Occupancy Type Mercantile Construction Type IIB Square Feet 8678
Occupant Load 160 ( Class B) Number of Stories 1 Access Box Required Access Key Switch
AFS Permit FA Permit FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all Inspections.
4. The respective Building Department shall schedule'all final inspections through the Fire Marshal's Office.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper LIL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections In the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
i19. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2012 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above ana Kequlrea Kevisions veiow
Notes *
1. If your HVAC system is sharing the same space and together the CFM is over 2000, HVAC detectors are required. Provide
remote test and inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector.
2. Place emergency lights in the both rest rooms. ,
Field inspections may require additional revisions.
Page of Reviewed by Tony Jerger Date 08-02-16.