 4. ALL BRANCH CIRCUITS IN RACEWAY OR NON METALLIC SHEATHED CABLE. VERTICAL: EGRBS WNDOWS SHALL HAVE A MINIMAL NET OPENING OF 24" HIGH, 20" WDE, AND MIN. NET 3. FINAL SIGNED AND SEALED ENGINEERED TRUSS DESIGN MUST BE SUBMITTED TO THIS AREA OF 5.7 S.F. FOR 2nd FLOOR WINDOWS AND 5.0 S.F. FOR let FLOOR WNDOWS. THE OFFICE FOR RENEW. TRUSS DESIGNERS MUST PROVIDE ALL TRUSS CONNECTIONS AS PART OF 5. COORDINATE RACEWAY INSTALLATIONS WITH OTHER TRADES PRIOR TO CONSTRUCTION. A. ASTM A615-94 PER REINFORCING SECTION (GRADE 60). BOTTOM E THE OPENING SHALL NOT BE MORE THAN 44" ABOVE THE FLOOR. THE DESIGN. 6. VERIFY ALL CONDUCTORS AND BREAKERS WITH EQUIPMENT MANUFACTURER B. WHEN A FOUNDATION DOWEL DOES NOT LINE UP WTH A VERTICAL CORE, IT SHALL NOT BE 4. TRUSS MANUFACTURER SHALL SUBMIT THREE (3) COPIES OF SHOP DRAWINGS AND SPECIFICATIONS. SLOPED MORE THAN ONE HORIZONTAL IN SIX VERTICAL ALIGNMENT, EVEN THOUGH IT IS IN AN 4. IL AREAS OTHER THAN HVHZ FIXED GLASS THICKNESS SHALL COMPLY WITH SECTION 2411 ENGINEERING CALCULATIONS SIGNED AND SEALED BY A FLORIDA REGISTERED ENGINEER, OF ADJACENT CELL TO THE VERTICAL WALL REINFORCING. OF LB.C. AS THE MINIMUM THICKNESS ALLOWED. THEIR ROOF TRUSS DESIGN FOR REVIEW INCLUDING TWO (2) COPIES FOR ARCHITECTS RENEW 7• PROVIDE DISCONNECT SWITCH OF SIZE AS REQUIRED BY LOAD AND UNITS. C. VERTICAL REINFORCING STEEL SHALL HAVE A MINIMUM CLEARANCE OF ONE-HALF INCH FROM 5. PROVIDE A MINIMUM OF 4' CLEAR ALL AROUND AIR HANDLER UNITS. PRIOR TO FABRICATION. RENEW VE TRUSS SHOP DRAWINGS IS A COURTESY RESPONSIBILITY THE THE OF SS FARCHITECTS T AND IN NO AFULLYEINTE SAFETYA/C EQUIP.AT 8. PROVIDE RSIBLESFROM CIRCUITT NEL SWITCHES THE MASONRY. SUPACTURER PROARCM ECA LAYOUT THAT INTEGS RATES THE ERSTRUCTURE. F� PUMPS NOT NBREAKER PER 6. AL DWELLING ROOMS MUST HAVE HVAC RETURNS. RETURNS MAY BE DUCTED, JUMPERS OR THERE IS ANY CONFLICT OR ADDITIONAL STRUCTURE NEEDED, THE TRUSS COMPANY SHALL RECOMMENDATIONS. M.C. MEDICINE CABINET SMS SHEET METAL SCREWS D. VERTICAL REINFORCING SHALL BE AS LOCATED ON THE PLAN AND AS INDICATED IN THE TRANSFER GRILLES. NOTIFY THE ARCHITECT IN WRITING OF THE SPECIFIC AREAS OF CONCERN. M.R.H. MEAN ROOF HEIGHT ST. STIRRUPS COLUMN SCHEDULE. 9. PROVIDE GFI BREAKERS FOR ALL BATHROOMS, GARAGE AND EXTERIOR OUTLETS AS M.T. METAL THRESHOLD STL STEEL 7. A/C UNITS MAY HAVE CONC. PAD OR OTHER APPROVED MATERIAL EXTENDING ABV. 5. TRUSSES TO BE DESIGNED TO CARRY LOADS OF ATTIC AHU AND MISC. EQUIPMENT. SHOWN ON PLANS, MAX. MAXIMUM SW SWTCH E. VERTICAL REINFORCING EACH SIDE OF ANY OPENING, IF REQUIRED, SHALL BE CONTINUOUS ADANING GRADE OR SHALL BE SUSPENDED A MIN. OF 6' ABV, ADJOINING GRADE. COORDINATE LOCATIONS WTH BUILDER PRIOR TO FABRICATION AND INDICATE R TRUSS MFR. MANUFACTURER TEMP. TEMPERED TO THE TIE BEAM. PRECAST UNTELS SHALL HAVE OPENINGS TO ALLOW REINFORCING BARS TO DRAWNGS. 10. ELECTRICAL FIXTURES, TRIM AND APPLIANCES SHALL BE UL APPROVED AND AS MICRO. MICROWAVE T.B. THROUGH BOLT CONTINUE UNINTERRUPTED. BEAM SCHEDULE NOTES SELECTED BY BUILDER, MIN. MINIMUM T.O. THROUGH OUT B. ALL INTERIOR LOAD BEARING PARTITIONS TO BE CONSTRUCTED WTH CUPS, TOP AND M.O. MASONRY OPENING T.O.B.B. TOP OF MASONRY BOND BEAM HORIZONTAL: BOTTOM EACH STUD, AS PER CODE 11. PROVIDE PRE -WIRED TELEPHONE OUTLETS AS SHOWN ON PLAN. MONO. MTL MONOLITHIC METAL T.O.PL T.O.T.B. TOP OF WOOD PLATE TOP OF TIE BEAM A. HORIZONTAL REINFORCEMENT SHALL BE PROVIDED AS SCHEDULED IN THE BEAM SCHEDULE. i. AL COMPOSITE UNTEL (MARK "L") TOP BARS SHALL BE CONTINUOUS UNLESS OTHERWSE 7. STRUCTURAL WOOD AND TIMBER FRAMING SHALL CONFORM TO THE "TIMBER CONSTRUCTION 12. PROVIDE PRE- WIRED T.V. OUTLETS FOR CABLE AS SHOWN ON PLANS. O.H.D. 0/C OVER HEAD DOOR ON CENTER .N. U.N.O.0 TYPICALO. UNLESS NOTED OTHERWISE5. GENERAL "BB" NOTID MANUAS PUBLISHED BY THE AMERICAN INSTITUTE OF TIMBER CONSTRUCTION. AL" 13. DEDICATED CIRCUITS SHALL HAVE NO MORE THEN 8 DUPLEX RECEPTACLES P.L.F. POUNDS PER LINEAR FOOT UL UNDERWRITERS LABORATORIES FIELD A. STRUCTURAL DESIGN IS IN ACCORDANCE WITH A.C.I. 530-05/ A.S.C.E. . BOND BEAMS (MARK REINFORCING SHALL BE CONTINUOUS THROUGH BOND A 2 ) BEPAS ONLY. ALL SPLICES TO BE A MINIMUM OF 48 BAR DIAMETERS. 8. ALL WOOD IN CONTACT WITH MASONRY CONCRETE SHALL E PRESSURE TREATED. 14. IN KITCHENS, DINING ROOMS AND BATHROOMS, RECEPTACLE OUTLETS FOR COUNTER P.S.F. POUNDS PER SQUARE FOOT V.I.F. W.A. VERIFY IN ANCHORS BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND THE 7-10/TTAR 4ON - PROVIDE AN APPROVED MOISTURE VAPOR BARRIER BETWEEN THE CONCRETE OR OTHER A SPACES SHALL BE GFq PROTECTED ACCORDING TO NEC 210-8(a). P.S.I. POUNDS PER SQUARE INCH WTH COMMENTARY ON BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES. BUILDING 3. aOND BEAM SCHEDULE DEPTHS ARE MINIMUM AND MAY BE INCREASED 8° TO FIT BLOCK CEMENTITOUS MATERIALS AND THE WOOD AS PER CODE. P.T. PARTN. PRESSURE TREATED PARTITION WC WATER CLOSET WOtK. 9. CARPENTER SHALL BE RESPONSIBLE FOR PROVIDING ADEQUATE BRACING AND BRIDGING USED 15. ALL CLOSET LIGHTING SHELL COMPLY WTH NEC SEC. 410.8. PKT, POCKET WD. WOOD B. CONSTRUCTION SHALL BE IN ACCORDANCE WTH A.C.I. 530.1-05/A.S.C.E. 7-10/T.M.S. 602- 05, SPECIFICATIONS FOR MASONRY STRUCTURES AND THE COMMENTARY ON SPECIFICATIONS 4. IEFER TO CONCRETE NOTES FOR INFORMATION ON CONCRETE AND STEEL SPECIFICATIONS 16. SMOKE DETECTORS SHALL BE CONNECTED TO KITCHEN OR BATH LIGHTING CIRCUITS PLYWD. R.O. PLYWOOD ROUGH OPENING FOR MASONRY STRUCTURES. 10, HEADERS FOR FRAMED OPENINGS GREATER THAN 6'-0" MUST BE ENGINEERED AND AHEAD OF SWITCH AND HAVE SELF CONTAINED BATTERY BACK-UP. DETECTORS SHALL BE S.C. SOLID CORE 6. VERTICAL CELLS FOR MASONRY TO BE GROUTED SHALL HAVE VERTICAL ALIGNMENT CONCRETE NOTES STAMPED BY THE TRUSS MANUFACTURER. (UNLESS NOTED OTHERWISE) TANDEM WIRED SO ALL DETECTORS SOUND SlMULTANEOUS-Y. S.G.D. SUDING GLASS DOOR SUFFICIENT TO MAINTAIN A CLEAR, UNOBSTRUCTED CONT. CELL 17. PRENRE FOR GARAGE DOOR OPENER SENSOR. SF SQUARE FOOT ti, ALL HEADERS OVER DOORS AND WINDOWS TO BE (2) OR (3) 2X12'S UNLESS OTHERWISE SH SINGE HUNG 7. CLEANOUT OPENINGS SHALL BE PROVIDED AT THE BOTTOM OF ROUTED CELLS AT EACH 1. (ONCRETE SHALL CONFORM TO ASTM C94-94 AND SHALL HAVE STRENGTH IN 28 DAYS AS NOTED. (FOR WOOD FRAME CONSTRUCTION DEPENDING ON ALL WALL THICKNESS). 18. ARC FAULT -INTERRUPTER PROTECTION PER NEC 210.12. REQUIRED FOR ALL 120-VOLT, LIFT OVER 4'-0' HIGH CLEANOUTS SHALL BE SEALED AFTER CLEANING AND INSPECTION AND SPEIFIED IN THE FOUNDATION AND MASONRY NOTES (UNLESS NOTED OTHERWISE) ALL SINGLE PHASE 15 AND 20 AMP BRANCH CIRCUITS SUPPLYING OUTLETS DWELLING UNITS ST. LUCIE COUNTY PRODUCT APPROVAL OPENINGS EDULE: OVERHEAD DOORS, SLIDING DOORS, FIXED GLASS, WINDOWS & SKYLIGHTS MODEL # MANUF. GLASS ATTACH. METHOD TYPE, SIZE, SPACING BUILDING DESIGN PRODUCT DESIGN OPEN ID PRODUCT DESCRIPTION AND EMBED. *FILL ALL MANUF. HOLES PRESSURE PRESSURE A FL-9174.10 R11 9100 OHD 16080 WAYNE DALTON N/A W/ 1-i/4' WASHER & 2-3/4" MIN. EMBED. DR = +28.5 PSF +39.2 PSF -43.7 PSF 2-3 4' MIN. EDGE DISTANCE. 6' FROM END -32.2 PSF 8 FL 17499.6 SH 35 W/ MI WNDOWS dO DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4" MIN EMBED D.P= +31.9 PSF 55.0 PSF -55.0 PSF FL 15349.1 F.G. ABV. 010' O/C MAX. SPACING At 2' FROM EDGE -34.8 PSF +60.0 PSF -60.0 PSF C FL 17499.6 SH H33 MI WNDOWS & DRS NON IMPACT 3/16- TAPCONS W/ 1-1/4' MIN EMBED DR= +33.5 PSF +55.0 PSF -55.0 PSF 010' O/C MAX. SPACING & 2' FROM EDGE -36.3 PSF D FL 17499.6 SH 35 MI WNDOWS & DRS NON IMPACT 3/16' TAPOONS W/ 1-1/4- MIN EMBED DR= +31.9 PSF +55.0 PSF -55.0 PSF 010' O/C MAY. SPACING & 2' FROM EDGE -34.8 PSF E FL 17499.6 SH 35 MI WINDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4- MIN EMBED D.P= +31.9 PSF +55.0 PSF -55.0 PSF 0 10" O/C MAX. SPACING & 2" FROM EDGE -34.8 PSF F FL 17499.6 SH H33 MI WNDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4' MIN EMBED D.P. +33.5 PSF +55.0 PSF -55.0 PSF 010' O/C MAX SPACING & 2' FROM EDGE -34.8 PSF G FL-7630.1 2680 SGL LITE DR THERMA TRU NON IMPACT 1/4' TAPCONS W/ 1-1/4' MIN. EMBED CORNERS 0 D.P.= +31.9 PSF +50.0 PSF -50.0 PSF 6" & 14" O/C MAX. SPACING. -34.8 PSF H FL 17499.6 (2) SH 26 MI WNDOWS & DRS NON IMPACT 3/16' TAPOONS W/ 1-1/4- MIN EMBED D.P= +29.9 PSF _ +55.0 PSF 55.0 PSF 0 10' 0/C MAX. SPACING & 2" FROM EDGE -32.7 PSF FL 15349.1 6414 TRANSOM MI WINDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4' MIN EMBED D.P.- +33.5 PSF +60.0 PSF -60.0 PSF EQUAL SPACING & 3' FROM EDGE -36.3 PSF J FL 17499.6 SH 36 MI WNDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4' MIN EMBED D.P= +31.9 PSF +55.0 PSF -55.0 PSF 0 10" O/C MAX. SPACING & 2' FROM EDGE -34.8 PSF K FL 15349.1 4614 TRANSOM MI WINDOWS &DRS NON IMPACT 3/16' TAPOONS W/ 1-1/4' MIN EMBED D.P.= +33.5 PSF +60.13 PSF -60.0 PSF EQUAL SPACING & 3' FROM EDGE -36.3 PSF L FL 15332.3 12080 SGD MI WNDOWS & DRS NON IMPACT 3/16' TAPOONS W/ 1-1/4' MIN EMBED D.P= +28.5 PSF +35.11 PSF -35.0 PSF 012' O/C MAX. SPACING -31.3 PSF M FL 15349.1 12014 TRANSOM MI WINDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4' MIN EMBED D.P= +31.9 PSF +60,0 PSF -60.0 PSF EQUAL SPACING & 3' FROM EDGE -34.8 PSF N FL-7630.1 2880 SGL LITE DR THERMA TRU NON IMPACT 1/4' TAPCONS W/ 1-1/4' MIN. EMBED CORNERS 0 OR= +31.9 PSF +50.0 PSF -50.0 PSF 8' & 14' O/C MAX. SPACING. -41.7 PSF Q FL 17499.6 (2) SH 35 MI WNDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4' MIN EMBED D.P= +29.9 PSF +55J7 PSF -55.0 PSF 0 10" O/C MAX. SPACING & 2' FROM EDGE -33.6 PSF P FL 17499.6 SH H33 MI WINDOWS & DRS NON IMPACT 3/16" TAPCONS W/ 1-1/4' MIN EMBED D.P.= +33.5 PSF +55.0 PSF -55.0 PSF 0 1C' O/C MAX. SPACING & 2' FROM EDGE -36.3 PSF Q FL 15349.1 6020 TRANSOM MI WINDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4' MIN EMBED D.P= +33.5 PSF +60.0 PSF -60.0 PSF EQUAL SPACING & 3' FROM EDGE -36.3 PSF R FL 17499.6 SH 35 MI WNDOWS & DRS NON IMPACT 3/16' TAPOONS W/ 1-1/4' MIN EMBED D.P= +31.9 PSF +55.10 PSF -55.0 PSF 0 10' O/C MAX. SPACING & 2' FROM EDGE -34.8 PSF S FL 17499.6 SH 15 MI WNDOWS & DRS NON IMPACT 3/16' TAPOONS W/ 1-1/4' MIN EMBED D.P= +33.5 PSF +55.0 PSF -55.0 PSF FL 15349.1 W/ F.G. ABV. 0 10" O/C MAX. SPACING & 2' FROM EDGE -36.3 PSF +60.0 PSF -60.0 PSF T FL-15037.4 PR 3080 DRS THERMA TRU N/A 1/4' TAPCONS W/ 1-1/4' MIN. EMBED CORNERS 0 O = +29.9 PSF +50.0 PSF -50.0 PSF 6' & W O/C MAX. SPACING. -32.7 PSF U FL 15349.1 6428 TRANSOM MI WNDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4" MIN EMBED D.P= +33.5 PSF +60.0 PSF -60.0 PSF EQUAL SPACING & Y FROM EDGE -36.3 PSF V FL 17499.6 SH 15 MI WNDOWS & DRS NON IMPACT 3/16' TAPCONS W/ 1-1/4- MIN EMBED D.P= +33.5 PSF +55.13 PSF -55.0 PSF FL 15349.1 W/ F.G. ABV. 010' O/C MAX. SPACING & 2' FROM EDGE -36.3 PSF +60.0 PSF -60.0 PSF W FL 17499.6 (2) SH 25 MI WINDOWS & DRS NON IMPACT 3/16' TAPOONS W/ 1-1/4" MIN EMBED D.P.= +29.9 PSF +55.0 PSF -55.0 PSF FL 15349.1 W/ F.G. ABV. 0 10' O/C MAX. SPACING & Y FROM EDGE -32.7 PSF +60.0 PSF -60.0 PSF ATTACHMENT METHOD BUILDING DESIGN PRODUCT DESIGN PRODUCT MODEL # MANUF. TYPE, SIZE, SPACING, EMBED., STIFFENERS, ETC PRESSURE PRESSURE MULLIONS MAX. 104-1/4" HORIZ I DOWS MNN DOORS 1/4' TAPOONS W/ 1-1/4- MIN EMBED (4) FASTENERS PER CUP TOP &BIM. 37.7 PSF 54.0 PSF -54.0 PSF FL 15353.4 ROOFING NOA NO. 16-0314-.06 EAGLE ROOFING (2) 10d RING SHANK NAILS -83.4 psf -172 psf. BEL-AIR CONCRETE TILE PRODUCTS ROOFING O. 17-A 14-.2 NOA NO. 17-0614-.22 POLYGLASS USA MEMBRANE: POLYSTICK TU MAX SELF ADHERED 1 OR MORE PLIES NAILS AND TIN CAPS 12' GRID, 6" O.C. AT A MIN. a N/A N/A UNDERLAYMENT PEEL & STICK SIBS INC. HEAD LAP SIDING STUCCO N/A N/A N/A N/A 2 RING SHANK ATTACHED TO UNDERSIDE OF TRUSS SOFFIT STUCCO N/A SPACED 0 EVERY HI RIB (4 O/C) W/ 1-3/4' EMBED. N/A N/A PER NAIL HURRICANE PANELS FL 16293-R1 HURRICANE STORM 1/4" -20 x 3/4" S.S. 37.7 PSF +49.) PSF -56.0 PS 120' MAX. SPAN GALV STEEL PANEL PANEL KNURLED STUDS 12-1/2' O.C. TOP AND BTM MANUFACTURING, NC ALL MANUFACTURES LABLES SHOWING U FACTORS AND SHGC COMPLIANCE WITH FBC ENERGY CODE MUST REMAIN ON ALL DOORS AND WINDOWS UNTIL INSPECTIONS ARE APPROVED CONCEALED FASTENERS ORATTACHVt T- ARE THE RESPONSIBIUV Of THE CONTRACTOR OF RECORD BEFORE GROUTING. CONCRETE WORK SHALL BE IN ACCORDANCE WITH ACI 318-11 AND ACI 301-05. ALL 12. DIMENSIONAL LUMBER SHALL BE SOUTHERN PINE NO. 2 OR BETTER AND SHALL PROVIDE COICRETE MASONRY WORK SHALL BE IN ACCORDANCE WITH ACI 530-11. ALLOWABLE STRESS VALUES OF 1200 PSI IN BENDING FOR A SINGLE MEMBER USES. 90 PSI 19. CARBON MONOXIDE DETECTORS REQUIRED WITHIN 10' OF ANY SLEEPING ROOM. FOUNDATION NOTES 2. IINIMUM CONCRETE COVER OVER REINFORCING SHALL BE: SLABS ON VAPOR BARRIER - IN HORIZONTAL SHEAR AND SHALL HAVE A MODULES ELASTICITY OF 1600 KS OR BETTER, AS DETERMINED BY AN APPROVED LUMBER GRADING AGENCY. 3/4 BEAMS AND COLUMNS - 1 1/2" FORMED CONCRETE BELOW GRADE-2- UNFORMED PLUMBING NOTES I. FLOOR SLAB TO BE 4' THICK POURED CONCRETE SLAB WITH FIBERMESH COICRETE BELOW GRADE-3" 13. NON -BEARING INTERIOR PARTITIONS MAY BE CONSTRUCTED OF 20 0 24" D.C. ON 0,006 MSQUEEN (OR EQUAL) ON CLEAN WELL COMPACTED FILL STUDS, WTH 1/2" GYPSUM DRYWALL EACH SIDE. ATTACH DRYWALL WITH 1' LONG 3. ENFORCING STEEL, GRADE 60 (FY-60.000) ASTM A615-94, BUGLE HEAD DRYWALL SCREWS AT 12' O/C MAX. 1. ALL PLUMBING FIXTURES SHALL BE INSTALLED IN ACCORDANCE WTH SECTION 405, F.B.C. 2. ALL REINFORCING STEEL TO BE GRADE 60. 4. ETAIL OF CONCRETE REINFORCEMENT SHALL BE IN ACCORDANCE WTH 'THE MANUAL OF 14. METAL LATH OVER SHEATHING SHALL BE 3/8' V-ROVE OR DIMPLED. FASTEN TO 2. ALL PLUMBING FIXTURES SHALL MEET THE REQUIREMENTS OF TABLE 604.3, F.B.C. STAIDARD PRACTICE FOR REINFORCED CONCRETE CONSTRUCTION" AS PUBLISHED BY THE SUBSTRATE AT 4' 0/0 AS FOLLOWS; 3. COLUMN AND WALL CENTERLINES SHALL COINCIDE WTH FOOTING CENTERLINES UNLESS CONCRETE REINFORCING STEEL INSTITUTE UNLESS NOTED OTHERWISE. CONCRETE: 3/4" LONG STUB NAILS W/ 3/8' HEAD. HORIZONTAL AND VERTICAL WOOD 3. DISPOSITION OF RAIN WATER SHALL COMPLY WTH F.B.C. PLUMBING CODE CHAPTER it. OTHERWISE NOTED. 5. ADEQUATE VERTICAL AND HORIZONTAL SHORING SHALL BE PROVIDED TO SAFELY SUPPORT FRAMING MEMBERS W/ NAILS OR STAPLES TO PROVIDE AT LEAST 1-3/4' PENETRATION INTO HORIZONTAL WOOD FRAMING MEMBERS, AND 3/4' PENETRATION INTO VERTICAL WOOD 4. ALL PLUMBING PENETRATIONS MUST BE A MINIMUM 10'-0' FROM ROOF JACKS. 4. FOOTING DESIGN BASED ON ASSUMED SOIL BEARING CAPACITY E 2500 P.S.F., ALLLOADS DURING CONSTRUCTION. FRAMING MEMBERS. ON VERTICAL WOOD FRAMING MEMBERS, COMMON NAILS SHALL BE 5. FILL PLACED WTHIN 5'-0' E THE CONSTRUCTION PERIMETER SHALL CONSIST OF CLEAN 6. IONCRETE BEAM SIZES MAY INCREASED (8' MAX.) AS REQUIRED FOR ARCHITECTURAL BENT OVER TO ENGAGE AT LEAST THREE STRANDS OF LATH, OR BE BENT OVER A RIB 5. CONDENSATE DRAINS MUST BE A MINIMUM R 12' OFF THE BUILDING. WELL GRADED SAND COMPACTED TO ACHIEVE A DETIILS OR FIT BLOCK COURSING, DROP BOTTOM OF TIE BEAM AS REQUIRED AT WINDOW AND WHEN RIB LATH IS INSTALLED. SHEATHING: 14 GAUGE STAPLES 1' LEG 7 16' CROWN METAL 6. INSTALL CHASE PIPE FOR HVAC. MINIMUM OF 95% MODIFIED PROCTOR ASTM D 1557. DOOR BEAMS (28' MAX.) AND ADD 2-#5 BARS BOTTOM IF DROP EXCEEDS 8". FRAMING: SELF TAPING SCREWS 12 x 1/2" WASHER HEAD STAPLES SHALL NOT BE USE USED FOR SOFFITS OR CEILINGS 6. ALL MONOLITHIC FOOTINGS HAVE BEEN CHECKED TO PREVENT THE USE OF TRANSFER REINFORCEMENT AT PERIMETER. RATIONAL ANALYSIS SHALL BE SUBMITTED, BUT ONLY IF 7. )OWELS COLUMN AND WALL REINFORCING TO FOOTING WTH SAME SIZE AND NUMBER R DONELS AS VERTICAL BARS ABOVE. 15. PNEUMATIC FASTENERS SYSTEM TO BE HILTI-COIL NAIL PROGRAM. TYPE TO BE CRF 112G MECHANICAL NOTES REQUESTED BY THE BUILDING OFFICIAL 1-1/2' LONG AND .120" DIAMETER U.N.O. 7. CONCRETE FOR FOUNDATIONS AND FOOTINGS SHALL BE 2500 PSI MIN. &REINFORCING STEEL SHALL BE LAPPED 48 BAR DIA. MIN. WHERE SPLICED AND SHALL BE WIED TOGETHER. PROVIDE CORNER BARS SAME SIZE AND NUMBER AS HORIZ. BEAM 16. TRUSS MANUFACTURER SHALL DESIGN TRUSSES TO COMPLY NTH ALL SUPERIMPOSED L ALL HEATING, AIR CONDITIONING, REFRIGERATION AND VENTILATION EQUIPMENT SHALL B. DAMAGE PROBABILITIES FROM TERMITE INFESTATION IS VERY HEAVY PER TABLE R301.2(1). RBNFORCING AT EACH FACE. LAP 48 BAR DIA. MIN. WND LOADS PER F.B.C. 2014 5TH EDITION & ASCE 7-10. CONFORM TO THE 28 REQUIREMIN THE "FLORIDA BUILDING CODE MECHANICAL" OF THE FENTS T FORTH AND E. 9. °LACING DRAWINGS ON BAR LISTS SHALL CONFORM TO ACI'S "MANUAL OF STANDARD PRLCTICE FOR DETAILING REINFORCED CONCRETE CONSTRUCTION AS PUBUSHED BY THE STEEL NOTES GARAGE NOTES CONCRETE REINFORCING STEEL INSTITUTE UNLESS NOTED OTHERWISE. 11 DAMAGE PROBABILITIES FROM WEATHERING IS NEGUGIBLE PER POO TABLE R301.2(1). 1. STRUCTURAL STEEL SHALL CONFORM TO THE AISC "SPECIFICATION FOR THE DESIGN, 1. OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE EQUIPPED WTH SOUD WOOD ST. LUC'E COUNTY HT1iS nTNC. TINTSION R17VTF.W ED FOR COMPLIANCE REVIEWED BY DATE PLANS ANT) PERMIT MUST HE iffPT 01jj0 OR NO INSPECTION WILL 13Ti MADE. N to 1 Bd" SH 15 ■ ■ M.O. 20 1/8' PROPOSED SINGLE FAMLY RESIDENCE BY: sKM[41�01*]LIWLI TACOMA LOT 170 MEADOWOOD COPYRIGHT W17 TYPICAL "MI" WINDOWS Ll [V ELl E N 36" 52d" 25;" SH 25 M.O. 38' 2x, OR 5/4 BOARD P.T. WOOD BUCK "xR" SH 35 M.O. 54 1/8" 1x, 2x, OR 5/4 BOARD P.T. WOOD BUCK -AA" SH H35 ■ ■ M.O. 271/2' FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS" 2005 EDITION. MATERIALS - DOORS NOT LESS THAN V" (35 MM) THICK, SOLID OR HONEYCOMB CORE STEEL DOORS NOT SHALL CONE E A PUCABLE ASTM SPECIFICATION AS FOLLOWS: SHAPES PLATES A-3 LESS THAN - SHA CONFORM 0 T THE P N �' (35 MM) THICK, OR 20 MINUTE FIRE -RATED DOORS. BOLTS - A 307-00 TUBULAR - A500-01a GRADE B (42 KS) Z DUCTS IN GARAGE AND DUCTS PENETRATING THE WALLS OR CEILINGS SEPARATING THE 2. WELDED CONSTRUCTION SHALL CONFORM TO THE AMERICAN WELDING SOCIETY "STRUCTURAL %nUNG FROM THE GARAGE SHALL BE CONSTRUCTED OF A MINIMUM, NO. 26 GAGE (0.48 MM) WELDING CODE'. ELECTRODES FOR FIELD AND SHOP WELDS SHALL BE A.W.S. A5.1 E70XX. SHEET STEEL OR OTHER APPROVED MATERIAL AND SHALL HAVE NO OPENINGS INTO THE GARAGE. 3. THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND ITS ATTIC AREA BY NOT LOAD SCHEDULE LESS THAN )" (12.7 MM) GYPSUM BOARD APPLIED TO THE GARAGE SIDE. LOCATION LDS DEAQ PARTN TOTAL GROUND FLOOR 40 50 10 100 SECOND FLOOR 40 15 10 65 ROOF 30 18 0 48 ATTIC 20 10 0 30 ANI : ULITIMATE WIND SPEED = 160 m.p.h. BUILDING RISK CATEGORY = II BUILDING DESIGN AS ENCLOSED EXPOSURE = C ROOF DEAD LOAD FOR WND DESIGN TAKEN AT 10 p.s.f. ROIEL THIS STRUCTURE IS DESIGNED IN ACCORDANCE WTH CHAPTER 16 OF THE FLORIDA BUILDING CODE AND ASCE 7-10. DEER PRESSURES FOR EXTERIOR DOORS AND WINDOWS ARE NOTED ON THE ELEVATIONS. WNDOW AND DOOR MANUFACTURERS SHALL MULTIPLY THE GIVEN DESIGN PRESSURES BY THE APPROPRIATE FACTORS TO OBTAIN TEST PRESSURES. MR po 2x P.T. WOOD BUCK SHOWN TYP. M.O. 35 1/4' W M.O. 37 1/4" W M.O. 41 1/4' W \ M.O. 55 1/2' W M.O. 77 1/2' W X 98 1/2' H X 96 1/2' H X 98 1/2" H \\\`. X 98 1/2' H X 98 3/4' H EDGE OF SLAB EDGE OF SLAB EDGE OF SLAB EDGE OF SLAB I ' EDGE OF SLAB 2680 EXT DR 2880 EXT DR 3080 EXT DR 3080 EXT DR W/ 14" SIDELITE PR 3080 DR (OUT SWING) (OUT SWING) (OUT SWING) (OUT SWING) (OUT SWING) DOOR INSTALLATION NOT: DOOR BUCKS USED MAY BE 24, 5/4' BOARD OR Ix6. CONCRETE SCREWS USED TO SECURE THE DOOR FRAMES TO THE OPENINGS MAY BE ANGLED SLIGHTLY WTHOUT APPRECIABLE LOSS IN RESISTANCE. ALL FASTENERS SHALL BE OR THE SZE, LENGTH AND SPACING AS REWIRED IN THE PRODUCT APPROVAL INSTALLATION PROCEDURES. SYMBOLS LEGEND DETAIL SCALE DETAIL DWG SCALE SECTION 4SCALE SECTION DWG SCALE # INTERIOR ELEV. SCALE B� BEAM LABEL QREVISION N NORTH ARROW BREAK LINE a�_��r�..�� S IM 1■ 1 /� GRAPHIC SCALE DRAWING INDEX C-1 COVER SHEET A-1 FOUNDATION PLAN A-2 FLOOR PLAN A-3 ELEVATIONS A-4 SECTIONS A-5 STRUCTURAL PLAN A-6 TRUSS PLAN E-1 ELECTRICAL PLAN M-1 MECHANICAL PLAN 1 4 DWG. 2 INTERIOR ELEVATION 3 C# COLUMN LABEL F# FOOTING LABEL Lu v u w J uj y z w T a = � O J w J w D Z 3�LL V u J Z. Z 0 J Q ro N Oa rn ❑ Z O C L a c ca'o d v 0 c o o c �•� �' au c}� as vroc E N O rn pT rn c rp c E OV 0. N O O 4:E; C ro Q a� E E o r-° o O S a U •� N N rn w > c O V E c " c p 2 EIf _ Z O co r1 t c.2 `O N- o ; av POT SHELF HEIGHT rEm / AS NOTED FFFIT %iffi/%fi�J%J�%J EAS NOTED I�-L f!//!U/L!!/11//!!/2 HEIGHT M Z - 1 LUL PLAN ARCHED OPENIELEVNG SEE MASONRY CONSTRUCTION TYPICAL ■■ GROUT FILLED CELL SEE FOUNDATION PLAN ELEV 0'-0' FIN. FL SLAB NON -BEARING FRAME CONSTRUCTION BEARING FRAME CONSTRUCTION BEAM HEIGHT CHANGE FLOOR ELEVATION LL a Z 0 O Q W W J 14" = 1'-0" U.N.O. COVER SHEET C-1 MW =170 FOOTING SCHEDULE MARK SIZE WxD REINFORCING DESCRIPTION DETAIL NO, F-1 20" x 18" X CONT. W/2 15 CONT. EXTERIOR MONOLITHIC ' F-2 20" x 18" X CONT. W/2 15 CONT. ® RECESSEXTERIORMONOL17HIC 38 F-3 2'-6" x 2'-6" x 12" W/3 #5 E. W. 87M. ISOLATED PAD 7 F-4 2'4" x 1-9' x 12" W/3 15 EW. BTU. MONOLITHIC 0 PAD 19 F-5 2'-6' x 2'-6" x 12" W/3 15 E.W. BTM. PAD 0 INTERIOR WOOD POST ISOLATED PAD 6 F-6 4'-6" x 3'-0" x 12" W/4 15 E, W. BTM. 7 TE-1 10' x DROP x CONT. W/115 CONT. THICKENED EDGE AT DROP 34 COLUMN SCHEDULE MARK SIZE TYPE DESCRIPTION CONC. BLK. W/ 1 FULLY GROUTED CELL W/1-15 VERT. 8x8 AT 6'-0" 0/C MAX. AND AT EVERY CORNER AND C-1 BLOCK BOTH SIDES OF ANY OPENING MORE THAN 6'-0" MDE 8x16 CONC BLOCK W/2 FULLY GROUTED CELLS W/1-15 VERT. EACH CELL C-2 BLOCK AS LOCATED ON PLANS 8x12 C-3 BLOCK CONC. BLOCK IN FULLY GROUTED CELL W/ 2-J/5 VERT. IRREGULAR 45' MITERED CONC BLOCK IN FULLY C_4 BLOCK GROUTED CELLS W/ 2-#5 VERT. 12x12 C-5 BLOCK CONC. BLOCK IN FULLY GROUTED CELL W/ 4-05 VERT. 4"X4" C-6 WOOD POST PROVIDE BASE AND CAP AS NOTED ON DETAILS CONC. POURED FILLED CELL W/ STL. PER PLA DOWELL & EPDXY (1) #5 REBAR INTO SLAB FILLED CELL LOCATION W, 4" MIN. EMBED. INTO SLA MISSED COLUMN STL. DETAIL TYP. HOLLOW MASONRY BLOCK RUNNING BOND PER PLAN 'ONC. SLAB & AONOLITHIC -OUNDATION PER PLAN 48 BAR DIA. SPLICE 8 X8" PRECAST L;. LINTEL. SEE LINTEL SHOP DWGS. FILL COLUMNS I` AND LINTEL SOLID +" W/ GROUT 8"x8" F'LLED CELLS W/ 1 5 VERT. (TYP.) TYPICAL DETAIL LINTEL ON COLUMN 48 BAR DIA. SPLICE SHI E"I SEE BEAM SCHEDULE FOR REINFORCEMENT m m FILL COLUMNS SOLID 8"x8" FILLED CELLS W/ PEA GRAVEL CONCRETE SEE PLAN AND COLUMN SCHEDULE FOR REINF. TYPICAL DETAIL BEAM HEIGHT CHANGE N I N 16'-0" 17'-0° 60'-0" 15'-8" (2) SLI 35 H HEAD 8'-01, C5 F C5 ■■ ■■ ■■ I 0 I ❑® ■ -------- —� F3 L_J L—J mm 2880 03 F3 �' 5'-8" 7'-1° 2'-11° -4" 11 6'-0" rom SGL UTE aim o d (2) SH 26 W 1'-7" '-2" 1'-8" I. 2'-6" ~ ~ FG 1 " HIGH Co FG ABV (SG 80 i ■ A4 HEAD 10'-0" LITE 0 C2 ® ■ ■ ■ ■ ®■ a ■ ifD I ® F---------— — — — — — — — 1 I I 3=>-0l I F1 I o M" 00 I FORM SHOWER PAN-1 ® $ N 4 0 1 1/2" LARGER ON ALL F1 I N = I SIDES THAN ACTUAL DIMS I -0" '-o" '-o FINISHED eSHOWN HERE 120BO SGD I 6" SHOWER l 0 W/ 12014 FG. BV. (4 PANEL) RECESS HEAD 0 10'-0" C I 15 6" --- --� N TF —1 F1 F5 FORM SHOWER PAN ■ 1 1/2" LARGER ON ALL SIDES THAN ACTUAL FINISHED DIMS, — — — SHOWN HERE d ` � p I F2 O � � 2 p 6" SHOWER w RECESS I i 0 I ■ I o 0 0 0 0 SUPPLY PLUMBING & o ELEC. TO ISLAND UNDER I C FLOOR OUTLET W/ SLAB I r BRASS COVER 1 NOTE: ALL COLUMNS ARE C1 U.N.O. 0'-0" FIN. FLOOR SLAB_ 5'-7" 7 C6 L_J F5 I I I si I TE-1 " I r 2-0 13'-10' 2' 4° I — 7F-, 7 7E-1 ,p F1 I J — — — — — -- o — o — a rd ® I N N PR 3080 DRS W/o FG TRANSOM ABV 4" I ■■ ■■ Asti \ F1 0 �y1�° ® j�90 9pcy�o F1 \ F2 10 ®�•------------ I \\ I CA _ \ ® ■ SH 35 ® ■ ■'• 4 C4 W2) RCHED ® d J \ \\ FG ABOVE-1 1/2' -11" '11' 2'-1 1/2'-1 2" _ 6-72' 6'-11' 3- ®■ C2 I \\ \\ ® I \\ L- _J I \\ \ C3 C3 m m ad cd of ai m m \\ UNDER S1 AB m m I B' W X 5-)¢" D RECESS \\ LINE CHASE mo o F6 F6 FOR PAVERS (FOOTING \\ �el I DEPTH MEASURED FROM \\ a I BOTTOM OF RECESS) W/ \\ 12'-2 6' W X 3/4" D RECESS \\ BEHIND (SLOPED) \ \ 0 p p -' N I F2 3'-91/2° 4'-11 1 2" SLOPE 2" I E I I IT I F1 EXTEN 5-1/2" DEEP R CESS 4" I ELEC. PANEL PAST DGE OF OPENING, TYP. NISH EDGE OF C NCRETE I F2 I A T RECESS, TYP. I A4 ■ L-----------------J C2 O N ® ■7SH M■35 W FG ABV EAD 8-2" 4'- °'"T.OB.B.11'-4 3'-7" -0 T.OB.B. 9'-2" -8" X-91/2" 4'-111/2" 7'-7" 7'-7" 14'-9" 81-9" 24'-4" 60'-0" PROJECT LOG ISSUED FOR PRECON 10-18-17 �j ISSUED FOR PERMIT 11-17-17 CONIC. PADio 0 W a: Lu o N W Lu Z M O Q m d — J Z Ij z U j m LL Z J Z 0 Q o a 0 d Z Ov o a 0 Q1 0 � c _ L SS 2 Q fl-CL E •� Q' 2O 3 0 o a"i vdi o Q w � i c C v a aoi Fu O O O t 6 .D .0 cL N O O C O w E E o o E o -o a u i •� N N C ai C ch ° a = v o L�• u E a 2f i ai a J O � LA_ O O Lu U � J W 1/4" = 1'-0" U.N.O. FOUNDATION PLAN -1 c° mw -A 70 TYP, ARCH ELEVATION C 9-4 CLG. TYP, ARCH ELEVATION C 11'-4" CLG. GARAGE CEILING f'iZ�9L1U] (2) 110 S.M.S. TOP & BOTTOM 0 EACH STUD -FINISHED CEILING - SEE TYP. WALL SECTION 2x6 BLOCKING CABINET LOCATIONS. FASTEN EA, END TO STUDS W/ (2) #10 S.M.S. EA. END 25 GAUGE CHANNEL SHAPED STUDS- X40/C) W/1 FULL (LENGTH24 STUDS 0 24LAYER 0 1/2" TYPE GYPSUM WALLBOARD O APPLIED VERTICALLY & ATTACHED W/ i" LONG BUGLE HEAD SCREWS TO EACH SIDE 0 12" 0/C CONT. 25 GAUGE METAL TRACKS TOP & BOTTOM CONC. FLOOR SLAB HIL71 PINS .145" DIA x 1" LG. 0 16" 0/C W/ I- WASHERS TYPICAL INTERIOR PARTITION ALONG CABINETRY BACKING SCALE 3/4" = i'0" 3 4" THK TEMP —\ MF AMELESS GL W/ CUPS 1/2" WALL CAP—. MTL FRAMING KNEEWALL W/ DRYWALL FINISH THIS SIDE TOP OF KNEEWALL W/ PT 2X TOP PLATE & 1/2 PLYWD & 1/2" MOISTURE RESISTANT DRYWALL KNEEWALL W/ MOISTURE RESISTANT DRYWALL ON SHOWER/TUB SIDE & TILE FINISH a U ROMAN SHWR ai PT 2X SILL PLATE L L ` m L-LLLL LLLLLL LLLLLL ( TYP. KNEE WALL SECTION 1/2" = 1'-0" ADDITIONAL NOTES: 1. STANDARD HOLLOW CORE RAISED PANEL DOORS. 2. TILE TO 7'-0" IN MASTER SHOWER AND 7'-0" IN OTHER LOCATIONS. 3. FIBERGLASS BOARD OR DUR-O-ROCK TO 7'-0" A.F.F. OR SOFFIT AROUND TUBS/SHOWERS AND TO 4'-0" A.F.F. 0 MARBLE TUBS 4. ROUNDED CORNERS AT ALL LOCATIONS EXCEPT CLOSETS, SLIDERS, WINDOWS, DOORS, VERTICAL EDGES OF CEILINGS OR AS NOTED ON PLANS. 5. KNOCKDOWN CEILING TEXTURE AND ORANGE PEEL WALL TEXTURE. 6. R-30 BLOWN -IN INSULATION AT ALL A/C AREAS R-30 BLOWN -IN FIBER GLASS INSULATION AT ALL A/C AREAS ALL INSULATION SHALL COMPLY WITH FBC R302.10 FLAME SPREAD COMPLIANCE 25. SMOKE DEVELOPED INDEX 50. ALL CEILING AND WALL FINISHES SUCH AS PAINT SHALL COMPLY WITH FBC R302.9.2 AND BE LESS THAN THE VALUE OF 200. GARAGE FLOOR ELECT. PANEL / CHASE CEILING TYPICAL Z 0 16° a FINISHED FLOOR SOAP NICHE (2) JIO S.M.S. TOP & BOTTOM 0 EACH STUD FINISHED CEILING - SEE O TYP. WALL SECTION CONT, 25 GAUGE METAL TRACKS TOP & BOTTOM W/ (1) #10 SMS 0 24" 0 25 GAUGE CHANNEL SHAPED STUDS 24" 0/C W/1 FULL LENGTH LAYER OF 1/2" TYPE GYPSUM WALLBOARD ol APPLIED VERTICALLY & ATTACHED W/ 1" LONG BUGLE HEAD SCREWS TO EACH SIDE 0 12" O/C CONC. FLOOR SLAB HILR PINS .145" DIA x i" LG. 0 16" 0/C W/ 1" WASHERS 1 INTERIOR PARTITION A 2 3/4 - 1.'0'. CALCULA TOTAL U/A COVERED ENTRY COVERED LANAI GARAGE TOTAL AREA TIONS 2522 S. F. 105 S.F. 325 S. F. 689 S.F. 3641 S.F. I WASHER 28 1/2 RACE DRYER VENT °n DRYER VENT LOCATION FRONT VIEW O �- I aC 12" AC CONC. PAD DIETAIL N.T.S. FINISHED CEILING 2x WD BLOCKINC O EACH SIDE OF P FOR MOUNTING Ll W (n 2x MTL. STUDS TYP. FINISHED FLOOR TYP. MEDICINE CABINET Ili]I'7L,1 (2) H 35 OO MIS I (EG ESS) 0 14'-8" / CR WN MOLDING \ DOES NOT INCLUDE COFFER \ STER ® SUITE 9'-4"/10 4" COFFERED CLG. 2'-0" 10'-8" 0 0 "2 I I I I I N \ / o K i lV IN I LN FLAT A CH - — SPRING ® '-10 °p TOP ® -6" c HIS 2680 I WIC r 2680 , c — — — — — — — — — — — — — — — — — — — — — — — — — 1880 17'-0" cd m " 5'-8es mm 00 o0 - o I A COVERED Z d W/)16HHI H OH2 O JUTE A4 LANAI FIG ABV scL ll'-4" CLG. 21111111130 (ABV MAIN SLAB) Oj AVERS In sa CROWNMOLl NG ; NOOK ■ 1l'-4" CL . i CLG." 2880 I 9 pl / ,p 12080 SGD 4 PANELS) •� W 16" HIGH FG TRANSOM ABV ` O ■� ` V 0p P CROWN MOLDING GREAT ROOM ll'-4" CLG. 0 ® Y WIC N U N M � �p M o I N N M 1 M 880 _ ff O N O o w° OM U' O Q t0 fV ° a _ ® MASTER <o IO 0I of UI 5 al la 0 i = J " 4'-0" 2'-,1b0. zfZj2-0. `o ISLAND 12 O U EE DW CROWN MOLDING DBL. IT OVEN ll'- CLG. 0 � I F z — —R 2680 _ = b.7 1 8" BATH 6' 5 1/2" 1'-a" •I o ROMAN o 9'-4" CLG, SHWR FL IT ARCH N ¢ 7 FLAT AROH 1'-5" SPRI G ® 9'-0" $ SPRING 0 7'- 0" BACKING ® 3 0 10-E" TOP ® 10'_6"— 91, 36" A.F.F. o NICHE c VANIT( o m — — Q O I0 36" AFFI 3CL RE CORNER m SOAP NICHE 6'-11" 9,_4" OSH 35 R 12'-2 1/2' BEAD. CROW FOYER MOLDING o 12' 4° CLG. I N UTIL :I m r _�� m a i WC6 I = i m m 3 -® d- CROWN MOLDING I 11¢®® � $ DINING m --I� m sNSH o I a ll'-4" CLG. I, OPT D I LT 1 J�ll N N I —�� ° 8" 7$ 91/2• GA RE N 0 DRS W 1-0 1/2" R- ARCTRANSOM 4D�F ABV F5 WA ®. ® w ® O O • O m I o OO JI ' " '-11" m 1 ECH 3'-1 G is ., \"" 0° COV RED (2 SH 25 \� s ENTRY 0 I Ow W1 FG ABV. 0 BEDROOM 3 9'-4" CLG. 12'-0" BEDROOM 2 9'-4" CLG. O O LOA :E SEPARAT ON REMENTS PER 302.6 BATT INSULATION FOR DEMISING PER ECALCS ° 2'-1 1/2" T-9 1/2" 2'-1 1/2° g° I EWH 22 54" 14'-8° CLG. 20 MIN. SOLID CORE PULL STAIR DOOR W/ RIVETED S V. LT. (ABV MAIN SLAB) JAMB OVERSIZED ` / ® PAVERS ® ® WEATHERSTRIPPING — — — — — — — 14'-9" m m m m GARAGE SMOOTH COAT a d m o °' 0 m o I STUCCO FINISH AT EXTERIOR I MASONRY WALLS. STUCCO TO ao I Lt I °<r'v I I I N STOP ®INTERIOR DRYWALL I I ATTACH P.T. 2X8 2 CAR GARAGE I o o ABV. GARAGE DOOR a W/ 3/16"X3' TAPCONS I = 3'-9 1/2" 4'-ll 1 2" 0 8" O.C. STAGGERED. C o to IZ 23' 0" BIBB ®i _�CH SE J 0 SEE DETAIL THIS PAGE FRAME -OUT ELEC. & CHASE ELEC. PANEL -- OSH 5 W/ F ABV. TO.B.B. '-0 3'-7" 9'-4" 3'-7" =0 11'-4" T.0.8.B. -B° 3'-91/2" 4'-ll 1/2" 7'-7" 9'-2" 7'-7" 24'-4" PROJECT LOG ISSUED FOR PRECON 10-18-17 ISSUED FOR PERMIT 11-17-17 LJJ CL o N u J LJJ z p � m W Z) W Z z n J x LL ^ ❑ Q a J Z o Q K o a n m w rn ❑ Z O 0 ` a "- o � U -6 cc:,)f1 d -E•� o a,),rn o o U a) 0- aj -0a +n a ,_ a) a) �E -o�-m n 'i o •� a) C(:d�6 2 � C � E Q C O o 5 a) o j C Q a) E E O 0 O E g o -0 2 V } E •s + a) a) v -00 :g' —0 � rn a) c o = c v o } O o- v N O 2-- z-c- a) J O LL O OU 0 w O o U I 0 J W OJ 2: C~ 1/4" = 1'-O" U.N.O. FLOOR PLAN �IJ A-2 mw =170 PROJECT LOG ISSUED FOR PRECON 10-18-17 ISSUED FOR PERMIT 11-17-17 FLAT CONCRETE 71LE 901 FELT SELF-ADHESIVE UNDERLAYMENT OVER 301 FELT TIN TAGGED TO EXT. GRADE PLYWD. SHEATHING (SEE DIAPHRAGM SCHEDULE FOR TYPE 12 & NAILING PATTERN) PRE-ENG. WOOD ROOF 7RUSSES 6 it 0/C TYPICAL W/APPROVED GALV TRUSS ANCHORS EA. END INSULA71ON PER ENERGY CALC. SEE PLAN/ ELEV. RAT RUNS PER o TRUSS MANE. 5/8" DRYWALL OR 112" "TOUGHROCK" GALV. MIL. DRIP (OR EQUAL) APPLIED TO ON 1X2 P.T. ; 0, UNDERSIDE OF TRUSSES FIRE STOP 2x8 PAINTED TEXTURED SPRUCE FASCIA 2•_p• CONT. 8"x16" MASONRY BOND BEAM CEMEN71TOUS FINISH ON METAL LATH ATTACHED TYP. O.H. W/ 1#5 CONT. TOP & BOT, - FILL W/ CONC. TO LEDGER & 2x4 BLOCKING CONT. METAL POUR STOP W1 3" CONTINUOUS VENTS ALL SIDES (TRUSS CO. TO PROVIDE FLAT SOFFIT) 1/2" DRYWALL IX2 P.T. FURRING ® 24" 0/C MEDIUM TEXTURE DECORATIVE EXTERIOR BLOCK WALL TO BE CEMENTITOUS FINISH OVER 8" CONC. BLOCK R 4.1 FI-FOIL BETWEEN STUDS WOOD BASE MONO. CONC. FOOTING SEE FOUNDATION PLAN FOR N07ES & DETAILS 0'-O" FIN. FL. SLAB 2 a ga °. a— Z =III—III=1I III —III —I _EIIII)EEIIII'a: ;.: III111III11 1II TYPICAL WALL SECTION SCALE 314" = ID" ATTIC VENT CALCULATION: (SQ IN) ROOF AREA CALCULATED ® 3641 (SQ.FT.) x 144 ae 524,304 SQ IN. / 150 = 3,495 SQ. IN. REQUIRED NET VENT AREA / 15 SQ IN. PER LINEAR FT. (270 LF) VENT = 4,050 SQ. IN. TOTAL NOTE: CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF VENTS vinylcorp com 1 8000 NW 79th Place : P305. 4776464 Sdarkwesstem F:etrah Building Systems ..0 Miami. Horde 33166 - F 305.477 4108 Soffit Vents (One Piece) Continuous one-piece Soffit Vent with reinforcing rib to key into stucco &amp; plaster. CS58-300V 1 5l5" 1 3" wide vent (one piece) 5" overall width, perforated flanges 1 15 3" Soffit Vents —Continuous one-piece Soffit Vent with reinforcing rib to key into stucco &amp. plaster. Vent Clips are provided to connect Soffit Vent and to assist in alignment. Vent area: 15 square inches per lineal 8. Caulk all Intersections, butt Joints, ends and corners at time of installation. a=6'-0' EDGE ZONE I I I COLUMNS TO BE SMOOT STUCCO FINISH MATCH TRII COLO U -34.8 PSF _gq,g p U -36.3 PSFU u.r.= +363BLW O -36.3 PSF O -32.7 PSF MASONRY OCONSTRUCTION, TYP. v FRONT ELEVATION -ARTISAN O D.P.= +29.9 PSF -32.7 PSF 34.8 PSF D.P.= +29.9 PSF D.P.= +33.5 PSF D.P.= +28.5 PSF D.P.= +31.9 PSF ,"ILVIV,"1 iLAIVINL -33.6 PSFCEM�J O O -32.7 PSF O -36.3 PSF O -31.3 PSF O -34.B PSF MASONRY CO FINISH CONSTRUCTION, REAR ELEVATION MASONRY CONSTRUCTION, TYP. iEl O D.P.= +33.5 PSF -36.3 PSF 12 �6 O D.P,= +33.5 PSF -36.3 PSF EDGE ZONE EDGE ZONE I I I I I I I I I I I I El O D.P.= +28.5 PSF -32.2 PSF LEFT ELEVATION 14'-8" T.0.8.8 11'-4" T.O.B.B. 9'-4" T.O.B.B. COLUMNS TO BE SMOOTH STUCCO FINISH MATCH TRIM COLOR 0'-0" FIN. FL. SLAB 14'-8" T.O.B.B. 11'-4" T.O.B.B. 9'-4" T.O.B.B. il 0'-0" FIN, FL SLAB ill 11'-4" T.O.B.B. 9'-4" T.O.B.B. 0'-0" FIN. FL. SLAB J L1J d W o N � W w � Z r ro M m o rn 9 li D LL J ^ z G n W J Z Q i J z 0 Q m � by, F C °- rn Z _ O 0 0 OIL _ o �o � canc c 0 o ra a n w Q— > `O a)i 2O �7 .n U .Q' w a a.., N y d d @ E"' O flu o to m w=wCOU to 0 -c3-. aj �0 E � � �0M0 N WEE 8 E o o CLU i� +� aj cn w w w o 9 u- O o 3 v E 7 CM a--, o = w F- E� ru 1—CD o � u N C7 OU >2 L lJ w 73 w A_ J O0 LL 0-0 0 O 1 O � 1W11 U f O � J W 1/4" = V-0" U.N.O. ELEVATIONS FM co , W -170 12 �6 PROJECT LOG ISSUED FOR PRECON 10-18-17 ISSUED FOR PERMIT 11-17-17 ■ " a=6 -0 EDGE ZONE l I I 1 APPLY CEMENTITIOUS MATERIAL PRIOR TO METER INSTALLATION STUCCO ATTACHED TO METAL LATH ATTACHED TO UNDERSIDE OF TRUSSES RAT RUNS PER TRUSS MAN'F. (MAX. 8' O.C) TYPICAL INSTALLATION WINDOW ASSEMBLY MARBLE SILL 5'-0" COVERED LANAI D.P.= +31.9 PSF BELOW: O K D•PD.P.=+33.5 PSF PSF ABOVE: -34.8 PSF O "'CONTRACTOR TO APPLY TO ALL SIDES OF MASONRY OPENING INCLUDING HEADER AND JAMBS PER FBC 2014 703.8 SHER—CRETE FLEXIBLE CONCRETE WATER PROOF — SMOOTH A5-200 SERIES SHERWIN WILLIAMS MANUFACTURER APPLY PRODUCT DIRECTLY TO CLEAN CAULK SEAM AT CONCRFTF SUBSTRATE PER MANUF. SPECS d.; a WINDOW INSTALLATIO ,'MORTAR OR GROUT," -- d.. SET SILL IN FULL d a DRYWALL ,"'A,. "'p MORTAR BED AND HEAD JOINT I STUCCO OR 'p a DECORATIVE 1�CEMENTITIOUS COATING I d. 3/4" FURRING TO 4 1 8" C.M.U. e MASONRY WALL FASTENERS AS REQUIRED BY WINDOW MANUFACTURER CAST-CRETE PRECAST SILL DETAIL SHERWIN WILLIAMS CONCRETE WATER PROOFING APPLICATION F1 O D.P.= +33.5 PSF -36.3 PSF PRE ENGINEERED WD. TRUSSES E @ 24" O/C TYPICAL KITCHEN BEYOND GREAT ROOM 0 7 CONC. COLUMN WEATHER STRIPPING BY DOOR MANE. GARAGE DOOR GALL STL VERT. TRACK BY MANE FASTENED TO �TRACK BRACKETS W/ 1/4"-20x1/2" CARRIAGE BOLTS & LOCK NUTS [=GALV. SR. TRACK BRACKETS FASTENED TO WOOD JAMB W/ 3/16"x1-1/4" LAG SCREWS 2x8 P.T. ATTACHED TO IANU.'S METHOD OF COLUMN W/ 5/8" WEDGE iTTACHMENT SHALL ANCHORS 0 2'-0" 0/C VERT. 'REVAIL WEN SUBMITTED VCOMPLETE WSTRU IIC ONS (6" MAX. FROM ENDS) AND 2 FROM INSIDE EDGE OF 2X8 JAMB DETAIL (GARAGE DOOR) IF GARAGE DOOR VERTICAL REINFORCEMENT REQUIRED, ADD (1) J" A.B. TO EACH SIDE OF THE BRACKET THRU THE HORIZONTAL 2X P.T. HEADER, 4" MIN. EMBED MAX. 6" FROM EACH SIDE OF THE BRACKET, O D.P.= +31.9 PSF -34.8 PSF OPENING TO DINING ROOM FOYER LOW WALL ALUMINUM FRAME, FASTEN TO STRUCTURE THRU BUCK W/ 3/16" TAPCON SCREWS 0 12 0/C. MIN. 1-1/4" EMB PERIMETER SEALANT STUCCO FINISH k—CONC. OR MASONRY 1x2 MIN. P.T. BUCK SET IN SEALANT AND NAILED W/1-1/2" CASE HARDENED COIL NAILS AT 12" 0/C. MAX. DRYWALL BOARD CAULKING JAMB DETAIL (WINDOW) WNDOW ATTACHED ACCORDING TO FBC 1707.4.4.2 0=_6'-0" a=6'-0" EDGE ZONE EDGE ZONE --i I I I I I � O D.P.= +31.9 PSF -34.8 PSF O D.P.= +33.5 PSF -34.8 PSF D.P.= +31.9 PSF -41.7 PSF O RIGHT ELEVATION 12 6 STUCCO ATTACHED TO METAL LATH ATTACHED TO UNDERSIDE OF TRUSSES RAT RUNS PER TRUSS MAN'F. (MAX. 8' O.C) I -I I -I I -I I.I I.I I-) I -I I•) 101 IN IN 101 ICI ICI ICI I=I ICI ICI ICI ICI ICI ImI ICI ICI ICI ICI I -I ICI Cm- � I I I I I _I I I ICI A -A SECTION - ARTISAN 14'-8" T.O.B.B. 9'-4" T.O.B.B. 0'-0" FIN. FL. SLAB 11'-4" T.O.B.B. OL 9'-4" T.O.B.B. 0'-0" FIN. FL. SLAB 1x2 MIN. P.T. BUCK SET IN SEALANT AND NAILED W/ STUCCO FINISH CONIC. OR MASONRY 1-1/2" CASE HARDENED COIL PERIMETER SEALANT NAILS AT 12" 0/C. MAX. CONC. OR MASONRY 2x6 P.T. BUCK RIPPED TO WIDTH OF DOOR JAM CONC. OR MASONRY 1x6 P.T. BUCK SET IN SEALANT AND NAILED SET IN SEALANT FASTEN W/ 114" DIA. x 3-114" Qoi, NI W/1-1/2" CASE HARDENE TAPCONS 3" FROM E.E. 0COIL NAILS AT 12" 0/C, 0 flOo o AND 6" 0/C MAX. ° 0°0 MAX.: RYWALL BOARD DOOR TRIM AULKING LUMINUM FRAME, FASTEN DRYWALL BOARD DOOR FRAME 7r--,cA O STRUCTURE THRU BUCK CAULKING FASTEN TO BUCK W/ / 3f16" TAPCON SCREWS (2) 16 GALV. x 2" 12 0/C. MIN. 1-1/4" EMB D DOOR FRAME FASTEN TO BUCK W/ SCREWS 0 2'-0" 0/C ERIMETER SEALANT (2) 3/16'x2-1/2" TAPCON DOOR TRIM TUCCO FINISH SCREWS 0 2'-0" O/C PERIMETER SEALANT HEAD DETAIL (WINDOW) JAMB/HEAD DETAIL (S.G.D.) STUCCO FINISH WNDOW ATTACHED ACCORDING TO FBC 1707.4.4.2 HEAD/JAMB DETAIL (DOOR) DOOR THRESHOLD SET ALUMINUM FRAME OOR FRAME FASTEN IN BED OF CAULK & D ` SECURE FRAME TO SILL TO BUCK W/(2) 3/16"x FASTENED TO SILL W/ WITH SILICONE 2-1/2" TAPCON #8 x 1 1/2" SCREWS L/ CAULKING SCREWS 0 2'-0" O/C ®18" PERIMETTERER SEALANT .... FLOOR COVERING FLOOR COVERING ...,fl Ooo .Oo...:q 0 0. OR POURED o. 600,PRECAST o o O '.o . SILL W/ 1 #5 BAR GROUT BED CONC. FLOOR SLAB PERIMETER SEALANT CONCRETE SLAB PERIMETER SEALANT SILL DETAIL (WINDOW) SILL DETAIL (S.G.D.) STUCCO FINISH SILL DETAIL (DOOR) WINDOW ATTACHED ACCORDING TO FBC 1707.4.4.2 w IL v Lu O � -j ui W ti Z M �rn m m rn v �+ m a LL J J z 0 w j LL Z a J Z O Q o� a m m Z O 1= �- o -0 N a _O i O ffl O � Q Q C •_ L5 OL O V .� — O N q� +� O dOj o rn ti aj o O IS O 7 0 d Loo w E E O 2 O o jJ E 2 o -o 0- v UCL) E 'E5 +-+ N L to o E o `�' ~ E 0'c r' n c o= O cn V GJ o 'a p E o i = OZ OU 0-ra cu 0-7 J O OW u O O U J 0 W U) 1/4" = 1'-0" U.N.O. SECTIONS ELEVATIONS A-4 721011-t- mw Milo NOTE: MAY 13E ATTACHED TO VERICAL TRUSS MEMBER FOR DESIRED INSTALLATION DUE TO TRUSS PROFILE DISCREPANCIES NOTE: FGTR MAY BE ATTACHED TO BOTTOM CHORD FOR DESIRED INSTALLATION DUE TO TRUSS PROFILE DISCREPANCIES PROJECT LOG ISSUED FOR PRECON 10-18-17 ISSUED FOR PERMIT 11-17-17 ENG. AND APPROVED WOOD TRUSSES SEE TiP. WALL SECTION FOR ACTUAL HEEL AND OVERHANG CONDITIONS SEE TRUSS CONNECTOR SCHEDULE SELECT CONNECTOR BASED ON LOADS SHOWN ON FRAMING PLANS INSTALL PER. MFR. SPECIFICATIONS \ _ SEE PLAN 0" CONT CONT. MASONRY BOND BEAM CONT. POUR STOP 8" CMU WALL 1 A5 CONNECTION DETAIL i lyF USP KCCQ44 OR )' SIMPSON CCQ44sds2.5 FASTEN PER MAN'F. SPECS 5680# MAX. I : WOOD POST SEE FRAMING PLAN (6) 1/4"x2-1/2" LG. SDS SCREWS TO POST SIMPSON HDU5 HOLD DOWN 56451 MAX. (1) 5/8" DIA. WEDGE ANCHOR 4" MIN. EMBED. A5 CONNECTION DETAIL NAIL SILL PLATE THROUGH TO CROSS BLOCK W/2-i6d NAILS AT EACH TRUSS FRAME KNEE WALL 2x4 STUDS ® 24" 0/C W/ 19/32" EXT. SHEATHING TOE NAIL TRUSS TO CAP W/3-i6d NAILS PRE-ENG. WOOD TRUSSES SEE TYP. WALL SECTIONS \ ACTUAL HEEL AND OVERHANG CONDITIONS TIE BEAM OR BOND BEAM 5/8p WEDGE ANCHORS 0 24" 0/C W/3 x3"x114 STEEL WASHERS EMBED (4) MIN. 2x4 CROSS BLOCK ® 24" O/C TYP. TOE NAIL EA. END W/(3) i6d NAILS TYPICAL TRUSS CONT. 2x4 RIBBON W/ 3-16d NAILS EA. STUD A5 CONNECTION DETAIL ALLOWABLE LOAD 1061 #/TRUSS UPLIFT (16) WSJ TO G. T. s e e SIMPSON KECCQ44 e e° OR APPROVED EQUAL. 7105# UPLIFT MAX. (14) WSJ TO WD. POST WOOD POST SEE FRAMING PLAN (14) 1/4' x 2-1/2" SDS THROUGH POST "SIMPSON HDU5" HOLD DOWN OR APPROVED EQUAL 5645# UPLIFT MAX. 5/8- DIA. )GE ANCHOR MIN. EMBED. A5 CONNECTION DETAIL (1) INTO oLAm n7 5" MIN. EMBED. SET IN EPDXY PRE-ENGINEERED WOOD ROOF TRUSS 0 24' 0/C 31MPSON MGT W/ 22-10d JAILS INTO TRUSS 'ONC. TIE BEAM OR MASONRY BOND BEAM MAX. UPLIFT = 3965# a5 CONNECTION DETAIL i12" DRYWALL OVE TYPICAL FURRING EXTRA LAYER OF 1 DRYWALL SURROND, FRAME ARCH TYPICAL FURRING APPLIED TO SHEA T 19/32 PLYWOOD Al SF PRE-ENGINEERED WOOD INVERTED GIRDER TRUSS SIMPSON FGTR W/ 18-SDS 1/4' X 3" SCREWS INTO GIRDER �CONC. TiE BEAM OR 2-1/2" X 5 TITEN MASONRY 13OND BEAM HD TO MASONRY WALL PER MANUF. SPECS MAX. UPLIFT (1) FGTR = 5000# 3 (2) DESIREDA PLLIIFTADDACHIEVE 9400# MAX a5 CONNECTION DETAIL CONT. 2x6 P.T. BUCK FASTENED TO LINTELS W/ 1/4'x3" LG. TAPCONS 0 12' 0/C MAX. AND TO BLOCK OR CONC'. W/ HILTI DNI-62-P8 08" 0/C MAX. 0 �0� 2X6 P.T. CROSS BLOCK REQUIRED ONLY IF FREE EDGE DIMENSION EXCEEDS 24" SEE DIMENSION. NAIL TO BUCK AT EACH A A END W/ (4) i6d NAILS. I EDGE OF MASONRY OPENING I 19/32 EXTERIOR SHEATHING W/PAPERBACKED HI RIB METAL LATH 2X4 PT BLOCKS ALONG ARCH NAIL TO PLYWD. EACH END W/(3) 10d x 1-1/2" COIL NAILS VIEW 4 A5 CONNECTION DETAIL "LOTTS" LINTEL BEAM SCHEDULE 1B/FT LINTEL LENGTH ALLOWED LOAD APPLIED LOAD ALLOWED UPLIFT APPLIED UPLIF1 LINTEL SPECIFICATION 1 1T-4" 1413 545 581 240 8724/181T 2 5'-4" 10000 668 5698 315 8F36/1BiT 3 3'-6" 10000 235 7428 114 BF16/1BiT 4 5'-4" 5809 264 3057 128 8Fi6/1B1T 5 5'-4" 5BO9 264 3057 128 BF16/iBiT 6 3'-6" 10000 104 7428 81 8F16/i13iT 7 4'-0" 10000 980 7184 275 8FIF38/iB1T BA 7'-6" 1078 0 733 0 ftFB/iBiT 8B 7'-6° 2882 1381 1548 533 8F16/1BiT 9A 5'-4" 1773 0 1135 0 8F8/1B1T 9B 5'-4" 5809 250 3057 100 8F16/iBiT 10A 13'-4" 504 0 396 0 BF8/iB1T 10B 13'-4" 1576 919 711 297 8F2O/lB1T 11 4'-0° 10000 416 7184 390 8F!F38/iBiT 12 5'-4" 5809 250 3057 120 8F16/161T 13 14'-B" 1079 197 477 160 8F16/1BiT 14 19'-4" 736 313 323 240 8F16/iB1T 15 10'-6" 1664 353 830 120 81-16 iB1T 16 3'-6" 10000 465 7428 205 SFi6/i13iT 17 7'-6" 2882 233 1548 103 8F16/iB1T 18 5'-4" 5809 1043 3057 531 8F16/iB1T 19 3'-6" 10000 667 9578 233 8772/iB1T 20 5'-10" 757 0 722 0 8RF6/1BiT 21 5'-10" 10000 674 5480 230 8F40/1B1T 22 3'-6" 10000 0 9578 0 8F72/iBiT 23 7'-6" 8615 1183 2879 429 8F28 iB1T 24 5'-4' 6077 434 5698 354 8F48/1B1T 25 13'-4" 2598 170 1022 130 SF28/181T 26 7'-6" 7857 318 3323 262 SF36/1B1T (3) i6D TYP 2 10d TYP. TRUSS REINFORCE VE OF GABLE ENE T-BRACE AT I NAIL w/16d N, as CONN, O�BOX -OUT DETAIL p 5 SCALE 1 4= i -0 ROOF SHEATHING NAIL PER SCHEDULE CONT. FASCIA BOARD (SEE WALL SECTION) NAIL TO LADDER W/ 16d 0 8" O/C 2x4 LADDER FOR O.H. 0 i.°" 0/C CONT. 2x4 LADDER PLATE ANCHORED TO GE TRUSS W/ i6d NAILS 0 8" O/C MAX. 2x4 DIAGONAL BRACE RESTRAINT 0 4'-0" O/C WALL SHEATHING NAIL PER SCHEDULE GABLE END FASTEN TO SLEEPER W/ 16d NAILS ® 4" O/C TYPICAL CONT. 2X4 SLEEPER FASTE14 TO BEAM W/ HILTI XDNI 2-5/8" LG. ® 6" O/C USP TA24R EMBEDDED STRAP W/ (4) i6d NAILS 0 EA. TRUSS VERT. WEB (24" 0/C) CONT. CONC. OR MASONRY TIE BEAM SEE TIE BEAM SCHEDULE 2x4 LATERAL BRACING 0 4'-0" O/C PRE-ENG WD. TRUSSES 0 24' O/C (SEE CONNEC77ON SCHEDULE) 19/32" EXT. GRADE PLYWD. NAILED ® 6" 0/C AT PANEL EDGES & 12" 0/C FOR THE REMAINING FIELD W/ i0d NAILS 2x8 VER7ICAL. NAILED TO ROOF TRUSS W/ (3)10d NAILS, NOTCHED AND TOENAILED W/ (3) 10d NAILS TO PLYWOOD ON BLOCK WALL. (3)i/2 x6' PCS. EXTERIOR PLYWOOD CUT TO CONTOUR OF ARCH, SHOT TO WALL W/ 3" PINS 0 12" 0/C (1 1/4" EMBED) FASTENERS ALLOWABLE LOADS SIMPSON MODEL N0. CMU CONCRETE UPLIFT GRAVITY HU28 6-1/4"x2-3/4" 6-1/4"xi-3/4' 575 LBS. 2400 TITEN TiTEN HU210 8-1/4"x2-3/4" 8-1/4'xi-3/4' 575 LBS. 2400 TiTEN T1TEN ui o N N W W w < Z r m a M M O a m W w 0 LL J J W K z O J Q o a a m p z O 0 0 `a c }a 0 0 0 ra ra Q a o.� o 0 U N d JJ a)� 'n 1 cr- +� ra aj E ra c a� ru a�j 2 .� c � o O- a o ram° oa�i o c a. `o au E E o o O V C — N cu Ln a� O O U E cn a) c o = cn V O } F- -0 V V O C7 O ou fa rn 4= c_n Z CL V O aj ai CL C Q t/ V E C 0 U L U 0) Lu :P c Q •G U v 0 J M N VQ cq hq O J O ccLL O O U 0 O 3. W oo J r o O W () 1/4" = 1'-0" U.N,O. STRUCTURAL PLAN MW=170 SECTION CONNECTION DETAIL 271 LBS. MAX. 665 LBS. MAX. 373 LBS MAX. E.E. 271 LBS MAX. �,�'PROJECT LOG TC-1 ?S] TC-1 TC-1 TC-1 ISSUED FOR PRECON 10-18-17 ISSUED FOR PERMIT 11-17-17 r N " BIZ 1551 LBS. MAX. (2) TC-1 J NOTE: THIS TYPICAL DETAIL TO BE USED WHERE CONDITIONS MAY OCCUR BASED ON TRUSS DESIGN AND FIELD CONDITIONS 12" I, 12" TYP, RIDGE CAP & I ROOF MEMBRANE 2x RIDGE BOARD (2) SIMPSON H10 CLIPS ON 1 SIDE OF TRUSS STAGG. & ATTACHED TO 2x6 CATS ® 24" O/C I BETWEEN TRUSS RUN PRE ENGINEERED ROOF TRUSSES SEE FRAMING PLAN FIELD FRAMED RIDGE DETAIL TRUSS CONNECTOR SCHEDULE FASTENERS PER ALLOWABLE UPLIFT PARALLEL LOAD (172) PERPEND. LOAD (Fl) CTOR TRUSS TIE -BEAM OR WALL SINGLE STRAP DOUBLE STRAP SINGLE STRAP DOUBLE STRAP SINGLE STRAP DOUBLE STRAP (5) 10d x 1-112" - 990 1980 335 670 245 490(7) PCONNECTOR 10d x 1-112' - 1205 2410 335 670 245 # 4906 (8) 10d x 1-1 2' (4) 1 4" x 1-314" WAB. 1225 - 1225 - 1225 9 10d x 1-112' - 1870 2430 710 1310 270 1215 (20) fOd x 1-112' (24 10d x 1-1/2" 1530 - - - - - 1) ALLOWABLE LOADS ARE BASED ON USP CATALOG 2015-16. 2) BLDR MAY USE LONGER STRAPS OF SAME TYPE SPECIFIED. 5) USE UALVANILtU NAILS UN WUUV SCREWS AS SPECIFIED BY MANUFACTURER. 4) TAPCONS SHOULD BE LOCATED AT THE FARTHEST POINT FROM THE TOP OF THE BEAM. 176Y1-11 LOCATION PANEL GRADE ROOF APA RATED SHEATHING EXPOSURE I, OR EQUAL DIAPHRAGM SCHEDULE (FASTENING REQUIREMENTS PER R803.2.3.1) FRAMING DIAPHRAGM SPACING BOUNDARIES EDGE INTER. EDGE 8d RING- Nd RING- 8d RING- Bd RING- 24' 0/C SHANK SHANK SHANK SHANK ,Mau a" n/c 6" O/C 6" 0/C 6" 0/C APA RATED SHEATHING EXT. EXPOSURE I, OR EQUAL 16" 0/C WALL SPAN RATING 40120 19132 MAX. APA RATED SHEATHING INT. EXPOSURE I, OR EQUAL 16" 0/C WALL SPAN RA77NG 32116 15132 MAX. 8d RING- I Nd RING- 1 8d RING- 2 INTER. ZONE EDGE 3 INTER. REMARKS W RING- 8d RING- 8d RING - SHANK SHANK SHANK BLOCKED AS 6" O C 4" O C 4" O C SHOWN ON PLAN NAIL CORNER STUDS AT 4" 0/C MAX. TYPICAL BLOCK FREE EDGES RING -SHANK NAILS TO HAVE T14E FOLLOWING DIMENSIONS 1. 0.113 INCH NOMINAL SHANK DIAMETER 2. RING DIAMETER OF 0.012 OVER SHANK DIAMETER J. 16 TO 20 RINGS PER INCH 4. 0.280 INCH FULL ROUND HEAD DIAMLIER 5. 2 INCH NAY'- LENGTH 11'-4 /K LG. LBS. M rl Q L Q S. MAX. CE a � J ti �o n w �EJ2 _ Q G. 856 M90 -4" C lo STON 9' 4" 3CYL T _ Q TC- K '-4 -4' E V CLG ER -1 T � a a0 Z Z 0] 9'-4" CLG. ERLINE OF BRG. COL SETBACK CENTERLINE OF BRG. COLUMN 4" C ZR Y G. R J[ Q o N T CR CI 4 9'_4" CLG. MV2 MV4 606G 4083 LBS. MAX. SEE DETAIL 3/A5 9'-4" CLG. 9'-4" CLG. 9'-4" CLG. w t 9'4" G. to Lo Li �EJ2 7EJ2A -EJ2B -EJ2B sw 0 N 3289 MAX. LBS, SEE DIET. 2/A5 1163 LBS. E.E. 9'-4" WALL HEIGHT 11'-4" WALL HEIGHT 11'-8" WALL HEIGHT 14'-8" WALL HEIGHT CONNECTION RESPONSIBILITY NOTE E.C.T. PROVIDES TRUSS TO TRUSS FACE MOUNT HANGERS ONLY. ALL OTHER TRUSS TO TRUSS OR TRUSS TO MASONRY CONNECTIONS ARE THE RESPONSIBILITY OF THE E.O.R. Indicates Left End Of Truss On Layout & Engineering Sheets a., EDGE STRIP DEFINED AS THE LESSER OF 10% OF LEAST HORIZONTAL DIMENSION OF BUILDING OR 40% OF HEIGHT H BUT T LESS THAN 4% OF LEAST HORIZONTAL DIMENSION OF BUILDING AND AT LEAST 3 FT. NOTE: SEE DIAPHRAGM SCHEDULE FOR ROOF ZONE NAILING REQUIREMENTS. O \�4 I -------------- IA I I I x � W o LL1 W w Z m m m m m O LL J J W D Z 3 w w J LL Z ❑ Ja Z O J Q N K o a r m ❑ z O m L a O O � N o a�E cl U aj o + _0 n += to E cu _ rn cu _ ai .Q- -p _o to n_ Oto =o E E o $ E E p o V y, i ;-, a) a) Ln o o ± E Cn cn C O L.0 vi aU _� in ' O -aE Otf V V U O fU 1Z f V J_ Ln d LL- 0-0 O 0 O � UJ ,^I o V o J O LLI 1/4" = 1'-0" U.N.O. TRUSS PLAN A-6 /I mw '170 8d RING- 1 Ad RING- 18d RING - BLOCK FREE EDGES ROOF ZONE DIAGRAM PROJECT LOG ISSUED FOR PRECON 10-18-17 ISSUED FOR PERMIT 11-17-17 ELECTRICAL SYMBOLS ® DUPLEX RECEPTACLE $ SWITCH TELEVISION JACK C7 DETECTOR EYEBALL I AT 12" A.F.F. SINGLE POLE 4 PRE WIRED SECURITY ' USB STA710AI Q� DUPLEX RECEPTACLE SWITCH 220 V. RECEPTACLE FLOOD LIGHTS F.P.&L. METERIB AT BASE �3 THREE WAY AT 12" A.F.F. SO SMOKE g & DISC. DETECTOR ?c DUPLEX RECEPTACLE AT 8" AB�4 FOURC WAY THERMOSTAT ® ® PANELBREAKER V. COUNTER SMOKE /CARBON MONOXIDE DETECTOR O INTERCOM EXHAUST DUPLEX RECEPTACLE SWITCH I AT 60" A.F.F. SWITCH y FAN O DISCONNECT FLUSH IN FLOOR R RHEOSTAT TELEPHONE OU11ET Q� FL EXHAUST FAN DUPLEX RECEPTACLE SWITCH® AT 12" A.F.F. x PADDLE FAN W/ LIGHT W/ OR WO/ LIGHT GFI LV DOOR GROUND FAULT o DIMMER FLUSHHINNFLOOR ET FLUORESCENT RELEASE DUPLEX RECEPTACLE SKATCH Q� SPEAKER FIXTURE CLG. MNTED.I v VOLUME TOP REC. SWITCHED K KEYED ® IN CLG. 1 INCANDESCENT LIGHT CONTROL Q� DUPLEX RECEPTACLE SECURITY SPEAKER �J FIXTURE CEILING MNTED. q®� QUADRUPLEX wp WATERPROOF KEYPAD WALL OUTLET INCANDESCENT LIGHT II RECEPTACLE Q DUPLEX RECEPTACLE JUNCTION FIXTURE WALL. MNTED. ® LOW VOLTAGE uc UNDER COUNTER BOX SPEAKER HI HAT HOME RUN ® CLG. MOUNTED TRANSFORMER O INTERCOM p DOOR CAT5 ® HI HAT Fg FAN BOX STATION I CHIME HOME RUN VAPOR PROOF IN CLG, ELEC. PANEL "A" 200 AMP CIRC. DESCRIPTION POLE BRKR WIRE VA. 100% 2 AHU HEAT STRIP 2 60 6 0 9.6 2 A/C COMPRESSOR 2 40 B 0 0 1 ELECTRIC COOKTOP 2 50 6 10.0 0 1 DBL, WALL OVEN 2 50 6 10.0 0 2 DRYER 2 30 10 5.0 0 2 WATER HEATER 2 30 10 4.5 0 1 LAUNDRY 1 20 12 1.5 0 1 MICROWAVE 1 20 12 1.5 0 1 DISHWASHER/DISPOSAL 1 20 12 1.2 0 1 REFRIGERATOR 1 20 12 1.2 0 3 SMALL APPLIANCE 1 20 12 4.5 0 1 BATH GFI 1 20 12 1.5 0 12 GEN. LIGHTING 1 15 14 6.3 0 47.2 9.6 1st 10,000 at 100% = 10.00 REMAINDER AT 40% = 14.88 A/C LOAD AT 657 = 6.24 TOTAL = 31.12 31.12 x 1000/240 = 129.6 AMPS (1) SETS OF (J) 14/0 AWG. THWN IN 2" CONDUIT 200 AMP SERVICE p METER DISC. CO PANEL 200 A 5/8" GDX 10' CU SUPPLEMENTAL GROUND ROD AND TO ONE REINFORCEING BAR IN THE FOUNDATION 20'-0" LONG MIN, ELECTRICAL RISER DIAGRAM CALCULATION NOTES: A. HEAT STRIP LOAD GOVERNS OVER CONDENSER UNIT LOAD. B. GENERAL LIGHTING CALCULATED 0 2522 (SQ.FT.) x 3 (WATTS/SQ.FT.) = 7566 / 12 (GEN.LTG.CIR.) = 630 (WATTS/EA.) C. A/C CONTRACTOR SHALL SIZE A/C UNITS. A/C UNITS SHOWN ARE FOR ELEC. CALC S. ONLY. NOTE: ALL VANITY YYALL LIGHTS TO BE 100" A.F.F. U.N.O. POWDER ROOM TO BE 86" A.F.F. IF APPLICABLE NOTE: ALL EDGE OF :TWITCH PLATES TO BE NO LESS THAN 4" FROM OPENINGS NOTE: GARAGE PIJSH BUTTON LOCATED 0 60" ABV GARAGE FLOOR 72" MAX. NOTE: PROVIDE ARC FAULT -INTERRUPTER PROTECTION FOR ALL DWELLING IJNIT BEDROOM RECEPTACLES. (PER NEC 210-12) NOTE: ACCEPTABLE SMOKE & CARBON DETECTORS TO BE INSTALLED ARE BRK SMOKE--9120B C/O-SC9120B KIDDE SMOKE-21007581 C/O 21006377-N USB *NOTE* - ALL ABOVE COUNTER AND ISLAND OUTLETS TO BE DECO - ALL SWITCHES TO BE DECO W g N � W LUJ J W N Z r m m M o m LL p J w D Z O K 3 w 3 z O Q N p Z O � t a o � o o c o o n3 = � a a E -0 o Q v� o W -o U0- cn -0�,,,, N a) aj aj ,N ;E:. `a n �_ E 0 aaoi-o 2 Q V E E E o 0 � E E � o -o Qv E •� +� a� aJ v Qj ai w o c°i E 0 CD � 0 _ cn o v o O 0 0 CD 2f � -1, Ln .— .' H E Q O LY u cL 71 E cy c O s U V CD C — "y C O V 0 1 N e oil —r 14 —0 J Or 0-0 � ILL. V [� Z �0 O uU 3 Lu . I J ' LLJ 1/4" = P-0" U.N.O. ELECTRICAL PLAN E-1 Z 3" 3" KITCHEN KI %II 2" VfR WL 2" G 2" SHWR LAV 3" 2" 3" 3° LAV 3" CO AW 2" 3' 2" 2° 0 LAV 2'LAUNDRY TUB MASTER BATH 3" BATH 2 3 WC 3" PLUMBING RISER DIAGRAM a WM 2" AW LAV m WC Dw 2" SHWR BATH 3 Job #: Tacoma Lot 170 Performed by Skyetec for: GHO Homes 9410 Pinebark Ct Ft. Pierce, FL 34951 Tacoma 5.0 Ton Scale: 1 : 115 Page 1 Right -Suite® Universal 2017 17.0.04 RS000269 2017-Nov-13 16:11:35 ...s\Skytec\Tacoma Lot 170 GL S.rup PROJECT LOG ISSUED FOR PRECON 10-18 ISSUED FOR PERMIT 11-17 w a a w o N � u W w Z r v M M M o m J zx z N J Z ^ 0 0 O Q ~ a rn v? z O o a t� � o " 'O O C fl- O- O E LM O O U a`ni N a� a +.+ (V o n v 2 33 33 E � Ora N — Cncu to c N O O p ra E 'v UO N E E 0-2 LO U C N N o o E m c 2 Ln p w E AD fo _ O Z a J-_ u Z a ^O 12 vi ® C fie 0 0 m O p/ ) C °= 4 C d lam iCUI oil0CN a O VL i o C i O o - Ow � I 1/4" = V-0" U.N.O. MECHANICAL PLAN M-1 MWW17C N 2„ AW LAV CO KITCHEN KIT AW WC 3 \ 2„ ViR` W 2" SHWR 3„ BATH 3 AW 3" WC CO 2" 2" SHWR 2" 3" 3„ LAV 3" wm LAV 3" CO AW 2" 3" 2" 2" D 2" LAUNDRY MASTER BATH LAV 3" BATH 2 3 WC TUB 3" PLUMBING RISER DIAGRAM Tacoma ook !t . ..- a '1 K + Or, �! r Bedroom 3,:. f+ � ..:3 �Gk ` ay + 0Ift ::. t Zvi - '� .o 12 23 P 10 tl LF F ) � + M emu i .o. .ry o; -a x s er Bath _._ N!•� hC�l �`� ff I 18 a `r� 14 x -14 T _ � +.4 a - yr�.wq�yt� (� �'LWrv✓V ..i Ntn� ., <r nrv.,^„rpyVnaga.,yw.t `^ S:P `t.9 Fi .(� <iA Q ( �r � l i r - a .4 ft Schedule Exhaust Fan F Range Vent O Dryer Vent O Rheem Equipment ARI 7943714 5.0 Ton 16 SEER RH1T60 AHU 5.0 Ton 16 SEER RA1660 Cond Job #: Tacoma Lot 170 Performed by Skyetec for: GHO Homes 9410 Pinebark Ct Ft. Pierce, FL 34951 PROJECT LOG ISSUED FOR PRECON 10-18-17 ISSUED FOR PERMIT 11-17-17 BLDG COMMENTS 02-05-18 uw ogw N � # wa w ~ m Z m 1� O m m e v w � J ^ LL J Z J w D LL J LL Z o J Z O Q m r�� o 0 a rn m Z Od Q o a O O O f C ` fl E s — OD N 2 O V M a En c r0 E O •� .N _V Tp }r cn •U, N OL -O } (D aJ O Q O a--r — c6 O Q a N O O C R Q N E E O 2 O .2 E d p -o O- V V o9 o u E Ch C 'F1 u C O p = (n V O Z O E Q 0 V o E ° OCIS 0 cn C — w o J 2 C%4 H 0 C 5.0 Ton o O o o w o O U � J ' W _J �K Lr) 1/4" = 1'-0" LIAO. MECHANICAL Scale: 1 : 115 PLAN Page 1 M-1 Right -Suite® Universal 2017 File Copy 17,0.04 RS000269 2017-Nov-1316:11:35 MW �� ...s\Skytec\Tacoma Lot 170 GL S.rup